HomeMy WebLinkAboutLOAD AND ENERGY CALCULATIONSProject #: 170093
ADG Port St. Lucie
Port St. Lucie, FI
Load and Energy Calculations
09-15-2017
RECEIVED
OCT 0 2 2017
PERMITTING
St. Lucie County, FL
SCgNN'E�D
St to By
1711,
MECHANICAL, ELECTRICAL,
PLUMBING, FIRE PROTECTION,
& COMMISSIONING
www.beacon-eng.com 100 NE 6" St., Suite 102 Boynton Beach, FL 33435 Tel no: 561.424.3270
i" ;Florida Building. Code, Fifth Edition (2014) Energy Conservation
. i
EnergyGauge Summit@ Fla/Com-2015, Effective Date: June 30, 2015
ASHRAE 90.1-2010 - Energy Cost Budget Option
Check List
Applications for compliance with the Florida Building Code, Energy Conservation shall
include:
[�Y This Checklist
dAn Input report generated from the software just after completing compliance
calculations without any further changes
The full compliance report generated by the software that contains the project
" summary, complaince summary, certifications and detailed component compliance
reports
Boxes appropriately checked in the Miscellanous report generated by the software at
the end of the compliance report
EnergyGauge Summit® Fla1Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
9/15/2017 Page 1 of 14
PROJECT SUMMARY
Short Desc: 170093 ADG PSL Description: ..........
Owner: ............
Addressl: Port St. Lucie City: Port St. Lucie
Addressl: State: FL
Zip: 0
Type: Office Class: Renovation to existing
Jurisdiction: PORT ST. JOE, GULF COUNTY, FL (331100)
Conditioned Area: 2387 SF Conditioned & UnConditioned Area: 2387 SF
No of Stories: 1 Area entered from Plans 2387 SF
Permit No: 0 Max Tonnage 7
If different, write in:
Component Design Criteria Result
Gross Energy Cost (in $) 833.0 1,287.0 PASSED
LIGHTING CONTROLS
EXTERNAL LIGHTING
HVAC SYSTEM
PLANT
WATER HEATING SYSTEMS
PIPING SYSTEMS
Met all required compliance from Check List?
PASSES
No Entry
PASSES
No Entry
PASSES
PASSES
Yes/No/NA
IMPORTANT MESSAGE
Info 5009 -- — — An input report of this design building must be submitted along with this
EnergyGauge Summit@ Fla/Com-2014. TAM 20%1.0 Compliant Software. Effective Date: June 30, 2015
9/15/2017 Page 2 of 14
a
CERTIFICATIONS
,ttoe¢ruou®eetee
,`%%%��
m
I hereby certify that the ns and edifi tiq ep d by this calculation are in compliance with the
Florida Energy Code ;
• * m
Prep m : An elo L da ilva : m Building Official:
e '•. C n „ O''. '�� Date:
���is/oNAI Eoae°%
I certify that this building is in cdtuegi✓i{h the Florida Energy Efficiency Code
Owner Agent: Date:
If Required by Florida law, I hereby certify (') that the system design is in compliance with the Florida
Energy Efficiency Code
Architect: Reg No:
Electrical Designer: Joeven M. Vatenzuela Reg No: 60287
Lighting Designer: Joeven M. Valenzuela Reg No: 60287
Mechanical Designer: Angelo L da Silva Reg No: 78400
Plumbing Designer: Angelo L da Silva Reg No: 78400
(*) Signature is required where Florida Law requires design to be performed by registered design
professionals. Typed names and registration numbers may be used where all relevant information is
contained on signed/sealed plans.
EnergyGauge Summiit@ Fla/Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
9/15/2017 Page 3 of 14
Project: 170093_ADG PSL
Title:..........
Type: Office
Building End Uses
1) Proposed
2) Baseline
Total
54.80
83.80
$834
$1,287
ELECTRICITY(MBtulkWhl$)
54.80
83.80
16064
24563
$834
$1,287
AREA LIGHTS
13.80
30.10
4041
8817
$210
$462
MISC EQUIPMT
33.90
33.90
9943
9943
$516
$521
PUMPS & MISC
0.10
0.00
32
7
$2
$0
SPACE COOL
3.10
7.90
909
2307
$47
$121
SPACE HEAT
0.50
0.10
149
18
$8
$1
VENT FANS
3.40
11.80
990
3471
$51
$182
Credits Applied: None
PASSES
Passing Criteria =1287
Design (including any credits) = 834
Passing requires Proposed Building cost to be at most 100% of
Baseline cost. This Proposed Building is at 64.8%
EnergyGauge Summit® Fla1Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
9/15/2017 Page 4 of 14
External Lighting Compliance
Description
Category Tradable? Allowance Area or Length ELPA CLP
(W/Unit) or No. of Units (W) (VV)
(Sgft or it)
None
Project: 170093_ADG PSL
Title: ..... _...
