HomeMy WebLinkAboutSPRINKLER CERTIFICATE-% '
METRO FIRE SPRRIRLER SERVICES, INC.
1501 S.E. DECKER AVENUE, BAY 522
Stuart, Florida 34994
PHONE: (772) 288-0615 FAX: (772) 288-5122
GENERAL INFORMATION
SCANNED
St. Lucie COUI71y
CONTRACTOR'S MATERIAL & TEST CERTIFICATE FOR ABOVEGROUND PIPINO
PROCEDURE
Upon completion of work, inspection and tests shall be made by the contractor's representative and witnessed by an owner's representative. All defects shall be
connected and system left in service before contractors personnel finally leave thejob.
A certificate shall be filled out and signed by both representatives. Copies shall be prepared for approving authorities, owners and contractor. It is understood the
owner's representative's signature in no way prejudices any claim against contractor for faulty material. Poor workmanship or failure to comply with approving
authority's requirements or local ordinances.
PROPERTYNAME
DATE ?^ pqM
Tattoo Yachts
PROPERTY ADDRESS
5350 Sun Citrus Blvd, Ft Pierce FL
PLANS
ACCEPTED BY APPROVING AUTHORITIES (NAMES)
St. Lucie CougV Fire Prevention
ADDRESS
5160 NW Milner Drive, Port St. Lucie, FL 34953
INSTALLATION CONFORMS TO ACCEPTED PLANS
YES ❑NO
EQUIPMENT USED IS APPROVED
OS'ES❑NO
IF NO, EXPLAIN DEVIATIONS
INSTRUCTION
HAS PERSON IN CHARGE OF FIRE EQUIPMENT BEEN INSTRUCTED AS TO LOCATION
YES []NO
OF CONTROL VALVES AND CARE AND MAINTENANCE OF THIS NEW EQUIPMENT
IF NO, EXPLAIN
HAVE COPIES OF THE FOLLOWING BEEN LEFT ON THE PREMISES
YES ]--]NO
1. SYSTEM COMPONENTS INSTRUCTION
ZTS ❑NO
2. CARE AND MAINTENANCE INSTRUCTIONS
KIES ❑NO
3. NFPA25
KM []NO
LOCATION OF
SUPPLIES BUILDINGS
SYSTEM
SAME
SPRINICLERS
MAKE
MODEL
YEAR OF
ORIFICE
QUANTITY
TEMPERATURE
MANUFACTURER
SIZE
RATING
iK1i1/A1,1150
7417qAiw
N
het5lZd!
1
PIPE AND FTrfINGS
TYPE OF PIPE It I'
TYPE OF FITTINGS
ALARM VALVE OR
ALARM DEVICE
MAXIMUM TUB TO OPERATE THROUGH TEST
FLOW INDICATOR
CONNECTION
TYPE
I MAKE
MODEL
I M.M.
SEC.
o1d
1 5.
DRY PIPE
DRY VALVEO.O.D.
OPERATING TEST
MAKE
MOD
I SERIALNO.
MAKE
MODEL III SERIOALNO.
TIME TO TRIP
WATER
AIR TRIP
POINT AIR
TIME WATER
ALARM
THROUGH TEST
PRESSURE
PRESSURE PRESSURE
I
REACHED TEST
OPERATED
CONNECTION
OUTLET
PROPERTLY
MIN. I
SEC.
PSI
PSI
PSI
MIN 1
SEC
YES
NO
WITHOUT
O.O.D.
WITH
O.O.D.
