Trane U.S. Inc. is pleased to provide the enclosed submittal for your review and approval.
Product Summary
Qty Product
1 Air -Cooled Condensing Units (Commercial)
1 Performance Climate Changer
Chris Cowling
Trane
6965 Vista Parkway North, Suite 11
West Palm Beach,. FL 33411
Phone: (561) 683-1521
Cell: (561) 683-1521
Fax: (561) 697-8714
Please Note;
The attached information describes the equipment we propose to
furnish for this project, and is submitted for your approval.
Product performance and submittal data is valid fora period of 6 months
from the date of submittal generation. If six months ormore has elapsed
between submittal generation and equipment release, the product
performance and submittal data will need to be verified. It is the
customers responsibility to obtain such verification.
• Contractor to review submittal for accuracy before rdering.
FIclu
ST LUCIE COUNTY BUII.DLNQDIVISION
REVIEWED FOR C LTAI3CE
REVI ST Y Q
DATE '
PLANS ANZI PERMIT MUST BE 8761'1�OON.70B
OR NO INSPECTION %11, BE MADE.
J11OBS146148438141REV Submittal - 40T AHU CU - St Lucie Church 5-10-17.doc
Table Of Contents
ProductSummary ........................................................................................................................... I
Air -Cooled Condensing Units (Commercial) (Item Al)
............................................................... 3
TagData ... .........................................................................................................................
; .................... 3
Product Data
3
Mechanical Specifications ........................................................................................................................
4
UnitDimensions ........................................................................................
5
Weight, Clearance & Rigging Diagram ..........................................
d .......................................................... 8
Accessory................................. w ......................................................................................
....................... 9
FieldWiring ............................................................................................................................................
10
PerformanceClimate Changer (Item BI) ......... . * * ............. * ........... ** ....... ...........................14
"
TagData ................................................................................................................................................
14
ProductData ..........................................................................................................................................
14
PerformanceData ............ * ................... ***"**'*" ..... ** ... *'*"**'*'*"*""*"*"****"******
.... * ........... ****"* ......... * ........ 15
MechanicalSpecifications ...................................... ...................................
*****'** .... * ... *'***'*"*"*"* ... **'*'***' 16
As -Built .......................................................................................................
*""** ... * .......... 19
FanCurve ....................................................................................................
*** ...... *'**'**'** ..... * ....... ... 27
Accessory...............................................................................................................
FieldWiring ............................................................................................................................................
* ..... **'**'* ....... ***'*"**'* 28
33 SCANNED
Field Installed Options - PartfOrder Number Summary
Air Condensing Units
............................................................34 St BY
Lucie County
-Cooled (Commercial) ..........................................................................................
34
Performance Climate Changer ............................ ..................................................................................
34
St. Lucie Church 40T Repl '- May 10. 2017
Tag Data -Air-Cooled Conii,._ . iaq Units (Commercial) (Qtv: 11
Item
Tags)
I Qt_y
I Description I Model Number
JA1
1.189.181711
11
140 Ton Air -Cooled Condensing Unit IRAIJJC40EC
Product Data - Air -Cooled Condensing Units (Commercial)
Item: Al Qty: 1 Tag(s): J89J81711
Condenser Air -Cooled
R41 OA Development Sequence
40 Ton Unit
200 Volt 60 Hertz 3 Phase
Constant Volume Control
Standard ambient control
cULus approval
Suction service valve .
Unit spring isolators (Fld)
2nd-5th Year Replacement Compressor Warranty
Factory Assisted Start-up
FLD = Furnished by Trans U.S. Inc. l Installed by Equipment Submittal Page 3 of 34
Others
St Lucie Church 40T Rep[ r _, - _ May 10, 2017
Mechanical Specifications - _._ —'Cooled Condensing Units (Commercial
Item: Al Qty: 1 Tag(s): J89J81711
General - R410
All condensing units are factory assembled and wired. Unit frames are constructed of 14 gauge welded galvanized steel
with 14 and 16 gauge galvanized steel panels and access doors. The unit surface is phbsphatized and finished with an
air-dry paint to withstand 500 hours of continuous salt spray solution in accordance with ASTM B117. Decorative
louvered panels provide condenser coil protection.
Compressors - R-410A .
Trans 3-D Scroll compressors have simple mechanical design with only three (3) major moving parts. Scroll type
compression provides inherently low vibration. 3-D compressors provide a completely enclosed compression chamber
with no leakage paths. The compressor is suction gas cooled, direct drive, 3600 RPM hermetic motors. The Scroll
compressor includes a centrifugal oil pump, oil level sight glass, and an oil charging valve.
Refrigerant Management - R410A
Split systems can have significantly more refrigerant than packaged systems and thus require controls to reliably
manage this excess refrigerant. Each compressor shall have crankcase heaters installed, properly sized to minimize
the amount of liquid refrigerant present in the oil sump during off cycles. Additionally, the condensing unit shall have
controls to initiate a liquid line solenoid closure when each refrigerant circuit shuts down. To be operational, the liquid
line requires a field supplied and installed isolated solenoid valve within 10 feet of the evaporator
Note: Under extreme conditions, R410a refrigerant can present special challenges with piping and system design.
Whenever refrigerant line set lengths approach 150 equivalent feet and/or design ambient temperature exceeds 115
degrees F, contact your Trans Account Executive to review application requirements.
Unit Control - R410A
Factory provided 115-volt control ciFcuit. includes fusing and control power transformer. The unit is wired with magnetic
contactors for compressor and condenser motors, three -leg solid-state compressor overload protection, and high/low
pressure cutouts. Charge isolation, reset relay and anti -recycle compressor timer is provided. Across -the -line start is
standard.
Dual Circuit, Condenser Coils for 40-60 Ton Units - R-410A
Condenser coils are dual circuited having an Aluminum Microchannel design. The coils are burst tested and leak tested.
Factory installed liquid line service valves are standard.
Dual Refrigerant Circuit w/Four Capacity Stages for 40-60 Ton Units - R410A.
Each unit has dual refrigeration circuits. Each circuit has two (2) compressors manifolded together utilizing a passive oil
system. Each unit has four capacity stages. Capacity modulation is accomplished by turning compressors on and off.
.Condenser Fans - R-410A
Condenser fans are direct driven with motors having thermal overload protection and permanently lubricated ball
bearings.
Standard Ambient Control - R-41CA
Standard ambient control allows unit operation from 40 F to 115 F 14.5 to 46.1 C].
Spring Vibration Isolators - R-410A
Spring vibration isolators are supplied for field installation under the unit base to minimize transmission of unit vibrations.
Field Installed; 30% Bleed Valve TXV
Installation shall require use of 30% bleed, Thermal Expansion Valves. Valves shall be field supplied and field installed.
