TESTING, ADJUSTING & BALANCING REPORT
for
STAN WEEKS & ASSOCIATES
EDWARDS LA730.
G
BUILDINP�®Q✓
June 24, 2019
+++ ALL BALANCING WORK PERFORMED IN ACCORDANCE WITH NCI STANDARDS AND PROCEDURES +++
Ct16�p'
BPI
Pro-Duct Services, 1915 Rio Vista Rd Fort Pierce, FL 34949
772.528.2076 pro-ductservicesJl@gmail.com
PRO -DUCT
SERVICES
BLOWER DOOR& DUCT LEAKAGETESTING
TESTING -ADJUSTING -BALANCING
Pro -Duct Services is a National Balancing Council (NBC) certified firm, through
the National Comfort Institute, NCI. The goal of the NBC certified technicians is to
work with the design professionals, building owners and other tradesmen to
achieve maximum system performance on all environmental systems.
Due to the complexity of today's HVAC systems and the unique demands of struc-
ture occupants, having a qualified, certified Testing -Adjusting -Balancing (TAB)
company balance these systems has now become more critical than it has ever
been. NBC certified firms are able to achieve total system balance better than
any other organization worldwide.
Worhing in partnership with the other trades involved in your project is hey to
overall project success. Pro -Duct Services will worn closely with all involved to en-
sure project schedules are met. By utilizing different pre -balance checklists with
the other trades, such as sheet metal, pipe fitters, HVAC and controls, project suc-
cess can be achieved more reliably and timely.
Utilizing NBC Procedural Standards is hey to achieving the design intent of today'
sophisticated buildings. Understanding systems, their installation, their service
maintenance requirements and procedures, and the manufacturer's start-up re-
port helps in achieving system total balance for today's structures. Our technical
testing and verification, coupled with repeat readings, ensure system functionality.
With Pro -Duct Services you can be sure that our testing and verification process
offers you the best value in the Testing, Adjusting, & Balancing industry.
C"I'*AV,
Pro-Duct Services, 1915 Rio Vista Rd, Fort Pierce, FL 34949
772.528.2076 pro-ductservices/1@gmaii.com
PRO=DUCT
SERVICES
BLOWERDOOR&DUCT LEAKAGETESTING
TESTING -ADJUSTING -BALANCING
TEST & BALANCE INSTRUMENTS
Evergreen Telemetry Capture Hood 151):
Range: 100-2500 CFM
Accuracy: +/- 3%
Calibration: May 17, 2019
Evergreen Telemetry Capture Hood 8D-14:
Range: 15-200 CFM
Accuracy: +/- 3%--
Calibration: May 29, 2019
Evergreen Pressure/Velocity/Flow Sensing Module —Model S-PVF-1:
Range: 1-2, 14-32 inches HG, 32° - 158* F
Accuracy: +/- 3%
Calibration: June 5, 2019
Evergreen Wrist Reporter WR-401
Pro -Duct Services Technician: Michael Faurot
Certified NCI Contractor/Supervisor/Technician
NCI Commercial Certification ID: 19-229-03
— Equipment re -calibration is performed as required by testing guidelines. —
Pro -Duct Services, 1915 Rio Vista Rd, Fort Pierce, FL 34949
772.528.2076 pro-ductservicesfl@gmarLcom
CUTIN
commencing 11"r Mancer
MICHAEL FAUROT
Has successfully completed the required training and passed
the written exam by the
Nallfln� couelorl IeMule, Im
to perform HUAC commercial system balancing up to 20 tons
according to NO practical standards and procedures.
Certified Since
,Lamfoh May 9, 2019
Certifled C as administered and recognized by
fdn�MPaN'im
\ l M15 r tartrnstltmrtu•rna Rob Falke, President
Pro -Duct Services, 1915 Rio Vista Rd, Fort Pierce, FL 34949
772.528.2076 pro-ductservicesj7@gmail.com
1-1D-(b-13
PRO -DUCT
SERVICES
BLOWERDOOR&DUCT LEAKAOETESTINO
TESTING -ADJUSTING -BALANCING
AIR OUTLET CHARACTERIZATION
for
STAN WEEKS & ASSOCIATES
Edwards Landing —BUILDING 13
3172 Morning Dew Lane, Fort Pierce, FL 34982
Description
Outlet
Number
type
file
Design
CFM
Pre Test
CFM
FINAL
CFM
Entrance
i
CD
8 x 4
30
53
27
Kitchen/Living Rm
2
CD
30 x 10
160
167
164
Bathroom
3
CD
8 x 4
15
30
32
Bedroom 1
4
CD
12 x 8
180
185
177
Bedroom 2 Vent 1
5
CD
10 x 10
125
102
119
Bedroom 2 Vent 2
6
CD
30 x 10
125
117
122
TOTAL
635
641
FAN DATA Panasonic Whispergreen Model FV-05-11USK1 Vent Fan
Mechanical components working as designed and match plan
COMMENTS requirements.