IF NO, EXPLAIN
DELUGE &
OPERATION
❑PNEUMATIC ❑ELECTRIC I ❑HYDRAULIC
PREACCION VALVES
PIPING SUPERVISED
❑YES LINO DECTING MEDIA SUPERVISED
❑YES LINO
DOES VALVE OPERATE FROM THE MANUAL IRIP ANDIOR REMOTE CONTROL STATIONS
❑YES ❑NO
IS THERE AN ACCESSIBLE FACILITY IN EACH CIRCUIT FOR TESING IF NO, EXPLAIN
MAKE
MODEL
DOES EACH CIRCUIT OPERATE SUPERVISION LASS
MAXIMUM TIME TO OPE
TE
ALARM DOES EACH CIRCUIT OPERATE VALVE RELEASE
RELEASE
YES
NO
MIN
SEC
LOCATION
MAKE&
SETTING
STATICPRFSSURE
MIDUALPKESSURE
FLOW RATE
PRESSURE
&FLOOR
MODEL
OIVING
REDUCING
LET(PSO
UrLET(PSO
IM.ET(PEI) urLEr(Psp
VALVE TEST
HYDROSTATIC: Hydrostatic tests shall be made at not less the 200 PSI (I3.6 bars) for two hours or 50 PSI (3.4 bars) above static
pressure in excess of 150 PSI (I0.2 bars) for two hours. Differential dry -pipe valve clappers shall be left open during test to prevent
TEST DESCRIPTION
damage. All aboveground piping leakage shall be stopped
PNEUMATIC: Establish 40 PSI (2.7 bars) air pressure and measure drop which shall not exceed 1 Y2 PSI (0.1 bars) in 24 hours. Test
ressure tanks at normal water level and air ressure and measure at r ressure dro which shall not exceed I %: PSI 0.1 barsin 24 hours.
ALL PIPING HYDROSTATICALLY TESTED AT PSI BARS FORHRS IF NO, STATE REASON
DRY PIPING PNEUMATICALLY TESTED []YES []NO
EQUIPMENT OPERATES PROPERLY ❑ YES []NO
DO YOU CERTIFY AS THE SPRINKLER CONTRACTOR THAT ADDITIVES AND CORROSIVE CHEMICALS, SODIUM
SILICATE OR DERIVATIVES OF SODIUM SILICATE, BRINE, OR OTHER CORROSIVE CHEMICALS WERE NOT USED FOR
TESTING SYSTEMS OR STOPPING LEAKS? ❑YES ❑NO
DRAIN READING OF GAGE LOCATED NEAR WATER SUPPLY TESTS PIPE:
RESIDUAL PRESSURE WITH VALVE IN
TESTS
TEST STATIC PRESSURE PSI
I TEST PIPE OPEN WIDE
UNDERGROUND MAINS AND LEAD IN CONNECTIONS TO SYSTEM RISER FLUSHED BEFORE CONNECTION MADE TO
SPRINKLER PIPING
VERIFIED BY COPY OF THE U FORM NO.85B []YES 21NO OTHER EXPLAIN
FLUSHED BY INSTALLER OF UNDERGROUND ❑YES [LINO
SPRINKLER PIPING
NUMBER USED
LOCATIONS
NUMB ER REMOVED
BLANK TESTING
I
GASKETS
WELDED PIPING EMS ❑NO
IF YES....
YES ❑NO
DO YOU CERTIFY AS THE SPRINKLER CONTRACTOR THAT WELDING PROCEDURES COMPLY WITH
THE REQUIREMENTS OF AT LEAST AWS DI0.9, LEVEL, AR-3?
YES []NO
DO YOU CERTIFY THAT THE WELDING WAS PERFORMED BY WELDERS QUALIFIED IN COMPLIANCE
WITH THE REQUIREMENTS OF AT LEAST AWS D 10.9, LEVEL AR-37
WELDING
DO YOU CERTIFY THAT WELDING WAS CARRIED OUT IN COMPLIANCE WITH A DOCUMENTED
QUALITY CONTROL PROCEDURE TO INSURE THAT ALL DISCS ARE RETRIEVED, THAT OPENINGS IN
PIPING ARE SMOOTH, THAT SLAG AND OTHER WELDING RESIDUE ARE REMOVED, AND THAT THE 'i ES LINO
INTERNAL DIAMETERS OF PIPING ARE NOT PENETRATED
DO YOU CERTIFY THAT YOU HAVE A CONTROL FEATURE TO ENSURE THAT ALL CUTOUTS YES LINO
ISICS ARE RETRIEVED
NAMEPLATE PROVIDED❑YES B O IF NO EXPLAIN Eaq/
DATE LEFT IN SERVICE WITH ALL CONTROL VALVES OPEN:
REMARKS
NAME OF SPRINKLER CONTRACTOR
Metro Fire Sprinkler Services Inc.
TESTS WITNESSED BY
TEST WITNESSED
FOR OWNER/OWNER'S REP (SIGNED)
TITLE
DATE
BY
$O$.SP LE RACJ'A (SIGNED)
TITL$
DATE
hUTHOR11 G JURISDICTION (SIGNED)
TITLE n
DATE
may!
