HomeMy WebLinkAboutLOAD AND ENERGY CALCULATIONSProject #: 170093 ADG Port St. Lucie Port St. Lucie, FI Load and Energy Calculations 09-15-2017 RECEIVED OCT 0 2 2017 PERMITTING St. Lucie County, FL SCgNN'E�D St to By 1711, MECHANICAL, ELECTRICAL, PLUMBING, FIRE PROTECTION, & COMMISSIONING www.beacon-eng.com 100 NE 6" St., Suite 102 Boynton Beach, FL 33435 Tel no: 561.424.3270 i" ;Florida Building. Code, Fifth Edition (2014) Energy Conservation . i EnergyGauge Summit@ Fla/Com-2015, Effective Date: June 30, 2015 ASHRAE 90.1-2010 - Energy Cost Budget Option Check List Applications for compliance with the Florida Building Code, Energy Conservation shall include: [�Y This Checklist dAn Input report generated from the software just after completing compliance calculations without any further changes The full compliance report generated by the software that contains the project " summary, complaince summary, certifications and detailed component compliance reports Boxes appropriately checked in the Miscellanous report generated by the software at the end of the compliance report EnergyGauge Summit® Fla1Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015 9/15/2017 Page 1 of 14 PROJECT SUMMARY Short Desc: 170093 ADG PSL Description: .......... Owner: ............ Addressl: Port St. Lucie City: Port St. Lucie Addressl: State: FL Zip: 0 Type: Office Class: Renovation to existing Jurisdiction: PORT ST. JOE, GULF COUNTY, FL (331100) Conditioned Area: 2387 SF Conditioned & UnConditioned Area: 2387 SF No of Stories: 1 Area entered from Plans 2387 SF Permit No: 0 Max Tonnage 7 If different, write in: Component Design Criteria Result Gross Energy Cost (in $) 833.0 1,287.0 PASSED LIGHTING CONTROLS EXTERNAL LIGHTING HVAC SYSTEM PLANT WATER HEATING SYSTEMS PIPING SYSTEMS Met all required compliance from Check List? PASSES No Entry PASSES No Entry PASSES PASSES Yes/No/NA IMPORTANT MESSAGE Info 5009 -- — — An input report of this design building must be submitted along with this EnergyGauge Summit@ Fla/Com-2014. TAM 20%1.0 Compliant Software. Effective Date: June 30, 2015 9/15/2017 Page 2 of 14 a CERTIFICATIONS ,ttoe¢ruou®eetee ,`%%%�� m I hereby certify that the ns and edifi tiq ep d by this calculation are in compliance with the Florida Energy Code ; • * m Prep m : An elo L da ilva : m Building Official: e '•. C n „ O''. '�� Date: ���is/oNAI Eoae°% I certify that this building is in cdtuegi✓i{h the Florida Energy Efficiency Code Owner Agent: Date: If Required by Florida law, I hereby certify (') that the system design is in compliance with the Florida Energy Efficiency Code Architect: Reg No: Electrical Designer: Joeven M. Vatenzuela Reg No: 60287 Lighting Designer: Joeven M. Valenzuela Reg No: 60287 Mechanical Designer: Angelo L da Silva Reg No: 78400 Plumbing Designer: Angelo L da Silva Reg No: 78400 (*) Signature is required where Florida Law requires design to be performed by registered design professionals. Typed names and registration numbers may be used where all relevant information is contained on signed/sealed plans. EnergyGauge Summiit@ Fla/Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015 9/15/2017 Page 3 of 14 Project: 170093_ADG PSL Title:.......... Type: Office Building End Uses 1) Proposed 2) Baseline Total 54.80 83.80 $834 $1,287 ELECTRICITY(MBtulkWhl$) 54.80 83.80 16064 24563 $834 $1,287 AREA LIGHTS 13.80 30.10 4041 8817 $210 $462 MISC EQUIPMT 33.90 33.90 9943 9943 $516 $521 PUMPS & MISC 0.10 0.00 32 7 $2 $0 SPACE COOL 3.10 7.90 909 2307 $47 $121 SPACE HEAT 0.50 0.10 149 18 $8 $1 VENT FANS 3.40 11.80 990 3471 $51 $182 Credits Applied: None PASSES Passing Criteria =1287 Design (including any credits) = 834 Passing requires Proposed Building cost to be at most 100% of Baseline cost. This Proposed Building is at 64.8% EnergyGauge Summit® Fla1Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015 9/15/2017 Page 4 of 14 External Lighting Compliance Description Category Tradable? Allowance Area or Length ELPA CLP (W/Unit) or No. of Units (W) (VV) (Sgft or it) None Project: 170093_ADG PSL Title: ..... _... Type: Office (WEA File: TALLAHASSEEXAM Lighting Controls Compliance Acronym Ashrae Description Area Design Min Compli- to (sq.ft) CT CP once light .light light 10,004 Exam/heatment (Hospital) 459 2 1 PASSES 17 Office - Enclosed 1,784 1 1 PASSES 1 Electrical Mechanical Equipment 144 1 1 PASSES Room - General PASSES EnergyGauge