STRUCTURAL ENGINEERS
19 December 2018
St. Lucie County
Planning & Developmental Services
2300 Virginia Ave.
Fort Pierce, FL 34982
Attn: _ Andrew Manero
Regarding: Advantage Self Storage
Steel Column Mark/Shop Drawings
Dear Mr. Manero,
SCANNED
BY
St. Lucie County
It has been brought to our attention that several steel column marks annotated on our structural
drawings do not match the steel columns that have been approved in the `Structural Steel Shop
Package' issued by I-MM Steel Corp and approved by our office on 05/29/18. The approved steel
shop drawings supersede the latest structural drawings.
The discrepancy occurs on gridline 11 of sheets S 104 & S 105, which illustrates an alternating
Column Type #1 & Column Type #2 pattern. This entire gridline should only annotate Column
Type #1, as illustrated in the approved shop drawing. In addition the column located at gridline
intersection R13 of S104 & S105 should also be a Column Type #1.
Thank you for your attention to the matter.
BRYNTESEN STRUCTURAL ENGINEERS
O``` �NI DN�>
co
f2
Murra1§rj en*P.E 0 :LL=
Floridaa.i fte`Nb 37162: 0t
a c
.... 1%%
�Ir--�E l�
I
DEC 2 6 2016
CONTRACTOR COPY
BY: — —
3045 NORTH FEDERAL HIGHWAY, BUILDING #80 ■ FORT LAUDERDALE, FLORIDA 33306 ■ TEL:954-568-1411 ■ FAX:954-568-9367
17r2-cowl
BRYINTESEN
STRUCTURAL ENGINEERS
19 December 2018
St. Lucie County
Planning & Developmental Services
2300 Virginia Ave.
Fort Pierce, FL 34982
Attn: Andrew Manero
Regarding: Advantage Self Storage
Steel Column Mark/Shop Drawings
Dear Mr. Manero,
It has been brought to our attention that several steel column marks annotated on our structural
drawings do not match the steel columns that have been approved in the `Structural Steel Shop
Package' issued by HM13 Steel Corp and approved by our office on 05/29/18. The approved steel
shop drawings supersede the latest structural drawings.
The discrepancy occurs on gridline 11 of sheets S 104 & S 105, which illustrates an alternating
Column Type 41 & Column Type 42 pattern. This entire gridline should only annotate Column
Type 91, as illustrated in the approved shop drawing. In addition the column located at gridline
intersection R13 of S104 & 5105 should also be a Column Type #1.
Thank you for your attention to the matter.
BRYNTESEN STRUCTURAL ENGINEERS
e`e�e®oeG Bl®®'B1�i
No 37162 .2 1
Florida Lfa,SL4 tnq -
a V
3045 NORTH FEDERAL HIGHWAY, BUILDING #80 InHT-FORT
FORT LAUDERDALE, FLORIDA 30 u TEL:954-56&1411 o FAX:954-568-9367
PjVENGINEERING INC.
Mechanical & Electrical Engineers
June 4 2018
Department of Building
Plumbing Reviewer
Fort Pierce, Port St Lucie County
Permit Number: 1712-0019
Reference Project: Advantage Self Storage.
Project Address: 605 Kitterman Rd & US-1, Port St Lucie, FL 34981
This is the response letter for the Plumbing comment, follow comment and response:
PLUMBING SECTION
ITEM
COMMENT
#
RESPONSE
PROVIDE HI-LO DRINKING FOUNTAINS AS
1
MUST HAVE HI-LO DRINKING FOUNTAINS PER SECTION 410.3 FBC
PER SECTION S P FBC. REFER TO
REVISED SHEETS P-2.10 AND P-3.10.
Thank you for your time please contact us if any questions on the above at 786-334-5683.
Marlon Lopez
MEP Designer.
;s
7791 NW 46' St, Suitc 413, Dm I, FL 33166 Ph: 786-334-5683 info@p vmg.wm w�%w.plvmg.com
PjV
ENGINEERING, INC.
Mechanical & Electrical Engineers
June 4, 2018
MEP
P-2.10- Revision to provide HI-LO drinking fountains.
