REVIEW COMMENTS
SCBVNEU
St tq
cie COr,ntt
1
Owner(s):
Beverly A Martino
Jurisdiction: SAINT LUCIE COUNTY
Lot#: 8 Block: 2
Stories: Automatic Sprinkler System? No
Fax Number:
Email: I n novationcontracti ng @Hot
mail.Com
REVIEWS AND COMMENTS
Review Type
Status Reviewed By
Date Started Date Completed Date Released
FIRE DEPARTMENT REVIEW
PENDING Tony Jerger
�". /ny r� q f fE
Comment:
/J/L��jj I(ll \\`Ifl � \\�j � I[�r''
FRONT COUNTER REVIEW
COMPLETE Angela Huff
11/1512017 11/1612017 11/1612017
Comment:
PLANS EXAMINER ELECTRIC
PENDING Walter Pride
Comment:
PLANS EXAMINER MECHANICAL
INCOMPLETE Carl Peterson
121812017
Comment:
PLEASE SHOW THE ASSEMBLY OCCUPANCY MEETING THE REQUIREMENTS FOR VENTILATION IN THE
12/8/2017
FLORIDA MECHANICAL CODE CHAPTER 4
AS REQUIRED IN SECTION 1009.1 OF THE 2014 FLORIDA
EXISTING BUILDING CODE.
PLANS EXAMINER PLUMBING
INCOMPLETE Greg Smyth
127712017
Comment:
AN OCCUPANT COUNT OVER 15 REQUIRES SEPARATE SEX RESTROOMS.SECTION 403.2 FPC 2014
12/7/2017
PLANS EXAMINER
REVIEW
Comment:
12/6/2017
12/6/2017
Comment:
12/6/2017
Comment:
12/6/2017
Comment:
INCOMPLETE Joe Cicio 121612017
FBC 107.1 REQUIRES ALL SUBMITTED DOCUMENTS TO BE PREPARED BY A REGISTERED DESIGN
PROFESSIONAL AS STATED IN F.S. 471 OR 481 ' MUST REMOVE THE DESIGNER LOGO RICHARD JEMISON
FROM ALL PLANS AND SUBMITTED DOCUMENTS
OCCUPANCY CLASSIFICATION ON PLANS IS INCORRECT FOR THIS TYPE OF SERVICE • SEE FBC 303.1.1
FOR SMALL TENANT SPACES AND CORRECT ALL PLANS'
ENGINEER TO DIMENSION THE PLANS PER FBC 107.2.1 • SHOW ALL INTERNAL SPACE DIMENSIONS
THE FRONT WAITING AREA MUST BE CALCULATED AS 6 S.F. NET • SEE TABLE 1004.1.2 [ NOT 151
Planning & Development Services
Building & Code Regulation Division
2300 Virginia Avenue
Fort Pierce, FL..M82
Phone:(772)462-2172 Fax:(772)462.6443
REVIEW COMMENTS
12/6/2017 Comment:
SHOW THE DINING SURFACE ACCESSIBILITY REQUIREMENTS ON PLANS PER FBC ACCESS: 902[902.2
AND 902.31 • SHOW THE CLEAR FLOOR SPACES AND FORWARD APPROACH PER 305 AND 306
Comment:
ENGINEER TO DESIGN THE ACCESSIBLE RESTROOM CORRECTLY' SHOW 5 TURNING RADIUS, CLEAR
FLOOR AREAS AT FIXTURES AND THE DOOR, GRAB BAR DETAILS W/ HEIGHTS, DISPENSOR HEIGHTS ETC,
FIXTURE DETAILS, MIRROR HEIGHTS PER CODE, LATCH APPROACH ON THE PULL SIDE OF THE
1217/2017
RESTROOM DOOR DOES NOT MEET FIG 404.2.4.1 ACCESSIBILITY CODE / SHOW CLEAR FLOOR AREA ON
PLANS IN AND OUTSIDE THE RESTROOM • SHOW THE FRONT APPROACH PULL SIDE ON PLANS W/ ALL
DIMENSIONS AND THE REQUIRED 18" CLEARANCE FBC ACCESS 404.2.4.1 ••' SEE FBC EXISTING BUILDING
CODE 1012.8 "'
1277/2017 Comment:
RESTROOM DOOR DOES NOT OPEN THE REQUIRED 90 DEGREE ANGLE AND DOES NOT PROVIDE THE
REQUIRED 32" CLEAR OPENING • FBC ACCESS 404.2
12/7/2017 Comment:
ENGINEER TO PROVIDE ACCESSIBILITY PLANS [ 3 SETS ]' SHOW ALL COMPLIANT DETAILS W/ TRAVEL
PATHS TO THE ACCESSIBLE PARKING AREA
1217/2017 Comment:
ENGINEER TO SHOW THE REQUIRED APPLIANCE PROTECTION ON PLANS FOR THE MECHANICAL
COMPRESSOR PER FBCM 303.4 • SWHOW APPROVED BARRIER DETAILS ON PLANS
12/7/2017 Comment:
ENGINEER TO SHOW THE GYP BOARD TESTING STANDARDS AND METHODS OF ATTACHMENT ON THE
PLANS PER ASTM 1280
1217/2017 Comment:
ENGINEER TO SHOW A FRONT WALL ELEVATION AND THE LOCATION OF THE MALTESE CROSS PER FAC
69A-60' SHOW ALL REQUIRED DIMENSIONS
12/7/2017 Comment:
ENGINEER TO SHOW THE TOILET AND RESTROOM FINISH REQUIREMENTS ON PLANS PER FBC SECTION
1210.2
12/7/2017 Comment:
ENGINEER TO DESIGN A REVISED INTERIOR WALL AND CEILING FINISH TABLE PER FBC 803.9 ON PLANS
12/7/2017 Comment:
ENGINEER TO DESIGN THE REQUIRED RATED CORRIDOR PER FBC TABLE 1018.1 AS THE OCCUPANT
LOAD IS GREATRER THAN 30' SUBMIT ALL TESTING CRITERIA ON PLANS
12/7/2017 Comment:
ALL ENERGY CALCS MUST BE ORIGINAL FORMAT, COMPLEfLY FILLED OUT, AND SIGNED BY THE
BUILDING OWNER OR HIS AGENT
12/8/2017
Comment: PLEASE NOTE: (1) ALL REVIEW COMMENTS WHEN ANSWERED WILL REQUIRE A COVER LETTER
ADDRESSING WHERE THE CHANGES WERE MADE, (2) ALL CHANGES WILL BE REQUIRED TO BE CLOUDED
ON THE PLANS AND (3) THE CONTRACTOR WHEN RESUBMITTING WILL BE REQUIRED TO INSERT THE
NEW UPDATED PAGES INTO THE PLANS OR IF THE CONTRACTOR PREFERS, A REVISED COMPLETE SET
OF PLANS CAN BE SUBMITTED
PLEASE NOTE THAT A SUBMITTAL CHECKLIST WILL BE REQUIRED STATING THE TYPE AND QUANTITY OF
DOCUMENTS SUBMITTED FOR RE -REVIEW SIGNED AND DATED BY THE CONTRACTOR
PLEASE NOTE ANY COMMENT NOT ADDRESED MAY BE SUBJECT TO AN ADDITIONAL REVIEW FEE PER ST.
LUCIE COUNTY RESOLUTION #13-196
COMMENTS SENT
PLEASE NOTE: FLORIDA HAS VERY BROAD PUBLIC RECORDS LAWS. MOST WRITTEN COMMUNICATIONS
TO OR FROM COUNTY OFFICIALS REGARDING COUNTY BUSINESS ARE PUBLIC RECORDS AVAILABLE TO
THE PUBLIC AND MEDIA UPON REQUEST. IT IS THE POLICY OF ST. LUCIE COUNTY THAT ALL COUNTY
RECORDS SHALL BE OPEN FOR PERSONAL INSPECTION, EXAMINATION AND / OR COPYING. YOUR E-MAIL
COMMUNICATIONS WILL BE SUBJECT TO PUBLIC DISCLOSURE UNLESS AN EXEMPTION APPLIES TO THE
COMMUNICATION. IF YOU RECEIVED THIS EMAIL IN ERROR, PLEASE NOTIFY THE SENDER BY REPLY E-
MAIL AND DELETE ALL MATERIALS FROM ALL COMPUTERS.
12/8/2017 Comment: COMMENTS E-MAILED AS OF THIS DATE
12/812017 Comment: PLEASE RE -SUBMIT ALL PLANS AND DOCS IN ORIGINAL FORMAT, SIGNED, SEALED AND DATED