Quantity and size shall. be determined by the application.
Note: Liquid line solenoids are required for all applications. Trim solenoids cannot be used
FLO = Fumished by Trane U.S. Inc. /Installed by Equipment Submittal Page 4 of 34
Others
St. Lucie Church 40T Repl --- - --- - - - - --May'10, 2017
Unit Dimensions - Air-Coolei . ,ndensing Units (Commercial)
Item: Al Oty: 1 Tag(s): J89J81711
GRILLE
3/4' X 6
MTG HOLES
5
O 36IN'
.. 889116'
NOTES:
1. SEE CONNECTION DRAWING FOR CONNECTION LOCATION AND SIZES.
2. LOW AMBIENT DAMPER ONLY COMES WITH SELECTED UNIT.
3. PRONT & BACK OF UNIT CLEARANCE 72'� LEFTS RIGHT SIDE OF UNIT CLEARANCE 42'
12' X
12'X 29
FRONT (SEE NOTE
361�,
FOR CLEARANCES)
1 3/4' KO LOI
pir VOLTAGE (3
1
� Ll 114
DOOR 431/4' W/
180 DEG SWING
CONTROLPANEL
(SEE DETAIL
FAN GRILLE
1
0
32 &
BOTTOM OF CONTROL
BOX (SEE DETAI
6'
79
11/4'x:
SLOT F(
VOLTCUNIHUL
40 TON UNIT
DIMENSIONAL DRAWING
DETAIL A
BOTTOM OF CONTROL BOX
INEL
CONDUIT
vN POWER
IS11e'
FLD = Furnished by Trane U.S. Inc. /Installed by Equipment Submittal Page 5 of 34
Others
St. Lucie Church 40T Repl— - May 10, 2017
Unit Dimensions -Air-Coole: _,ondensing Units (Commercial)
Item: Al Qty: 1 Tag(s): J89J81711
a
CONTROL PANEL (LEFT) SIDE VIEW OF UNIT
CONNECTION DRAWING
40 TON UNIT
NOTES:
1. VERIFY WEIGHT, CONNECTION, AND ALL DIMENSION WITH
INSTALLER DOCUMENTS BEFORE INSTALLATION
(OPTIONAL)
-1 SW O.D.
'SUCTION LINE
PPN 50E ACCESS
ORIENTATION VIEW OF UNIT
ISOMETRIC DRAWING
BACKMEW OF UNIT
CONNECTION DRAWING
IS"
FLO = Furnished by Trane U.S. Inc. /Installed by Equipment Submittal Page 6 of 34
Others
St. Lucie Church 40T Repl 1' - May 10, 2017
Unit Dimensions - Air-Coole _ 'mdensing Units (Commercial)
Item: Al Qty: 1 Tag(s): J89JS1711
GENERAL ELECTRICAL DATA
GENERAL
OUTDOOR MOTOR
Tonnage/kW:
40 L140.0 Will
Number.
4
Unit Operating Voltage Range:
180-220
Horsepaser.
1.0
Unit Primary Voltage:
200
Motor Speed(rpm):
1,140
Unit Hens
60
Outdoor Motor Full Load amps:
4.1
Unit Phase:
3
Outdoor Motor Locked Rotor amps:
20.7
Minimum ClrcultAmpaoty. (3)
193.0
Maximum Overcurrent Protection Device:
(2) 225.0
Recommended Dual Element Fuse: (4)
225.0
COMPRESSOR
REFRIGERANT
Ctrcu@A1/A2- Circuit 81182
Tom (as):
10.0110.0-10.0110.0
Type:
R410A
Compressor Pa dLoad Amps (as):
41.4/41A-41.4/41.4
Number of Circuits:
2
Lockett Rotor Amps (ad):
267.01261.0 - 257.01267.0
Condenser Storage Capacity.
23.511,
Refrigerant Operating Charge (Condenser Only):
23.7 lb
Notes
1. Electrical data is foreaes individual motor.
2 Maximum overcurrent protection permitted by nec 440-22 is 225 percent of largest compressor motor RLA plus the remaining
motor RLA and FLA values.
3. Minimum circuit ampacity is 125 percent of the largest cmnpressar motor RLA plus the remaining motor RLA and FLA values.
4. Recommended dual element fuse s® is 150 percent of the largest compressor motor RLA plus the remaining motor RLA and
FLA values.
5. Loral codes may take precedence.
FLD = Furnished by Trane U.S. Inc. /Installed by Equipment Submittal Page 7 of 34
Others
St Lucle Church 40T Repl May 10, 2017
Weight, Clearance & RigginL — P igram - Air -Cooled Condensing Units (' dmercial)
Item: Al Qty: 1 Tag(s): J89JB1711
)LES
40 TON RIGGING
e\
WEIGHTS AND LOAD POINTS
OPERATING: 2532.01b
`CLENRANCE
SHIP
LINE
POINTS 1: 452.30
I
77
I
LOAD POINTS 2: 415.7 lb
LOAD POINTS 3: 440.31b
I^—X
I
LOAD POINTS 4. 403.71b
LOAD POINTS 5: 391.8 b
LOAD POINTS fi:
`2
4
8
'ALL WEIGHTS ARE
r_
I
APPROXIMATE
Y
i
I
CENTER OF GRAVITY
I
I
X. 43 aW
CONTROL
Y. 4T
I
I
BOX
I
ADD WEIGHTS
/.3
SHIPPING: RI
oT
a5
I.
OPERATING: I4I
42
42"
NOTES:
1. OPERATING WEIGHT INCLUDES REFRIGERANT, OILAND WATER
I
I
2. SHIPPING WEIGHT INCLUDES REFRIGERANT AND OIL CHARGES
CENTER OF GRAVITY
3. THEACTUALWEIGHT IS SHOWN ON THE NAMEPLATE. WEIGHT.
72"
I
SHOWN REPRESENT TYPICAL SHIPPING AND OPERATING WEIGHTS FOR
I
I
THE UNITSELECTED. '
4. ADD WEIGHTTO TOTAL WEIGHT OF UNIT
FRONT OF UNIT
I
5, IF UNITS IS INSTALLED IN A WELL, THE DEPTH OFTHE WELL MUST NOT
EXCEEDTHETOPHEIGHTOFTHEUNIT. THETOP OF THE UNIT MUST
---_-------
- -
--�
HAVE UNRESTRICTED AIRFLOW. PLEASE REFERENCE RECOMMENDED
CLEARANCES.
WARNINGI
40TON CENTER OF GRAVITY AND CLEARANCES
TO PREVENT INJURY OR DEATH AND POSSIBLE EQUIPMENT DAMAGE
DO NOT USE CHAIN (CABLES)OR SLINGS EXCEPT AS SHOWN
WEIGHTAND RIGGING
AND USE CABLES STRONG ENOUGH TO SUPPORT UNIT WEIGHT.