+++ALL BALANCING WORK PERFORMED INACCORDANCE WITH NCI STANDARDSAND PROCEDURES..
Pro -Duct Services, 1915 Rio Vista R4 Fort Pierce, FL 34949
772.528.2076 pro-ductservicesjf@gmail.com
n
PR0-0UCT
SERVICES
BLOWERDOOR&DUCTLEAKAGETESTING
TESTING -ADJUSTING -BALANCING
r
1-7)o0D_3
AIR OUTLET CHARACTERIZATION
for
STAN WEEKS & ASSOCIATES
Edwards Landing —BUILDING 13
3174 Morning Dew Lane, Fort Pierce, FL 34982
Description
Outlet
Number
Type
She
Design
CFM
Pre Test
CFM
FINAL
CFM
Entrance
1
CD
8 x 4
30
52
39
Kitchen/Living Rm
2
CD
10 x 10
160
170
163
Bathroom
3
CD
8 x 4
15
42
23
Bedroom 1
4
CD
12 x 8
180
130
176
Bedroom 2 Vent 1
5
CD
10 x 10
125
118
125
Bedroom 2 Vent 2
6
CD
30 x 10
125
109
116
TOTAL
635
642
FAN DATA Panasonic Whispergreen Model FV-05-11USK1 Vent Fan
Mechanical components working as designed and match plan
COMMENTS requirements.
+++ ALL BALANCING WORK PERFORMED IN ACCORDANCE WITH NCI STANDARDS AND PROCEDURES...
Pro -Duct Services, 1915 Rio Vista Rd, Fort Pierce, FL 34949
772.528.2076 pro-ductservicesfl@gmaii.com
)_T D -00-73
PRO -DUCT
SERVICES
BLOWERDOOR& DUCTLEAKAOETESTINO
TESTING -ADJUSTING -BALANCING
AIR OUTLET CHARACTERIZATION
for
STAN WEEKS & ASSOCIATES
Edwards Landing —BUILDING 13
3176 Morning Dew Lane, Fort Pierce, FL 34982
Description
Outlet
Number
Type
Size
Design
CFM
Pre Test
CFM
FINAL
CFM
Entrance
i
CD
8 x 4
30
35
31
Kitchen/Living Rm
2
CD
10 x 10
160
145
176
Bathroom
3
CD
8 x 4
15
40
20
Bedroom 1
4
CD
12 x 8
180
156
172
Bedroom 2 Vent 1
5
CD
10 x 10
125
120
125
Bedroom 2 Vent 2
6
CD
10 x 30
125
108
114
TOTAL
635
638
FAN DATA Panasonic Whispergreen Model FV-05-11USK1 Vent Fan
Mechanical components working as designed and match plan
COMMENTS I requirements.
+++ ALL BALANCING WORK PERFORMED IN ACCORDANCE WITH NCI STANDARDS AND PROCEDURES...
Pro -Duct Services, 1915 Rio Vista Rd, Fort Pierce, FL 34949
772.528.2076 pro-ductservicesfl@gmail.com
l� 0-c)-v73
PRO -DUCT
SERVICES
BLOWERDOOR&DUCTLEAKAOETESTINO
TESTING -ADJUSTING -BALANCING
AIR OUTLET CHARACTERIZATION
• for
STAN WEEKS & ASSOCIATES
Edwards Landing —BUILDING 13
3178 Morning Dew Lane, Fort Pierce, FL 34982
Description
outlet
Number
Type
She
Design
CFM
Pre Test
CFM
FINAL
CFM
Entrance
1
CD
8 x 4
30
32
39
Kitchen/Living Rm
2
CD
30 x 10
160
166
169
Bathroom
3
CD
8 x 4
15
41
27
Bedroom 1
4
CD
12 x 8
180
175
183
Bedroom 2 Vent 1
5
CD
10 x 10
125
92
118
Bedroom 2 Vent 2
6
CD
10 x 30
125
119
121
TOTAL
635
657
FAN DATA Panasonic Whispergreen Model FV-05-11USK1 Vent Fan
Mechanical components working as designed and match plan
COMMENTS I requirements.