P-3.10-Revision to change sanitary and cold water riser.
7791 NW 46" St. Suitc 413. Daml. FL 33166 Ph: 786-334-5683 infotuipjvmg.mm www.pjvcngccm
P ENGINEERING, INC.
Mechanical & Electrical Engineers
April 24 2018
Department of Building
Mechanical & Fire Protection Reviewers
Fort Pierce, Port St Lucie County
Permit Number: 1712-0019
Reference Project: Advantage Self Storage.
Project Address: 605 Kitterman Rd & US-1, Port St Lucie, FL 34981
This is the response letter for the Fire Safety and Mechanical comments, follows comments and responses:
FIRE SAFETY SECTION
ITEM
COMMENT
#
RESPONSE
FIRE SPRINKLER PLANS HAVE ALREADY
SUBMIT ALL FIRE SPRINKLER PLANS IN TRIPLICATE WITH CRITERIA.
BEEN SUBMITTED.
MECHANICAL SECTION
ITEM
COMMENT
#
RESPONSE
PRODUCT AFFIDAVITS SUBMITTED ARE INCORRECT AND/OR
INCOMPLETE' MUST BE THE ST LUCIE COUNTY' PRODUCT REVIEW
ADDED ST LUCIE COUNTY" PRODUCT
AFFIDAVITS" COMPLETELY FILLED OUT INCLUDING ALL FASTENER
REVIEW AFFIDAVITS'.
TYPE, SPACING, SIZE AND EMBED, THEN SIGNED, SEALED AND DATED
BY THE DESIGN PROFESSIONAL OF RECORD.
z
SUBMIT (3) ORIGINAL, SIGNED, SEALED AND DATED MECHANICAL LOAD
ADJUSTED MECHANICAL LOAD CALCS
CALCS DESIGNED TO FT. PIERCE WEATHER FOR MECHANICAL
DESIGNED TO FT. PIERCE WEATHER
REVIEWER, NOT WEST PALM BEACH.
Thank you for your time please contact us if any questions on the above at 786-334-5683.
Marlon Lopez
MEP Designer.
7791 NW 461" St. Suite 413, Doml, FL 33166 Ph: 786-334-5683 info@pjveng.com % wW.pjveng.com
P11V ENGINEERING, INC.
Mechanical & Electrical Engineers
April 24, 2018
MEP
M-2.10-Revision due new office layout.
M-2.20-Revision to Add mechanical ventilation for 3nd floor new bathrooms.
M-3.10-Revision to addition In -line Exhaust Fan Detail and EF-12&13 on Restroom & Janitor
Closet Exhaust Fan Schedule.
E-2.00- Revision to update Electrical Legend and Notes
E-2.10- Revision to update new Office Layout.
E-2.11- Revision to update new Office Layout.
E-2.20-Revision to add new bath on second floor.
E-3.10-Revision to update Power Riser.
E-3.11-Revision to add FPL Letter.
EL-2.10- Revision to update new Office Layout.
EL-2.20-Revision to add new bath on second floor.
ELP-2.10- Revision to update new Office Layout.
ELP-2.20-Revision to add new bath on second floor.
FA-2.10- Revision to update new Office Layout.
FA-2.20-Revision to add new bath on second floor.
FA-3.10-Revision to update Fire Alarm Riser.
P-2.00 Revision to addition IEWH-3 on Instant Water Heater Schedule.
P-2.10- Revision due new office layout and restrooms sanitary lines.
P-2.20- Revision to addition 2nd floor new restrooms and ventilation line.
P-2.30- Revision to addition ventilation line.
P-2.40- Revision to addition ventilation line.
P-3.10-Revision to change sanitary, condensate and cold water riser.
FP-1.10- Revision due new office layout.
FP- 1.21- Revision to addition 2nd floor new restrooms.
