HomeMy WebLinkAboutTESTING, ADJUSTING & BALANCING REPORTRECEIVED4201 JUN 2 4 019 PRO -DUCT PermittingSt. Lucie Cpartniounty t BLOW SERVICES REETESTING TESTING -ADJUSTING -BALANCING SCANNED BY St. Lucie County TESTING, ADJUSTING & BALANCING REPORT for STAN WEEKS & ASSOCIATES EDWARDS LA730. G BUILDINP�®Q✓ June 24, 2019 +++ ALL BALANCING WORK PERFORMED IN ACCORDANCE WITH NCI STANDARDS AND PROCEDURES +++ Ct16�p' BPI Pro-Duct Services, 1915 Rio Vista Rd Fort Pierce, FL 34949 772.528.2076 pro-ductservicesJl@gmail.com PRO -DUCT SERVICES BLOWER DOOR& DUCT LEAKAGETESTING TESTING -ADJUSTING -BALANCING Pro -Duct Services is a National Balancing Council (NBC) certified firm, through the National Comfort Institute, NCI. The goal of the NBC certified technicians is to work with the design professionals, building owners and other tradesmen to achieve maximum system performance on all environmental systems. Due to the complexity of today's HVAC systems and the unique demands of struc- ture occupants, having a qualified, certified Testing -Adjusting -Balancing (TAB) company balance these systems has now become more critical than it has ever been. NBC certified firms are able to achieve total system balance better than any other organization worldwide. Worhing in partnership with the other trades involved in your project is hey to overall project success. Pro -Duct Services will worn closely with all involved to en- sure project schedules are met. By utilizing different pre -balance checklists with the other trades, such as sheet metal, pipe fitters, HVAC and controls, project suc- cess can be achieved more reliably and timely. Utilizing NBC Procedural Standards is hey to achieving the design intent of today' sophisticated buildings. Understanding systems, their installation, their service maintenance requirements and procedures, and the manufacturer's start-up re- port helps in achieving system total balance for today's structures. Our technical testing and verification, coupled with repeat readings, ensure system functionality. With Pro -Duct Services you can be sure that our testing and verification process offers you the best value in the Testing, Adjusting, & Balancing industry. C"I'*AV, Pro-Duct Services, 1915 Rio Vista Rd, Fort Pierce, FL 34949 772.528.2076 pro-ductservices/1@gmaii.com PRO=DUCT SERVICES BLOWERDOOR&DUCT LEAKAGETESTING TESTING -ADJUSTING -BALANCING TEST & BALANCE INSTRUMENTS Evergreen Telemetry Capture Hood 151): Range: 100-2500 CFM Accuracy: +/- 3% Calibration: May 17, 2019 Evergreen Telemetry Capture Hood 8D-14: Range: 15-200 CFM Accuracy: +/- 3%-- Calibration: May 29, 2019 Evergreen Pressure/Velocity/Flow Sensing Module —Model S-PVF-1: Range: 1-2, 14-32 inches HG, 32° - 158* F Accuracy: +/- 3% Calibration: June 5, 2019 Evergreen Wrist Reporter WR-401 Pro -Duct Services Technician: Michael Faurot Certified NCI Contractor/Supervisor/Technician NCI Commercial Certification ID: 19-229-03 — Equipment re -calibration is performed as required by testing guidelines. — Pro -Duct Services, 1915 Rio Vista Rd, Fort Pierce, FL 34949 772.528.2076 pro-ductservicesfl@gmarLcom CUTIN commencing 11"r Mancer MICHAEL FAUROT Has successfully completed the required training and passed the written exam by the Nallfln� couelorl IeMule, Im to perform HUAC commercial system balancing up