... ALL BALANCING WORK PERFORMED IN ACCORDANCE WITH NCI STANDARDS AND PROCEDURES...
Pro -Duct Services, 1915 Rio Vista Rd, Fort Pierce, FL 34949
772.528.2076 pro-ductservicesJl@gmail.com
�T1;'i: D -6)073
PRO -DUCT
SERVICES
BLOWERDOOR&DUCT LEAKAGETESTING
TESTING -ADJUSTING -BALANCING
AIR OUTLET CHARACTERIZATION
for
STAN WEEKS & ASSOCIATES
Edwards Landing —BUILDING 13
3180 Morning Dew Lane, Fort Pierce, FL 34982
Desaiptlen
Outlet
Number
Type
file
Design
CFM
Pre Test
CFM
FINAL
CFM
Entrance
1
CD
8 x 4
30
41
36
Kitchen/Living Rm
2
CD
10 x 30
160
183
182
Bathroom
3
CD
8 x 4
15
43
26
Bedroom 1
4
CD
12 x 8
180
148
167
Bedroom 2 Vent 1
5
CD
30 x 10
125
117
118
Bedroom 2 Vent 2
6
CD
10 x 10
125
124
127
TOTAL
635
656
FAN DATA Panasonic Whispergreen Model FV-05-11USK1 Vent Fan
Mechanical components working as designed and match plan
COMMENTS requirements.
... ALL BALANCING WORK PERFORMED IN ACCORDANCE WITH NCI STANDARDS AND PROCEDURES..
Pro -Duct Services, 1915 Rio Vista Rit Fort Pierce, FL 34949
772.528.2076 pro-ductservicesjl@gmaii.com
PRO -DUCT
SERVICES
BLOWERDOOR&DUCTLEAKAGETESTING
TESTING -ADJUSTING -BALANCING
AIR OUTLET CHARACTERIZATION
for
STAN WEEKS & ASSOCIATES
Edwards Landing —BUILDING 13
3182 Morning Dew Lane, Fort Pierce, FL 34982
Description
Outlet
Number
Type
Size
Design
CFM
Pre Test
CFM
FINAL
CFM
Entrance
1
CD
8 x 4
30
41
37
Kitchen/Living Rm
2
CD
10 x 30
160
201
159
Bathroom
3
CD
8 x 4
15
42
29
Bedroom 1
4
CD
12 x 8
180
152
181
Bedroom 2 Vent 1
5
CD
30 x 10
125
110
119
Bedroom 2 Vent 2
6
CD
10 x 10
125
121
121
TOTAL
635
646
FAN DATA Panasonic Whispergreen Model FV-05-11USK1 Vent Fan
Mechanical components working as designed and match plan
COMMENTS requirements.
+++ ALL BALANCING WORK PERFORMED IN ACCORDANCE WITH NCI STANDARDS AND PROCEDURES +++
Pro -Duct Services, 1915 Rio Vista R64 Fort Pierce, FL 34949
772.528.2076 pro-ductservicesff@gmail.com
PRO -DUCT
SERVICES
BLNMOOR&DUCTLEAKAGETESTING
TESTING -ADJUSTING -BALANCING
TESTING, ADJUSTING, & BALANCING WARRANTY
for
Jtan Weeks & Associates
Edwards Landing —BUILDING 13
All Testing, Adjusting, & Balancing performed on this project by Pro -Duct Services is under
warranty for a period of One Year from the date of completion of the Test & Balance, unless
otherwise noted. Warranty will be considered null and void if another TAB company is
brought in to evaluate the project without notifying Pro -Duct Services to be present at the
time of the additional testing.
Date of TAB Testing: 6/21/2019 Warranty Expiration Date: 6/30/2020
Pro -Duct Services Authorized Signature:
Pro -Duct Services Technician: Michael Faurot
Certified NCI Contractor/Supervisor/Technician
NCI Commercial Certification ID: 19-229-03
BPI Certification ID:
5059122
+++ ALL BALANCING WORK PERFORMED IN ACCORDANCE WITH NCI STANDARDS AND PROCEDURES...
pCO Certlfled vG
Z wnaso
c^.mi
Pro -Duct Services, 1915 Rio Vista Rd Fort Pierce, FL 34949
772.528.2076 pro-ductservicesJl@gmaii.com
PRO -DUCT
SERVICES
BLOWERDOOR& DUCT LEAKAGE TESTING
TESTI NG-ADJ USTI NG-BALANCING
Pro -Duct Services, 1915 Rio Vista Rd, Fort Pierce, FL 34949
772.528.2076 pro-ductservicesJl@gmail.com