7791 NW 46" SL Suite 413, Dora], FL 33166 Ph: 786-334-5683 info@Pjreng.com N wM.pjvengxom
Florida Power & Light Company
FPL
April 10, 2018
ERIK SOMMER
266 E. Jericho Turnpike
Huntington Station, N.Y. 11746
Re: Farrell Storage at 605 Kitterman Road, Port Saint Lucie
Dear Erik:
This is to confirm that, at the present time, FPL has sufficient capacity to provide electric service to the above
captioned property. This service will be furnished in accordance with applicable rates, rules and regulations.
Preliminary analysis of your request has indicated that a line extension will be required and will most likely
require a Contribution in Aid of Construction to be paid in order to provide service.
Please provide the final site plan, site survey and electrical load data as soon as possible so the necessary
engineering can begin.
Early contact with FPL is essential so that resources may be scheduled to facilitate availability of service
when required.
Sincerely,
Diana Villages
Engineer I
a NEXTera ENERGY Company
FRANK C� RELF
ARCHITECT, P.C.
T '01271.0
FM M271A5
April 19, 2018
Re: 605 Kitterman Road, Port St Lucie FL
Advantage Self Storage
To: Port Saint Lucie Department of Buildings,
Frank Relf Architect has been working with Advantage Self Storage to design and provide
drawings for their latest facility located on 605 Kitterman Rd. in Port St. Lucie FL. We
originally filed our permit set (permit number 1712-0019) back in November, and are now
resubmitting our revised drawings as required to address several comments related to our
scope of work. Outlined below is a written narrative as to which sheets have been revised,
and how each corresponding comment was resolved.
Building Department Comments
Comment: The square footage on the plot plan on T-000.00 for building D is incorrect.
Response: The plot plan on T-000 has been revised to show the correct square footage.
Sheet T-001, drawing index, has also been revised as needed.
Comment: Occupant load is wrong. All buildings must be included in occupant count for
plumbing fixture requirements per section 403.1 Florida Building Code 2014
Response: A-010, Revised occupancy calculations and plumbing fixture count as needed to
comply with section 403.1 of the 2014 Florida Building Code. Floor plans have been revised
accordingly to show (2) additional H.C. Toilet rooms on sheet A-103.
Comment: Design professional is to provide a code section as to the elimination of the
occupant count for building D as stated on plan sheet A-020.00
Response: A-020, Building D has no interior corridors or occupied space, as it is made up
entirely of drive up storage units that are accessible from the exterior only. The floor plan
has been added to sheet A-020 and the calculations for S-1 occupancy (1 per 500sf) have
been added as needed.
Comment: The note (4) on A-080.00 ASCE7-94 is not a reference standard in the current
FBC for windows.
Response: Revised note 4 on sheet A-080 as required.
Comment: Product affidavits submitted are incorrect and or incomplete. Must be the St
Lucie County Product Review Affidavits completely filled out including all fastener type,
spacing, size and embed, then signed, sealed and dated by the design professional of record.
Three signed and sealed copies are required.
Response: Product affidavit has been revised accordingly, as well as signed and sealed as
required.
35 Pinelawn Road I Suite 207W • Melville • NY • 11747 • www.fgrelf.com
1146
FRANK Cz RELF
ARCHITECT, P.C.
�- B11271.44M
FN W1271ASU
April 19, 2018
Re: 605 Kitterman Road, Port St Lucie FL
Advantage Self Storage
To: Port Saint Lucie Department of Buildings,
Frank Relf Architect has been working with Advantage Self Storage to design and provide
drawings for their latest facility located on 605 Kitterman Rd. in Port St. Lucie FL. We
originally filed our permit set (permit number 1712-0019) back in November, and are now
resubmitting our revised drawings as required to address several comments related to our
scope of work. Outlined below is a written narrative as to which sheets have been revised,
and how each corresponding comment was resolved.
Building Department Comments
Comment: The square footage on the plot plan on T-000.00 for building D is incorrect.
Response: The plot plan on T-000 has been revised to show the correct square footage.
Sheet T-001, drawing index, has also been revised as needed.
Comment: Occupant load is wrong. All buildings must be included in occupant count for
plumbing fixture requirements per section 403.1 Florida Building Code 2014
Response: A-010, Revised occupancy calculations and plumbing fixture count as needed to
comply with section 403.1 of the 2014 Florida Building Code. Floor plans have been revised
accordingly to show (2) additional H.C. Toilet rooms on sheet A-103.
