Loading...
HomeMy WebLinkAboutPROJECT INFORMATION 1L�I�L�U,./L Du MAY - 9 RECD # 17/2- W36 3-28-18 SCANNED BY St. Lucie County 1 I - WWI- 1,V., IIII CI IGIRI 1 F I INIC 48X24 2-24" WOKS. 2-18X18 GRIDDLE.2H 2-1H FRYERS.2-2H NOZZLE. NOZZLES. NOZZLES. N.H.24-48" N.H.24-48" N.H. 24-48" OHIKU HIBACHI-4882 W KINGS HWY, FT PIERCE BLD #1712-0236 4. RICE COOKER. NO COVERAGE PLANS ARE TO INSTALLA PYRO CHEM PRE ENGINEERED FIRE SUPPRESSION SYSTEM UNDER TWO EXHAUST HOODS. A PCL 600 CYLINDER WILL BE USED. IT IS CAPABLE OF 20 FLOW POINTS AND 16 WILL BE USED. WHEN THE FIRE SYSTEM IS ACTIVATED IT WILL SHUT DOWN THE GAS AND ELECTRIC. AN ALARM WILLTHEN SOUND. IF NO ALARM IS PRESENT AN ALARM BELL WILL THEN RING. THERE ARE 2 10' LONG EXHAUST HOODS AND THEY WILL BE PROTECTED BY A 1H NOZZLE EACH. THERE IS AN EXHAUST DUCT IN EACH HOOD WITH A DIAMETER OF 16". THEY WILL BE PROTECTED BY A 2D NOZZLE EACH. THERE ARE 3-360 DEGREE FUSIBLE LINKS IN EACH HOOD. ALL SCHEDULE 40 BLACK PIPE WILL BE USED. THE CLASS K WILL BE MOUNTED WITH A PLACARD ABOVE IT. THE REMOTE PULL WILL BE INSTALLED 10-20' FROM THE EXHAUST HOOD IN THE ROUTE OF EGRESS. ALL NFPA CODES FROM 17A-2009 AND 96-2011 WILL BE FOLLOWED. THE FIRE SYSTEM WILL BE UL 300.