HomeMy WebLinkAboutMANDATORY REQUIREMENTS4.
BY
St. Lucie I
Mandatory Requirements (as applicable) Mandatory requirements compiled by US Department
of Energy and Pacific Northwest National Laboratory.
Adopted with permission
Section Com
Yes N/A Exempt
Fenestration 5.8.2.3,5.5.3.6
Envelope U-factor of opaque doors associated with the
®
®
❑
building thermal envelope meets requirements.
QN ion 6.4.4.1.6
Envelope Bottom surface of floor structures incorporating
El
El
El
radiant heating insulated to >=R-3.5.
Insulation 5.5.3.1.1
Envelope High-albedo roofs satisfy one of the following:
Solar reflectance >= 0.55 and thermal emittance
>= 0.75, Solar reflectance index >= 64.0, or
increased insulation (assembly <= U-0.03 or>=
R-33.0 insulation).
Wattage 9.4.3
Exterior Lighting Exterior grounds lighting over 100 W provides >60
ImAN unless on motion sensor or fixture is exempt
from scope of code or from external LPD.
Wattage 9.4.2
Interior Lighting Exit signs do not exceed 5 watts per lace.
Controls 10.4.3
Mechanical Elevators are designed with the proper lighting,
-
ventilation power, and standby mode.
HVAC 6.5.6.1
Mechanical Exhaust air energy recovery on systems meeting
Table 6.5.6.1.
SYSTEM —SPECIFIC 6.5.1.4
Mechanical Economizer operation will not increase heating
energy use during normal operation.
SYSTEM —SPECIFIC 6.5.2.2.1
Mechanical Three -pipe hydronic systems using a common
return for hot and chilled water are not used.
SYSTEM —SPECIFIC 6.5.2.2.3
Mechanical Hydronic heat pump systems connected to a
common water loop meet heat rejection and heat
addition requirements.
SYSTEM —SPECIFIC 6.5.2.4
Mechanical Water economizer specified on hydronic cooling
and humidification systems designed to maintain
inside humidity al>35 OF dewpoint If an
economizer is required.
SYSTEM —SPECIFIC 6.5.3.1.1
Mechanical HVAC fan systems at design conditions do not
El
El0
exceed allowable fan system motor nameplate hp
or fan system bhp.
SYSTEM —SPECIFIC 6.5.3.1.2
Mechanical HVAC fan motors not larger than allowable limits.
SYSTEM —SPECIFIC 7.4.2
Mechanical Service water heating equipment meets efficiency
requirements.
SYSTEM_ SPECIFIC 7.5.2
Mechanical Service water heating equipment used for space
heating complies with the service water heating
equipment requirements.
Air Leakage 5.4.3.4 Envelope
Insulation
Plan Review
5.8.1.7.3 Envelope
4.2.2,5.4.3.1.1,5.7 Envelope
Vestibules are installed where building entrances
separate conditioned space from the exterior, and
meet exterior envelope requirements. Doors have
self -closing devices, and are >=7 ft apart.
Insulation in contact with the ground has <=0.3%
®® El
water absorption rate per ASTM C272.
Plans and/or specifications provide all information
with which compliance can be determined for the
building envelope and document where
exceptions to the standard are claimed.
EnergyGauge Summit@ Fla/Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
Florida Building Code, Fifth Edition (2014) - Energy Conservation ASHRAE 90.1-2010 - Energy Cost Budget Option
9/2/2017 Page 9 of 15
.• 4
Plan Review 9.7 Exterior Lighting Plans, specifications, and/or calculations provide
all information with which compliance can be
determined for the exterior lighting and electrical
systems and equipment and document where
exceptions to the standard are claimed.
Information provided should include exterior
lighting power calculations, wattage of bulbs and
ballasts, transformers and control devices.
Wattage 9.4.3 Exterior Lighting
Exterior lighting power is consistent with what is
011
shown on the approved lighting plans,
demonstrating proposed watts are less than or
equal to allowed watts.
Plan Review 4.2.2,9.4.4,9.7 Interior Lighting
Plans, specifications, and/or calculations provide
®,'
®
13
all information with which compliance can be
determined for the interior lighting and electrical
systems and equipment and document where
exceptions to the standard are claimed.
Information provided should include interior
lighting power calculations, wattage of bulbs and
ballasts, transformers and control devices.
HVAC 6.4.3.4.4 Mechanical
Ventilation fans >0.75 hp have automatic controls
13
El
to shut off fan when not required.
HVAC 6.4.3.9 Mechanical
Demand control ventilation provided for spaces
>500 112 and >40 people11000 ff2 occupant
density and served by systems with air side
economizer, auto modulating outside air damper
control, or design airflow>3,000 cfm.
HVAC 6.4.4.1.4 Mechanical
Thermally ineffective panel surfaces of sensible
heating panels have insulation >= R-3.5.
HVAC 6.5.2.3 Mechanical
Dehumidification controls provided to prevent
❑
®
❑
reheating, recooling, mixing of hot and cold
airstreams or concurrent heating and cooling of
the same airstream.