^ ,
ADDITIONAL
EXPLANATION
NOTES
METRO FIRE SPRINKLER SERVICES, INC.
1501 S.E. DECKER AVENUE, BAY 522
Stuart, Florida 34994
PHONE: (772) 288-0615 FAX: (772) 288-5122
GENERAL INFORMATION
CONTRACTOR'S MATERIAL & TEST CERTIFICATE FOR ABOVEGROUND PIPING
PROCEDURE
Upon completion of work, inspection and tests shall be made by the contractor's representative and witnessed by an owner's representative. All defects shall be
connected and system left in service before contractor's personnel finally leave thejob.
A certificate shall be filled out and signed by both representatives. Copies shall be prepared for approving authorities, owners mid contractor. It is understood the
owner's representative's signature in no way prejudices any claim against contractor for faulty material. Poor workmanship or failure to comply with approving
authority's requirements or local ordinances.
PROPERTY NAME
Tattoo Yachts
DATE �i
�% /7 /0
PROPERTY ADDRESS
5350 Sun Citrus Blvd., FT PIERCE 34950
PLANS
ACCEPTED BY APPROVING AUTHORITIES (NAMES)
St. Lucie County Fire Prevention
ADDRESS
5160 NW Milner Drive, Port St. Lucie, FL 34953
INSTALLATION CONFORMS TO ACCEPTED PLANS
EQUIPMENT USED IS APPROVED
IF NO, EXPLAIN DEVIATIONS
YES NO
Cx1'ES ❑NO
INSTRUCTION
HAS PERSON IN CHARGE OF FIRE EQUIPMENT BEEN INSTRUCTED AS TO LOCATION
OF CONTROL VALVES AND CARE AND MAINTENANCE OF THIS NEW EQUIPMENT
IF NO, EXPLAIN
YES NO
HAVE COPIES OP 711E FOLLOWING BEEN LEFT ON THE PREMISES
1. SYSTEM COMPONENTS INSTRUCTION
2. CARE AND MAINTENANCE INSTRUCTIONS
3. NFPA25
S NO
YES ❑NO
MWES ❑NO
YES ❑NO
LOCATION OF
SYSTEM
SUPPLIES BUILDINGS
SAME /d�n
�l•
SPRINKLERS
MAKE
MODEL
YEAR OF
MANUFACTURER
ORIFICE
SIZE
QUANTITY
TEMPERATURE
RATING
PIPE AND FITTINGS
TYPE OF PIPE
TYPE OF FITTINGS
ALARM VALVE OR
FLOW INDICATOR
ALARM DEVICE
MAXIMUM TIME TO OPERATE THROUGH TEST
CONNECTION
TYPE
MAKE
MODEL
MIN.
SEC.
DRY PIPE
DRY VALVEQ.O.D.
OPERATING TEST
MAKE
I MODEL
SERIAL NO.
MAKE I MODEL I SERIOALNO.
TIME TO TRIP
THROUGH TEST
CONNECTION
WATER
PRESSURE
AIR TRIP
PRESSURE PRESSURE
POINT AIR
TIME WATER
REACHED TEST
OUTLET
ALARM
OPERATED
PROPERTLY
MIN.
SEC.
PSI
PSI
PSI
MIN I
SEC
YES
NO
WITHOUT
O.O.D.
WITH
O.O.D.
IF NO, EXPLAIN
DELUGE &
OPERATION
UPNEUMATIC DELECTRIC
HYDRAULIC
PPEACTION VALVES
pIPINGSUPERVISED
UYrS LINO DECTING MEDIA SUPERVISED
DYES EINO
DOES VALVE OPERATE FROM THE MANUAL TRIP AND/OR REMOTE CONTROL STATIONS
UYES UNO
IS THERE AN ACCESSIBLE FACILITY IN EACH CIRCUIT FOR TESING IF NO, EXPLAIN
MAKE
MODEL
DOES EACH CIRCUIT OPERATE SUPERVISION LOSS
MAXIMUM TIME TO OPE TE
ALARM DOES EACH CIRCUIT OPERATE VALVE RELEASE
RELEASE
YES
NO
MIN
SEC
PRESSURE
LOCATION
MAKE&
SETTING
STATICPRESSURE
RSSIDUALPRFSSURE
FLOW RATE
&FLOOR
MODEL
FLOWING
REDUCING
LET(PSI)
OILET(PSO
THLETtPSO UMET(PSI)
VALVE TEST
HYDROSTATIC: Hydrostatic tests shall be made at not less the 200 PST (13.6 bars) for two hours or 50 PSI (3.4 bars) above static
pressure in excess of 150 PSI (10.2 bars) for two hours. Differential dry -pipe valve clappers shall be left open during test to prevent
TEST DESCRIPTION
damage. All aboveground piping leakage shall be stopped.