TEST LIFT UNIT TO ENSURE PROPER BALANCE AND RIGGING.
FLO = Furnished by Trans U.S. Inc. /Installed by Equipment Submittal Page 8 of 34
Others
St Lucie Church 40T Repl - - _ _ May 10. 2017
Accessory -Air-Cooled Con: sing Units (Commercial)
Item: Al Qty: 1 Tag(s): J89J81711
NEOPRENE PAD
NOTES:
1. MOUNTING LOCATIONS CORRELATE WITH MOUNTING
LOCATIONS SHOWN IN CLEARANCE DRAWING.
2 VERIFY WEIGHT, CONNECTION, AND ALL DIMENSION
WRH INSTALLER DOCUMENTS BEFORE INSTALLATION
MOUNTING LOCATIONS
LOCATION 1
LOCATION
'CPID510
LOCATION
'CP1D510
LOCATION
'CPID510
LOCATION
'CP/D510 '
LOCATIONS
'CPID510
MOUNTING ISOLATOR (SPRING)
DIMENSIONAL ACCESSORIES DRAWING
FLO = Furnished by Trane U.S. Inc. llnstalled by Equipment Submittal - Page 9 R 34
Others
St Lucie Church 40T Repl 1 -, _ May 10, 2017
Field Wiring - Air -Cooled Col•, _ •.,ising Units (Commercial)
Item: Al Qty-. 1 Tag(s): J89J81711
Required Components for Refrigerant Circuits
Trans Condensing Unit
Pon
All items numbered
are field supplied.
Acmaa Port
ahutaftNehre 1. SuNsn �3. Shutoff Valve
Llna 2. Suction Line
(Unit Option) Filer
ShvLae 4. Liquic
Valve Velvs VaM Line
Evaporator Call
9. Maisueand S. Shutoff 6. Access
S. ShutaH
Expansron Valve 6. Soleni
Valve
Fmstal
SUCTION LINE
1. Interconnected Tubing (Suction Ime)
Maxhnum also feet Ifcondenser is above evaporator(if rbemare more than 50feet, me app6cotion must be viewedbyTrene) Referto SS-APG012-EN
farmoredetails
2. Suction Line
Filter Drier 1 / do suction filler should be the replaceabe-com type, and a clean core should be Installed after the system is cleared up
3. Shut-0H Valve
Manual ball valves for 2 118'-tubing.
LIQUID LINE
4. Interconnected Tubing (Liquid Line)
Refartu applications guide SS-APGO12 - EN forvertiral S hm®ntal piping limitations.
S. Shut -Off Valve
2 Manual ball valves
6. Access Port
Part used to delemime suction pressure. This port is usually Schmeder valve with a core.
7. Liquid Lire
Filter Drier 1 I ckt liquid filter should be the replaceablecom type, and a clean core should be installed after the system is cleaned up.
B. Solenoid Valves
Liquid line requires a field supplied and installed isolation solenoid valve within 10 feel of the evaporator. The suggested solenoid uses a 120- % service and require;
code-compliarn widrg to the RAUJ condemu g unit.
Nola: Trim solenoids cannot be used. They ere not compatible with Miaoclsnnel condenser coils
9. Molslure and Liquid Indicator
One moisture -Indicating sight glass is to be installed In the main liquid line. .
FLD = Furnished by Trane U.S. Inc. /Installed by Equipment Submittal Page 10 of 34
Others
St. Lucie Church 40T Rapt — _ _ May 10, 2017
Field Wiring - Air -Cooled Co. ising Units (Commercial)
Item: Al Qty: 1 Tag(s): J89J81711
EVAPORATOR
10. Fromst(not required) -The control is mechanically attached to the outside of the refrigerant One, near the evaporator, and Wired to the unit
control panel See application guide S3-APG012-EN for selection information.
11. Expansion Valves -Sea application guide SS,AP6012-EN for selecting valve quantity and s®.
Note., Units with Miaecharmel condenser coils applied with DX systems wUl require 30 percent bleed valves.
Expansion Velvee for2050T NICHE (30 precem Bleed) Evap Circuit Tonnage
REFRIGERANT
MIN.
MAX.
SPORLAN MODEL NUMBER
TRANE PART .
R4111A `
2.0
3.0
BBIZE-1-12-GA(BP20)
VAL1007
R410A
2.5
3.5
BBIZE-2-GA (BP/30)
VAL1048B
R410A
3.5
5.0
BBIZE3GA(BP/30)
VALID489
R410A
4.5
7.0
BBIZE4-GA(BP/W)
VAL10490
R410A
6.0
8.5
BBIZESGA(BP/30)
VALIC491
R410A.
7.0
10.0
BBlZES-GA(BP/30)
VAL10492
R410A
5.0
13.5
BBIZE41GA(BP/30)
-VAL10493
R410A
11.0
17.5
BBIZE-12-12-GA(BPI30)
VAL10494
R410A
14.0
21.5
BBEtISGASP/J0)
VALID495
R410A
17.0
28.5
OZE-20-GA(BP/Jol
VAL704S6
R410A 12ZO
130.0 1
0ZE-25-GA(BPI30)
VALI 497
(1) Ton par distributor, choose the valve that matches the avap coil circuit
capacity theta serves.
(2) Provide and instal one expansion valve per distributor..*
Refrigerant Charge and Maximum Line Length
Total interconnecting line Imp (per dron0)
50 ft
100 fi
150 it
Condenser and line set appmx. refrigermt
WA
WA
WA
charge (Per cimrit) - evaporatorc aMo not included
If total imenwnnecting line length is more than 150 feet, the appricallon must be reviewed by Trana
"Contact product support for information an refrigeration components and piping applications assistance
Suction une Piping
1. Do not use suction line traps.
Installation Guidelines
2. Do not use double fisem.
4. Route suction lines a9 short and direct as possible.
5. 51ope suction Ora sway from the condeaing unit 1 Inch forevery 10 feet
a. insulate suction line.
7. The suction filter should be located as claw to the compressors as possible.
3 A.Wpu0mgsuction
lugs mdergmand.