HVAC 6.6.4.1 Mechanical
HVAC pumping systems >10 hp designed for
variable fluid flow.
HVAC 6.5.7.1.1 Mechanical
Kitchen hoods >5,000 cfm have make up air
>=50% of exhaust air volume.
HVAC 6.5.7.2 Mechanical
Fume hoods exhaust systems >=15,000 cfm have
11
VAV hood exhaust and supply systems, direct
make-up air or heat recovery.
HVAC 6.5.8.1 Mechanical
Unenclosed spaces that are heated use only
radiant heat.
HVAC 6.4.3.3.2 Mechanical
Setback controls allow automatic restart and
temporary operation as required for maintenance.
Other Equipment 10.4.1 Mechanical
Electric motors meet requirements where
applicable.
Plan Review 4.22,6.4.4.2.1,6.7.2 Mechanical
Plans, specifications, and/or calculations provide
®
❑
❑
all information with which compliance can be
determined for the mechanical systems and
equipment and document where exceptions to the
standard are claimed. Load calculations per
acceptable engineering standards and
handbooks.
Plan Review 4.2.2.7.7.1,10.4.2 Mechanical
Plans, specifications, and/or calculations provide
El
1:1
El
all information with which compliance can be
determined for the service water heating systems
and equipment and document where exceptions
to the standard are claimed. Hot water system
sized per manufacturer's sizing guide.
Plan Review 6.7.2.4 Mechanical
Detailed instructions for HVAC systems
El
®
❑
commissioning included on the plans or
specifications for projects >=50,000 U.
SYSTEM 6.4.3.10 Mechanical
Single zone HVAC systems with fan motors >=5
—SPECIFIC
hp have variable airflow controls. Air conditioning
equipment with a cooling capacity >=110,000
Btu/h has variable airflow controls.
EnergyGauge Summit@ Fla/Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
Florida Building Code, Fifth Edition (2014) - Energy Conservation ASHRAE 90.1-2010 - Energy Cost Budget Option
9/2/2017 Page 10 of 15
SYSTEM —SPECIFIC 6.5.1,6.5.1.1,6.5.1.3 Mechanical
Air economizers provided where required, meet
®
u
the requirements for design capacity, control
signal, ventilation controls, high -limit shut-off,
Integrated economizer control, and provide a
means to relieve excess outside air during
operation.
SYSTEM —SPECIFIC 6.5.1,6.5.1.2,6.5.1.3 Mechanical
Water economizers provided where required,
meet the requirements for design capacity,
maximum pressure drop and integrated
economizer control.
SYSTEM —SPECIFIC 6.5.3.2.1 Mechanical
VAV fan motors >=10 hp lobe driven by variable
speed drive, have a vane -axial fan with variable
pitch blades, or have controls to limit fan motor
demand.
SYSTEM SPECIFIC 6.5.3.2.3 Mechanical
Reset static pressure setpoint for DDC controlled
®
❑
❑
VAV boxes reporting to central controller based on
the zones requiring the most pressure.
SYSTEM —SPECIFIC 6.5.3.3 Mechanical
Multiple zone VAV systems with DDC of individual
zone boxes have static pressure setpoint reset
controls.
SYSTEM —SPECIFIC 6.5.3.4 Mechanical
Multiple zone HVAC systems have supply air
temperature reset controls.
SYSTEM —SPECIFIC 6.5.4.2 Mechanical
Reduce flow in pumping systems >10 hp. to
13
multiple chillers or boilers when others are shut
down.
SYSTEM —SPECIFIC 6.5.4.3 Mechanical
Temperature reset by representative building
El
El
1:1
loads in pumping systems >10 hp for chiller and
boiler systems >300,000 Bluth.
SYSTEM —SPECIFIC 6.5.4.4.1 Mechanical
Two -position automatic valve interlocked to shut
0
❑
❑
off water flow when hydronic heat pump with
pumping system >10 hp is off.
SYSTEM —SPECIFIC 6.5.4.4.2 Mechanical
Hydronic heat pumps and water-cooled unitary air
conditioners with pump systems >5 hp have
controls or devices to reduce pump motor
demand.
SYSTEM —SPECIFIC 6.5.5.2 Mechanical
Fan systems with motors >=7.5 hp associaled
with heat rejection equipment to have capability to
operate at 2/3 of full -speed and auto speed
controls to control the leaving fluid temperature or
condensing temp/pressure of heat rejection
device.
SYSTEM —SPECIFIC 6.5.6.2 Mechanical
Condenser heat recovery system that can heal
®
®
❑
water to 85 OF or provide 60% of peak heat
rejection is installed for preheating of service hot
water in 2417 facility, water cooled systems reject
>6 MMBtu, SHW load >=1 MMBtu.
SYSTEM —SPECIFIC 6.5.7.1.2 Mechanical
Conditioned supply air to space with a kitchen
®®
El
hood shall not exceed the greater of a) supply
flow required to meet space heating or cooling, or
b) hood exhaust flow minus the available air
transfer from available spaces.
