HomeMy WebLinkAboutPANEL PLANS,A
e
Existing
400A Fused
Existing
Existing
M
Main
200A Panel
200A Panel
Disconnect
Existing
120/240V
120240V
120240V
3 Phase
3 Phase
3 Phase
Existing
Existing Gutter
1
` Intersect Existing Conduit
1 - C dyit 1 1/4" Conduit
w/4-#3 & 1#8 w/4-93 & 1#8
NEW
200A Rated Existing
Existing Automatic 100A
100A Transfer Office
Disc. Switch Panel
120240V
DATE: Sea Coast Air Conditioning
" II Location: Fort Pierce,
31st. Street -
E Ill Fort Pierce, FL
FLORIDA
New
1" PVC w/446 & 1410
TO THE GENERATOR
a
Reny AIC#1
Load Control Modules
1;Ar AIC #2
New
SCANNED
BY
St. Lucie County
20KW Generator
120240V 3 Phase
PANEL SCHEDULE/LOAD CALCS
A/C #1 -0-1 KVA
A/C #2--- --
4.1 KVA
—3.0 KVA
A/C #4----
3.0 KVA
OFFICE RECEPTACLES-1.0
KVA
OFFICE RECPETACLES—.08
KVA
OFFICE RECEPTACLES—.06
KVA
OFFICE RECEPTACLES--1.0
KVA
OFFICE LIGHTS------.08 KVA
OFFICE LIGHTS--=.08
KVA
OFFICE LIGHTS-----.08
KVA
OFFICE COMPUTERS-1.0
KVA
OFFICE COMPUTERS-1.0
KVA
SERVER-------1.2
KVA
TOTAL KVA .
19.78 KVA @ 240V
TOTAL LOAD -,------_.7.58A @ 240V
ST. LUt ,COUNTY BUILDLYG D
REVIEWED FOR CiZX1 ]ACE IVISION
REVI✓IVED By
DATE_—R,/7
PLANS AAa� FERMTI MUST BE KZ
OR NO INSPECTION IVILL BE MADE O JOB
PRIDE ELECTRICAL SERVICES
OF FLORIDA, INC
S47SOUIHxPIrd FrA'S MILE772461-22717
IURTFURCE, R 34M FA@7P-461?713