PNEUMATIC: Establish 40 PSI (2.7 bars) air pressure and measure drop which shall not exceed l h PSI (0. I bars) in 24 hours. Test
pressure tanks at nomaal water level and air ressure and measure air assure dro which shall not exceed 1 'h PSI (0.1 barsin 24 hours.
ALL PIPING HYDROSTATICALLY TESTED AT PSI FOR HRS IF NO, STATE REASON
_BARS
DRY PIPING PNEUMATICALLY TESTED OYES ❑NO
EQUIPMENT OPERATES PROPERLY ❑ YES ❑NO
DO YOU CERTIFY AS THE SPRINKLER CONTRACTOR THAT ADDITIVES AND CORROSIVE CHEMICALS, SODIUM
SILICATE OR DERIVATIVES OF SODIUM SILICATE, BRINE, OR OTHER CORROSIVE CHEMICALS WERE NOT USED FOR
TESTING SYSTEMS OR STOPPING LEAKS? ❑YES LINO
DRAIN READING OF GAGE LOCATED NEAR WATER SUPPLY TESTS PIPE: RESIDUAL PRESSURE WITH VALVE IN
TESTS
TEST STATIC PRESSURE PSI I TEST PIPE OPEN WIDE
I
UNDERGROUND MAINS AND LEAD IN CONNECTIONS TO SYSTEM RISER FLUSHED BEFORE CONNECTION MADE TO
SPRINKLER PIPING
VERIFIED BY COPY OF THE U FORM NO.85B []YES ONO OTHER EXPLAIN
FLUSHED BY INSTALLER OF UNDERGROUND ❑YES [:]NO
SPRINKLER PIPING
NUMBERUSED
LOCATIONS
NUMBER REMOVED
BLANKTESTNG
GASKETS
I
WELDED PIPING rjYES UNO
1F YES....
YES NO
DO YOU CERTIFY AS THE SPRINKLER CONTRACTOR THAT WELDING PROCEDURES COMPLY WITH
THE REQUIREMENTS OF AT LEAST AWS D 10.9, LEVEL, AR-3?
R(YES []NO
DO YOU CERTIFY THAT THE WELDING WAS PERFORMED BY WELDERS QUALIFIED IN COMPLIANCE
WITH THE REQUIREMENTS OF AT LEAST AWS DI0.9, LEVEL AR-3?
WELDING
DO YOU CERTIFY THAT WELDING WAS CARRIED OUT IN COMPLIANCE WITH A DOCUMENTED
QUALITY CONTROL PROCEDURE TO INSURE THAT ALL DISCS ARE RETRIEVED, THAT OPENINGS IN
PIPING ARE SMOOTH, THAT SLAG AND OTHER WELDING RESIDUE ARE REMOVED, AND THAT THE )YES ❑NO
INTERNAL DIAMETERS OF PIPING ARE NOT PENETRATED
DO YOU CERTIFY THAT YOU HAVE A CONTROL FEATURE TO ENSURE THAT ALL CUTOUTS YES EINO
DISKS ARE RETRIEVED
NAMEPLATE PROVIDED EIYLS EINO IF NO, EXPLAIN
DATE LEFT IN SERVICE WITH ALL CONTROL VALVES OPEN:
REMARKS
NAME OF SPRINKLER CONTRACTOR
Metro Fire S rin1der Services, Inc.
TESTS WITNESSED BY
TESTWITNESSED
BY
FOR OWNER/OWNER'S REP (SIGNED)
TITLE -
DATE
FO NTRACTO (SIGNED)
f
DATE `
LITHORIftYH&ING
JURISDICTION (SIGNED)
TITLE-H
DA / ,7 /OO
ADDITTONAL
EXPLANATION
NOTES
/-7iz- 05-3s
METRO FIRE SPRINKLER SERVICES, INC.