SYSTEM —SPECIFIC 6.5.7.1.3 Mechanical
Kitchen hoods with a total exhaust airflow rate
110
❑
>5000 cfm meet replacement air, ventilation
system, or energy recovery requirements shown
in Table 6.5.7.1.3.
SYSTEM —SPECIFIC 6.5.7.1.4 Mechanical
Kitchen hoods with a total exhaust airflow rate
®
0
❑
>5000 cfm meet replacement air, ventilation
system, or energy recovery requirements.
SYSTEM SPECIFIC 6.5.9 Mechanical
Hot gas bypass limited to:
El
El
13
<=240 kBtu/h — 50%
>240 kBtu/h — 25%
SYSTEM —SPECIFIC 7.5.1 Mechanical
Combined space and water heating system not
allowed unless standby loss less than calculated
maximum. AHJ has approved or combined
connected load <150 kBtu/h.
SYSTEM SPECIFIC 6.4.3.1.1 Mechanical
Heating and cooling to each zone is controlled by
a thermostat control.
SYSTEM —SPECIFIC 6.4.3.3.3 Mechanical
Systems with air capacity >10,000 cfm include
El
El
0
optimum start controls.
SYSTEM SPECIFIC 6.4.3.5 Mechanical
Heat pump controls prevent supplemental electric
resistance heat from coming on when not needed.
EnergyGauge Summit® FlatCom-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
Florida Building Code, Fifth Edition (2014) - Energy Conservation ASHRAE 90.1-2010 - Energy Cost Budget Option
9/2/2017 Page 11 of 15
Oft. a ,
SYSTEM —SPECIFIC 7.4.4.3 Mechanical Public lavatory faucet water temperature <=110°F.
Controls 8.4.2 Project At least 50% of all 125 volt 15- and 20-Amp
receptacles are controlled by an automatic control
device.
Plan Review 4.2.2,8.4.1.1,8.4.1.2 Project Plans, specifications, and/or calculations provide
all Information with which compliance can be
determined for the electrical systems and
equipment and document where exceptions are
claimed. Feeder connectors sized in accordance
with approved plans and branch circuits sized for
maximum drop of 3%.
Air Leakage
5.4.3.1
Envelope
Continuous air barrier is wrapped, sealed,
caulked. gasketed, and/or taped in an approved
manner, except in semihealed spaces and in
climate zones 1-6.
Air Leakage
5.4.3.2
Envelope
Factory -built fenestration and doors are labeled
El
0
as meeting air leakage requirements.
Air Leakage
5.4.3.1
Envelope
All sources of air leakage in the building thermal
11
envelope are sealed, caulked, gasketed, weather
stripped or wrapped with moisture
vapor -permeable wrapping material to minimize
air leakage.
Fenestration
5.8.2.1
Envelope
Fenestration products rated in accordance with
NFRC.
Fenestration
5.8.2.2
Envelope
Fenestration products are certified as "to"
performance labels or cerfificates provided.
Insulation
5.8.1.2
Envelope
Below -grade wall insulation installed per
manufacturer's instructions.
Insulation
5.8.1.2
Envelope
Slab edge insulation installed per manufacturer's
instructions.
Insulation
6.5.3.1
Envelope
Roof R-value. For some ceiling systems,
verification may need to occur during Framing
Inspection.
Insulation
5.8.1.2,5.8.1.3
Envelope
Roof insulation installed per manufacturers
®
❑
❑
instructions. Blown or poured loose -fill Insulation
is installed only where the roof slope is <=3 in 12.
Insulation
5.5.3.1
Envelope
Skylight curbs are insulated to the level of roofs
❑
®
❑
with insulation above deck or R-5.
Insulation
5.8.1.2
Envelope
Above -grade wall insulation installed per
®
❑
manufacturer's instructions.
Insulation
5.8.1.2
Envelope
Floor insulation installed per manufacturers
instructions.
Insulation
6.8.1.1
Envelope
Building envelope insulation is labeled with
0
❑
R-value or insulation certificate providing R-value
and other relevant data.
Insulation
5.8.1.4
Envelope
Eaves are baffled to deflect air to above the
insulation.
Insulation
5.8.1.5
Envelope
Insulation is installed in substantial contact with
the Inside surface separating conditioned space
from unconditional space.
Insulation
5.8.1.6
Envelope
Recessed equipment installed in building
envelope assemblies does not compress the
adjacent insulation.
Insulation
5.8.1.7
Envelope
Extedor insulation is protected from damage with
El
El
0
a protective material. Verification for exposed
foundation insulation may need to occur during
Foundation Inspection.
Insulation
5.8.1.7.1
Envelope
Attics and mechanical rooms have Insulation
protected where adjacent to attic or equipment
access.
Insulation
5.8.1.7.2
Envelope
Foundation vents do not interfere with insulation.
EnergyGauge Summit® Fla/Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
Florida Building Code, Fifth Edition (2014) - Energy Conservation ASHRAE 90.1-2010 - Energy Cost Budget Option
9/2/2017 Page 12 of 15
al