FLD=Fumished byTrane U.S. Inc. /Installed by Equipment Submittal Page 110/34
Others
St. Lucle Church 40T Repl _ May 10, 2017
Field tiring - Air -Cooled Cal insing Units (Commercial)
Item: Al Qty: 1 Tag(s): J89JO1711
Required Components for Refrigerant Circuits Continued
Liquid Line Piping
1. Awid pu*V liquid lines underground
2. Route liqul d fines as sh art and d've at as pass[ ble.
3. Slope liqui d line away from the condensing unit 1 inch for every 10 feet.
4. Only insulate liqui dIt nes th at pass tiv augh heats d areas.
5. Whe solenoid valve per fel d cmmcall on diagram.
S. The liqui d f ne filter drier should be as close to the solenoid valve as pass! ble.
Evaporator P431 ng
1. Insist TXV dim city to unit 1[qui d connection.
2. Locate TXV bulb midway between 90F bends an top of suclian W be as shown.
3. Secure bulb to Wbe with the two clamps prow ded by the manul aclurer and insulate bulb.
4. Insist the TXV equalaser line close to S downstre am of the bulb, on lop of the horizontal suasion fine.
S. Install frost at per kit insbu adore an the common suction line as close to the evaporator as pass!ble.
See SS-APGO12-EN. for DX evaporator piping details.
FLO = Fumished by Trane U.S. Inc. llnstalled by Equipment Submittal Page 12 of 34
Others
On
II
CUSTOMER WIRE SELECTION TABLE.
POWER WIRE SELECTION TO DISCONNECT SWITCH (1S1)
FACTORY INSTALLED DISCONNECT SWITCHSIZE
CONNECTOR WIRE RANGE
POWER WIRE SELECTION TO MAIN TERMINAL BLOCK (iTBI)
TERMINAL BLOCK SIZE
CONNECTOR WIRE RANGE
335 AMP
(1) 06-360 MCM
CONTROL WIRE SELECTION
WIRE GAUGE
OHMS PER 12000" MAX WIRE LENGTH
18AWG
a 60DO"
16AWG
5 12000" .
14 AWG
3 24DOW
SHIELDED WIRE TABLE
WIRE GAUGE
MAX WIRE LENGTH
16 AWG
5pgp^
14AWG
12000"
°h WARNING
DISCONNECTALL ELECTRIC POWER
INCLUDING REMOTE DISCONNECTS
BEFORE SERVICING.
FAILURE TO DISCONNECT POWER
BEFORE SERVICING CAN CAUSE
SEVERE PERSONAL INJURY OR
DEATH.
Zt CAUTION
USE COPPER CONDUCTORS ONLYI
UNIT TERMINALS ARE NOT
DESIGNED TO ACCEPT OTHER
TYPES OF CONDUCTORS.
FAILURE TO DO SO MAY CAUSE
DAMAGE TO THE EQUIPMENT.
NOTES:
1. All wiring and componets shown dashed to be supplied and installed bycustamer in accordance with local and national electrical eodes.
2. All wiring to be NEC Class 1 based on 60 degree C wire unless speemed.
3. CAUTION -Do not run lawvoltage wire (30 volts maximum) In eandu@ or racawaywith higher voltage w%ua.
4. Customer supplied heater contactor control elreult-120w240w1 ph max rating = 750VA InmshT75VA sealed; 24v1I ph max rating = 2401A irvushl60VA sealed.
0 AVERTISSEMENT
VOLTAGE HASARDEUXI
DECONNECTEZ TOUTES LES SOURCES
ELECTRIQUES INCLUANT LES
DISJONCTEURS SITUES A DISTANCE
AVANT D•EFFECTUER UENTRETIEN.
FAUTE DE DECONNECTER LA SOURCE
ELECTRIQUE AVANT D'EFFECTUER
UENTRETIEN PELT ENTRAINER DES
BLESSURES CORPORELLES SEVERES
OU LA MORT.
IMPORTANT!
DO NOT ENERGIZE
UNIT UNTIL CHECK-OUT
AND START-UP PROCEDURE
HAS BEEN COMPLETED
W
3
a
c
UO
c-
oo
-4 L
St Lucie Church 40T Rapt /— May 10, 2017
Tag Data -Performance Clin, ! Changer (Qtv:1l
Item
Tag(s)
Qty
Description
Moi r lumber
Spec
Number
JAHU-3
B1
K89K30715
1
Performance Climate Changer(CSAA
CSAA025UA
Product Data - Performance Climate Changer
Item: B1 Qty: 1 Tag(s): K89K30715
Unit level options
Indoor unit
Unit size 25
2.5in. integral base frame
UL listed unit
Multiple composite handles/latches
78.38 Unit length
56.50 Second level length
Warranty
Standard 1 year Parts warranty only
Air mixing section (Pos #1)
Air mixing section
Reduced length mixing box
Door- right side
Front full face opening
Bottom rectangular opening
2in. filter frame
MERV 8 Pleated media -1 set (Fld)
Coil section (Pos #2)
Vertical coil
Large
Stainless steel drain pan
Right side - drain connection
Right side - coil supply
Service panel coil connection side
Unit coil height
Cooling coil '
Refrigerant
Type "UF" coil
6 rows
127 fins per foot nominal fin spacing
Aluminum fins
Delta flo H (Hi efficient)
Internally enhanced Cu .016 (0.406 mm)
1/2in. tube diameter (12.7 mm)
Galvanized steel coil casing
Fan section (Pos #3)
Fan section
Supply fan
Door- right side
Outward swing
22in. diameter AF, H press
Top -back discharge
Right side. drive
NEMA premium compliant ODP
Voltage 200-208/3
15 HP
1800 RPM
FLD = Furnished by Trane U.S. Inc. /Installed by Equipment Submittal Page 14 of 34
Others
St. Lucie Church 40T Rep] "1 , -� May 10, 2017
Performance Data - Perform Jt Climate Changer
Tags
K89K30715
Unit level options
Position
Length in
78.375
Width in
80.000
Height in
126.500
Rigging weight(lb)
2905.3
Installed weight(lb)
2905.3
Actual airflow cfm
13500
Unit elevation ft
0.00
Shipping split 1 weight(lb)
453.0
Shipping split 2 weight(lb)
930.0
Shipping split 3 weight(lb)
1447.0
Fan section
Position
#3
Fan airflow cfm
13500
Overall ESP in H2O
1.500
Total static pressure in H2O
3.141
Fan pressure drop in H2O
1.500
Fan outlet velocity fNmin)
2436
Speed (rpm)
1627'
Total brake horsepower h
12.186
Unit static efficiency %
54.85
Outlet area (sq ft
5:54
Motor hertz Hz
60
Coil section
Position
#2
Coil performance airflow cfm
13500
Coil face area (sq ft
24.97
Coil face velocity ft/min)
541
Air pressure drop in H2O
6.992
Coil rigging weight(lb)
353.0
Leaving dry bulb F
53.70
Leaving wet bulb F
53.45
Entering dry bulb F
80.00
Entering wet bulb F
67.00
Fluid volume al
15.76
Liquid temp entering TXV F
116.00
Saturated suction temperature F
48.20
Suction superheat F
8.00
Sensible capacity MBh
389.52
Total capacity MBh
560.00
Air mixing section
Position
#1
Opening 1 front - area (sq ft
29.03
Opening 1 bottom — areas ft
6.55
Opening 1 bottom - face velocity fNmin)
2063
Opening 1 bottom total pressure drop in H2O
0.000
Bottom inlet type
Ducted
Filter condition
Mid-life
Filter airflow cfm
13500
Filter area (sq ft
27.11
Filter face veloci ft/min
498
Filterpress ure dro in H2O
0.648
Total mixing section pressure drop in H2O
0.648
FLD = Furnished by Trane U.S. Inc. /Installed by Equipment Submittal Page 15 of 34
Others
St Luclechurch 40T Repl J'1, - -- - 1, May 10, 2017
Mechanical Specifications Jormance Climate Changer
Item: B7 Qty: 1 Tag(s): K89K30715
GENERAL
Per ASHRAE 62.1 recommendation, indoor air handling units will be shipped stretch -wrapped to protect unit from- -
in -transit rain and debris.