1501 S.E. DECKER AVENUE, BAY 522
Stuart, Florida 34994
PHONE: (772) 288-0615 FAX: (772) 288-5122
GENERAL INFORMATION
CONTRACTOR'S MATERIAL & TEST CERTIFICATE FOR ABOVEGROUND PIPING
PROCEDURE
Upon completion of Work, inspection and tests shall be made by die contractor's representative and witnessed by an owner's representative. All defects shall be
connected and system left in service before contractor's personnel finally leave thejob.
A certificate shall be filled out and signed by both representatives. Copies shall be prepared for approving authorities, owners and contractor. It is understood the
owner's representative's signature in no way prejudices any claim against connector for faulty material. Poor workmanship or failure to comply with approving
authority's requirements or local ordinances.
PROPERTY NAME
Tattoo Yachts
DATE '•
PROPERTYADDRESS
5350 Sun Citrus Blvd, Ft Pierce, FL
PLANS
ACCEPTED BY APPROVING AUTHORITIES (NAMES)
St. Lucie County Fire Prevention
ADDRESS
5160 NW Milner• Drive Port St. Lucie, FL 34953
INSTALLATION CONFORMS TO ACCEPTED PLANS
)FES []NO
EQUIPMENT USED IS APPROVED
ZYES [:]NO
IF NO, EXPLAIN DEVIATIONS
INSTRUCTION
HAS PERSON IN CHARGE OF FIRE EQUIPMENT BEEN INSTRUCTED AS TO LOCATION
06S ❑NO
OF CONTROL VALVES AND CARE AND MAINTENANCE OF THIS NEW EQUIPMENT
IF NO, EXPLAIN
HAVE COPIES OF THE FOLLOWING BEEN LEFT ON THE PREMISES
S ❑NO
L. SYSTEM COMPONENTS INSTRUCTION
S [:]NO
2. CARE AND MAINTENANCE INSTRUCTIONS
S ❑NO
3. NFPA25
YES NO
LOCATION OF
SUPPLIES BUILDINGS
SYSTEM
SAME
NC0�
gST '"!
SPRINKLERS
MAKE
MODEL
YEAR OF
ORIFICE
QUANTITY
TEMPERATURE
MANUFACTURER
SIZE
RATING
Y
7
k
Al
%D d '
/IL N
Z
/
Y
7
9' /
PIPE AND FITTINGS
TYPE OF PIPE
NOX
TYPE OF FITTINGS
ALARM VALVE OR
ALARM DEVICE
MAXIMUM TIME TO OPERATE THROUGH TEST
FLOW INDICATOR
CONNECTION
YPE
MAKE
MODEL
MIN.
SEC.
S•
DRY PIPE
DRY VALVEQ.O.D.
OPERATING TEST
MAKE
MODEL
SERIAL. NO.
MAKE I
MODEL SE GAL NO.
TIME TO TRIP
WATER
AIR TRIP
POINT AIR
TIME WATER
ALARM
THROUGHTEST
PRESSURE
PRESSURE PRESSURE
REACHED TEST
OPERATED
CONNECTION
OUTLET
PROPERTLY
MIN.
SEC.
PSI
PSI
PSI
MIN
SEC
YES
NO
WITHOUT
O.O.D.
WITH
O.O.D.
IF NO. EXPLAIN
DELUGE &
OPERATION
[]PNEUMATIC
❑ELECTRIC ❑HYDRAULIC
PREACrION VALVES
PIPING SUPERVISED
❑YES
❑NO DECTING MEDIA SUPERVISED
❑YES ❑NO
DOES VALVE OPERATE FROM THE MANUAL TRIP ANDIOR REMOTE CONTROL STATIONS
❑YES ONO
IS THERE AN ACCESSIBLE FACILITY IN EACH CIRCUIT FOR TESING IF NO, EXPLAIN
MAKE
MODEL
DOES EACH CIRCUIT OPERATE SUPERVISION LOSS
MAXIMUM TIME TO OPE
TE
ALARM DOES EACH CIRCUIT OPERATE VALVE RELEASE
RELEASE
YES
NO
MIN
SEC
PRESSURE
LOCATION
MAKE&
SETTING
STATIC PRESSURE
RESIDUALPRESSURE
FLOWRAIM
&FLOOR
MODEL
REDUCING
LET(Psn
OUTLET(PSI)
INIM(PSI) Vruaws)
VALVE TEST
HYDROSTATIC: Hydrostatic tests shall be made at not less the 200 PSI (13.6 bars) for two hours or 50 PSI (3.4 bars) above static
pressure in excess of 150 PSI (10.2 bus) for two hours. Differential dry -pipe valve clappers shall be left open during test to prevent
TEST DESCRIPTION
damage. All aboveground piping leakage shall be stopped.