Type: Office
(WEA File: TALLAHASSEEXAM
Lighting Controls Compliance
Acronym
Ashrae Description Area Design Min Compli-
to (sq.ft) CT CP once
light
.light
light
10,004 Exam/heatment (Hospital) 459 2 1 PASSES
17 Office - Enclosed 1,784 1 1 PASSES
1 Electrical Mechanical Equipment 144 1 1 PASSES
Room - General
PASSES
EnergyGauge Summit® FlaICom-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
9/15/2017 Page 5 of 14
Project: 170093_ADG PSL
Title:..........
Type: office
(WEA File: TALLAHASSEE.TMY)
System Report Compliance
AHUI System 1
Constant Volume Air Cooled No. of Units
Split System < 65000 Btu/hr
1
Component
Category
Capacity
Design Eff Design IPLV
Comp-
Eff Criteria IPLV Criteria
liance
Cooling System
Air Conditioners Air Cooled
28900
13.00 13.00 12.50
PASSES
Split System < 65000 Btu/h
Cooling Capacity
Heating System
Electric Furnace
17060
1.00 1.00
PASSES
Air Handling -
Air -Handler (Supply) - -
1000
- 0.30 0.82
PASSES
System -Supply
Constant Volume
Ai3U2 System 2
Constant Volume Packaged No. of Units
System-902
1
Component
Category
Capacity
Design BIT Design IPLV
Comp-
Eff Criteria IPLV Criteria
liance
Cooling System
Air Conditioners Air Cooled
83700
11.50 11.20 12.50 11.40
PASSES
65000 to 135000 Btu/h
Cooling Capacity
Heating System
Electric Furnace
25590
1.00 1.00
PASSES
Air Handling
Air Handler (Supply) -
2400
0.30 0.82
PASSES
System -Supply
Constant Volume
AHU3 System 1
Constant Volume Air Cooled No. of Units
Split System < 65000 Btu/hr
1
Component
Category
Capacity
Design Eff Design IPLV
Comp-
Eff Criteria IPLV Criteria
liance
Cooling System
Air Conditioners Air Cooled
52400
13.00 13.00 12.50
PASSES
Split System <65000 Btu/h
Cooling Capacity
Heating System
Electric Furnace
34120
1.00 1.00
PASSES
Air Handling
Air Handler (Supply) -
2200
0.30 0.82
PASSES
System -Supply
Constant Volume
PASSES
EnergyGauge Summit0 Fla/Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
9/15/2017 Page 6 of 14
Plant Compliance
Description Installed Size Design Min Design Min Category Comp
No Eff Eff IPLV IPLV !lance
None
Project: 170093_ADG PSL
Title:.......... _
-
- -
Type: Office
(WEA File: TALLAHASSEE.TMY)
Water Heater Compliance
D
Description Type
Design Mn
Category
Design Max Comp
Eff Eff
Loss Loss liance
Water Heater 1 Electric water heater <= 12 [kW] 0.94 0.93
PASSES
PASSES
Project: 170093_ADG PSL
Title:..........
Type: Office
(WEA File: TALLAHASSEE.TM])
Piping System Compliance
Category
Pipe Din Is Operating Ins Cond
Ins Req Ins Compliance
[inches] Runout? Temp [Btu-in/hr Thick [in] Thick [in]
[F] SF.F1
Domestic and Service Hot Water
0.25 False 110.00 0.28
1.00 0.50 PASSES
Systems
PASSES
EnergyGauge Summit@ FIalCom-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
9/15/2017 Page 7 of 14
Project Name: 170093 ADG PSL
Project Title: ..........
Address: Port St. Lucie
State: FL
Zip: 0
Owner: ----.