to 20 tons according to NO practical standards and procedures. Certified Since ,Lamfoh May 9, 2019 Certifled C as administered and recognized by fdn�MPaN'im \ l M15 r tartrnstltmrtu•rna Rob Falke, President Pro -Duct Services, 1915 Rio Vista Rd, Fort Pierce, FL 34949 772.528.2076 pro-ductservicesj7@gmail.com 1-1D-(b-13 PRO -DUCT SERVICES BLOWERDOOR&DUCT LEAKAOETESTINO TESTING -ADJUSTING -BALANCING AIR OUTLET CHARACTERIZATION for STAN WEEKS & ASSOCIATES Edwards Landing —BUILDING 13 3172 Morning Dew Lane, Fort Pierce, FL 34982 Description Outlet Number type file Design CFM Pre Test CFM FINAL CFM Entrance i CD 8 x 4 30 53 27 Kitchen/Living Rm 2 CD 30 x 10 160 167 164 Bathroom 3 CD 8 x 4 15 30 32 Bedroom 1 4 CD 12 x 8 180 185 177 Bedroom 2 Vent 1 5 CD 10 x 10 125 102 119 Bedroom 2 Vent 2 6 CD 30 x 10 125 117 122 TOTAL 635 641 FAN DATA Panasonic Whispergreen Model FV-05-11USK1 Vent Fan Mechanical components working as designed and match plan COMMENTS requirements. +++ALL BALANCING WORK PERFORMED INACCORDANCE WITH NCI STANDARDSAND PROCEDURES.. Pro -Duct Services, 1915 Rio Vista R4 Fort Pierce, FL 34949 772.528.2076 pro-ductservicesjf@gmail.com n PR0-0UCT SERVICES BLOWERDOOR&DUCTLEAKAGETESTING TESTING -ADJUSTING -BALANCING r 1-7)o0D_3 AIR OUTLET CHARACTERIZATION for STAN WEEKS & ASSOCIATES Edwards Landing —BUILDING 13 3174 Morning Dew Lane, Fort Pierce, FL 34982 Description Outlet Number Type She Design CFM Pre Test CFM FINAL CFM Entrance 1 CD 8 x 4 30 52 39 Kitchen/Living Rm 2 CD 10 x 10 160 170 163 Bathroom 3 CD 8 x 4 15 42 23 Bedroom 1 4 CD 12 x 8 180 130 176 Bedroom 2 Vent 1 5 CD 10 x 10 125 118 125 Bedroom 2 Vent 2 6 CD 30 x 10 125 109 116 TOTAL 635 642 FAN DATA Panasonic Whispergreen Model FV-05-11USK1 Vent Fan Mechanical components working as designed and match plan COMMENTS requirements. +++ ALL BALANCING WORK PERFORMED IN ACCORDANCE WITH NCI STANDARDS AND PROCEDURES... Pro -Duct Services, 1915 Rio Vista Rd, Fort Pierce, FL 34949 772.528.2076 pro-ductservicesfl@gmaii.com )_T D -00-73 PRO -DUCT SERVICES BLOWERDOOR& DUCTLEAKAOETESTINO TESTING -ADJUSTING -BALANCING AIR OUTLET CHARACTERIZATION for STAN WEEKS & ASSOCIATES Edwards Landing —BUILDING 13 3176 Morning Dew Lane, Fort Pierce, FL 34982 Description Outlet Number Type Size Design CFM Pre Test CFM FINAL CFM Entrance i CD 8 x 4 30 35 31 Kitchen/Living Rm 2 CD 10 x 10 160 145 176 Bathroom 3 CD 8 x 4 15 40 20 Bedroom 1 4 CD 12 x 8 180 156 172 Bedroom 2 Vent 1 5 CD 10 x 10 125 120 125 Bedroom 2 Vent 2 6 CD 10 x 30 125 108 114 TOTAL 635 638 FAN DATA Panasonic Whispergreen Model FV-05-11USK1 Vent Fan Mechanical components working as designed and match plan COMMENTS I requirements. +++ ALL BALANCING WORK PERFORMED IN ACCORDANCE WITH NCI STANDARDS AND PROCEDURES... Pro -Duct Services, 1915 Rio Vista Rd, Fort Pierce, FL 34949 772.528.2076 pro-ductservicesfl@gmail.com l� 0-c)-v73 PRO -DUCT SERVICES BLOWERDOOR&DUCTLEAKAOETESTINO TESTING -ADJUSTING -BALANCING AIR OUTLET CHARACTERIZATION • for STAN WEEKS & ASSOCIATES Edwards Landing —BUILDING 13 3178 Morning Dew Lane, Fort Pierce, FL 34982 Description outlet Number Type She Design CFM Pre Test CFM FINAL CFM Entrance 1 CD 8 x 4 30 32 39 Kitchen/Living Rm 2 CD 30 x 10 160 166 169 Bathroom 3 CD 8 x 4 15 41 27 Bedroom 1 4 CD 12 x 8 180 175 183 Bedroom 2 Vent 1 5 CD 10 x 10 125 92 