HomeMy WebLinkAboutHVAC CERTIFICATION0
PROFESSIONAL AIR BALANCING, INC.
3350 Ulmerton Road Suite 21 o Clearwater, Florida 33762 0 (727) 592-9666 o Fax (727) 561-4382
HVAC
Testing & Balancing RECEr,fED
Certification ]AN 2 ti an+n
SCANNED permitting Department
Project Name: Burger King Store # 929 BY St. Lucie County
Address: 10855 S. Highway 1 Port St. Lucie FL St. LUCie County
Engineering Firm: Engineering Professionals
Engineer: Gary Stenlund
E-Mail: stenlund@engrpros.com
Address: 1717 N. Howard Ave. Tampa Fl. 33607
Air conditioning, heating and ventilating systems have been balanced as per plans
and specifications. Work performed is in accordance with AABC standards. Unless
otherwise specifically specified, all balancing is performed on the basis of plus or
minus 10% of required reading as having achieved the specified air quantities. Any
exceptions will be noted on a "General Notes" page preceding the test data.
James Trafford
Technician
01-10-19
Date Completed
P� ALB i0
Professional Air Balancing AABC . CERTIFIED
.ABC
Associated Air Balance Council
�13!
Annua04embership Certificate
vt45•
Awarded to
Professional Air Balancing,Inc.
.:
as a member in goodstanding of the AssociatedAir Bafance Counciffor the year
.t
2019
This member das inet aLfrequirements for mem6ersfiip and is entitredto all
v
rights andprivireges of MBC certification. This certificate is renewa6re
:qua
on an annu4L6asis and e-Vires �Decetnber3l, 2019.
-:
Benjiman J. Link, President
�`PEO p�R nA(gNCFCo
O a Gm_q„,N 2
Raymond R. Berr, E;tecurivu Director
P A B
;=I�
Professional Air Balaneing
Professional Air
go
Air Handler Data Sheet
Proiect: Burger King / #A29752 St. Lucie (PAB#19004) Date: 1/10/19
CERTIFIED
Identification
RTU-1
RTU-2
ment Location / Service
Roof
Roof
ment Manufacturer
E
Carrier
Carrier
Number
50HCAOSA2A5AOAOA0
50HCA06A2A5AOAOAO
Number
3818C87104
3B18C87105
FAN DATA
DESIGN
TEST
DESIGN
TEST
Fan CFM
2000
—
2000
--
Outlet CFM
2000
2100
2000
2150
Return Air CFM
1500
1645
1500
1690
Outside Air CFM
500
455
500
460
Static Pressure Total 1 External
NG 10.75
0.93 / 0.73
NG / 0.75
0.87 / 0.68
Fan Inlet Pressure
NG
0.61
NG
0.58
Fan Discharge Pressure
NG
0.32
NG
0.29
Return Pressure
NG
0.41
NG
0.39
Fan RPM
NG
NG
MOTOR DATA
DESIGN
TEST
DESIGN
TEST
Motor Manufacturer( Frame
--
Marathon
—
Marathon
Motor H.P.I RPM
2.9 Bhp. / NG
NG 11725
2.9 Bhp. I NG
NG / 1725
Volts I Phase
20813
21113
208 / 3
21013
Amperage
8.6
7.7
8.6
7.8
Motor Service Factor
NG
1.15
NG
1.15
Starter Heater Size
NG
Breaker
NG
Breaker
Starter Heater Rating
Motor Sheave I Open Turns
NG Breaker
1 VP39 x 6/813
NG Breaker
1VP39 x 518 / 2
Fan Sheave
AFD44 x 518
AFD44 x 5/8
Belts I Center To Center
A38 / 14118'
A381141/8'
COIL DATA
DESIGN
TEST
DESIGN
TEST
GPM
DX
DX
DX
DX
EWT 1 LWT Degrees F
DX
DX
DX
DX
Water A T
DX
DX
DX
DX