Comment: Design professional is to provide a code section as to the elimination of the
occupant count for building D as stated on plan sheet A-020.00
Response: A-020, Building D has no interior corridors or occupied space, as it is made up
entirely of drive up storage units that are accessible from the exterior only. The floor plan
has been added to sheet A-020 and the calculations for S-1 occupancy (1 per 500so have
been added as needed.
Comment: The note (4) on A-080.00 ASCE7-94 is not a reference standard in the current
FBC for windows.
Response: Revised note 4 on sheet A-080 as required.
Comment: Product affidavits submitted are incorrect and or incomplete. Must be the St
Lucie County Product Review Affidavits completely filled out including all fastener type,
spacing, size and embed, then signed, sealed and dated by the design professional of record.
Three signed and sealed copies are required.
Response: Product affidavit has been revised accordingly, as well as signed and sealed as
required.
35 Pinelawn Road I Suite 207W • Melville • NY • 11747 • www.fgrelfcom
Wo
FPL
April 10, 2018
ERIK SOMMER
266 E. Jericho Turnpike
Huntington Station, N.Y. 11746
Re: Farrell Storage at 605 Kitterman Road, Port Saint Lucie
Dear Erik:
Florida Power & Light Company
This is to confirm that, at the present time, FPL has sufficient capacity to provide electric service to the above
captioned property. This service will be furnished in accordance with applicable rates, rules and regulations.
Preliminary analysis of your request has indicated that a line extension will be required and will most likely
require a Contribution in Aid of Construction to be paid in order to provide service.
Please provide the final site plan, site survey and electrical load data as soon as possible so the necessary
engineering can begin.
, 1.
Early contact with FPL is essential so that resources may be scheduled to facilitate availability of service
when required.
Sincerely,
Diana ViIlegas
Engineer I
a NEXTera ENERGY Company
ENGINEERING, INC.
P1JV Mechanical 8t Electrical Engineers
April 24 2018
Department of Building
Mechanical & Fire Protection Reviewers
Fort Pierce, Port St Lucie County
Permit Number: 1712-0019
Reference Project: Advantage Self Storage.
Project Address: 605 Kitterman Rd & US-1, Port St Lucie, FL 34981
This is the response letter for the Fire Safety and Mechanical comments, follows comments and responses:
FIRE SAFETY SECTION
ITEM
COMMENT
#
RESPONSE
FIRE SPRINKLER PLANS HAVE ALREADY
7
SUBMIT ALL FIRE SPRINKLER PLANS IN TRIPLICATE WITH CRITERIA.
BEEN SUBMITTED.
MECHANICAL SECTION
ITEM
COMMENT
#
RESPONSE
PRODUCT AFFIDAVITS SUBMITTED ARE INCORRECT AND/OR
INCOMPLETE' MUST BE THE ST LUCIE COUNTY" PRODUCT REVIEW
ADDED ST LUCIE COUNTY" PRODUCT
t
AFFIDAVITS" COMPLETELY FILLED OUT INCLUDING ALL FASTENER
REVIEW AFFIDAVITS".
TYPE, SPACING, SIZE AND EMBED, THEN SIGNED, SEALED AND DATED
BY THE DESIGN PROFESSIONAL OF RECORD.
2
SUBMIT (3) ORIGINAL, SIGNED, SEALED AND DATED MECHANICAL LOAD
ADJUSTED MECHANICAL LOAD CALCS
CALCS DESIGNED TO FT. PIERCE WEATHER FOR MECHANICAL
DESIGNED TO FT. PIERCE WEATHER
REVIEWER, NOT WEST PALM BEACH.
Thank you for your time please contact us if any questions on the above at 786-334-5683.
Marlon Lopez
MEP Designer.