Installing contractor is responsible for long term storage in accordance with the Installation, Operation, and Maintenance
manual (CLCH-SVX07B-EN).
Unit shall be UL and C-UL Listed.
Supply fans within the scope of AHRI Standard 430 shall be certified in accordance with AHRI Standard 430.
Unit sound" performance data shall be provided using AHRI Standard 260 test methods and reported as sound power.
Trane, in providing this program and data, does not certify or warrant NC levels. These levels are affected by factors
specific to each application and/or installation and therefore unable to be predicted or certified by Trane. Referto
product data for speck fan footnote references.
- Footnote 4: Sound Power Levels are in accordance with AHRI 260
Unit Construction
All unit panels shall be 2" solid, double -wall construction to facilitate cleaning of unit interior. Unit panels shall be
provided with a mid -span, no -through -metal, internal thermal break. Casing thermal performance shall be such that
under 55OF supply air temperature and design conditions on the exterior of the unit of 81 OF dry bulb and 730F wet bulb,
condensation shall not form on the casing exterior.
All exterior and interior indoor AHU panels will be made of galvanized steel.
Casing Deflection
The casing shall not exceed 0.0042 inch deflection per inch of panel span at 1.00 times design static pressure.
Maximum design static shall not exceed +8 inches w.g, in all positive pressure sections and -8 inches w.g. in all negative
pressure sections.
Floor Construction
The unit floor shall be of sufficient strength to support a 300.0 lb load during maintenance activities and shall deflect no
more than 0.0042 inch per inch of panel span.
Unit base
Manufacturer to provide a full perimeter integral base frame for either ceiling suspension of units or to support and raise
all sections of the unit for proper trapping. Indoor unit base frame will either be bolted construction or welded
construction. All outdoor unit base frames shall be welded construction. For indoor units, refer to schedule for base
height and construction type. Contractor will be responsible for providing a housekeeping pad when unit base frame is
not of sufficient height to properly trap unit._ Unit base frames not constructed of galvanized steel shall be chemically
cleaned and coated with both a -rust -inhibiting primer and finished coat of rust -inhibiting enamel. Unit base height to be
included in total height required for proper trap height.
Insulation
Panel insulation shall provide a minimum thermal resistance (A) value of 13 ft'-h "F/Btu throughout the entire unit.
Insulation shall completely fill the panel cavities in all directions so that no voids exist and settling of insulation is
prevented. Panel insulation shall comply with NFPA 90A.
Drain Pan
In sections provided with a drain pan, the drain pan shall be designed in accordance with ASHRAE 62.1. To address
indoor air quality (IAQ) the drain pan shall be sloped in two planes promoting positive drainage to eliminate stagnant
water conditions. Drain pan shall be insulated, and of double wall construction. The outlet shall be the lowest point on
the pan, and shall be of sufficient diameter to preclude drain pan overflow under normally expected operating
conditions. All drain pans connections shall have a threaded connection, extending a minimum of 2-1/2" beyond the unit
base, and shall be made from the same material as the drain pan. Drain pan located under a cooling coil shall be of
sufficient size to collect all condensate produced from the coil.
Refer to Product Data for speck information on which sections are supplied with a drain pan, the drain pan material
and connection location.
FLO = Furnished by Trane U.S. Inc. /Installed by Equipment Submittal - Page 16 of 34
Others
St Lucie Church 40T Repl '- - -- - May 10, 2017
Access Door Construction
Access doors shall be 2" double wall construction. Interior and exterior door panels shall be of the same construction as
the interior and exterior wall panels respectively. All doors shall be provided with a thermal break construction.of door
panel and door frame. Gasketing shall be provided around the full perimeter of the doors to prevent air leakage. Surface
mounted handles shall be provided to allow quick access to the interior of the -functional section and to prevent through
cabinet penetrations that could likely weaken the casing leakage and thermal performance. Handle hardware shall be
designed to prevent unintended closure. Access doors shall be hinged and removable for quick easy access. Hinges
shall be interchangeable with the door handle hardware to allow for alternating door swing in the field to minimize
access interference due to unforeseen job site obstructions. Door handle hardware shall be adjustable and visually
indicate locking position of door latch external to the section. Door hinges shall be galvanized.
All doors shall be a minimum of 60" high when sufficient height is available or the maximum height allowed by the unit
height.
Door handles shall be provided for each latching point of the door necessary to maintain the specified air leakage
integrity of the unit. Optionally for indoor AHUs and as standard on outdoor AHUs, outward swing doors are provided
with a single handle linked to multiple latching points. An optional shatterproof window shall be provided in access doors
where indicated on the plans. Window shall either be single pane, or thermal dual pane, as defined on schedule.
Window shall be capable of withstanding unit operating pressures and shall be safe for viewing UV-C lamps.
Refer to Product Data for speck information on which sections are supplied with an access door, the door location, a
single handle and a window.
MIXING SECTION
A mixing section shall be provided to support the damper assembly for outdoor, return, and/or exhaust air.
The following specifications apply only to units with outside air and return air dampers, with actuators. The 5 year
warranty applies only to these items.
This unit contains Economizer that meets or exceeds all mandatory requirements prescribed by Title 24, including but
not limited to:
- 5 yr parts only warranty
- Successfully tested to 60,000 Actuations
- Less than 10 cfm/sq.ft. of damper leakage at 1" WG per AMCA 500L
Filters
Mixing sections shall be provided with a filter rack as indicated in the Product Data and As -Built sections of the submittal
2-inch pleated media filters made with 100% synthetic fibers that are continuously laminated to a supported steel -wire
grid with water repellent adhesive shall be provided.. Filters shall be capable of operating up to 625 fpm face velocity
without loss of filter efficiency and holding capacity. The filters shall have a MERV 8 rating when tested in accordance
with the ANSI/ASHRAE Standard 52.2.
