HomeMy WebLinkAboutENERGY EFFICIENCY CODEENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION
Florida Department of Community Affairs
EnergyGaugeFlaCom v1.22 FORM 40OB-2001
Component Performance Method for Commercial Buildings
Jurisdiction: DADE COUNTY, DADE COUNTY, FL (231000)
' Short Dese:
IVDS005702
Owner:
MOD SPACE
Address:
UNKNOWN
UNKNOWN
City:
UNKNOWN
State:
FLORIDA
Tap:
0
Project: 'C` NS AND ALL PROPOSFD WORK
ARE SWIECT TO A N (,CT,1FCTIONS
SCANNED REOL4RED CY FII;LO INSr)EC'rUrls "rHAT
BY AWAY dE NECESSARY IN ORDEA TO
St. Lucie Countyer,nitNo: 0--CpNp6Y Wl1' "AppWQAGLE CODES. '
Storeys: Ps
Type: Office (Business) GrossArea: 2016
Class: New Finished building Net Area: 2016
Max Tonnage: 3 (if different, write in)
Compliance Summary
Component
Design Criteria
Result
ENVELOPE
7.38 62.49
PASSES
Other Envelope Requirements - B
ST. LUCIE COUNTY
PASSES
LIGHTING POWER
REVIEW
PLAINNR1.32 403.20
PASSESEVI
LIGHTING
LIGHTING CONTROLS
PASSES
EXTERNAL LIGHTING
BLDG:
PASSES
HVAC SYSTEM
DATE: :2b /17
PASSES
PLANT
ELEC:
DATE:
PASSES
WATER HEATING SYSTEMS
PASSES
PASSES
PIPING SYSTEMS
DATE: ��
PASSES
Met all required compliance from Check LiWCH:
Yes/No/NA
DATE:
IMPORTANT NOTE. An input report Print -Out from Energy Gauge FlaCom of
this design building must be submitted along with this Compliance Report
CONCEALED FASTENERS OR ATTACHMENTS
_.AREVERESPONSISILIT`IOfTHE
CONTR.ACTOROFRECORD
LJ�P
8/24/2017
EnergyGauge FlaCom FLCCSB v1.22
r
1
COMPLIANCE CERTIFICATION:
I hereby certify that the plans and
Review of the plans and specifications covered by this
specifications covered by this calculation are
calculation indicates compliance with the Florida Energy
in compliance with the Florida Energy
Code. Before construction is completed, this building will be
Efficiency Code.
inspected for compliance in accordance with Section
553.908, F.S.
PREP D
BUILDING OFFICIAL:
DA 2 ! ,
DATE:
I here thatIthisildi is incompliance
with the Florida Enn Code.
OWNER AGENT
DATE:
If required by Florida law, I hereby certify (`)
that the system design is in
compliance with the Florida Energy Code.
REGISTRATION
No.
ARCHITECT:
APMOSO
ELECTRICAL SYSTEM DESIGNER:
LIGHTING SYSTEM DESIGNER:
MECHANICAL SYSTEM DESIGNER:
PLUMBING SYSTEM DESIGNER:
(`) Signature is required where Florida Law requires design to be performed by registered design professionals.
Typed names and registration numbers may be used where all relevant information is contained on signed/sealed
tans.
Project: MDS005702
Title: MOD SPACE
Type: Office (Business)
Location: DADE COUNTY, DADE COUNTY, FL (231000)
(WEA File: Miami.tmy)
Envelope Compliance
Design Load Criteria
Zone Heating
Cooling Heating Cooling
OFFICE AREA (CONDITIONED) -1.02
16.36 -12.03 50.46
Total Loads: Desien=17.375 Criteria=62.488
1 PASSES
4 X�
8/24/2017 EnergyGauge FlaCom FLCCSB v1.22
Project: MDS005702
Title: MOD SPACE
Type: Office (Business)
Location: DADE COUNTY, DADE COUNTY, FL (231000)
(WEA File: Miami.tmy)
Other Envelope Requirements
Item Zone Description
Design Limit Meet Req.
OFFICE ARE % Skylight - Max % Limit
0.00 4.30 Yes
OFFICE ARE OFFICE ARE Exterior Roof - Max Uo Limit
0.05 0.08 Yes
Meets Other Envelope Requirements
External Lighting Compliance
Description Category Allowance Area or Length ELPA CLP
(W/Unit) or No. of Units (W) (W)
(Sgft or ft)
None
Project: MDS005702
Title: MOD SPACE
Type: Office (Business)
Location: DARE COUNTY, DADE COUNTY, FL (231000)
(WEAFile: Miami.tmy)
Lighting Power Compliance
Space Ashrae Description
Area Height No. of AF
Design Effective Allowance
ID
(sq.ft) (ft) Spaces
(VV) (VV) (Vt)
OFFICE 0 Unclassified
2,016 8.0 1 1.00
88 61 403
ADRA
Design 87.6 (W)
PASSES
Effective: 61.32 (W)
Allowance: 403.2 (W)
i
8/24/2017 EnergyGauge FlaCom FLCCSB v1.22 3
Project: M 8005702
Title: MOD SPACE
Type: Office (Business)
Location: DADE COUNTY, DADE COUNTY, FL (231000)
(WEA File: Miami.tmy)
Lighting Controls Compliance
Acronym Ashrae Description
Area No. of Design Min Compli-
ID
(sq.ft) Tasks CP CP ance
OFFICE AREA 0 Unclassified
2,016 30 70 31 PASSES
PASSES
Project: MDS005702
Title: MOD SPACE
Type: Office (Business)
Location: DADE COUNTY, DADE COUNTY, FL (231000)
(WEA File: Miami.tmy)
System Report Compliance
Prosyl System 1
Packaged Terminal Systems No. of Units
1
Component Category Capacity
Design Eff Design IPLV Comp-
Eff Criteria IPLV Criteria liance
Coaling System PTAC > 15000 Btu/h
10.00 7.60 PASSES
(Cooling Mode)
Heating System Electric Furnace
1.00 1.00 PASSES
Air Handling Air Handler (Supply) -
0.80 0.80 PASSES
System -Supply Constant Volume
PASSES
Plant Compliance
Description Installed Size Design Min
Design Min Category Comp
No Eff Eff
IPLV D?LV liance
None
8/24/2017 EnergyGauge FlaCom FLCCSB v1.22
Water Heater Compliance
Description Type Category Design
Eff
Min Design Max Comp
Eff Loss Loss liance
None
Piping System Compliance
Category
Pipe Dia Is Operating Ins Cond Ins Req Ins
Compliance
[inches] Runout? Temp [Btu-in/hr Thick [in] Thick [in]
[F] SF.F]
None
Project: MDS005702
Title: MOD SPACE
Type: Office (Business)
Location: DADE COUNTY, DADE COUNTY, F
Other Required Compliance
Category
Section
Requirement (write N/A in box if not applicable)
Check
Infiltration
406.1
Infiltration Criteria have been met
❑V
System
407.1
HVAC Load sizing has been performed
E
Ventilation
409.1
Ventilation criteria have been met
ADS
410.1
Duct sizing and Design have been performed
T & B
410.1
Testing and Balancing will be performed
0
Electrical
413.1
Metering criteria have been met
0
Motors
414.1
Motor efficiency criteria have been met
13
Lighting
415.1
Lighting criteria have been met
El
O & M
102.1
Operationtmaintenance manual will be provided to owner
Roof/Cell
404.1
R-19 for Roof Deck with supply plenums beneath it
Report
101
Input Report Print -Out from EnergyGauge FlaCom attached?
8/24/2017 EnergyGauge FlaCom FLCC v .