7791 NW 46ib St, Suite 413, Doml, FL 33166 Ph: 786-334-5683 info@pjveng.com % w .pjveng.com
MIR
FRANK C� RELF
ARCHITECT, P.C.
iEl' WI..MAW
FAX WiStaW
SCANNED
BY
St. Lucie County
Re: 605 Kitterman Road, Port St Lucie FL
Advantage Self Storage
To: Port Saint Lucie Department of Buildings,
SCANNED
BY
St. Lucie County
Frank Relf Architect has been working with Advantage Self Storage to design and provide
drawings for their latest facility located on 605 Kitterman Rd. in Port St. Lucie FL. We
originally filed our permit set (permit number 1712-0019) back in November, and are now
resubmitting our revised drawings as required to address several comments we received on
5/15/18. Outlined below is a written narrative as to which sheets have been revised, and
how each corresponding comment was resolved.
Building Departtrtent Comments
Commene Submit (3) St. Lucie County product review affidavits signed, sealed and dated in
original format. Sheet A-320.00 and A-321.00 spec overhead doors by Janus and product
affidavits spec DBCI 690 series doors. Be sure that these affidavits coincide with all plan
notes and product approval information proposed for use.
Response: (3) St, Lucie County product review affidavits submitted. Sheets A-320.00and A-
321.00 revised to reflect product approvals.
Comment: The design pressure tables calculated by engineer must coincide with pressures
on the product affidavits. Carlisle roof covering pressure is too low for actual pressures.
Res onse See Carlisle product approvals provided and revised St Lucie County affidavit.
We will be using (2) different approved attachment methods (SC-77 & SC-84) by Carlisle at
building C. Areas that require greater pressures will utilized system SC-84. All items fisted on
the product review affidavit have been coordinated with the structural engineers design
pressure tables. Roof product approval systems have also been reviewed, byBryntesen for
submittal to the city. Once approved by the city, all product approvals for fenestration and
roofing systems will receive shop; stamp approval by Bryntesen prior to construction.
Comment: Sheet A-106.00 shows different outside dimensions and shows the building to be
155' long, plot plan on T-000.00 shows the 15' and 20' dimensions reversed.
Response: Revised dimensions for building D on sheet T-000.00.
Comment, The engineer is specifying 10 mil vapor barrier and the architect is specifying
Grace Pteprufe waterproofing membrane?
Response: Sheets A-081, 300, 301, 310, 311, 320, 321, 330 revised to show the use of a 6
mil vapor barrier. Grace Preprafe waterproofing membrane is to be used at the elevator pit
only.
35 Pinclaw-n Road l Suite 207W • Melville • NY • 31747 • w- nv rgrelf.corn
Co
.y
Comment Must have hi-Lo drinking fountains per section 410.3 FPC
liesoonse: M-lo drinking fountain added to sheets A-102.00 and A-400.00. Plumbing
drawings have been revised as well.
Comment: Per plan sheet S001.00 the buildings have been designed to 160 mph exposure
C, per plan sheet s002.00 the uplift and service pressures are designed to 170 mph exposure
C. The building components and cladding must match. Design professional to show all
window and door flashing on plans per FBC 1405.4
Response: Sheets S001.00 and S002.00 have been revised as needed to be properly
coordinated, and reflect the correct exposure/pressures.
Comment: The engineers specifying a 10 mil vapor barrier and the architect is specifying
grace prepmfe waterproofing membrane.
Response: The architectural drawings have been revised to show a 6 mil vapor barrier at all
floor slabs. The waterproofing by grace will remain at the elevator pit in building C.
Buildings A,B, and D have been revised by Bryntesen to incorporate a 4" slab on grade with
a 6 mil vapor barrier. Additionally, building C has been revised to incorporate a 4" slab on
grade with •mono -footings at each column line utilizing 6 mil. vapor barrier. The spread
footing under the elevator core will utilize waterproofing by Grace.
This concludes our narrative in regards to the changes made to the drawings per the
Owner's request, as well as to address comments from the Port St Lucie Building
Department:
Sincerely,
Charles Caeciabaudo
Project Architect
Frank Reif Architect P.C.