118 Bedroom 2 Vent 2 6 CD 10 x 30 125 119 121 TOTAL 635 657 FAN DATA Panasonic Whispergreen Model FV-05-11USK1 Vent Fan Mechanical components working as designed and match plan COMMENTS I requirements. ... ALL BALANCING WORK PERFORMED IN ACCORDANCE WITH NCI STANDARDS AND PROCEDURES... Pro -Duct Services, 1915 Rio Vista Rd, Fort Pierce, FL 34949 772.528.2076 pro-ductservicesJl@gmail.com �T1;'i: D -6)073 PRO -DUCT SERVICES BLOWERDOOR&DUCT LEAKAGETESTING TESTING -ADJUSTING -BALANCING AIR OUTLET CHARACTERIZATION for STAN WEEKS & ASSOCIATES Edwards Landing —BUILDING 13 3180 Morning Dew Lane, Fort Pierce, FL 34982 Desaiptlen Outlet Number Type file Design CFM Pre Test CFM FINAL CFM Entrance 1 CD 8 x 4 30 41 36 Kitchen/Living Rm 2 CD 10 x 30 160 183 182 Bathroom 3 CD 8 x 4 15 43 26 Bedroom 1 4 CD 12 x 8 180 148 167 Bedroom 2 Vent 1 5 CD 30 x 10 125 117 118 Bedroom 2 Vent 2 6 CD 10 x 10 125 124 127 TOTAL 635 656 FAN DATA Panasonic Whispergreen Model FV-05-11USK1 Vent Fan Mechanical components working as designed and match plan COMMENTS requirements. ... ALL BALANCING WORK PERFORMED IN ACCORDANCE WITH NCI STANDARDS AND PROCEDURES.. Pro -Duct Services, 1915 Rio Vista Rit Fort Pierce, FL 34949 772.528.2076 pro-ductservicesjl@gmaii.com PRO -DUCT SERVICES BLOWERDOOR&DUCTLEAKAGETESTING TESTING -ADJUSTING -BALANCING AIR OUTLET CHARACTERIZATION for STAN WEEKS & ASSOCIATES Edwards Landing —BUILDING 13 3182 Morning Dew Lane, Fort Pierce, FL 34982 Description Outlet Number Type Size Design CFM Pre Test CFM FINAL CFM Entrance 1 CD 8 x 4 30 41 37 Kitchen/Living Rm 2 CD 10 x 30 160 201 159 Bathroom 3 CD 8 x 4 15 42 29 Bedroom 1 4 CD 12 x 8 180 152 181 Bedroom 2 Vent 1 5 CD 30 x 10 125 110 119 Bedroom 2 Vent 2 6 CD 10 x 10 125 121 121 TOTAL 635 646 FAN DATA Panasonic Whispergreen Model FV-05-11USK1 Vent Fan Mechanical components working as designed and match plan COMMENTS requirements. +++ ALL BALANCING WORK PERFORMED IN ACCORDANCE WITH NCI STANDARDS AND PROCEDURES +++ Pro -Duct Services, 1915 Rio Vista R64 Fort Pierce, FL 34949 772.528.2076 pro-ductservicesff@gmail.com PRO -DUCT SERVICES BLNMOOR&DUCTLEAKAGETESTING TESTING -ADJUSTING -BALANCING TESTING, ADJUSTING, & BALANCING WARRANTY for Jtan Weeks & Associates Edwards Landing —BUILDING 13 All Testing, Adjusting, & Balancing performed on this project by Pro -Duct Services is under warranty for a period of One Year from the date of completion of the Test & Balance, unless otherwise noted. Warranty will be considered null and void if another TAB company is brought in to evaluate the project without notifying Pro -Duct Services to be present at the time of the additional testing. Date of TAB Testing: 6/21/2019 Warranty Expiration Date: 6/30/2020 Pro -Duct Services Authorized Signature: Pro -Duct Services Technician: Michael Faurot Certified NCI Contractor/Supervisor/Technician NCI Commercial Certification ID: 19-229-03 BPI Certification ID: 5059122 +++ ALL BALANCING WORK PERFORMED IN ACCORDANCE WITH NCI STANDARDS AND PROCEDURES... pCO Certlfled vG Z wnaso c^.mi Pro -Duct Services, 1915 Rio Vista Rd Fort Pierce, FL 34949 772.528.2076 pro-ductservicesJl@gmaii.com PRO -DUCT SERVICES BLOWERDOOR& DUCT LEAKAGE TESTING TESTI NG-ADJ USTI NG-BALANCING Pro -Duct Services, 1915 Rio Vista Rd, Fort Pierce, FL 34949 772.528.2076 pro-ductservicesJl@gmail.com