EAT DB I WB Degrees F
80.0 / 67.0
76 / 65
80.0 / 67.0
77 / 65
LAT DB 1 WB Degrees F
NG / NG
55 / 53
NG / NG
56 154
Filter Manufacturer IS!;
16 x 20 x 2 (4)
16 x 20 x 2 (4)
Remarks:
P A B
=t-
Pm(es tonal Air Salancln9
a
Professional Air
do
�-dwft-
Iw
Air Handler Data Sheet
Proiect: Burger King / #A29752 St. Lucie (PAB#19o04) Date: 1/10/19
C'L•'RTIFIGD
System Identification
RTU-3
RTU-4
Equipment Location I Service
Roof
Roof
Equipment Manufacturer
Carrier
Carrier
Model Number
50HCD09A2A5AOAOAO
50HCD08A2A5AOAOAO
Serial Number
4318P39394
4418P40160
FAN DATA
DESIGN
TEST
DESIGN
TEST
Fan CFM
3400
--
3000
--
Outlet CFM
3400
3300
3000
3170
Return Air CFM
2720
2565
2400
2510
Outside Air CFM
680
735
600
660
Static Pressure Total / External
NG 10.75
1.04 / 0.62
NG / 0.75
1.0410.65
Fan Inlet Pressure
NG
0.71
NG
0.66
Fan Discharge Pressure
NG
0.33
NG
0.38
Return Pressure
NG
0.29
NG
0.27
Fan RPM
NG
--
NG
--
MOTOR DATA
DESIGN
TEST
DESIGN
TEST
Motor Manufacturer I Frame
--
Marathon
--
Marathon
Motor H.P. I RPM
3.71 NG
NG / 1725
2.91 NG
NG / 1725
Volts/Phase
208/3
21113
208/3
21113
Amperage
6.9
5.8
6.9
5.9
Motor Service Factor
NG
1.15
NG
1.15
Starter Heater Size
NG
Breaker
NG
Breaker
Starter Heater Rating
Motor Sheave 1 Open Turns
NG Breaker
1VP40 x 518" 14
NG Breaker
1VP40 x 5l8" / 2
Fan Sheave
AFD74x10
AFD74x1"
Belts I Center To Center
A48116 518"
A48 / 16 518"
COIL DATA
DESIGN
TEST
DESIGN
TEST
GPM
DX
DX
DX
DX
EWT 1 LWT Degrees F
DX
DX
DX
DX
Water T
DX
DX
DX
DX
EAT DB I WB Degrees F
80.0 / 67.0
76 / 68
80.0 / 67.0
77166
LAT DB I WB Degrees F
NG/NG
57/54
NGING
58/54
Filter Manufacturer 1
1 20 x 25 x 2 (4)
20 x 25 x 2 (4)
Remarks:
P A a
4=2t-
Professional Air Balancing
M
Professional Air Balan
go
Air Cooled Condenser Data Sheet
Project: Burger King / #A29752 St. Lucie (PAB#19004) Date: 1110119
B.
0
CERTIFIED
System Identification
RTU-1
RTU-2
Equipment Manufacturer
See Air Handler Data Sheet
See Air Handler Data Sheet
Model Number
See Air Handler Data Sheet
See Air Handler Data Sheet
Serial Number
See Air Handier Data Sheet
See Air Handler Data Sheet
DESIGN
TEST
DESIGN
TEST
E.A.T. DB
95.0
79.0
95.0
78.0
L.A.T. DB
--
94.0
--
93.0
DESIGN
TEST
DESIGN
TEST
DESIGN
TEST
DESIGN
TEST
Compressor#
1
1
—
1
1
—
—
Amperage
15.9
13.7
—
—
15.9
13.4—
Volts
208
210
—
—
208
211
—
—
Phase
3
3
—
—
3
3
—
—
System Identification
RTU-3
RTU-4
Equipment Manufacturer
See Air Handler Data Sheet
See Air Handler Data Sheet
Model Number
See Air Handler Data Sheet
See Air Handler Data Sheet
Serial Number
E.A.T. DB
L.A.T. DB
See Air Handler Data Sheet
DESIGN TEST
95.0 78.0
-- 94.0
See Air Handler Data Sheet
DESIGN TEST
95.0 78.0
-- 93.0
DESIGN
TEST
DESIGN
TEST
DESIGN
TEST
DESIGN
TEST
Compressor#
1
1
2
2
1
1
2
2
Amperage
13.7
11.9
13.7
12.2
13.6
12.1
13.6
12.2
Volts
208
210
208
211
208
210
208
211
Phase
3
3
3
3