545 East Jericho Turnpike, Huntington Station, NY 11746 . www.fgrelf.com
I.
is
PRANK Ci R£:LF
ARCHITECT, CC.
r M' zrtau
FP OU71 M
20'�8
Re: 605 Kitterman Road, Port St Lucie FL _SECO-%/O
Advantage Self Storage 4i:La-
To: Port Saint Lucie Department of Buildings, '"
Frank Relf Architect has been working with Advantage Self storage to design and provide
drawings for their latest facility located on 605 Kitterman Rd. in Port St. Lucie FL. We
originally filed our permit set (permit number 1712-0019) back in November, and are now
resubmitting our revised drawings as required to address several comments we received on
5/15/18. Outlined below is a written narrative as to which sheets have been revised, and
how each corresponding comment was resolved.
y;r"�•r' Building Department Comments
Comment. Submit (3) St. Lucie County product review affidavits signed, sealed and dated in
original format. Sheet A-320.00 and A-321.00 spec overhead doors by Janus and product
affidavits spec DBCI 690 series doors. Be sure that these affidavits coincide with all plan
notes and product approval information proposed for use.
Response: (3) St Lucie County product review affidavits submitted. Sheets A-320.00 and A-
321.00 revised to reflect product approvals.
? Comment: The design pressure tables calculated by engineer must coincide with pressures
on the product affidavits. Carlisle roof covering pressure is too low for actual pressures.
Response: See Carlisle product approvals provided and revised St Lucie County affidavit. 1
We will be using (2) different approved attachment methods (SC-77 & SC-84) by Carlisle at
building C. Areas that require greater pressures will utilized system SC-84. All items listed on
the product review affidavit have been coordinated with the structural engineers design
pressure tables. Roof product approval systems have also been reviewed, by Bryntesen for
submittal to the city. Once approved by the city, all product approvals for fenestration and
roofing systems will receive shop stamp approval by Bryntesen prior to construction.
Comment: Sheet A-106.00 shows different outside dimensions and shows the building to be
155' long, plot plan onT-000.00 shows the 15' and 20' dimensions reversed.
Response: Revised dimensions for building D on sheet T-000.00.
Comment: The engineer is specifying 10 mil vapor barrier and the architect is specifying
Grace Preprufe waterproofing membrane?
Response: Sheets A7081, 300, 301, 310, 311, 320, 321, 330 revised to show the use of a 6
mil vapor barrier. Grace Preprufe waterproofing membrane is to be used at the elevator pit
only.
35 Pinclaw-n Road Suite 207W • Melville • NY • 11747 • wcinu. fp,relf.com
--,
Comment: Must have hi-Lo drinking fountains per section 410.3 FPC
Response: fir-Io drinking fountain added to sheets A-102.00 and A-400.00. Plumbing
drawings have been revised as well.
Comment: Per plan sheet S001.00 the buildings have been designed to 160 mph exposure
C, per plan sheet sQ02.00 the uplift and service pressures are designed to 170 mph exposure
C. The building components and cladding must match. Design professional to show all
window and door flashing on plans per FBC 1405.4
Response: Sheets 5001.00 and S002.00 have been revised as needed to be properly
coordinated and reflect the correct exposure/pressures.
Comment: The engineer is specifying a 10 mil vapor barrier and the architect, is specifying
grace prepmfe waterproofing membrane.
Response: The architectural drawings have been revised to show a 6 mil vapor barrier at all
floor slabs. The waterproofing by grace will remain at the elevator pit in building C.
Buildings A;B, and D have been revised by Bryntesen to incorporate a 4" slab on grade with
a 6 mil vapor barrier. Additionally, building C has been revised to incorporate a V slab on
grade with mono -footings at each column line utilizing 6 mil. vapor barrier. The spread
footing under the elevator core will utilize waterproofing by Grace.
This concludes our narrative in regards to the changes made to the drawings per the
Owner's request, as well as to address comments from the Port St Lucie Building
Department.
Sincerely,
Charles Cacciabaudo
Project Architect
Frank Reif Architect P.C.
545 East Jericho Turnpike, Huntington Station, NY 11746 • www.fgreif com
•t
FRANK G. RELF
ARCHITECT, P.C.