EnergyGauge Summit® v5.20
INPUT DATA REPORT
Proiect Information
Orientation: ,North
Building Type: Office
Building Classification: Renovation to existing building
No.of Stories: I
GrossArea: 2387 SF
Zones
No
Acronym
Description
Type
Area
Multiplier
Total Area
lsfl
lS11
1
AHU1
Zone 1
CONDITIONED
459.0
1
459.0
❑
2
AHU2
Zone 1
CONDITIONED
1784.0
1
1784.0
❑
3
AHU3
Zone 1
CONDITIONED
144.0
1
144.0
❑
9/15/2017 EnergyGauge Summit® v5.20 1
Spaces
No Acronym
Description
Type
Depth
Width
Height
Multi Total Area Total Volume
[ft]
[ft]
[ft]
plier [sf]
[cf]
In Zone: AHU1
1 light
ZOOSpI
Exam/freatment(Hospital) 1.00
459.00
10.00
1 459.0
4590.0
❑
In Zone: AHU2
1 light
ZOOSpI
Office - Enclosed
1.00
1784.00
10.00
1 1784.0
17840.0
In Zone: AHU3
1 light
ZOOSpI
Electrical Mechanical
1.00
144.00
10.00
1 144.0
1440.0
El
Equipment Room - General
Lighting
No
Type
Category
No. of
Watts per
Power
Control Type
No.of
Luminaires
Luminaire
[W]
Ctrl pts
In Zone: AHUI
In Space: light
1
LED
General Lighting
6
31
188
Manual On/Off
1
❑
2
LED
General Lighting
4
17
68
Occupancy sensor without
1
❑
Daylighting
In Zone: AHU2
In Space: light
1
LED
General Lighting
59
17
1003
Occupancy sensor without
1
❑
Daylighting
In Zone: AHU3
In Space: light
1
LED
General Lighting
2
30
60
Occupancy sensor without
1
❑
Daylighting
9/15/2017 EnergyGauge Summit® v5.20
Walls
No Description Type
Width H (Effec) Multi Area
Ift] [ft] plier Isl]
Orientation Conductance
[Btu/hr. sf. F]
Heat Dens. R-Value
Capacity [lb/cf] [h.sGF/Btu]
[Btu/sf.F]
In Zone:
Windows
No Description Orientation
Shaded U SHGC
[Bta/hr sf F]
Vis.Tra
W H (Effec) Multi Total Area
Ift] [ft] plier [sfJ
In Zone:
In Wall:
Doors
No Description Type
Shaded? Width H (Effec) Multi
Ift] Ift] plier
Area
[sf]
Cond. Dens. Heat Cap. R-Value
[Btu/hr. sL F] Ilb/cf] [Btu/sG F] [h.sf.FBtu]
In Zone:
In Wall:
Roofs
No Description Type
Width H (Effec) Multi
Ift] Ift] plier
Area
Isf]
Tilt
[deg]
Cond.
[Btu/hr. SE F]
Heat Cap Dens. R-Value
[Btu/sf. F] Ilb/cl] [h.sf.F/Btu]
In Zone:
El
9/15/2017 EnergyGauge Summit® v5.20
Skylights
No Description Type
U SHGC Vis.Trans W H (Effec) Multiplier Area Total Area
[Btu/hr sf F] IN IN [Sf] [S11
In Zone:
LIn Roof:
Floors
No Description Type
Width H (Effec) Multi Area Cond. Heat Cap. Dens. R-Value
[it] [ft] plier [sf] [Btu/hr. sE F] [Btu/sE F] [lb/cf] [h.sEFBtu]
In Zone:
Systems
AHU1
System I
Constant Volume Air Cooled Split No. Of Units 1
System < 65000 Btu/hr
Component
Category
Capacity Efficiency H'LV
1
2
3
Cooling System
Heating System
Air Handling System -Supply
28900.00 13.00 12.50
17060.00 1.00
1000.00 0.30
El
AHU2
System 2
Constant Volume Packaged No. Of Units 1
System-902
Component
Category
Capacity Efficiency H'LV
I
2
3
Cooling System
Heating System
Air Handling System -Supply
83700.00 11.50 12.50
25590.00 1.00
2400.00 0.30
El
9/15/2017 EnergyGauge Summit® v5.20
AE1U3 System 1
Constant Volume Air Cooled Split No. Of Units 1
System < 65000 Btu/hr
Component Category
Capacity Efficiency IPLV
1 Cooling System
2 Heating System
3 Air Handling System -Supply
52400.00 13.00 12.50
34120.00 1.00
2200.00 0.30
❑
❑
❑
Plant
Equipment
Category Size Inst.No Eff. IFLV
Water Heaters
W-Heater Description
CapacitlCap.Unit I/P Rt. Efficiency Loss
1 Electric water heater
30 [Gal] 5 [kW] 0.9400 [Eff [Btu/h]
❑
EA -Lighting
Description Category No. of Watts per Area/Len/No. of units
Luminaires Luminaire [sf/ft/No]
Control Type
Wattage
[W]
Piping
No Type Operating Insulation
Temperature Conductivity
[F] [ Btu-in/h.sLF]
Nomonal pipe
Diameter
[in]
Insulation
Thickness
[in]
Is Runout?
