DESIGN OF HAPCO ALUMINUM LIGHTING POLES
CATALOG No. RTA21B6BE
PROJECT: SAVANNA CLUB EAGLE'S LANDING POOL
St. Lucie County, Florida
DESIGN CRITERIA: FLORIDA BUILDING CODE 2014
170 MPH (max with Gust) Using ASCE7-10, Per Section 1601 & 1819
Date: 8-9-2017
References:
ASCE 7-10 — Minimum Design Loads for Buildings & Other Structures
Florida Building Code 2014 Chapter 16 for Structures and 18 for Foundations Cat.I
AASHTO Standard Specifications for Highway Signs, Luminaries and Traffic Signals
1994 & 2010
FDOT Standard Specifications
Catalog Cut Sheets
Prepared By: James E. Wild, P.E.
592 Lancaster Gate SE.
North Canton Ohio 44709
Submitted By: Precision Outdoor Lighting, Inc.
3832 Shipping Ave
Miami, Fl 33146
POLE ID RA21B6BE
By: J.Wild, PE ver 10-1-12
"% (29' OAH, 21' MH)
Date: 8/9/2017
Project: . Savanna Club Eagle's
Landing Pool
General Data:
Calculations: ASCE 7-10 & 2014 FBC
C.G of Fixture
21 ft q = 0.000256 *VA 2 = 73.984 psf
Base Height Above Ground
0 ft Wind Pressure = 0.00256'Kz'Kzt•Kd'v^2
C.G. of Fixture from Pole CL
1 ft P = 65.39 psf
EPA of Fixture (total)
1.1 sf Fixtures:
Weight of Fixture (total)
40 Ibs Dead Load 40 Ibs
Wind Speed (V)
170 mph Wind Load 71.93 Ibs
OT Moment 1510.55 ft-Ibs
Material for Pole & Arm
Alum 6063
Pole Data:
Pole:
Shape of Pole
Rd Dead Load: 82.25 Ibs
Embedment Depth
8 ft EPA 4.13 sf
Length
29 ft Wind Load: 270.35 Ibs
Base OD
6 in C.G. of Pole 14.50 ft
Top OD
4.5 in OT Moment 3920.12 ft-Ibs
Wall Thickness
0.125 in Torsion M 71.93 ft-Ibs
Aver. Unit Wt /LF
2.84 Ibs/If
Area Aver.
2.01 in^2 Sum of Loads @ Base:
r = (OD-t)12 aver
2.56 in axial 122.25 Ibs
r = (od@base-t)/2 @ base
2.94 in shear 342.28 Ibs
Area @ Base
2.31 in moment 5430.67 ft-Ibs
Section Modulus @ Base
3.39 in^3 torsion 71.93 ft-Ibs
Mom. of Inertia @ Base
9.95 in14
Torsion Constant (J)
6.77 in^4
Projected Area of Pole
9.19 sf
Exposure category
C
Kz for Pole:
0.91
Cf for Pole:
0.45 (based on wind tunnel testing)
Kzt - use 1.0
1.00
Kd :
0.97
Overload factor =
1.33
Stress Calculations:
Allowable Stresses:
Pole: fa = axial / Area =
53.0 psi Fa = Fcy/ny = 17,727 psi
fb = OT Mom / Sect Mod. = 19241.5 psi Fb = 1.17-Fty/1.65 = 17,727 psi
fv = (2'shear/a)+(torsion/1)
= 424.3 psi or Fb = 1.24'Ftull.95 = 19,077 psi
CSR's:
use use 17,727 psi
Post: CSR = fa/Fa + (fb/Fb)+(fv/Fv)^2
= 0.82 Fv = Fsy/ny = 13,473 psi
csr < 1.0 so OK!
Check Embedment Depth of Pole:
REF: FBC Table 1819.6 &1819.7.2.1
d=•0.5A(1 +(1 +(4.36h/A))^1 /2)
Where:
A = 2.34P/(S1 b), where S1 = 2'S'd/3, S = 150.00 psf
d= Depth of Embedment in feet 8.00 ft
b = Diam of Post, Concr or compacted fill 0.50 ft
S1 = Soil Pressure = 800 psf
(load that produces GrdLine Mom)
P = Maximum Lateral Load 258.60 Ibs - load that produces GrdLine Mom)
(assume load at fixture height)
h = Dist from Load to Groundline 21 ft - assume load at fixtures IN"#,,,
SOLVE -for do --
A = 2.34P/(S1b) = 1.51 44
♦e 1
d=0.5A(1+(1+(4.36hlA))^1/2)= 6.69 ft .`0 , " I P nfQaao
Embedment Depth Shown > Calculated so OK
01. fE OF
0
R
;;
"A"
9FT BURIAL F
ounting Height:
21
Wall Thickness:
in
Butt Diameter:
6 in
Tap Diameter:—z4.5
in_
Base Diameter:
in
Bolt Circle:
4 in
Bolt Projection:
in
Bolt Size:
Net Weight:
70
minary Weight:
100
Arm Length:
Quantity:
Club Eagle's Landing Pool
"D" i
Tap
Diameter
RTA21B6BE-BH
Notes: 21 FT
POLE EPA-
Embedded
Cast Alum: Pole Cap
With Stainless Steel Screws
RTA DIRECT BURIED
for Lithonia KAX2 LED
Luminaire / Arm Drilling Per Customer
Specifications
RTA2i1666E BH
Optional Tenon Mounting (specify)
Internal Damper (For Poles with 6"-10" butt diameters only)
(Installed) Reference pages 105-106
for bull horn arms and
"B" Wall Alloy 6063 T6 CrosSarms
Satin Ground or Powder Coated Finish
per Customer Specification
Grounding Provision
SLA
WARNING: Do not
install light pole
without luminaire.
- Reinforced Handhole with Cover and Stainless Steel Hex Hd Screws
for Poles (3" x 5" For 6" 'Poles 4" x 6" for 7" and larger Poles)
- Handhole (2" x 5'1 with Cover and Stainless Steel Hex Hd Screws for
Poles with 5" butt diameter
,/ "C" Butt Diameter
Ground Line
13/4" Dia. Wire Hole With
1 1/2" I.D. Rubber Grommet
34'
O�
Maximum EPA
70: 11.9
80: 8.3
90: 6.2
100: 4.8
110: 3.8