COIL SECTION WITH FACTORY INSTALLED COIL
The coil section shall be provided complete with coil and coil holding frame. The coils shall be installed such that
headers and return bends are enclosed by unit casings. If two or more cooling coils are stacked in the unit, an
intermediate drain pan shall be installed between each coil and be of the same material as the primary drain pan. Like
the primary drain pan, the intermediate drain pan shall be designed being of sufficient size to collect all condensation
produced from the coil and sloped to promote positive drainage to eliminate stagnant water conditions. The
intermediate pan shall begin at the leading face of the water -producing device and be of sufficient length extending
downstream to prevent condensate from passing through the air stream of the lower coil. Intermediate drain pan shall
include downspouts to, direct condensate to the primary drain pan. The outlet shall be located at the lowest point of the
pan and shall be sufficient diameter to preclude drain pan overflow under any normally expected operating condition.
In lieu of a door, an easily removable service panel shall be provided in sections as specified, to facilitate access to unit
for periodic servicing, or for removal and replacement of coils. Removal of service panel will not impact the structural
integrity of the unit.
No casing penetrations supplied for hydronic drain and vents: If required, piping contractor will need to drill drain and
vent penetrations using factory located features provided in coil panel.
Refrigerant Cooling Coils
The coils shall have aluminum fins and seamless copper tubes. The fins shall have collars drawn, belled, and_finnly
bonded to tubes by mechanical expansion of the tubes. Suction and liquid line connections shall extend to the, unit
exterior. The coil casing may be galvanized or stainless steel. Refer to the Product Data section of the submittal for the
FLO = Furnished byTrane U.S. Inc. /Installed by Equipment Submittal Page 17 of34
Others
St Lucie Church 40T Repl /",, - May 14 2017
coil casing material.
The coils shall be proof -tested to 450 psig and leak -tested to 300 psig air pressure under water. After testing, the inside
of the coils shall be dried, all connections shall be sealed, and the coil shall be shipped with a charge of dry air.
Suction headers and liquid connections shall be constructed of copper tubing with connections penetrating unit casings
to permit sweat connections to refrigerant lines. The coils shall have equalizing vertical distributors sized according -to
the capacities of the coils. Coils are certified in accordance with the AHRI Forced -Circulation Air -Cooling and
Air -Heating Coils Certification Program which is based on AHRI Standard 410 within the Range of Standard Rating
Conditions listed in Table 1 of the Standard. Certified units may be found in the AHRI Directory at www.anddirectory.org.
Refrigerant coil tubes are 1/2" [13mm] OD, 0.016" [0.406mm] thick, internally enhanced copper.
AF FAN SECTION
The fan type shall be provided as required for stable operation and optimum energy efficiency. The fan shall be a
double -width, double -inlet, multiblade-type, airfoil (AF) fan. The fan shall be equipped with self -aligning, antifriction
bearings with an L-50 life of 200,000 hours, as calculated per ANSI/AFBMA Standard 9. For any bearing requiring
relubrication, the grease line shall be extended to the.fan support bracket on the drive side. The fan shall be statically
and dynamically balanced at the factory as a complete fan assembly (fan wheel, motor, drive, and belts). The fan shaft
shall not exceed 75 percent of its first critical speed at any cataloged speed. Fan wheels shall be keyed to the fan shaft'
to prevent slipping. The fan shafts shall be solid steel. The fan section shall be provided with an access door on the drive
side of`the fan. Fan performance shall be certified as complying with AHRI Standard 430.
Drive Service Factor
The drives shall be constant speed with fixed -pitch sheaves. The drives shall be selected at a minimum 50 percent
larger than the motor brake horsepower (1.5 service factor).
Motor Frame
The motor shall be mounted integral to the isolated fan assembly and furnished by the unit manufacturer. The motor is
mounted inside the unit casing on an adjustable base to permit adjustment of drive belt tension (not applicable for direct
drive plenum fans). The motor shall meet or exceed all NEMA Standards Publication MG 1 requirements and comply
With NEMA Premium efficiency levels when applicable except for fractional horsepower motors which are not covered
by the NEMA classification. The motor shall be T-frame, squirrel cage with size, type, and electrical characteristics as
shown on the equipment schedule. Refer to the Product Data section for selected fan motors within each unit.
Two -Inch Spring Isolators
The fan and motor assembly (on sizes 10 to 120) shall be internally isolated from the unit casing with 2-inch (50.8 mm)
deflection spring isolators, fumished and installed by the unit manufacturer. The isolation system shall be designed to
resist loads produced by external forces, such as earthquakes, and conform to the current IBC seismic requirements.
Multiple Belt Drive
The fan section with a belt -driven fan shall be provided with a multiple belt drive. Refer to the Product Data section of
the submittal for selected fans with multiple belt drives.
Lifting Instructions
The air handling units must be rigged, lifted, and installed in strict accordance with the Installation, Operation, and
Maintenance manual'(CLCH-SVX07G-EN). The units are also to be installed in strict accordance with the specifications.
Units may be shipped fully assembled or disassembled to the minimum functional section size in accordance with
shipping and job site requirements.
Indoor units shall be shipped on an integral base frame (variable from the standard 2.5" to 87height) for the purpose of
mounting units to a housekeeping pad and providing additional height to properly trap condensate from the unit. The
integral base frame may be used for ceiling suspension, external isolation, or as a housekeeping pad. Indoor sizes 3 to'
30 will also be shipped with a shipping skid designed for forklift transport. Refer to the unit As -Built or Product Data
section of the submittal for the base frame height of each unit.
All units will be shipped with an integral base frame designed with the necessary number of lift points for safe
installation. All lifting lugs an- to be utilized during lift. The lift points will be designed to accept standard rigging devices
and be removable after installation. Units shipped in sections will have a minimum of fourpoints of lift.
FLD=FurnishedbyTraneU.S.Inc. /Installedby Equipment Submittal Page IS of34
Others
Formaneuvadng purposes, Indude 1.125 Inch as to each
27" 27"
panel gange. Flange will not add to overall Installed unit length shown.
I 7PBK discharge opening
28.380 x 28.380
2 Housed fen - 221n'
diameter AF, H press
Supply fan 15 hp
200-20813
3 Cooling mil -B Coil type
OF
Doors
27 width x 55 height
1 a
PNmuic.G O
m3
14
include 1.1251nehes to each ship spl It length for overlapping panel flange. Flange will not add to overall Installed unit length shown.
1 TPBK discharge opening
A
28.380 x 28.380
2 Housed fan -22in.
diameter AF, H press
Supply ten 15 hp
200-208r3
3 Co ling coil - 6 Coil type
UF
4 1"N.P.T.E
N
Doors =
27 width x 55height pp 3
to r.
C4
w,
V go .