1 Domestic and Service Hot Water Systems 110.00 0.28
0.25
1.00
No ❑
9/15/2017 EnergyGauge Summit® v5.20
Fenestration Used
Name Glass Type No. of Glass SHGC
Panes Conductance
[Btu/h.sLF]
VLT
7
Materials Used
Mat No Acronym Description Only R-Value RValue Thickness
Used [h.sf.F/Btu] [ft]
Conductivity
[Btu/h.ft.F]
Density
[lb/cf]
SpecificHeat
[Btu/ib.F]
Constructs Used
No Name Simple Massless Conductance Heat Capacity
Construct Construct [Btu/h.sGF] [Btu/sLF]
Density
[ib/cf]
RValue
[h.sGF/Btu]
Layer Material Material Thickness
No. [ft]
Framing
Factor
El
9/15/2017 EnergyGauge Summit® v5.20
Air System Sizing Summary for AHU-1
Project Name: 170093-ADG Port St. Lucie 09/15/2011
Prepared by: Beacon Consulting Engineers 10:21AN
Air System information
Air System Name ......................................... AHU-1
Equipment Class .................................... SPILT AHU
Air System Type .......................................... SZCAV
Sizing Calculation Information
Calculation Months ................................ Jan to Dec
Sizing Data ............................................ Calculated
Central Cooling Coil Sizing Data
Number of zones.......................................................... 1
Floor Area............................................................. 459.0 ft'
Location .............................. West Palm Beach, Florida
Zone CFM Sizing .............. Sum of space airflow rates
Space CFM Sizing .......... Individual peak space loads
Total coil load .....................................................
2.4
Tons
Load occurs at .................................................
Jul 1400
Total coil load ...................................................
28.4
MBH
OA DB / WB..................................................
90.6 / 77.9
OF
Sensible coil load .............................................
26.1
MBH
Entering DB / WB..........................................
76.7162.1
OF
Coil CFM at Jul 1400.......................................
1061
CFM
Leaving DB / WB...........................................
63.9 / 62.5
OF
Max block CFM...............................................
1061
CFM
Coll ADP.................................................................
51.4
OF
Sum of peak zone CFM...................................
1061
CFM
Bypass Factor .......................................................
0.100
Sensible heat ratio ..........................................
0.919
Resulting RH..............................................................
43
%
ft'/Ton.............................................................
194.1
Design supply temp.................................................
53.0
OF
BTU/(hr-ft-) .......................................................
61.8
Zone T-stat Check ................................................
1 of 1
OK
Water flow @ 10.0 OF rise ..................................
NIA
Max zone temperature deviation ...............................
0.0
OF
. Central Heating Coil Sizing Data
Max coil load ......................................................
6.9 MBH
Load occurs at .................................................
Des Htg
Coil CFM at Des Htg........................................
1061 CFM
BTU/(hr-ft-) ..............................................................
15.0
Max coil CFM..................................................
1061 CFM
Ent. DB / Lvg DB...........................................
69.0 / 75.0 OF
Water flow @20.0•F drop ................................
NIA
Supply Fan Sizing Data
Actual max CFM..............................................
1061
CFM
Fan motor BHP .......................................................
0.15
BHP
Standard CFM.................................................
1060
CFM
Fan motor kW .........................................................
0.12
kW
Actual max CFM/ft2...........................................
2.31
CFM/ft'
Fan static................................................................
0.50
in wg
Outdoor Ventilation Air Data
Design airflow CFM.............................................
43
CFM
CFM/person..........................................................
14.18
CFM/person
CFM/ft'.............................................................
0.09
CFM/ft'
`,,,���0 eL a r�q S eso6
`��� / \7840 o
* u
Program v4.91
I. Air System Sizing Summary for AHU-2
Project Name: 170093-ADG Port St. Lucie 09/15/2011
Prepared by: Beacon Consulting Engineers 10:33AN
Air System Information
Air System Name .........................................
AHU-2
Number of zones..........................................................
1
Equipment Class ....................................
SPLTAHU
Floor Area...........................................................
1784.0 ft2
Air System Type ..........................................
SZCAV
Location ..............................
West Palm Beach, Florida
Sizing Calculation Information
Calculation Months ................................
Jan to Dec
Zone CFM Sizing ..............
Sum of space airflow rates
Sizing Data ............................................
Calculated
Space CFM Sizing ..........
Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load .....................................................
5.8
Tons
Load occurs at .................................................
Jul 1500
Total coil load ..................................................:
69.6
MBH
CA DB / WB..................................................
91.0 / 78.0
OF
Sensible coil load .............................................
57.8
MBH
Entering DB / WB..........................................
77.5 / 63.9
OF
Coil CFM at Jul 1500.......................................
