HomeMy WebLinkAboutREVIEW COMMENTSjG. lmci ' {/pLNlwl
Planning & Development Services
Building &Code Regulation Division
2300 Virginia Avenue
Fort Plerce, FL 34982
Phone:(772)462-2172 Fex:(772)462.6443
PROPERTY INFORMATION
Address: 4551 St Lucie Blvd
City / State / Zip: Fort Pierce, FI 34946
Parcel#: 1431-120-0000-000/6
Zoning: IL
APPLICATION INFORMATION
Permit Number: 1711-0360
Permit Type: SLAB ONLY
CONTRACTOR INFORMATION
Contractor Name:
Ronald H Foulks
Business Name:
R F Concrete Construction Inc
Business Addr:
664 Old Dixie Hwy
City / State / Zip:
Vero Beach, FI 32962
REVIEWS AND COMMENTS
Review Tvoe
DOCUMENTS MISSING
11/14/2017
Comment:
11/14/2017
Comment:
Comment:
11/14/2017
11/15/2017
Comment:
Comment:
11/15/20W
11/1512017 Comment:
ENGINEERING DEPARTMENT
Comment:
ENVIRONMENTAL REVIEW
Comment:
FIRE DEPARTMENT REVIEW
Comment:
FRONT COUNTER REVIEW
Comment:
SCANNED
REVIEW COMMENTS BY
,t Lucie County
1
Owner(s):
Maverick Boat Group Inc
Jurisdiction: SAINT LUCIE COUNTY
Lot#: Block:
Stories- Automatic Sprinkler System? No
Fax Number: 772-778-2142
Email: Terri@Rfcconstruction.Com
Status Reviewed By Date Started Date Completed Date Released
PENDING Lashahna Ingram
FILLED LANDS AFFIDAVIT./I/30t/
RECORDED NOTICE OF COMMENCEMENT.✓///SO// /
VEGETATION REMOVA OR EMPTION PERMIT AT TIME OF PICKUP. PLEASE SUBMIT APPLICATION AS
SOON� . POSSIBLE.✓ �j3Fi//"%
DRIVEWAY PERMIT APPLICATION.
A COPY OF THE PAID UTILITY SERVICE RECEIPT FOR WATER AND SEWER FROM FPUA OR A LETTER
FROM THE UTILITY SERVICES PROVIDER STATING SERVICES ARE AVAILABLE (ABILITY TO CONNECT AT
THE SUBJECT LOCATION)
A COPY OF THE PAID UTILITY SERVICE RECEIPT FOR ELECTRIC SERVICE OR A LETTER FROM THE
ELECTRICAL UTILITY PROVIDER THAT ELECTRIC WILL BE AVAILABLE TO THE LOCATION.
PENDING
PENDING
PENDING
COMPLETE Lashahna Ingram 11/1412017 1111412017 1111412017
Planning & Development Services
Building & Code Regulation Division
2300 Virginia Avenue
Fort Pierce, FL 34982
Phone:(772)462-2172 FaX:(772)462-6443
REVIEW COMMENTS
2
PLANS EXAMINER ELECTRIC
INCOMPLETE waver rnue ninmu If
Comment:
ELECTRICAL PLAN SHEETS EO.1—E5.1 ARE COMPLETE,O.K. TO DO SLAB WORK AND UNDER GROUND
11/22/2017
ELECTRICAL AND GROUNDING,BONDING OF STEEL,WALTER PRIDE SR.
PLANS EXAMINER MECHANICAL
INCOMPLETE Carl Peterson 1112112017
Comment:
IS THERE ANY MECHANCIAL CHASES IN THE SLAB THERE IS NOTHING SHOWEN ON SLAB PLAN?
11/21/2017
PLANS EXAMINER PLUMBING
INCOMPLETE Carl Peterson 1112112017
11121/2017 Comment:
PLEASE CORRECTTHE FIXTURE COUNT WHEN THE OCCUPANT IS CORRECTED.
Comment:
PLEASE SHOW THE EYEWASH AND EMERGENCY SHOWER REQUIRED IN TABLE 403.1 MEETING THE
STANDARDS ISEA Z358.1. IN 411 IF IT IS THE ONE INSIDE THE RESTROOM. IF IT IS NOT IN THE RESTROOM
11/21/2017
PLEASE SHOW THE LOCATION ON PLANS. EMERGENCY SHOWERS AND EYE WASHES SHOULD BE
READIIYACCESIBLEAND NOT BEHIND CLOSED DOORS.
Comment:
PLEASE ADD FUTHER AREA SHOWEN ON PLANS PAGE A5 OF 61N THE OCCUPANT LOAD SO THE
11/2112017
FIXTURES WILL NOT HAVE TO BE ADDED IN THE FUTHER FOR A HIGHER OCCUPANT LOAD.
Comment:
PLEASE SHOW HOT WATER IN ACCORDANCE WITH 607.1 OF THE 2014 FLORIDA PLUMBING CODE.
11/27/2017
Comment:
PLEASE SPECIFY HOW THE FLOR DRAIN TRAPS WILL BE SEALED OR PRIMED IN ACCORDANCE WITH
11/27/2017
1002.4 OF THE 2014 OF THE FLORIDA PLUMBING CODE
PLANS EXAMINER REVIEW
INCOMPLETE Ed Roseberry 1111712017
Comment:
THIS IS AN F-1 FACTORY INDUSTRIAL OCCUPANCY CLASSIFICATION. AS SUCH, PER TABLE 1004.1.2,
INDUSTRIAL AREAS, THE OCCUPANT LOAD SHOULD BE CALCULATED AT too SF/OCCUPANT. PLEASE
11/20/2017
ADJUST OCCUPANT LOAD, OR SUBMIT DETAILED RATIONAL ANALISYS TO BUILDING OFFICIAL, PER FBC
1004.1.2 EX., FOR APPROVAL USING A DESIGN OCCUPANT LOAD.
ZONING REVIEW
INCOMPLETE . Lydia Galbraith 11/14/2017
Comment:
PLEASE PROVIDE4 SIGNED AND SEALED SETS OF CIVIL DRAWINGS
11/1412017
Comment:
PLEASE PROVIDE 3 BOUNDARY SURVEYS WITH ALL ELEVATIONS IN NAVD
11/14/2017