ME 01271'1932
Re: 605 Kitterman Road, Port St Lucie FL
Advantage Self Storage
To: Port Saint Lucie Department of Buildings,
ril h}, 2 ili8
0-,pTryr.✓,Q1.
Frank Relf Architect has been working with Advantage Self Storage to design and provide
drawings for their latest facility located on 605 Kitterman Rd. in Port St. Lucie FL. We
originally filed our permit set (permit number 1712-0019) back in November, and are now
resubmitting our revised drawings as required to address several comments related to our
scope of work. Outlined below is a written narrative as to which sheets have been revised,
and how each corresponding comment was resolved.
Building Department Comments
Comment: The square footage on the plot plan on T-000.00 for building D is incorrect.
Response: The plot plan on T-000 has been revised to show the correct square footage.
Sheet T-001, drawing index, has also been revised as needed.
Comment: Occupant load is wrong. All buildings must be included in occupant count for
plumbing fixture requirements per section 403.1 Florida Building Code 2014
Response: A-010, Revised occupancy calculations and plumbing fixture count as needed to
comply with section 403.1 of the 2014 Florida Building Code. Floor plans have been revised
accordingly to show (2) additional H.C. Toilet rooms on sheet A-103.
Comment: Design professional is to provide a code section as to the elimination of the
occupant count for building D as stated on plan sheet A-020.00
Response: A-020, Building D has no interior corridors or occupied space, as it is made up
entirely of drive up storage units that are accessible from the exterior only. The floor plan
has been added to sheet A-020 and the calculations for S-1 occupancy (1 per 500sf) have
been added as needed.
Comment: The note (4) on A-080.00 ASCE7-94 is not a reference standard in the current
FBC for windows.
Response: Revised note 4 on sheet A-080 as required.
Comment: Product affidavits submitted are incorrect and or incomplete. Must be the St
Lucie County Product Review Affidavits completely filled out including all fastener type,
spacing, size and embed; then signed, sealed and dated by the design professional of record.
Three signed and sealed copies are required.
Response: Product affidavit has been revised accordingly, as well as signed and sealed as
required.
35 Pinelawn Road I Suite 207W • Melville • NY • 11747 • www.fgrelf.com
Comment: The test criteria on sheet 5001.0 is not what has been submitted for review.
Respnse: Geotech report information on sheet 5001 has been updated to match submitted
report.
Comment: Submit an original signed, sealed and dated structural inspection plan in
triplicate, generated by the design professional of record to be used by the threshold
inspector. See FBC 110.8.1. This is noted within section III Note 4, sheet 5001.00
Response: Threshold Inspection plan not required, as building is not over 50 ft or more
than three stories. Reference to Threshold has been removed.
Comment: Submit 3 St Lude certification for design load compliance sheets completely
filled out in original format, then signed, sealed and dated by design professional.
Response: (3) PSL Certification For Design Load Compliance forms submitted.
Comment: Submit in triplicate original engineered shops with calculations for the staircases,
landings, guard rails and hand rails with all connections. Must be reviewed and approved by
PE Murray Bryntesen, see notes S001.00
Comment: Submit in triplicate original SSD engineered shops for the fabrication and
assembly of the structural steel roof system per AISC standards (see 5001.00) Must include
all connections and weld specs. These shops must be reviewd and approved by P.E. Murray
Bryntesen.
Response: Regarding shop drawings (staircases+misc metals, PEMB roof, roof trusses,
structural steel), GC to submit drawings as they are prepared to Bryntesen for review.
Delegated engineered items (stairs, PEMB, trusses) to be signed and sealed by delegated
engineer and shall include calculations of member and connection designs with loads
imposed to supporting structure.
Additional Drawing Revisions, Owner Requested
A-090 —Note 3 of the storage door schedule has been revised to specify the use of a
different door system for all exterior storage doors. Product approvals have been provided,
and product affidavit has been revised accordingly to reflect this change.
A-102 — Revisions to the office configuration/layout per the owners request have been made
A-400 — Owner requested revisions to office layout/configuration have been added
A-401 — Owner requested revisions to office layout/configuration have been added
A-402 — Owner requested revisions to office layout/configuration have been added, as well
as all required millwork details
This concludes our narrative in regards to the changes made to the drawings per the
Owner's request, as well as to address comments from the Port St Lucie Building
Department.
