Building Inspector
St Lucie County Building Department
121 SW Port St Lucie Blvd
Port St Lucie, FL 34984
Re:1709-0462 7041 US Hwy 1, Port St. Lucie
SCANNED
BY
5t. Lucie County
The purpose of this letter is to describe the method of attachment of the new exterior wall masonry at the rear
of the tenant space to the existing masonry construction.
The new masonry is doweled into the existing masonry with #5 dowels, 12" long at 24" o.c. vertically and
horizontally. Embed is 6" each side. Each side has filled cells. This is in lieu of the masonry ties as shown
on the drawings.
If you should have any questions or concerns, please do not hesitate to contact me.
Chris Hair —Architect
;C.O. HAIR AR ITECT:
' AR96136
r U -
-NOV 2 1 2017
SCANNED
BY
BY: 8461 Lake Worth Road Suite 159 Luciee
Lake Worth, FL 33467 St County
(561) 209.6050
AR-96135
Narrative
DATE: 11.17.17 COMM: 17-015
TO: St Lucie County RE: Permit revisions
FROM: Chris Hair- Architect ADG MRI
CC: Kevin Johnson F
1709-0462
Please see below responses to the permit comments. The revisions are marked as Revision no.
01 and dated 11.17.17
Zoning- Galbraith:
1. Comment: Resolution 07-293 for St Lucie Oaks Commercial indicate a 4,613 sf
restaurant. To be able to change the use to a medical center the resolution will need
to be changed. Please contact planning Dept for information about a major
adjustment to the existing PNRD which requires a Board of County Commissioners
approval.
Response: An amendment to the PNRD has been completed.
r
Building- Ed Roseberrv:
Comment: Please show FBC accessibility for all counter heights, including Break
Room and Examination Treatment areas.
Response: The door leading into the MR Exam room has been changed to
swing outwards. Please see revised sheet A210. Note, the door does not have
a combination of a closer and a latch. The counter heights for all of the
counter heights including the Break Room were originally shown on sheet
A320 of the permit set Note: The Break room sink cabinet doors have an
integral kick which allows front access with the required knee clearance. Refer
to cabinet section 04 on Sheet A320 on the originally submitted permit set
2. Comment: Please submit one corrected digital plan on CD and triplicate corrected
plan sheets.
Response: Noted, will comply.
END OF NARRATIVE
9 Page 2
MECHANICAL. ELECTRICAL,
P L U M B I N G, FIRE PROTECTION.
& COMMISSIONING
November 17, 2017
Planning & Development Services Building & Code Regulation Division
Fort Pierce, FL 34982
Project Name: Advanced Diagnostic Group
Project Address: 7041 S Us hwy 1.
Port St Lucie, FL.
Permit #: 1709-0462
Subject: Response to comments issued by Building Department
Bold print refers to response to Department Comments
Italic print refers to Department Comments
Mechanical
Plans Examiner: Carl Peterson
Date of Comments: 10/26/17
1. Comment:
Please show that air handler units are not in what is considered attic
space in accordance with 403.2.7.6 of the 2014 Florida Energy Code.
Response:
Refer to added note on sheet M-1 for clarity. The AHUs are not
located on what is considered attic space in accordance with
403.2.7.6 of the 2014 Florida Energy Code.
1
www.beacon-eng.com 625 Casa Loma Blvd. Suite 106 Boynton Beach, FL 33435
Tel no: 561.424.3270
L
MECHANICAL, ELECTRICAL,
PLUMBING, FIRE PROTECTION,
& C O M M I S S I O N I N G
2. Comment:
Please remove all references to the international codes and please
reference the Florida Building Codes on page M3.1 per 101.4 of the
2014 Florida Building Code.
Response:
Refer to revised sheet M-3 for corrections.
3. Comment:
Please submit a Commissioning Plan per Florida Building Code Energy
Section C408.2.1.
Response:
Refer to revised sheet M1.1 for added Commissioning Notes and
the Chiller Installation Checklist.
END OF RESPONSES
If you have any further questions, or if we can be of any further assistance,
please do not hesitate to call.
Sincerely,
Angelo L. da Silva, P.E., Senior Project Manager