PNEUMATIC: Establish 40 PSI (2.7 bars) air pressure and measure drop which shall not exceed 1 %. PSI (0.1 bars) in 24 hours. Test
pressure tanks at normal water level and air pressure and ensure air pressure drop which shall not exceed 1 V2 PSI 0.1 barsin 24 hours.
ALL PIPING HYDROSTATICALLY TESTED AT M PSI BARS FOR HRS IF NO, STATE REASON
DRY PIPING PNEUMATICALLY TESTED YES []NO
EQUIPMENT OPERATES PROPERLY ❑ YES EINO
DO YOU CERTIFY AS THE SPRINKLER CONTRACTOR THAT ADDITIVES AND CORROSIVE CHEMICALS, SODIUM
•
SILICATE OR DERIVATIVES OF SODIUM SILICATE, BRINE, OR OTHER CORROSIVE CHEMICALS WERE NOT USED FOR
TESTING SYSTEMS OR STOPPING LEAKS? []YES QN0
TESTS
DRAIN READING OF GAGE LOCATED NEAR WATER SUPPLY TESTS PIPE: RESIDUAL PRESSURE WITH VALVE IN
I
TEST STATIC PRESSURE PSI TEST PIPE OPEN WIDE
UNDERGROUND MAINS AND LEAD IN CONNECTIONS TO SYSTEM RISER FLUSHED BEFORE CONNECTION MADE T'O
SPRINKLER G
VERIFIED BY COPY OF THE U FORM NO.85B []YESPYES NO OTHER EXPLAIN
FLUSHED BY INSTALLER OF UNDERGROUND []YES OR�NO
SPRINKLER PIPING
BLANKTESTING
NUMBER USED LOCATIONS
NUMBER REMOVED
GASKETS
I
WELDED PiFIN( 6flYES ❑NO
IF YES....
LOJYES ❑NO
DO YOU CERTIFY AS THE SPRINKLER CONTRACTOR THAT WELDING PROCEDURES COMPLY WITH
THE REQUIREMENTS OF AT LEAST AWS D10.9, LEVEL, AR-3?
YES ONO
DO YOU CERTIFY THAT THE WELDING WAS PERFORMED BY WELDERS QUALIFIED INCOMPLIANCE
WELDING
WITH THE REQUIREMENTS OF AT LEAST AWS D 10.9, LEVEL AR-37
DO YOU CERTIFY THAT WELDING WAS CARRIED OUT IN COMPLIANCE WITH A DOCUMENTED
QUALITY CONTROL PROCEDURE TO INSURE THAT ALL DISCS ARE RETRIEVED, THAT OPENINGS IN
PIPING ARE SMOOTH, THAT SLAG AND OTHER WELDING RESIDUE ARE REMOVED, AND THAT THE BYES ❑NO
INTERNAL DIAMETERS OF PIPING ARE NOT PENETRATED
DO YOU CERTIFY THAT YOU HAVE A CONTROL FEATURE TO ENSURE THAT ALL CUTOUTS S LINO
DISKS ARE RETRIEVED
NAMEPLATE PROVIDED YES NO IF NO EXPLAIN
DATE LEFT IN SERVICE WITH ALL CONTROL VALVES OPEN: '
RENIARKS
NAME OF SPRINKLER CONTRACTOR
Metro Fire Sprinkler Services Inc.
TEST WITNESSED
- TESTS WITNESSED
BY
BY
FOR OWNER/OWNER'S REP (SIGNED)
TITLE
DATE
FOR SPRI k CON OR (SIG )
TITLE /it4A11'I
DATE/� n/
Gf
FO 0 JURISDICTION (SIGNED)
TITLE
DATE
ADDITIONAL
EXPLANATION
NOTES