3
3
3
3
Remarks:
P A B M
Pmfessiona�6 ofng Professional Air Balancin
Fan Data Sheet
Project: Burger King / #A29752 St. Lucie (PAB#19004)
v
AABC _ C'ERTIFfEU
Date: 1/10/19
Fan Identification
EF-1
EF-2
Service
Broiler Hood
Fryer Hood
Equipment Location
Roof
Roof
Equipment Manufacturer
Cook
Cook
Model Number
120OPS
100CPS
Serial Number
007SH820380010003001
007SH5890400l0000701
DESIGN
TEST
DESIGN
TEST
Fan CFM
1100
800
Inlet I Outlet CFM
1100
1010
800
585
Total Static Pressure
1.85
Not Obtainable
2.50
Not Obtainable
Fan Inlet Pressure
NG
Not Obtainable
NG
Not Obtainable
Fan Discharge Pressure
NG
Not Obtainable
NG
Not Obtainable
Fan RPM
1957
1 669
2657
2457
DESIGN
TEST
DESIGN
TEST
Motor Manufacturer I Frame
--
Century
—
Century
Motor Horsepower
1.0
1.0
1.0
1.0
Volts / Phase
20811
211 / 1
208 / 1
211 / 1
Amperage
6.2
5.6
6.2
6.1
Motor RPM
NG
1725
NG
1725
Motor Service Factor
NG
1.25
NG
1.25
Starter Heater Size
NG
Breaker
NG
Breaker
Starter Heater Rating
NG
Breaker
NG
Breaker
Motor Sheave I Open Turns
MVL40B x 5/8" / 1
MVL44 x 518"11
Fan Sheave
AK32 x 1"
AK32 x 1"
Belts / Center to Center
A30110 718"
A31111 118"
Remarks:
P A B
Professional Air Balancing
Lil
Professional Air B
Fan Data Sheet
of
Project: Burger King / #A29752 St. Lucie (PAB#19004) Date: 1/10/19
s
A-AAC _ CERTt FLED
Fan Identification
EF-3
Service
Restroom Exhaust
Equipment Location
Roof
Equipment Manufacturer
Cook
Model Number
100ACEH
Serial Number
001 SH6258801 / 0000701
DESIGN
TEST
DESIGN
TEST
Fan CFM
225
--
Inlet lOutlet CFM
225
245
Total Static Pressure
0.25
0.29
Fan Inlet Pressure
NG
0.29
Fan Discharge Pressure
NG
Atmos.
Fan RPM
911
Direct Drive
DESIGN
TEST
DESIGN
TEST
Motor Manufacturer Frame
--
Fasco
Motor Horsepower
1/25
1/25
Volts IPhase
12011
116
Amperage
1A
0.93
Motor RPM
NG
1050
Motor Service Factor
NG
1.0
Starter Heater Size
NG
Thermally Protected
Starter Heater Rating
NG
Thermally Protected
Motor Sheave I Open Turns
Direct Drive
Fan Sheave
Direct Drive
Belts I Center to Center
Direct Drive
Remarks:
P A B
Profewiona�ncing Professional Air Balancin
Air Distribution Sheet
Project: Burger King / #A29752 St. Lucie (PAB#19004)
Svstem: RTU-1 / RTU-2 / EF-3
0
AAB0 _ CERTIFIED
Date: 1110119
����'
MM
MM
_--_---
_imilm
-�
-_--
iII
—_-_iI----
Remarks:
P A B
;=-1
Professional Air Balancing
40
M
Professional Air Balan
Air Distribution Sheet
Project: Burger King / #A29752 St. Lucie (PAB#19004)
S stem: RTU-3
.ate
^ABC _ CERTIFIED
Date: 1/10/19
®®MMMMMM®M®M®
Remarks:
Remarks:
P A B
Pmfewlona�landng Professional Air Balancin
Air Distribution Sheet
Project: Burger King / #A29752 St. Lucie (PAmi9om)
System: RTU-4
0
AABC - (,'ERTIFIED
Date: 1/10/19
Terminal
�0=1
���
Type
I Size
I AKJ:��[7i�CFM
-�----
Ali
-----®I
MM
MM
MM
=-
MMM
MM
MM
MM
MM
MMMM
=-
MMM
MM
MM
MM
MM
=-
MMM
MM
MM
MM
MM
-MMM
MM
MM
MM
MM
Remarks: