HomeMy WebLinkAboutEQUPMENT SUBMITTALTRAAFE• Submiftal. Prepared For. Date: May 10, 2017 Airstron SCANNED Customer P.O. Number: BY CustomerProject Number., St. dude COUllty Sold To: Job Number. - Job Name: St. Lucie Church 40T Repi Trane U.S. Inc. is pleased to provide the enclosed submittal for your review and approval. Product Summary Qty Product 1 Air -Cooled Condensing Units (Commercial) 1 Performance Climate Changer Chris Cowling Trane 6965 Vista Parkway North, Suite 11 West Palm Beach,. FL 33411 Phone: (561) 683-1521 Cell: (561) 683-1521 Fax: (561) 697-8714 Please Note; The attached information describes the equipment we propose to furnish for this project, and is submitted for your approval. Product performance and submittal data is valid fora period of 6 months from the date of submittal generation. If six months ormore has elapsed between submittal generation and equipment release, the product performance and submittal data will need to be verified. It is the customers responsibility to obtain such verification. • Contractor to review submittal for accuracy before rdering. FIclu ST LUCIE COUNTY BUII.DLNQDIVISION REVIEWED FOR C LTAI3CE REVI ST Y Q DATE ' PLANS ANZI PERMIT MUST BE 8761'1�OON.70B OR NO INSPECTION %11, BE MADE. J11OBS146148438141REV Submittal - 40T AHU CU - St Lucie Church 5-10-17.doc Table Of Contents ProductSummary ........................................................................................................................... I Air -Cooled Condensing Units (Commercial) (Item Al) ............................................................... 3 TagData ... ......................................................................................................................... ; .................... 3 Product Data 3 Mechanical Specifications ........................................................................................................................ 4 UnitDimensions ........................................................................................ 5 Weight, Clearance & Rigging Diagram .......................................... d .......................................................... 8 Accessory................................. w ...................................................................................... ....................... 9 FieldWiring ............................................................................................................................................ 10 PerformanceClimate Changer (Item BI) ......... . *­ ­­* ............. * ........... ** ....... ...........................14 " TagData ................................................................................................................................................ 14 ProductData .......................................................................................................................................... 14 PerformanceData ............ * ................... ***"**'*" ..... ** ... *'*"**'*'*"*""*"*"****"****** .... * ........... ****"* ......... * ........ 15 MechanicalSpecifications ...................................... ................................... *****'** .... * ... *'***'*"*"*"* ... **'*'***' 16 As -Built ....................................................................................................... *""** ... * .......... 19 FanCurve .................................................................................................... *** ...... *'**'**'** ..... * ....... ... 27 Accessory............................................................................................................... FieldWiring ............................................................................................................................................ * ..... **'**'* ....... ***'*"**'* 28 33 SCANNED Field Installed Options - PartfOrder Number Summary Air Condensing Units ............................................................34 St BY Lucie County -Cooled (Commercial) .......................................................................................... 34 Performance Climate Changer ............................ .................................................................................. 34 St. Lucie Church 40T Repl '- May 10. 2017 Tag Data -Air-Cooled Conii,._ . iaq Units (Commercial) (Qtv: 11 Item Tags) I Qt_y I Description I Model Number JA1 1.189.181711 11 140 Ton Air -Cooled Condensing Unit IRAIJJC40EC Product Data - Air -Cooled Condensing Units (Commercial) Item: Al Qty: 1 Tag(s): J89J81711 Condenser Air -Cooled R41 OA Development Sequence 40 Ton Unit 200 Volt 60 Hertz 3 Phase Constant Volume Control Standard ambient control cULus approval Suction service valve . Unit spring isolators (Fld) 2nd-5th Year Replacement Compressor Warranty Factory Assisted Start-up FLD = Furnished by Trans U.S. Inc. l Installed by Equipment Submittal Page 3 of 34 Others St Lucie Church 40T Rep[ r _, - _ May 10, 2017 Mechanical Specifications - _._ —'Cooled Condensing Units (Commercial Item: Al Qty: 1 Tag(s): J89J81711 General - R410 All condensing units are factory assembled and wired. Unit frames are constructed of 14 gauge welded galvanized steel with 14 and 16 gauge galvanized steel panels and access doors. The unit surface is phbsphatized and finished with an air-dry paint to withstand 500 hours of continuous salt spray solution in accordance with ASTM B117. Decorative louvered panels provide condenser coil protection. Compressors - R-410A . Trans 3-D Scroll compressors have simple mechanical design with only three (3) major moving parts. Scroll type compression provides inherently low vibration. 3-D compressors provide a completely enclosed compression chamber with no leakage paths. The compressor is suction gas cooled, direct drive, 3600 RPM hermetic motors. The Scroll compressor includes a centrifugal oil pump, oil level sight glass, and an oil charging valve. Refrigerant Management - R410A Split systems can have significantly more refrigerant than packaged systems and thus require controls to reliably manage this excess refrigerant. Each compressor shall have crankcase heaters installed, properly sized to minimize the amount of liquid refrigerant present in the oil sump during off cycles. Additionally, the condensing unit shall have controls to initiate a liquid line solenoid closure when each refrigerant circuit shuts down. To be operational, the liquid line requires a field supplied and installed isolated solenoid valve within 10 feet of the evaporator Note: Under extreme conditions, R410a refrigerant can present special challenges with piping and system design. Whenever refrigerant line set lengths approach 150 equivalent feet and/or design ambient temperature exceeds 115 degrees F, contact your Trans Account Executive to review application requirements. Unit Control - R410A Factory provided 115-volt control ciFcuit. includes fusing and control power transformer. The unit is wired with magnetic contactors for compressor and condenser motors, three -leg solid-state compressor overload protection, and high/low pressure cutouts. Charge isolation, reset relay and anti -recycle compressor timer is provided. Across -the -line start is standard. Dual Circuit, Condenser Coils for 40-60 Ton Units - R-410A Condenser coils are dual circuited having an Aluminum Microchannel design. The coils are burst tested and leak tested. Factory installed liquid line service valves are standard. Dual Refrigerant Circuit w/Four Capacity Stages for 40-60 Ton Units - R410A. Each unit has dual refrigeration circuits. Each circuit has two (2) compressors manifolded together utilizing a passive oil system. Each unit has four capacity stages. Capacity modulation is accomplished by turning compressors on and off. .Condenser Fans - R-410A Condenser fans are direct driven with motors having thermal overload protection and permanently lubricated ball bearings. Standard Ambient Control - R-41CA Standard ambient control allows unit operation from 40 F to 115 F 14.5 to 46.1 C]. Spring Vibration Isolators - R-410A Spring vibration isolators are supplied for field installation under the unit base to minimize transmission of unit vibrations. Field Installed; 30% Bleed Valve TXV Installation shall require use of 30% bleed, Thermal Expansion Valves. Valves shall be field supplied and field installed. Quantity and size shall. be determined by the application. Note: Liquid line solenoids are required for all applications. Trim solenoids cannot be used FLO = Fumished by Trane U.S. Inc. /Installed by Equipment Submittal Page 4 of 34 Others St. Lucie Church 40T Repl --- - --- - - - - --May'10, 2017 Unit Dimensions - Air-Coolei . ,ndensing Units (Commercial) Item: Al Oty: 1 Tag(s): J89J81711 GRILLE 3/4' X 6 MTG HOLES 5 O 36IN' .. 889116' NOTES: 1. SEE CONNECTION DRAWING FOR CONNECTION LOCATION AND SIZES. 2. LOW AMBIENT DAMPER ONLY COMES WITH SELECTED UNIT. 3. PRONT & BACK OF UNIT CLEARANCE 72'� LEFTS RIGHT SIDE OF UNIT CLEARANCE 42' 12' X 12'X 29 FRONT (SEE NOTE 361�, FOR CLEARANCES) 1 3/4' KO LOI pir VOLTAGE (3 1 � Ll 114 DOOR 431/4' W/ 180 DEG SWING CONTROLPANEL (SEE DETAIL FAN GRILLE 1 0 32 & BOTTOM OF CONTROL BOX (SEE DETAI 6' 79 11/4'x: SLOT F( VOLTCUNIHUL 40 TON UNIT DIMENSIONAL DRAWING DETAIL A BOTTOM OF CONTROL BOX INEL CONDUIT vN POWER IS11e' FLD = Furnished by Trane U.S. Inc. /Installed by Equipment Submittal Page 5 of 34 Others St. Lucie Church 40T Repl— - May 10, 2017 Unit Dimensions -Air-Coole: _,ondensing Units (Commercial) Item: Al Qty: 1 Tag(s): J89J81711 a CONTROL PANEL (LEFT) SIDE VIEW OF UNIT CONNECTION DRAWING 40 TON UNIT NOTES: 1. VERIFY WEIGHT, CONNECTION, AND ALL DIMENSION WITH INSTALLER DOCUMENTS BEFORE INSTALLATION (OPTIONAL) -1 SW O.D. 'SUCTION LINE PPN 50E ACCESS ORIENTATION VIEW OF UNIT ISOMETRIC DRAWING BACKMEW OF UNIT CONNECTION DRAWING IS" FLO = Furnished by Trane U.S. Inc. /Installed by Equipment Submittal Page 6 of 34 Others St. Lucie Church 40T Repl 1' - May 10, 2017 Unit Dimensions - Air-Coole _ 'mdensing Units (Commercial) Item: Al Qty: 1 Tag(s): J89JS1711 GENERAL ELECTRICAL DATA GENERAL OUTDOOR MOTOR Tonnage/kW: 40 L140.0 Will Number. 4 Unit Operating Voltage Range: 180-220 Horsepaser. 1.0 Unit Primary Voltage: 200 Motor Speed(rpm): 1,140 Unit Hens 60 Outdoor Motor Full Load amps: 4.1 Unit Phase: 3 Outdoor Motor Locked Rotor amps: 20.7 Minimum ClrcultAmpaoty. (3) 193.0 Maximum Overcurrent Protection Device: (2) 225.0 Recommended Dual Element Fuse: (4) 225.0 COMPRESSOR REFRIGERANT Ctrcu@A1/A2- Circuit 81182 Tom (as): 10.0110.0-10.0110.0 Type: R410A Compressor Pa dLoad Amps (as): 41.4/41A-41.4/41.4 Number of Circuits: 2 Lockett Rotor Amps (ad): 267.01261.0 - 257.01267.0 Condenser Storage Capacity. 23.511, Refrigerant Operating Charge (Condenser Only): 23.7 lb Notes 1. Electrical data is foreaes individual motor. 2 Maximum overcurrent protection permitted by nec 440-22 is 225 percent of largest compressor motor RLA plus the remaining motor RLA and FLA values. 3. Minimum circuit ampacity is 125 percent of the largest cmnpressar motor RLA plus the remaining motor RLA and FLA values. 4. Recommended dual element fuse s® is 150 percent of the largest compressor motor RLA plus the remaining motor RLA and FLA values. 5. Loral codes may take precedence. FLD = Furnished by Trane U.S. Inc. /Installed by Equipment Submittal Page 7 of 34 Others St Lucle Church 40T Repl May 10, 2017 Weight, Clearance & RigginL — P igram - Air -Cooled Condensing Units (' dmercial) Item: Al Qty: 1 Tag(s): J89JB1711 )LES 40 TON RIGGING e\ WEIGHTS AND LOAD POINTS OPERATING: 2532.01b `CLENRANCE SHIP LINE POINTS 1: 452.30 I 77 I LOAD POINTS 2: 415.7 lb LOAD POINTS 3: 440.31b I^—X I LOAD POINTS 4. 403.71b LOAD POINTS 5: 391.8 b LOAD POINTS fi: `2 4 8 'ALL WEIGHTS ARE r_ I APPROXIMATE Y i I CENTER OF GRAVITY I I X. 43 aW CONTROL Y. 4T I I BOX I ADD WEIGHTS /.3 SHIPPING: RI oT a5 I. OPERATING: I4I 42 42" NOTES: 1. OPERATING WEIGHT INCLUDES REFRIGERANT, OILAND WATER I I 2. SHIPPING WEIGHT INCLUDES REFRIGERANT AND OIL CHARGES CENTER OF GRAVITY 3. THEACTUALWEIGHT IS SHOWN ON THE NAMEPLATE. WEIGHT. 72" I SHOWN REPRESENT TYPICAL SHIPPING AND OPERATING WEIGHTS FOR I I THE UNITSELECTED. ' 4. ADD WEIGHTTO TOTAL WEIGHT OF UNIT FRONT OF UNIT I 5, IF UNITS IS INSTALLED IN A WELL, THE DEPTH OFTHE WELL MUST NOT EXCEEDTHETOPHEIGHTOFTHEUNIT. THETOP OF THE UNIT MUST ---_------- - - --� HAVE UNRESTRICTED AIRFLOW. PLEASE REFERENCE RECOMMENDED CLEARANCES. WARNINGI 40TON CENTER OF GRAVITY AND CLEARANCES TO PREVENT INJURY OR DEATH AND POSSIBLE EQUIPMENT DAMAGE DO NOT USE CHAIN (CABLES)OR SLINGS EXCEPT AS SHOWN WEIGHTAND RIGGING AND USE CABLES STRONG ENOUGH TO SUPPORT UNIT WEIGHT. TEST LIFT UNIT TO ENSURE PROPER BALANCE AND RIGGING. FLO = Furnished by Trans U.S. Inc. /Installed by Equipment Submittal Page 8 of 34 Others St Lucie Church 40T Repl - - _ _ May 10. 2017 Accessory -Air-Cooled Con: sing Units (Commercial) Item: Al Qty: 1 Tag(s): J89J81711 NEOPRENE PAD NOTES: 1. MOUNTING LOCATIONS CORRELATE WITH MOUNTING LOCATIONS SHOWN IN CLEARANCE DRAWING. 2 VERIFY WEIGHT, CONNECTION, AND ALL DIMENSION WRH INSTALLER DOCUMENTS BEFORE INSTALLATION MOUNTING LOCATIONS LOCATION 1 LOCATION 'CPID510 LOCATION 'CP1D510 LOCATION 'CPID510 LOCATION 'CP/D510 ' LOCATIONS 'CPID510 MOUNTING ISOLATOR (SPRING) DIMENSIONAL ACCESSORIES DRAWING FLO = Furnished by Trane U.S. Inc. llnstalled by Equipment Submittal - Page 9 R 34 Others St Lucie Church 40T Repl 1 -, _ May 10, 2017 Field Wiring - Air -Cooled Col•, _ •.,ising Units (Commercial) Item: Al Qty-. 1 Tag(s): J89J81711 Required Components for Refrigerant Circuits Trans Condensing Unit Pon All items numbered are field supplied. Acmaa Port ahutaftNehre 1. SuNsn �3. Shutoff Valve Llna 2. Suction Line (Unit Option) Filer ShvLae 4. Liquic Valve Velvs VaM Line Evaporator Call 9. Maisueand S. Shutoff 6. Access S. ShutaH Expansron Valve 6. Soleni Valve Fmstal SUCTION LINE 1. Interconnected Tubing (Suction Ime) Maxhnum also feet Ifcondenser is above evaporator(if rbemare more than 50feet, me app6cotion must be viewedbyTrene) Referto SS-APG012-EN farmoredetails 2. Suction Line Filter Drier 1 / do suction filler should be the replaceabe-com type, and a clean core should be Installed after the system is cleared up 3. Shut-0H Valve Manual ball valves for 2 118'-tubing. LIQUID LINE 4. Interconnected Tubing (Liquid Line) Refartu applications guide SS-APGO12 - EN forvertiral S hm®ntal piping limitations. S. Shut -Off Valve 2 Manual ball valves 6. Access Port Part used to delemime suction pressure. This port is usually Schmeder valve with a core. 7. Liquid Lire Filter Drier 1 I ckt liquid filter should be the replaceablecom type, and a clean core should be installed after the system is cleaned up. B. Solenoid Valves Liquid line requires a field supplied and installed isolation solenoid valve within 10 feel of the evaporator. The suggested solenoid uses a 120- % service and require; code-compliarn widrg to the RAUJ condemu g unit. Nola: Trim solenoids cannot be used. They ere not compatible with Miaoclsnnel condenser coils 9. Molslure and Liquid Indicator One moisture -Indicating sight glass is to be installed In the main liquid line. . FLD = Furnished by Trane U.S. Inc. /Installed by Equipment Submittal Page 10 of 34 Others St. Lucie Church 40T Rapt — _ _ May 10, 2017 Field Wiring - Air -Cooled Co. ising Units (Commercial) Item: Al Qty: 1 Tag(s): J89J81711 EVAPORATOR 10. Fromst(not required) -The control is mechanically attached to the outside of the refrigerant One, near the evaporator, and Wired to the unit control panel See application guide S3-APG012-EN for selection information. 11. Expansion Valves -Sea application guide SS,AP6012-EN for selecting valve quantity and s®. Note., Units with Miaecharmel condenser coils applied with DX systems wUl require 30 percent bleed valves. Expansion Velvee for2050T NICHE (30 precem Bleed) Evap Circuit Tonnage REFRIGERANT MIN. MAX. SPORLAN MODEL NUMBER TRANE PART . R4111A ` 2.0 3.0 BBIZE-1-12-GA(BP20) VAL1007 R410A 2.5 3.5 BBIZE-2-GA (BP/30) VAL1048B R410A 3.5 5.0 BBIZE3GA(BP/30) VALID489 R410A 4.5 7.0 BBIZE4-GA(BP/W) VAL10490 R410A 6.0 8.5 BBIZESGA(BP/30) VALIC491 R410A. 7.0 10.0 BBlZES-GA(BP/30) VAL10492 R410A 5.0 13.5 BBIZE41GA(BP/30) -VAL10493 R410A 11.0 17.5 BBIZE-12-12-GA(BPI30) VAL10494 R410A 14.0 21.5 BBEtISGASP/J0) VALID495 R410A 17.0 28.5 OZE-20-GA(BP/Jol VAL704S6 R410A 12ZO 130.0 1 0ZE-25-GA(BPI30) VALI 497 (1) Ton par distributor, choose the valve that matches the avap coil circuit capacity theta serves. (2) Provide and instal one expansion valve per distributor..* Refrigerant Charge and Maximum Line Length Total interconnecting line Imp (per dron0) 50 ft 100 fi 150 it Condenser and line set appmx. refrigermt WA WA WA charge (Per cimrit) - evaporatorc aMo not included If total imenwnnecting line length is more than 150 feet, the appricallon must be reviewed by Trana "Contact product support for information an refrigeration components and piping applications assistance Suction une Piping 1. Do not use suction line traps. Installation Guidelines 2. Do not use double fisem. 4. Route suction lines a9 short and direct as possible. 5. 51ope suction Ora sway from the condeaing unit 1 Inch forevery 10 feet a. insulate suction line. 7. The suction filter should be located as claw to the compressors as possible. 3 A.Wpu0mgsuction lugs mdergmand. FLD=Fumished byTrane U.S. Inc. /Installed by Equipment Submittal Page 110/34 Others St. Lucle Church 40T Repl _ May 10, 2017 Field tiring - Air -Cooled Cal insing Units (Commercial) Item: Al Qty: 1 Tag(s): J89JO1711 Required Components for Refrigerant Circuits Continued Liquid Line Piping 1. Awid pu*V liquid lines underground 2. Route liqul d fines as sh art and d've at as pass[ ble. 3. Slope liqui d line away from the condensing unit 1 inch for every 10 feet. 4. Only insulate liqui dIt nes th at pass tiv augh heats d areas. 5. Whe solenoid valve per fel d cmmcall on diagram. S. The liqui d f ne filter drier should be as close to the solenoid valve as pass! ble. Evaporator P431 ng 1. Insist TXV dim city to unit 1[qui d connection. 2. Locate TXV bulb midway between 90F bends an top of suclian W be as shown. 3. Secure bulb to Wbe with the two clamps prow ded by the manul aclurer and insulate bulb. 4. Insist the TXV equalaser line close to S downstre am of the bulb, on lop of the horizontal suasion fine. S. Install frost at per kit insbu adore an the common suction line as close to the evaporator as pass!ble. See SS-APGO12-EN. for DX evaporator piping details. FLO = Fumished by Trane U.S. Inc. llnstalled by Equipment Submittal Page 12 of 34 Others On II CUSTOMER WIRE SELECTION TABLE. POWER WIRE SELECTION TO DISCONNECT SWITCH (1S1) FACTORY INSTALLED DISCONNECT SWITCHSIZE CONNECTOR WIRE RANGE POWER WIRE SELECTION TO MAIN TERMINAL BLOCK (iTBI) TERMINAL BLOCK SIZE CONNECTOR WIRE RANGE 335 AMP (1) 06-360 MCM CONTROL WIRE SELECTION WIRE GAUGE OHMS PER 12000" MAX WIRE LENGTH 18AWG a 60DO" 16AWG 5 12000" . 14 AWG 3 24DOW SHIELDED WIRE TABLE WIRE GAUGE MAX WIRE LENGTH 16 AWG 5pgp^ 14AWG 12000" °h WARNING DISCONNECTALL ELECTRIC POWER INCLUDING REMOTE DISCONNECTS BEFORE SERVICING. FAILURE TO DISCONNECT POWER BEFORE SERVICING CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. Zt CAUTION USE COPPER CONDUCTORS ONLYI UNIT TERMINALS ARE NOT DESIGNED TO ACCEPT OTHER TYPES OF CONDUCTORS. FAILURE TO DO SO MAY CAUSE DAMAGE TO THE EQUIPMENT. NOTES: 1. All wiring and componets shown dashed to be supplied and installed bycustamer in accordance with local and national electrical eodes. 2. All wiring to be NEC Class 1 based on 60 degree C wire unless speemed. 3. CAUTION -Do not run lawvoltage wire (30 volts maximum) In eandu@ or racawaywith higher voltage w%ua. 4. Customer supplied heater contactor control elreult-120w240w1 ph max rating = 750VA InmshT75VA sealed; 24v1I ph max rating = 2401A irvushl60VA sealed. 0 AVERTISSEMENT VOLTAGE HASARDEUXI DECONNECTEZ TOUTES LES SOURCES ELECTRIQUES INCLUANT LES DISJONCTEURS SITUES A DISTANCE AVANT D•EFFECTUER UENTRETIEN. FAUTE DE DECONNECTER LA SOURCE ELECTRIQUE AVANT D'EFFECTUER UENTRETIEN PELT ENTRAINER DES BLESSURES CORPORELLES SEVERES OU LA MORT. IMPORTANT! DO NOT ENERGIZE UNIT UNTIL CHECK-OUT AND START-UP PROCEDURE HAS BEEN COMPLETED W 3 a c UO c- oo -4 L St Lucie Church 40T Rapt /— May 10, 2017 Tag Data -Performance Clin, ! Changer (Qtv:1l Item Tag(s) Qty Description Moi r lumber Spec Number JAHU-3 B1 K89K30715 1 Performance Climate Changer(CSAA CSAA025UA Product Data - Performance Climate Changer Item: B1 Qty: 1 Tag(s): K89K30715 Unit level options Indoor unit Unit size 25 2.5in. integral base frame UL listed unit Multiple composite handles/latches 78.38 Unit length 56.50 Second level length Warranty Standard 1 year Parts warranty only Air mixing section (Pos #1) Air mixing section Reduced length mixing box Door- right side Front full face opening Bottom rectangular opening 2in. filter frame MERV 8 Pleated media -1 set (Fld) Coil section (Pos #2) Vertical coil Large Stainless steel drain pan Right side - drain connection Right side - coil supply Service panel coil connection side Unit coil height Cooling coil ' Refrigerant Type "UF" coil 6 rows 127 fins per foot nominal fin spacing Aluminum fins Delta flo H (Hi efficient) Internally enhanced Cu .016 (0.406 mm) 1/2in. tube diameter (12.7 mm) Galvanized steel coil casing Fan section (Pos #3) Fan section Supply fan Door- right side Outward swing 22in. diameter AF, H press Top -back discharge Right side. drive NEMA premium compliant ODP Voltage 200-208/3 15 HP 1800 RPM FLD = Furnished by Trane U.S. Inc. /Installed by Equipment Submittal Page 14 of 34 Others St. Lucie Church 40T Rep] "1 , -� May 10, 2017 Performance Data - Perform Jt Climate Changer Tags K89K30715 Unit level options Position Length in 78.375 Width in 80.000 Height in 126.500 Rigging weight(lb) 2905.3 Installed weight(lb) 2905.3 Actual airflow cfm 13500 Unit elevation ft 0.00 Shipping split 1 weight(lb) 453.0 Shipping split 2 weight(lb) 930.0 Shipping split 3 weight(lb) 1447.0 Fan section Position #3 Fan airflow cfm 13500 Overall ESP in H2O 1.500 Total static pressure in H2O 3.141 Fan pressure drop in H2O 1.500 Fan outlet velocity fNmin) 2436 Speed (rpm) 1627' Total brake horsepower h 12.186 Unit static efficiency % 54.85 Outlet area (sq ft 5:54 Motor hertz Hz 60 Coil section Position #2 Coil performance airflow cfm 13500 Coil face area (sq ft 24.97 Coil face velocity ft/min) 541 Air pressure drop in H2O 6.992 Coil rigging weight(lb) 353.0 Leaving dry bulb F 53.70 Leaving wet bulb F 53.45 Entering dry bulb F 80.00 Entering wet bulb F 67.00 Fluid volume al 15.76 Liquid temp entering TXV F 116.00 Saturated suction temperature F 48.20 Suction superheat F 8.00 Sensible capacity MBh 389.52 Total capacity MBh 560.00 Air mixing section Position #1 Opening 1 front - area (sq ft 29.03 Opening 1 bottom — areas ft 6.55 Opening 1 bottom - face velocity fNmin) 2063 Opening 1 bottom total pressure drop in H2O 0.000 Bottom inlet type Ducted Filter condition Mid-life Filter airflow cfm 13500 Filter area (sq ft 27.11 Filter face veloci ft/min 498 Filterpress ure dro in H2O 0.648 Total mixing section pressure drop in H2O 0.648 FLD = Furnished by Trane U.S. Inc. /Installed by Equipment Submittal Page 15 of 34 Others St Luclechurch 40T Repl J'1, - -- - 1, May 10, 2017 Mechanical Specifications Jormance Climate Changer Item: B7 Qty: 1 Tag(s): K89K30715 GENERAL Per ASHRAE 62.1 recommendation, indoor air handling units will be shipped stretch -wrapped to protect unit from- - in -transit rain and debris. Installing contractor is responsible for long term storage in accordance with the Installation, Operation, and Maintenance manual (CLCH-SVX07B-EN). Unit shall be UL and C-UL Listed. Supply fans within the scope of AHRI Standard 430 shall be certified in accordance with AHRI Standard 430. Unit sound" performance data shall be provided using AHRI Standard 260 test methods and reported as sound power. Trane, in providing this program and data, does not certify or warrant NC levels. These levels are affected by factors specific to each application and/or installation and therefore unable to be predicted or certified by Trane. Referto product data for speck fan footnote references. - Footnote 4: Sound Power Levels are in accordance with AHRI 260 Unit Construction All unit panels shall be 2" solid, double -wall construction to facilitate cleaning of unit interior. Unit panels shall be provided with a mid -span, no -through -metal, internal thermal break. Casing thermal performance shall be such that under 55OF supply air temperature and design conditions on the exterior of the unit of 81 OF dry bulb and 730F wet bulb, condensation shall not form on the casing exterior. All exterior and interior indoor AHU panels will be made of galvanized steel. Casing Deflection The casing shall not exceed 0.0042 inch deflection per inch of panel span at 1.00 times design static pressure. Maximum design static shall not exceed +8 inches w.g, in all positive pressure sections and -8 inches w.g. in all negative pressure sections. Floor Construction The unit floor shall be of sufficient strength to support a 300.0 lb load during maintenance activities and shall deflect no more than 0.0042 inch per inch of panel span. Unit base Manufacturer to provide a full perimeter integral base frame for either ceiling suspension of units or to support and raise all sections of the unit for proper trapping. Indoor unit base frame will either be bolted construction or welded construction. All outdoor unit base frames shall be welded construction. For indoor units, refer to schedule for base height and construction type. Contractor will be responsible for providing a housekeeping pad when unit base frame is not of sufficient height to properly trap unit._ Unit base frames not constructed of galvanized steel shall be chemically cleaned and coated with both a -rust -inhibiting primer and finished coat of rust -inhibiting enamel. Unit base height to be included in total height required for proper trap height. Insulation Panel insulation shall provide a minimum thermal resistance (A) value of 13 ft'-h "F/Btu throughout the entire unit. Insulation shall completely fill the panel cavities in all directions so that no voids exist and settling of insulation is prevented. Panel insulation shall comply with NFPA 90A. Drain Pan In sections provided with a drain pan, the drain pan shall be designed in accordance with ASHRAE 62.1. To address indoor air quality (IAQ) the drain pan shall be sloped in two planes promoting positive drainage to eliminate stagnant water conditions. Drain pan shall be insulated, and of double wall construction. The outlet shall be the lowest point on the pan, and shall be of sufficient diameter to preclude drain pan overflow under normally expected operating conditions. All drain pans connections shall have a threaded connection, extending a minimum of 2-1/2" beyond the unit base, and shall be made from the same material as the drain pan. Drain pan located under a cooling coil shall be of sufficient size to collect all condensate produced from the coil. Refer to Product Data for speck information on which sections are supplied with a drain pan, the drain pan material and connection location. FLO = Furnished by Trane U.S. Inc. /Installed by Equipment Submittal - Page 16 of 34 Others St Lucie Church 40T Repl '- - -- - May 10, 2017 Access Door Construction Access doors shall be 2" double wall construction. Interior and exterior door panels shall be of the same construction as the interior and exterior wall panels respectively. All doors shall be provided with a thermal break construction.of door panel and door frame. Gasketing shall be provided around the full perimeter of the doors to prevent air leakage. Surface mounted handles shall be provided to allow quick access to the interior of the -functional section and to prevent through cabinet penetrations that could likely weaken the casing leakage and thermal performance. Handle hardware shall be designed to prevent unintended closure. Access doors shall be hinged and removable for quick easy access. Hinges shall be interchangeable with the door handle hardware to allow for alternating door swing in the field to minimize access interference due to unforeseen job site obstructions. Door handle hardware shall be adjustable and visually indicate locking position of door latch external to the section. Door hinges shall be galvanized. All doors shall be a minimum of 60" high when sufficient height is available or the maximum height allowed by the unit height. Door handles shall be provided for each latching point of the door necessary to maintain the specified air leakage integrity of the unit. Optionally for indoor AHUs and as standard on outdoor AHUs, outward swing doors are provided with a single handle linked to multiple latching points. An optional shatterproof window shall be provided in access doors where indicated on the plans. Window shall either be single pane, or thermal dual pane, as defined on schedule. Window shall be capable of withstanding unit operating pressures and shall be safe for viewing UV-C lamps. Refer to Product Data for speck information on which sections are supplied with an access door, the door location, a single handle and a window. MIXING SECTION A mixing section shall be provided to support the damper assembly for outdoor, return, and/or exhaust air. The following specifications apply only to units with outside air and return air dampers, with actuators. The 5 year warranty applies only to these items. This unit contains Economizer that meets or exceeds all mandatory requirements prescribed by Title 24, including but not limited to: - 5 yr parts only warranty - Successfully tested to 60,000 Actuations - Less than 10 cfm/sq.ft. of damper leakage at 1" WG per AMCA 500L Filters Mixing sections shall be provided with a filter rack as indicated in the Product Data and As -Built sections of the submittal 2-inch pleated media filters made with 100% synthetic fibers that are continuously laminated to a supported steel -wire grid with water repellent adhesive shall be provided.. Filters shall be capable of operating up to 625 fpm face velocity without loss of filter efficiency and holding capacity. The filters shall have a MERV 8 rating when tested in accordance with the ANSI/ASHRAE Standard 52.2. COIL SECTION WITH FACTORY INSTALLED COIL The coil section shall be provided complete with coil and coil holding frame. The coils shall be installed such that headers and return bends are enclosed by unit casings. If two or more cooling coils are stacked in the unit, an intermediate drain pan shall be installed between each coil and be of the same material as the primary drain pan. Like the primary drain pan, the intermediate drain pan shall be designed being of sufficient size to collect all condensation produced from the coil and sloped to promote positive drainage to eliminate stagnant water conditions. The intermediate pan shall begin at the leading face of the water -producing device and be of sufficient length extending downstream to prevent condensate from passing through the air stream of the lower coil. Intermediate drain pan shall include downspouts to, direct condensate to the primary drain pan. The outlet shall be located at the lowest point of the pan and shall be sufficient diameter to preclude drain pan overflow under any normally expected operating condition. In lieu of a door, an easily removable service panel shall be provided in sections as specified, to facilitate access to unit for periodic servicing, or for removal and replacement of coils. Removal of service panel will not impact the structural integrity of the unit. No casing penetrations supplied for hydronic drain and vents: If required, piping contractor will need to drill drain and vent penetrations using factory located features provided in coil panel. Refrigerant Cooling Coils The coils shall have aluminum fins and seamless copper tubes. The fins shall have collars drawn, belled, and_finnly bonded to tubes by mechanical expansion of the tubes. Suction and liquid line connections shall extend to the, unit exterior. The coil casing may be galvanized or stainless steel. Refer to the Product Data section of the submittal for the FLO = Furnished byTrane U.S. Inc. /Installed by Equipment Submittal Page 17 of34 Others St Lucie Church 40T Repl /",, - May 14 2017 coil casing material. The coils shall be proof -tested to 450 psig and leak -tested to 300 psig air pressure under water. After testing, the inside of the coils shall be dried, all connections shall be sealed, and the coil shall be shipped with a charge of dry air. Suction headers and liquid connections shall be constructed of copper tubing with connections penetrating unit casings to permit sweat connections to refrigerant lines. The coils shall have equalizing vertical distributors sized according -to the capacities of the coils. Coils are certified in accordance with the AHRI Forced -Circulation Air -Cooling and Air -Heating Coils Certification Program which is based on AHRI Standard 410 within the Range of Standard Rating Conditions listed in Table 1 of the Standard. Certified units may be found in the AHRI Directory at www.anddirectory.org. Refrigerant coil tubes are 1/2" [13mm] OD, 0.016" [0.406mm] thick, internally enhanced copper. AF FAN SECTION The fan type shall be provided as required for stable operation and optimum energy efficiency. The fan shall be a double -width, double -inlet, multiblade-type, airfoil (AF) fan. The fan shall be equipped with self -aligning, antifriction bearings with an L-50 life of 200,000 hours, as calculated per ANSI/AFBMA Standard 9. For any bearing requiring relubrication, the grease line shall be extended to the.fan support bracket on the drive side. The fan shall be statically and dynamically balanced at the factory as a complete fan assembly (fan wheel, motor, drive, and belts). The fan shaft shall not exceed 75 percent of its first critical speed at any cataloged speed. Fan wheels shall be keyed to the fan shaft' to prevent slipping. The fan shafts shall be solid steel. The fan section shall be provided with an access door on the drive side of`the fan. Fan performance shall be certified as complying with AHRI Standard 430. Drive Service Factor The drives shall be constant speed with fixed -pitch sheaves. The drives shall be selected at a minimum 50 percent larger than the motor brake horsepower (1.5 service factor). Motor Frame The motor shall be mounted integral to the isolated fan assembly and furnished by the unit manufacturer. The motor is mounted inside the unit casing on an adjustable base to permit adjustment of drive belt tension (not applicable for direct drive plenum fans). The motor shall meet or exceed all NEMA Standards Publication MG 1 requirements and comply With NEMA Premium efficiency levels when applicable except for fractional horsepower motors which are not covered by the NEMA classification. The motor shall be T-frame, squirrel cage with size, type, and electrical characteristics as shown on the equipment schedule. Refer to the Product Data section for selected fan motors within each unit. Two -Inch Spring Isolators The fan and motor assembly (on sizes 10 to 120) shall be internally isolated from the unit casing with 2-inch (50.8 mm) deflection spring isolators, fumished and installed by the unit manufacturer. The isolation system shall be designed to resist loads produced by external forces, such as earthquakes, and conform to the current IBC seismic requirements. Multiple Belt Drive The fan section with a belt -driven fan shall be provided with a multiple belt drive. Refer to the Product Data section of the submittal for selected fans with multiple belt drives. Lifting Instructions The air handling units must be rigged, lifted, and installed in strict accordance with the Installation, Operation, and Maintenance manual'(CLCH-SVX07G-EN). The units are also to be installed in strict accordance with the specifications. Units may be shipped fully assembled or disassembled to the minimum functional section size in accordance with shipping and job site requirements. Indoor units shall be shipped on an integral base frame (variable from the standard 2.5" to 87height) for the purpose of mounting units to a housekeeping pad and providing additional height to properly trap condensate from the unit. The integral base frame may be used for ceiling suspension, external isolation, or as a housekeeping pad. Indoor sizes 3 to' 30 will also be shipped with a shipping skid designed for forklift transport. Refer to the unit As -Built or Product Data section of the submittal for the base frame height of each unit. All units will be shipped with an integral base frame designed with the necessary number of lift points for safe installation. All lifting lugs an- to be utilized during lift. The lift points will be designed to accept standard rigging devices and be removable after installation. Units shipped in sections will have a minimum of fourpoints of lift. FLD=FurnishedbyTraneU.S.Inc. /Installedby Equipment Submittal Page IS of34 Others Formaneuvadng purposes, Indude 1.125 Inch as to each 27" 27" panel gange. Flange will not add to overall Installed unit length shown. I 7PBK discharge opening 28.380 x 28.380 2 Housed fen - 221n' diameter AF, H press Supply fan 15 hp 200-20813 3 Cooling mil -B Coil type OF Doors 27 width x 55 height 1 a PNmuic.G O m3 14 include 1.1251nehes to each ship spl It length for overlapping panel flange. Flange will not add to overall Installed unit length shown. 1 TPBK discharge opening A 28.380 x 28.380 2 Housed fan -22in. diameter AF, H press Supply ten 15 hp 200-208r3 3 Co ling coil - 6 Coil type UF 4 1"N.P.T.E N Doors = 27 width x 55height pp 3 to r. C4 w, V go . N go M PorDvmuseC � N O 'I SL Lucie Church 40T Rep] - - - - -- _ - May 10, 2017 As -Built - Performance Clim', 'Thanger Item: B1 Qtv: 1 Tan(s): K89K30715 2112 Overall Elevation View: Right - Shipping splits indicated by bold outline. - Measurements in inches For maneuvering purpose; Include 1.125 inches to each ship split length for overlapping panel Huge. Flange will not add to overall Installed unit length Pas# Module Length Weight 3 Fan section 56112 1447.00 2 Coil section 46 118 930.00 1 Air mbdng section 32 318 453.00 Installed Unit Weight 2830.00 Ibs Basil Inches anoiu amnom TRIMS W. anon Ci v FLO = Furnished byTmne U.S. Inc. /Installed by Equipment Submittal Page 21 at 34 Others St. Lucie Church 40T Repl / � -- - -- - - _ _ - - May 10, 2017 As -Built - Performance Ulm?__, -changer ` Item: B1 Qty: 1 Tag(s): K89K30715 t y G _ 1 T 3 A 32 318 fit 8 1/8 Right Side of Unit . Detailed Plan View: Top -Measurements in inches Left Side is in inches ' 7WAAIff o FLO = Furnished by Tune U.S. Inc. /Installed by Equipment Submittal Page 22 of 34 Others St Lucie Church 40T Repl - _ - May 10, 2017 As -Built - Performance Ciur Changer Item: B1 MY: 1 Tagts): K89K30715 14 3/4-mom 3 r "tx 4 N Detailed Elevation View: Right -Measurements in inches Data /2 n inches 'l8 aW7 0e lame, PbtEfly Cnub FLO = Furnished by Trans U.S. Inc. /Installed by Equipment Submittal Page 23 of 34 Others St. Lucie Church 40T Rapt May 10,, 2017 As -Built - Performance Clim ,,hanger Item: B1 Qty: 1 Tag(s): K89K30715 Detailed Elevation View: Front -Measurements in inches Detail ies law M1,WiNOLIlnvb 06yV FLO= Furnished byTrans U.S.Inc. /Installed by Equipment Submittal Page 24of34 Others cdon Can. Sudan Can. ]1st. Id Dist. Call connection view: Right. Measurements in inches NPTI : National Pipe Thread Internal Connection NPTE : National Pipe Thread External Connection m Und size: 25 ob Name: jUnft Casing: On Double Well Faam V m rodud gran :Indoor unit Pm osal Numher. O me ral base frame: 2.5in. into ral basefreme dual airflow: 13500 cfm Vt PaInt ttnnaintedaiald nnbdad Sqlmq OfCP' .............. _____... _____.. F.b.. nO.— -d 'rR yp 75 3/8 Coil connection View: Left- Measurements in Inches NPTI : National Pipe Thread Internal Connection NPTE : National Pipe Thread External Connection c 3 N V Unit size: 25 Job Name: Und Casing: 2in Double Wall Foam �o roduct rou : Indoor undt _ _ Pro osal Number. ®� e m ,. dual airflow: 13500 cfm v.e„moo»m. a.m. St. Lucie Church 40T Repl Fan Curve - Performance CV 1e Changer Item: B1 Qty: 1 Tag(s): 1(hu-M50715 May 10, 2017 O 2 125 d 10.0 CL 7.5 co _ 5b ~ 25� Mt' Supply Size 25Vertical Iaaw-' hruCauierSvwl 22inch AF Hpress - Single Fan �M_�/�_.70 F/ `�\ \�I ffi RMAQ It „ •,ice ►� a �►� Y�ia031ININ11rle 0 w 10000 15700 2M 2 000 Arflcv(cfrn) Size25VeticalL7raw-TtmCbuterSw1d 22kx:hAF Hpress Sard Rmer Lewis are in accadm=withAHRI250. at 129t 230-Iz 800Hz 1 Wk 2M-k 41ft 81ft 87 85 83 77 74 63 48 47 86 84 83 83 75 70 64 59 95 99 101 96 94 87 82 78 PLO = Fumished by Trane U.S. Inc. /Installed by Equipment Submittal Page 27 0134 Others St. Lucie Church 40T Repl - May. 10, 2017 Accessory - Performance C' ite Changer Item: B1 Qty: 1 Tag(s): Kbmir:40715 Base Detail FLO = Furnished by Trane U.S. Inc. /Installed by Equipment Submittal Page 28 of 34 Others EXAMPLE UNIT - NOT CONFIGURED AS SELECTED. Filter mixing box 7114-wid" II' Fan I L 125 \C Service Clearance for Control Box ass Note: At a minimum, these clearance dimensions are Component All recommended on one side of the unit for regular - Sizes service and maintenance. Referto ao-bu0t submittal for locations of items such as filter access doom, G (Control box HV or 9 F coil, piping connections, motor locations, etc. LV > 18 pt or UC600 36 sufficient clearance must be provided on all sides of controller) unit for removal of panels or sectioMo-section G (control box LV 18 13 attachment. Clearance for starters. VFOs, or other high -voltage devices must be provided per NEC pt or less) requirements. 21 25 30 35 40 50 57 Component 3 4 6 8 10 12 14 17 21 25 30 35 40 5o 57 66 80 100 120 TALL TALL TALL TALL TALL TALL TALL A (filter) 48 48 48 48 48 4B 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 52 55 58 58 B (coil, humidifier) 48 59 59 66 77 82 87 87 95 77 95 77 109 87 115 96 128 96 141 110 141 110 156 156 170 197 B (staggered coil) WA NIA N/A NIA N/A N/A N/A N/A 67 N/A 67 WA 76 N/A 80 N/A 88 N/A 96 N/A 96 N/A 105 105 113 129 C (UV Lights) 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 52 56 58 58 C (TCAC) 43 59 59 63 75 81 83 83 58 75 58 1 75 1 83 83 75 59 83 83 83 83 1 83 1 83 83 83 75 83 D (Extemal Starter _ VFD, LV box or 61 61 61 61 61 61 61 61 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 Overload box) D (Intemal Starter or 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 E (fan) 48 48 48 48 51 54 58 61 60 1 51 1 66 51 66 58 1 66 1 60 1 70 60 1 77 1 66 1 77 1 66 1 93 93 1 1011 101 F (Gas Heat WA WA 89 90 108 100 100 105 115 WA 1 115 WA 118 N/A 136 NIA 140 WA 156 WA 156 WA 170 179 . 180 NIA Ext Vestible) F (Gas Heat WA WA 56 63 74 79 84 84 92 NIA 92 WA 106 N/A 1 112 1 WA 1 125 1 WA 1 138 1 WA 138 WA 1 153 153 1 167 194 Int Vestible) N O V St. Lucie Church 40T Repl -_ Accessory - Performance Cl' `te Changer Item: B1 Qty: 1 Tag(s): KBaL.-_0715 May 10, 2017 EXPANDI GRID BACKIN( E 11 lip Hit/8 STANDARD CONSTRUCTION 1. 100 % Synthetic White Un-Dyed Media 2. 10.0 Pleats Per Fool 3. Expanded Metal Pleat Supports 4. Moisture Resistant Beverage Board Frame 5. Double Wall Frame NOTES 1. MERV 8-A Per ASHRAE 52.2-2007 Appendix J. 2. Final Resistance: 1/d' W.G. 3. Rated Velocity. 500 FPM 4. Class 2 Filter Per U.L. Standard 900 5. Maximum Operating Temperature: 225 DEG. F MODEL NUMBER NOMINAL SIZE IN.WXHXD ACTUAL SIZE IN.W X HXD RATED AIRFLOW CFM INITIAL RESISTANCE IN. W.G. MEDIAAREA SO Fr. MX40-STD2-217 10 X 20 X 2 9-1/2 X 19-12 X 1-314 700 0.29 4.7 MX40-STD2-220 12 X 20 X 2 11-12 X 19-1/2 X 1-3/4 840 0.29 5.5 MX40-STD2-210 12 X 24 X 2 113/8 X 23-38 X 1-3/4 1000 0.29 6.2 MX40-STD2-239 i4 X 20 X 2 13-12 X 19-1/2 X 1-3/4 980 0.29 5.7 MX40-2TD2-241 14 X 25 X 2 13-12 X 24-1/2X 1-3/4 1220 0.29 7.1 MX40STD2-245 15 X 20 X 2 14172 X 19-12 X 1-3/4 1050 0.29 6.2 MX4D-STD2-201 16 X 20 X 2 15-12 X 19-12 X 1-3/4 1120 0.29 6.7 MX40-STD2-216 16 X 24 X 2 15318 X 2338 X 13/4 1340 0.29 6.0 MX40STD2-202 16 X 24 X 2 15-12 X 24-12 X 13/4 1400 0.29 8.0 MX40-STD2-280 15 X 20 X 2 17-12 X 19-1/2 X I V4 1250 029 7.8 MX40STD2-212 18 X 24 X 2 17-38 X 2338 X 13/4 1600 0.29 9.3 MX40STD2-285 18 X 25 X 2 17-12 X 24-12 X 13/4 1570 0.29 9.7 MX40STD2-2D3 20 X 20 X 2 19-12 X 19-12 X I V4 1400 0.29 8.3 MX40STD2411 20 X 24 X 2 1938 X 2338 X 13/4 1670 0.29 9.9 MX40-STD2-204 20 X 25 X 2 19.1/2 X 24-12 X 1-V4 1750 0.29 10.3 MX40-STD2-205 24 X 24 X 2 233/8 X 2338 X 13/4 2000 0.29 11.7 MX40-STD2-225 25 X 25 X 2 24-12 X 24-12 X 13/4 2170 0.29 13.6 FLO= Fumishedby Trane US. Inc. /Installedby Equipment Submittal Page 30 Df34 Others St. Lucie Church 40T Rep[ Accessory - Performance C''te Changer Trap Schedule Item: B1 Qty: 1 Tag(s): K89K30715 Drain pan trapping for section under negative pressure L = H +J + pipe diameter where: H = 1 inch for each inch of negative pressure (loaded filters) plus 1 inch J=%H Drain pan trapping for section under positive pressure L = H +J + pipe diameter where: H = 1/2 inch (minimum) J = 3� inch plus the unit positive static pressure at coil discharge (loaded filters) May 10 2017 Entering Ext. Static Discharge Ext. Static Drain pan Recommended Trap Dimensions Selected Unit Unit Pressure Pressure Section H J L BaseraI, Ta s Size in H2O in H2O Location in in in Hei ht A. 1<891<30715z Unit size 25 0.750 0.750 Coil s2ection 3.742 1.871 6.614 MOO To ensure proper condensate trapping the field installed housekeeping pad height is the responsibility of the contractor. 2 The external static pressure used for fan selection was assumed to be divided 50% to entering duct external static pressure and 50% discharge external static pressure. Trane Others rage st St. Lucie Church 40T Rapt _ _ - May 10, 2017 Accessory Performance Ch ' e Changer Filter Schedule Item: B1 Qty: 1 Tag(s): K89K3O715 Unit Unit Filter Filter Filter Filter MERV Filter Filter Ta s Size Location Arrangement Depth Type Rating Quantity Size K89K30715 Unit size 25 Air mixing _ 2in. filter Pleated media MERV 8 3 2 12in.x24in. section [1] frame - run set 6 20ln.x20in. 0in.x20in. PLO = Furnished by Trans U.S. Inc. /Installed by Equipment Submittal Page 32 of34 Others St. Lucie Church 40T Repl .. Field Wiring - Performance 1 ate Changer MCA MOP Schedule Item: B1 Qty: 1 Tag(s): K89K30715 Unit Ta s Circuit Circuit Description Volta a/Phase/Hz I MCA K89K30715 1 Supply fan 200-208/3/60 tAMOP(A) 54.2 90.00 motors May 10, 2017 FLD = Furnished by Trane U.S. Inc. /Installed by Equipment Submittal Page 33 of 34 Others May 10, 2017 This is a report to help you locate field installed options that arrive at the jobsite. This report provides part or order numbers for each field installed option, and references it to a specific product tag. It is NOT intended as a bill of Product Family - Air -Cooled Condensing Units (Commercial) Item Tag(s) I City I Description I Model Number Al 1.189.181711 11 140 Ton.Air-Cooled Condensin Unit IRAUJC40EC Field Installed Option Description PartfOrdering Number Unitspring isolators Product Family - Performance Climate Changer Item Ta s Q Description Model Number Sec Number Bi K89K30715 1 Performance Climate Changer CSAA CSAA025UA I AHU-3 Field Installed Option Description Part/OrderingNumber Pleated media - 1 set FLD = Furnished by Trans U.S. Inc. /Installed by Equipment Submittal Page 34 of 34 Others