Summit® FlaICom-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015 9/15/2017 Page 5 of 14 Project: 170093_ADG PSL Title:.......... Type: office (WEA File: TALLAHASSEE.TMY) System Report Compliance AHUI System 1 Constant Volume Air Cooled No. of Units Split System < 65000 Btu/hr 1 Component Category Capacity Design Eff Design IPLV Comp- Eff Criteria IPLV Criteria liance Cooling System Air Conditioners Air Cooled 28900 13.00 13.00 12.50 PASSES Split System < 65000 Btu/h Cooling Capacity Heating System Electric Furnace 17060 1.00 1.00 PASSES Air Handling - Air -Handler (Supply) - - 1000 - 0.30 0.82 PASSES System -Supply Constant Volume Ai3U2 System 2 Constant Volume Packaged No. of Units System-902 1 Component Category Capacity Design BIT Design IPLV Comp- Eff Criteria IPLV Criteria liance Cooling System Air Conditioners Air Cooled 83700 11.50 11.20 12.50 11.40 PASSES 65000 to 135000 Btu/h Cooling Capacity Heating System Electric Furnace 25590 1.00 1.00 PASSES Air Handling Air Handler (Supply) - 2400 0.30 0.82 PASSES System -Supply Constant Volume AHU3 System 1 Constant Volume Air Cooled No. of Units Split System < 65000 Btu/hr 1 Component Category Capacity Design Eff Design IPLV Comp- Eff Criteria IPLV Criteria liance Cooling System Air Conditioners Air Cooled 52400 13.00 13.00 12.50 PASSES Split System <65000 Btu/h Cooling Capacity Heating System Electric Furnace 34120 1.00 1.00 PASSES Air Handling Air Handler (Supply) - 2200 0.30 0.82 PASSES System -Supply Constant Volume PASSES EnergyGauge Summit0 Fla/Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015 9/15/2017 Page 6 of 14 Plant Compliance Description Installed Size Design Min Design Min Category Comp No Eff Eff IPLV IPLV !lance None Project: 170093_ADG PSL Title:.......... _ - - - Type: Office (WEA File: TALLAHASSEE.TMY) Water Heater Compliance D Description Type Design Mn Category Design Max Comp Eff Eff Loss Loss liance Water Heater 1 Electric water heater <= 12 [kW] 0.94 0.93 PASSES PASSES Project: 170093_ADG PSL Title:.......... Type: Office (WEA File: TALLAHASSEE.TM]) Piping System Compliance Category Pipe Din Is Operating Ins Cond Ins Req Ins Compliance [inches] Runout? Temp [Btu-in/hr Thick [in] Thick [in] [F] SF.F1 Domestic and Service Hot Water 0.25 False 110.00 0.28 1.00 0.50 PASSES Systems PASSES EnergyGauge Summit@ FIalCom-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015 9/15/2017 Page 7 of 14 Project Name: 170093 ADG PSL Project Title: .......... Address: Port St. Lucie State: FL Zip: 0 Owner: ----. EnergyGauge Summit® v5.20 INPUT DATA REPORT Proiect Information Orientation: ,North Building Type: Office Building Classification: Renovation to existing building No.of Stories: I GrossArea: 2387 SF Zones No Acronym Description Type Area Multiplier Total Area lsfl lS11 1 AHU1 Zone 1 CONDITIONED 459.0 1 459.0 ❑ 2 AHU2 Zone 1 CONDITIONED 1784.0 1 1784.0 ❑ 3 AHU3 Zone 1 CONDITIONED 144.0 1 144.0 ❑ 9/15/2017 EnergyGauge Summit® v5.20 1 Spaces No Acronym Description Type Depth Width Height Multi Total Area Total Volume [ft] [ft] [ft] plier [sf] [cf] In Zone: AHU1 1 light ZOOSpI Exam/freatment(Hospital) 1.00 459.00 10.00 1 459.0 4590.0 ❑ In Zone: AHU2 1 light ZOOSpI Office - Enclosed 1.00 1784.00 10.00 1 1784.0 17840.0 In Zone: AHU3 1 light ZOOSpI Electrical Mechanical 1.00 144.00 10.00 1 144.0 1440.0 El Equipment Room - General Lighting No Type Category No. of Watts per Power Control Type No.of Luminaires Luminaire [W] Ctrl pts In Zone: AHUI In Space: light 1 LED General Lighting 6 31 188 Manual On/Off 1 ❑ 2 LED General Lighting 4 17 68 Occupancy sensor without 1 ❑ Daylighting In Zone: AHU2 In Space: light 1 LED General Lighting 59 17 1003 Occupancy sensor without 1 ❑ Daylighting In Zone: AHU3 In Space: light 1 LED General Lighting 2 30 60 Occupancy sensor without 1 ❑ Daylighting 9/15/2017 EnergyGauge Summit® v5.20 Walls No Description Type Width H (Effec) Multi Area Ift] [ft] plier Isl] Orientation Conductance [Btu/hr. sf. F] Heat Dens. R-Value Capacity [lb/cf] [h.sGF/Btu] [Btu/sf.F] In Zone: Windows No Description Orientation Shaded U SHGC [Bta/hr sf F] Vis.Tra W H (Effec) Multi Total Area Ift] [ft] plier [sfJ In Zone: In Wall: Doors No Description Type Shaded? Width H (Effec) Multi Ift] Ift] plier Area [sf] Cond. Dens. Heat Cap. R-Value [Btu/hr. sL F] Ilb/cf] [Btu/sG F] [h.sf.FBtu] In Zone: In Wall: Roofs No Description Type Width H (Effec) Multi Ift] Ift] plier Area Isf] Tilt [deg] Cond. [Btu/hr. SE F] Heat Cap Dens. R-Value [Btu/sf. F] Ilb/cl] [h.sf.F/Btu] In Zone: El 9/15/2017 EnergyGauge Summit® v5.20 Skylights No Description Type U SHGC Vis.Trans W H (Effec) Multiplier Area Total Area [Btu/hr sf F] IN IN [Sf] [S11 In Zone: LIn Roof: Floors No Description Type Width H (Effec) Multi Area Cond. Heat Cap. Dens. R-Value [it] [ft] plier [sf] [Btu/hr. sE F] [Btu/sE F] [lb/cf] [h.sEFBtu] In Zone: Systems AHU1 System I Constant Volume Air Cooled Split No. Of Units 1 System < 65000 Btu/hr Component Category Capacity Efficiency H'LV 1 2 3 Cooling System Heating System Air Handling System -Supply 28900.00 13.00 12.50 17060.00 1.00 1000.00 0.30 El AHU2 System 2 Constant Volume Packaged No. Of Units 1 System-902 Component Category Capacity Efficiency H'LV I 2 3 Cooling System Heating System Air Handling System -Supply 83700.00 11.50 12.50 25590.00 1.00 2400.00 0.30 El 9/15/2017 EnergyGauge Summit® v5.20 AE1U3 System 1 Constant Volume Air Cooled Split No. Of Units 1 System < 65000 Btu/hr Component Category Capacity Efficiency IPLV 1 Cooling System 2 Heating System 3 Air Handling System -Supply 52400.00 13.00 12.50 34120.00 1.00 2200.00 0.30 ❑ ❑ ❑ Plant Equipment Category Size Inst.No Eff. IFLV Water Heaters W-Heater Description CapacitlCap.Unit I/P Rt. Efficiency Loss 1 Electric water heater 30 [Gal] 5 [kW] 0.9400 [Eff [Btu/h] ❑ EA -Lighting Description Category No. of Watts per Area/Len/No. of units Luminaires Luminaire [sf/ft/No] Control Type Wattage [W] Piping No Type Operating Insulation Temperature Conductivity [F] [ Btu-in/h.sLF] Nomonal pipe Diameter [in] Insulation Thickness [in] Is Runout? 1 Domestic and Service Hot Water Systems 110.00 0.28 0.25 1.00 No ❑ 9/15/2017 EnergyGauge Summit® v5.20 Fenestration Used Name Glass Type No. of Glass SHGC Panes Conductance [Btu/h.sLF] VLT 7 Materials Used Mat No Acronym Description Only R-Value RValue Thickness Used [h.sf.F/Btu] [ft] Conductivity [Btu/h.ft.F] Density [lb/cf] SpecificHeat [Btu/ib.F] Constructs Used No Name Simple Massless Conductance Heat Capacity Construct Construct [Btu/h.sGF] [Btu/sLF] Density [ib/cf] RValue [h.sGF/Btu] Layer Material Material Thickness No. [ft] Framing Factor El 9/15/2017 EnergyGauge Summit® v5.20 Air System Sizing Summary for AHU-1 Project Name: 170093-ADG Port St. Lucie 09/15/2011 Prepared by: Beacon Consulting Engineers 10:21AN Air System information Air System Name ......................................... AHU-1 Equipment Class .................................... SPILT AHU Air System Type .......................................... SZCAV Sizing Calculation Information Calculation Months ................................ Jan to Dec Sizing Data ............................................ Calculated Central Cooling Coil Sizing Data Number of zones.......................................................... 1 Floor Area............................................................. 459.0 ft' Location .............................. West Palm Beach, Florida Zone CFM Sizing .............. Sum of space airflow rates Space CFM Sizing .......... Individual peak space loads Total coil load ..................................................... 2.4 Tons Load occurs at ................................................. Jul 1400 Total coil load ................................................... 28.4 MBH OA DB / WB.................................................. 90.6 / 77.9 OF Sensible coil load ............................................. 26.1 MBH Entering DB / WB.......................................... 76.7162.1 OF Coil CFM at Jul 1400....................................... 1061 CFM Leaving DB / WB........................................... 63.9 / 62.5 OF Max block CFM............................................... 1061 CFM Coll ADP................................................................. 51.4 OF Sum of peak zone CFM................................... 1061 CFM Bypass Factor ....................................................... 0.100 Sensible heat ratio .......................................... 0.919 Resulting RH.............................................................. 43 % ft'/Ton............................................................. 194.1 Design supply temp................................................. 53.0 OF BTU/(hr-ft-) ....................................................... 61.8 Zone T-stat Check ................................................ 1 of 1 OK Water flow @ 10.0 OF rise .................................. NIA Max zone temperature deviation ............................... 0.0 OF . Central Heating Coil Sizing Data Max coil load ...................................................... 6.9 MBH Load occurs at ................................................. Des Htg Coil CFM at Des Htg........................................ 1061 CFM BTU/(hr-ft-) .............................................................. 15.0 Max coil CFM.................................................. 1061 CFM Ent. DB / Lvg DB........................................... 69.0 / 75.0 OF Water flow @20.0•F drop ................................ NIA Supply Fan Sizing Data Actual max CFM.............................................. 1061 CFM Fan motor BHP ....................................................... 0.15 BHP Standard CFM................................................. 1060 CFM Fan motor kW ......................................................... 0.12 kW Actual max CFM/ft2........................................... 2.31 CFM/ft' Fan static................................................................ 0.50 in wg Outdoor Ventilation Air Data Design airflow CFM............................................. 43 CFM CFM/person.......................................................... 14.18 CFM/person CFM/ft'............................................................. 0.09 CFM/ft' `,,,���0 eL a r�q S eso6 `��� / \7840 o * u Program v4.91 I. Air System Sizing Summary for AHU-2 Project Name: 170093-ADG Port St. Lucie 09/15/2011 Prepared by: Beacon Consulting Engineers 10:33AN Air System Information Air System Name ......................................... AHU-2 Number of zones.......................................................... 1 Equipment Class .................................... SPLTAHU Floor Area........................................................... 1784.0 ft2 Air System Type .......................................... SZCAV Location .............................. West Palm Beach, Florida Sizing Calculation Information Calculation Months ................................ Jan to Dec Zone CFM Sizing .............. Sum of space airflow rates Sizing Data ............................................ Calculated Space CFM Sizing .......... Individual peak space loads Central Cooling Coil Sizing Data Total coil load ..................................................... 5.8 Tons Load occurs at ................................................. Jul 1500 Total coil load ..................................................: 69.6 MBH CA DB / WB.................................................. 91.0 / 78.0 OF Sensible coil load ............................................. 57.8 MBH Entering DB / WB.......................................... 77.5 / 63.9 OF Coil CFM at Jul 1500....................................... 2381 CFM Leaving DB / WB........................................... 55.0 / 53.7 OF Max block CFM............................................... 2381 CFM Coil ADP................................................................. 62.5 OF Sum of peak zone CFM................................... 2381 CFM Bypass Factor ....................................................... 0.100 Sensible heat ratio .......................................... 0.830 Resulting RH.............................................................. 46 % ft2fron............................................................. 307.4 Design supply temp . ................................................ 63.0 OF BTU/(hr-ft2)....................................................... 39.0 Zone T-stat Check ................................................ 1 of 1 OK Water flow @ 10.0 OF rise .................................. NIA Max zone temperature deviation ............................... 0.0 OF Central Heating Coil Sizing Data Max coil load .................................................... 22.4 MBH Load occurs at ................................................. Des Htg Coil CFM at Des Htg........................................ 2381 CFM BTU/(hr-ft2).............................................................. 12.5 ' Max coil CFM.................................................. 2381 CFM Ent. DB / Lvg DB........................................... 67.6 / 76.4 OF Water flow @ 20.0 OF drop ................................ NIA Supply Fan Sizing Data Actual max CFM.............................................. 2381 CFM Fan motor BHP Standard CFM................................................. 2379 CFM Fan motor kW Actual max CFM/ft2........................................... 1.33 CFM/ft' Fan static ....... Outdoor Ventilation Air Data Design airflow CFM........................................... 206 CFM CFM/person ... CFM1ft2............................................................. 0.12 CFM/ft2 ...... 0.33 BHP ...... 0.26 kW ...... 0.60 in wg 9.35 CFM/person Hourly Analysis Program v4.91 Page 1 of 1 " Air System Sizing Summary for AHU-3 Project Name: 170093-ADG Port St. Lucie 09/15/201 i Prepared by: Beacon Consulting Engineers 10:33AN Air System Information Air System Name ......................................... AHU-3 Equipment Class .................................... SPILT AHU Air System Type .......................................... SZCAV Sizing Calculation Information Calculation Months ................................ Jan to Dec Sizing Data ............................................ Calculated Central Cooling Coil Sizing Data Number of zones.......................................................... 1 Floor Area............................................................. 144.0 ft Location .............................. West Palm Beach, Florida Zone CFM Sizing .............. Sum of space airflow rates Space CFM Sizing .......... Individual peak space toads Total coil load ..................................................... 3.7 Tons Load occurs at ................................................. Jul 1400 Total coil load ................................................... 43.9 MBH OA DB / WB.................................................. 90.6 / 77.9 'F Sensible coil load ............................................. 43.5 MBH Entering IDS /WB.......................................... 76.7 / 61.7 °F Coil CFM at Jul 1400....................................... 1807 CFM Leaving DB / WB........................................... 64.4 / 63.0 °F Max block CFM............................................... 1807 CFM Coil ADP................................................................. 52.0 'F Sum of peak zone CFM................................... 1807 CFM Bypass Factor ....................................................... 0.100 Sensible heat ratio .......................................... 0.991 Resulting RH.............................................................. 42 % 112/Ton............................................................... 39.3 Design supply temp................................................. 53.0 °F BTU/(hr-ft�..................................................... 305.0 Zone T-stat Check ................................................ 1 of 1 OK Water flow @ 10.0 °F rise .................................. NIA Max zone temperature deviation ............................... 0.2 °F , Central Heating Coil Sizing Data Max coil load ...................................................... 0.7 MBH Load occurs at ................................................. Des Htg Coil CFM at Des Htg........................................ 1807 CFM BTU/(hr-ft2)................................................................ 4.9 Max coil CFM.................................................. 1807 CFM Ent. DB / Lvg DB........................................... 69.9 / 70.3 'F Water flow @ 20.0 °F drop ................................ NIA Supply Fan Sizing Data Actual max CFM.............................................. 1807 CFM Fan motor BHP ....................................................... 0.25 BHP Standard CFM................................................. 1806 CFM Fan motor kW ......................................................... 0.20 kW Actual max CFM/ft2......................................... 12.66 CFM/ft Fan static................................................................ 0.60 In wg Outdoor Ventilation Air Data Design airflow CFM............................................... 0 CFM CFM/person............................................................ 0.00 CFM/person CFM/ft2............................................................. 0.00 CFM/ft2 e `%%%%.VO L. D,q 'rfoo 0 0 401 o°• T� 145�2017�vc pRtN�v�ee 000�sr 10 .S�C?e� Hourly Analysis Program v4.91 Page 1 of 1