2381
CFM
Leaving DB / WB...........................................
55.0 / 53.7
OF
Max block CFM...............................................
2381
CFM
Coil ADP.................................................................
62.5
OF
Sum of peak zone CFM...................................
2381
CFM
Bypass Factor .......................................................
0.100
Sensible heat ratio ..........................................
0.830
Resulting RH..............................................................
46
%
ft2fron.............................................................
307.4
Design supply temp . ................................................
63.0
OF
BTU/(hr-ft2).......................................................
39.0
Zone T-stat Check ................................................
1 of 1
OK
Water flow @ 10.0 OF rise ..................................
NIA
Max zone temperature deviation ...............................
0.0
OF
Central Heating Coil Sizing Data
Max coil load ....................................................
22.4
MBH
Load occurs at .................................................
Des Htg
Coil CFM at Des Htg........................................
2381
CFM
BTU/(hr-ft2)..............................................................
12.5
' Max coil CFM..................................................
2381
CFM
Ent. DB / Lvg DB...........................................
67.6 / 76.4
OF
Water flow @ 20.0 OF drop ................................
NIA
Supply Fan Sizing Data
Actual max CFM..............................................
2381
CFM
Fan motor BHP
Standard CFM.................................................
2379
CFM
Fan motor kW
Actual max CFM/ft2...........................................
1.33
CFM/ft'
Fan static .......
Outdoor Ventilation Air Data
Design airflow CFM...........................................
206
CFM
CFM/person ...
CFM1ft2.............................................................
0.12
CFM/ft2
...... 0.33 BHP
...... 0.26 kW
...... 0.60 in wg
9.35 CFM/person
Hourly Analysis Program v4.91 Page 1 of 1
" Air System Sizing Summary for AHU-3
Project Name: 170093-ADG Port St. Lucie 09/15/201 i
Prepared by: Beacon Consulting Engineers 10:33AN
Air System Information
Air System Name ......................................... AHU-3
Equipment Class .................................... SPILT AHU
Air System Type .......................................... SZCAV
Sizing Calculation Information
Calculation Months ................................ Jan to Dec
Sizing Data ............................................ Calculated
Central Cooling Coil Sizing Data
Number of zones.......................................................... 1
Floor Area............................................................. 144.0 ft
Location .............................. West Palm Beach, Florida
Zone CFM Sizing .............. Sum of space airflow rates
Space CFM Sizing .......... Individual peak space toads
Total coil load .....................................................
3.7
Tons
Load occurs at .................................................
Jul 1400
Total coil load ...................................................
43.9
MBH
OA DB / WB..................................................
90.6 / 77.9
'F
Sensible coil load .............................................
43.5
MBH
Entering IDS /WB..........................................
76.7 / 61.7
°F
Coil CFM at Jul 1400.......................................
1807
CFM
Leaving DB / WB...........................................
64.4 / 63.0
°F
Max block CFM...............................................
1807
CFM
Coil ADP.................................................................
52.0
'F
Sum of peak zone CFM...................................
1807
CFM
Bypass Factor .......................................................
0.100
Sensible heat ratio ..........................................
0.991
Resulting RH..............................................................
42
%
112/Ton...............................................................
39.3
Design supply temp.................................................
53.0
°F
BTU/(hr-ft�.....................................................
305.0
Zone T-stat Check ................................................
1 of 1
OK
Water flow @ 10.0 °F rise ..................................
NIA
Max zone temperature deviation ...............................
0.2
°F
, Central Heating Coil Sizing Data
Max coil load ......................................................
0.7 MBH
Load occurs at .................................................
Des Htg
Coil CFM at Des Htg........................................
1807 CFM
BTU/(hr-ft2)................................................................
4.9
Max coil CFM..................................................
1807 CFM
Ent. DB / Lvg DB...........................................
69.9 / 70.3 'F
Water flow @ 20.0 °F drop ................................
NIA
Supply Fan Sizing Data
Actual max CFM..............................................
1807
CFM
Fan motor BHP .......................................................
0.25
BHP
Standard CFM.................................................
1806
CFM
Fan motor kW .........................................................
0.20
kW
Actual max CFM/ft2.........................................
12.66
CFM/ft
Fan static................................................................
0.60
In wg
Outdoor Ventilation Air Data
Design airflow CFM...............................................
0
CFM
CFM/person............................................................
0.00
CFM/person
CFM/ft2.............................................................
0.00
CFM/ft2
e
`%%%%.VO L. D,q 'rfoo
0
0 401
o°• T� 145�2017�vc
pRtN�v�ee
000�sr 10 .S�C?e�
Hourly Analysis Program v4.91 Page 1 of 1