N go
M
PorDvmuseC �
N
O
'I
SL Lucie Church 40T Rep] - - - - -- _ - May 10, 2017
As -Built - Performance Clim', 'Thanger
Item: B1 Qtv: 1 Tan(s): K89K30715
2112
Overall Elevation View: Right - Shipping splits indicated by bold outline. - Measurements in inches
For maneuvering purpose; Include 1.125 inches to each ship split length for overlapping panel Huge. Flange will not add to overall Installed unit length
Pas#
Module
Length
Weight
3
Fan section
56112
1447.00
2
Coil section
46 118
930.00
1
Air mbdng section
32 318
453.00
Installed Unit Weight 2830.00 Ibs
Basil
Inches
anoiu amnom
TRIMS
W. anon Ci v
FLO = Furnished byTmne U.S. Inc. /Installed by Equipment Submittal Page 21 at 34
Others
St. Lucie Church 40T Repl / � -- - -- - - _ _ - - May 10, 2017
As -Built - Performance Ulm?__, -changer `
Item: B1 Qty: 1 Tag(s): K89K30715
t
y
G
_ 1
T
3
A
32 318
fit
8 1/8
Right Side of Unit . Detailed Plan View: Top -Measurements in inches
Left Side
is in inches
' 7WAAIff o
FLO = Furnished by Tune U.S. Inc. /Installed by Equipment Submittal Page 22 of 34
Others
St Lucie Church 40T Repl - _ - May 10, 2017
As -Built - Performance Ciur Changer
Item: B1 MY: 1 Tagts): K89K30715
14 3/4-mom
3
r
"tx
4
N
Detailed Elevation View: Right -Measurements in inches
Data
/2
n inches
'l8 aW7 0e
lame,
PbtEfly Cnub
FLO = Furnished by Trans U.S. Inc. /Installed by Equipment Submittal Page 23 of 34
Others
St. Lucie Church 40T Rapt May 10,, 2017
As -Built - Performance Clim ,,hanger
Item: B1 Qty: 1 Tag(s): K89K30715
Detailed Elevation View: Front -Measurements in inches
Detail
ies
law
M1,WiNOLIlnvb 06yV
FLO= Furnished byTrans U.S.Inc. /Installed by Equipment Submittal Page 24of34
Others
cdon Can.
Sudan Can.
]1st.
Id Dist.
Call connection view: Right. Measurements in inches
NPTI : National Pipe Thread Internal Connection
NPTE : National Pipe Thread External Connection
m Und size: 25 ob Name: jUnft Casing: On Double Well Faam V
m rodud gran :Indoor unit Pm osal Numher. O
me ral base frame: 2.5in. into ral basefreme dual airflow: 13500 cfm
Vt PaInt ttnnaintedaiald nnbdad Sqlmq OfCP' .............. _____... _____.. F.b.. nO.—
-d
'rR
yp
75 3/8
Coil connection View: Left- Measurements in Inches
NPTI : National Pipe Thread Internal Connection
NPTE : National Pipe Thread External Connection
c 3
N
V Unit size: 25 Job Name: Und Casing: 2in Double Wall Foam
�o roduct rou : Indoor undt _ _ Pro osal Number. ®� e
m ,. dual airflow: 13500 cfm
v.e„moo»m. a.m.
St. Lucie Church 40T Repl
Fan Curve - Performance CV 1e Changer
Item: B1 Qty: 1 Tag(s): 1(hu-M50715
May 10, 2017
O
2
125
d
10.0
CL
7.5
co
_ 5b
~ 25�
Mt'
Supply
Size 25Vertical Iaaw-' hruCauierSvwl 22inch AF Hpress - Single Fan
�M_�/�_.70
F/
`�\
\�I
ffi
RMAQ
It
„ •,ice
►� a
�►� Y�ia031ININ11rle
0 w 10000 15700 2M 2 000
Arflcv(cfrn)
Size25VeticalL7raw-TtmCbuterSw1d 22kx:hAF Hpress
Sard Rmer Lewis are in accadm=withAHRI250.
at
129t 230-Iz 800Hz 1 Wk 2M-k
41ft
81ft
87
85 83 77 74 63
48
47
86
84 83 83 75 70
64
59
95
99 101 96 94 87
82
78
PLO = Fumished by Trane U.S. Inc. /Installed by Equipment Submittal Page 27 0134
Others
St. Lucie Church 40T Repl - May. 10, 2017
Accessory - Performance C' ite Changer
Item: B1 Qty: 1 Tag(s): Kbmir:40715
Base Detail
FLO = Furnished by Trane U.S. Inc. /Installed by Equipment Submittal Page 28 of 34
Others
EXAMPLE UNIT - NOT CONFIGURED AS SELECTED.
Filter mixing box
7114-wid"
II'
Fan I L 125 \C
Service Clearance
for Control Box
ass Note: At a minimum, these clearance dimensions are
Component
All
recommended on one side of the unit for regular
-
Sizes
service and maintenance. Referto ao-bu0t submittal
for locations of items such as filter access doom,
G (Control box HV or
9 F coil, piping connections, motor locations, etc.
LV > 18 pt or UC600
36
sufficient clearance must be provided on all sides of
controller)
unit for removal of panels or sectioMo-section
G (control box LV 18
13
attachment. Clearance for starters. VFOs, or other
high -voltage devices must be provided per NEC
pt or less)
requirements.
21
25
30
35
40
50
57
Component
3
4
6
8
10
12
14
17
21
25
30
35
40
5o
57
66
80
100
120
TALL
TALL
TALL
TALL
TALL
TALL
TALL
A (filter)
48
48
48
48
48
4B
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
52
55
58
58
B (coil, humidifier)
48
59
59
66
77
82
87
87
95
77
95
77
109
87
115
96
128
96
141
110
141
110
156
156
170
197
B (staggered coil)
WA
NIA
N/A
NIA
N/A
N/A
N/A
N/A
67
N/A
67
WA
76
N/A
80
N/A
88
N/A
96
N/A
96
N/A
105
105
113
129
C (UV Lights)
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
52
56
58
58
C (TCAC)
43
59
59
63
75
81
83
83
58
75
58
1 75
1 83
83
75
59
83
83
83
83 1
83
1 83
83
83
75
83
D (Extemal Starter
_
VFD, LV box or
61
61
61
61
61
61
61
61
64
64
64
64
64
64
64
64
64
64
64
64
64
64
64
64
64
64
Overload box)
D (Intemal
Starter or
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
E (fan) 48 48 48 48 51 54 58 61 60 1 51 1 66 51 66 58 1 66 1 60 1 70 60 1 77 1 66 1 77 1 66 1 93 93 1 1011 101
F (Gas Heat WA WA 89 90 108 100 100 105 115 WA 1 115 WA 118 N/A 136 NIA 140 WA 156 WA 156 WA 170 179 . 180 NIA
Ext Vestible)
F (Gas Heat WA WA 56 63 74 79 84 84 92 NIA 92 WA 106 N/A 1 112 1 WA 1 125 1 WA 1 138 1 WA 138 WA 1 153 153 1 167 194
Int Vestible)
