HomeMy WebLinkAboutKSM PAPPERS'!A' CM e i A1DO&AV1111111 KELLER, SCHLEICHER &IMacWILLIAM ENGINEERING AND TESTING, INC. MARTIN (772) 337-7755 P.O. BO 78-1377 SEBASTIAN FL 32978-1377 SEBASTIAN (772) 589-0712 PALM BEACH (561) 845-7445 www.ksmengineering.net MELBOURNE (321) 768-8488 FAX (561) 845-8876 E-Mail: KSM@KSMENGINEERING.NET ST. LUCIE (772) 229-9093 C.A.: 5693 FAX (772) 589-6469 October 30, 2017 I SCANNED Eric Machado i BY Secure Gas, Inc. t Lucie County 1064 Persian Lane Sebastian, Florida 3295 Re: 250 Gallon Underground Tank 6251 N. U.S. Hig way 1 Fort Pierce, Flori a KSM Project#: 473253-lpgas Dear Mr. Machado: Please see attached detoil for how to tie down the 250 gallon underground tank at the referenced site. ljhe following are general notes concerning the attached drawing. 1. Prior to installing t e earth augers, check for underground utilities. 2. Earth auger and cables shown are designed to resist buoyancy forces from an empty tank fully submerged. 3. Earth augers type, and length is dependent of Soil Class. For this site soil is assumed as Class 4 Soil. If the onsite soils are not Class 4, engineer is to be notified. 4. Earth auger shall Ilave a tested minimum pull out value of 3000 lbs. 5. Location of tanks re dependent on local codes and are the responsibility of the persons obItining the permit. Please accept this letter hs certification that it is our intent to meet the regulations as specified in Section �30.07(2)(g) of Indian River County's Land Development Code. : No. please feel free to contact the office. Ronald G. Keller. 37293 / SI Lic, No.: 860 / Julie E. Keller, P.E.: 68366 Td 001,9.88£-ZLL 'oul'seE)emoeS d9Z:bO'L1,60AoN