N
O
V
St. Lucie Church 40T Repl -_
Accessory - Performance Cl' `te Changer
Item: B1 Qty: 1 Tag(s): KBaL.-_0715
May 10, 2017
EXPANDI
GRID BACKIN(
E
11
lip
Hit/8
STANDARD CONSTRUCTION
1. 100 % Synthetic White Un-Dyed Media
2. 10.0 Pleats Per Fool
3. Expanded Metal Pleat Supports
4. Moisture Resistant Beverage Board Frame
5. Double Wall Frame
NOTES
1. MERV 8-A Per ASHRAE 52.2-2007 Appendix J.
2. Final Resistance: 1/d' W.G.
3. Rated Velocity. 500 FPM
4. Class 2 Filter Per U.L. Standard 900
5. Maximum Operating Temperature: 225 DEG. F
MODEL NUMBER
NOMINAL SIZE
IN.WXHXD
ACTUAL SIZE
IN.W X HXD
RATED
AIRFLOW
CFM
INITIAL
RESISTANCE
IN. W.G.
MEDIAAREA
SO Fr.
MX40-STD2-217
10 X 20 X 2
9-1/2 X 19-12 X 1-314
700
0.29
4.7
MX40-STD2-220
12 X 20 X 2
11-12 X 19-1/2 X 1-3/4
840
0.29
5.5
MX40-STD2-210
12 X 24 X 2
113/8 X 23-38 X 1-3/4
1000
0.29
6.2
MX40-STD2-239
i4 X 20 X 2
13-12 X 19-1/2 X 1-3/4
980
0.29
5.7
MX40-2TD2-241
14 X 25 X 2
13-12 X 24-1/2X 1-3/4
1220
0.29
7.1
MX40STD2-245
15 X 20 X 2
14172 X 19-12 X 1-3/4
1050
0.29
6.2
MX4D-STD2-201
16 X 20 X 2
15-12 X 19-12 X 1-3/4
1120
0.29
6.7
MX40-STD2-216
16 X 24 X 2
15318 X 2338 X 13/4
1340
0.29
6.0
MX40STD2-202
16 X 24 X 2
15-12 X 24-12 X 13/4
1400
0.29
8.0
MX40-STD2-280
15 X 20 X 2
17-12 X 19-1/2 X I V4
1250
029
7.8
MX40STD2-212
18 X 24 X 2
17-38 X 2338 X 13/4
1600
0.29
9.3
MX40STD2-285
18 X 25 X 2
17-12 X 24-12 X 13/4
1570
0.29
9.7
MX40STD2-2D3
20 X 20 X 2
19-12 X 19-12 X I V4
1400
0.29
8.3
MX40STD2411
20 X 24 X 2
1938 X 2338 X 13/4
1670
0.29
9.9
MX40-STD2-204
20 X 25 X 2
19.1/2 X 24-12 X 1-V4
1750
0.29
10.3
MX40-STD2-205
24 X 24 X 2
233/8 X 2338 X 13/4
2000
0.29
11.7
MX40-STD2-225
25 X 25 X 2
24-12 X 24-12 X 13/4
2170
0.29
13.6
FLO= Fumishedby Trane US. Inc. /Installedby Equipment Submittal Page 30 Df34
Others
St. Lucie Church 40T Rep[
Accessory - Performance C''te Changer
Trap Schedule
Item: B1 Qty: 1 Tag(s): K89K30715
Drain pan trapping for section
under negative pressure
L = H +J + pipe diameter where:
H = 1 inch for each inch of negative
pressure (loaded filters) plus 1 inch
J=%H
Drain pan trapping for section
under positive pressure
L = H +J + pipe diameter where:
H = 1/2 inch (minimum)
J = 3� inch plus the unit positive static
pressure at coil discharge (loaded
filters)
May 10 2017
Entering
Ext. Static
Discharge
Ext. Static
Drain pan
Recommended
Trap Dimensions
Selected
Unit
Unit
Pressure
Pressure
Section
H
J
L
BaseraI,
Ta s
Size
in H2O
in H2O
Location
in
in
in
Hei ht A.
1<891<30715z
Unit size 25
0.750
0.750
Coil s2ection
3.742
1.871
6.614
MOO
To ensure proper condensate trapping the field installed housekeeping pad height is the responsibility of the
contractor.
2 The external static pressure used for fan selection was assumed to be divided 50% to entering duct external static
pressure and 50% discharge external static pressure.
Trane
Others
rage st
St. Lucie Church 40T Rapt _ _ - May 10, 2017
Accessory Performance Ch ' e Changer
Filter Schedule
Item: B1 Qty: 1 Tag(s): K89K3O715
Unit
Unit
Filter
Filter
Filter
Filter
MERV
Filter
Filter
Ta s
Size
Location
Arrangement
Depth
Type
Rating
Quantity
Size
K89K30715
Unit size 25
Air mixing
_
2in. filter
Pleated media
MERV 8
3
2
12in.x24in.
section [1]
frame
- run set
6
20ln.x20in.
0in.x20in.
PLO = Furnished by Trans U.S. Inc. /Installed by Equipment Submittal Page 32 of34
Others
St. Lucie Church 40T Repl ..
Field Wiring - Performance 1 ate Changer
MCA MOP Schedule
Item: B1 Qty: 1 Tag(s): K89K30715
Unit Ta s
Circuit
Circuit Description
Volta a/Phase/Hz
I MCA
K89K30715
1
Supply fan
200-208/3/60
tAMOP(A)
54.2
90.00
motors
May 10, 2017
FLD = Furnished by Trane U.S. Inc. /Installed by Equipment Submittal Page 33 of 34
Others
May 10, 2017
This is a report to help you locate field installed options that arrive at the jobsite. This report provides part or order
numbers for each field installed option, and references it to a specific product tag. It is NOT intended as a bill of
Product Family - Air -Cooled Condensing Units (Commercial)
Item
Tag(s)
I City
I Description
I Model Number
Al
1.189.181711
11
140 Ton.Air-Cooled Condensin Unit
IRAUJC40EC
Field Installed Option Description
PartfOrdering Number
Unitspring isolators
Product Family - Performance Climate Changer
Item
Ta s
Q
Description
Model Number
Sec Number
Bi
K89K30715
1
Performance Climate Changer CSAA
CSAA025UA
I AHU-3
Field Installed Option Description
Part/OrderingNumber
Pleated media - 1 set
FLD = Furnished by Trans U.S. Inc. /Installed by Equipment Submittal Page 34 of 34
Others