Sincerely,
Charles Cacciabaudo
Project Manager
Frank Relf Architect P.C.
545 East Jericho Turnpike, Huntington Station, NY 11746 • www.fgrelf.corn
I11MENJilih, Florida's Leading Engineering Source
Environmental • Geotechnical • Construction Materials Testing • Threshold and Special Inspections • Plan Review& Code Compliance
F I
LE C%=tnk a All OF I y 7
October 18 2018
Park East Construction Corp.
Attn: Mr. Erik Sommer
266 E Jericho Turnpike
Huntington Station, New York 11746
Subject: Pad Certification Letter
Farrell Storage at Kitterman
606 Kitterman Road
Port St. Lucie, Florida
GFA Project No. 18-3920.00
OCT 1 8 HELD
Re: Tierra South Florida Project No. 7111-16-0202 dated August 8, 2016
Dear Mr. Sommer:
GFA International, Inc. (GFA) has completed testing services during the site preparation phase for
the above referenced project. A review of GFA's field density test report indicates the soils placed
as fill within the building pad achieved a minimum of 95 percent of the maximum dry density as
determined by the modified Proctor test (ASTM D1557).
Based on the test results, the soils have been prepared in general accordance with the
recommendations presented in the referenced Tierra South Florida report dated August 8, 2016.
The soils upon which the referenced structure will rest are capable of providing a safe bearing
capacity of 3,000 psf.
We appreciate the opportunity to be of service to you during this project. Please contact the
undersigned if you have any questions or comments, or if we may further assist you.
Respectfully Submitted,
GFA INTERNATIONAL, INC.
Florida Certificate of Authorization No. 4930
1 Digitally signed
John
by John Kent
Date: 2018.10.18
Ke n t; 08: 9 1-04'00'
John Kent, P.E.
Senior Project Engineer
Florida Registration No. 63218
This item has been digitally signed and sealed by John Kent, P.E. on the
dale adjacent to the seal. Printed copies of this document are not
considered signed and sealed and the signature must be verified on any
electronic copies.
607 NW Commodity Cove • Port St. Lucie, Florida 34986 • (772) 924.3575 • (772) 924.3580 (fax) • www.teamgfa.com
OFFICES THROUGHOUT FLORIDA
A City for All Ages"
February 11, 2020
Heather Burford
CITY OF �DRT ST. LUCIE
UTILITY SYSTEMS DEPARTMENT
900 SE Ogden Lane
Port St. Lucie, FL 34986
(772) 873-6400 — TDD Accessible
(772) 871-7615 — FAX Brad Macek, Director
St. Lucie County a43DI-is
Via e-mail: burfordh@luawv
stlucieco.org N�eaacbu'VW'aa
wi l L 933
SUBJECT: Advantage Self Storage oara'3.4'
605 Kitterman Rd
PSLUSD File No. 5258
Dear Mrs. Burford:
The above -referenced project has tied into the City of Port St. Lucie Utility Systems
Department (PSLUSD) water and wastewater we have performed the final inspection.
Should you have any questions or need further clarification, please do not hesitate at all to
contact me at (772) 873-6459.
Sincerely,
Con r�n'm
Lila Gorman
Project Coordinator
c: Project File
Steve Harnage, Commercial Development Manager
Colleen Jacobsen, Project Coordinator
1oft
Or
v
Florida's Leading
Environmental-Geotechnlcal - Construction Materials Testing • Threshold and Special Inspections - Plan Review &
x
knor� " allo f
Park East Construction Corp.
Attn: Mr. Erik Sommer
266 E Jericho Turnpike
Huntington Station, New York 11746
Subject: Pad Certification Letter
Farrell Storage at Kitterman
605 Kitterman Road
Port St. Lucie, Florida
GFA Project No. 18-3920.00
October 18, 2018
RECEIVED
OCT 3 0 2918
ST- Lucie County, permitpryg
Re: Tierra South Florida Project No. 7111-16-0202 dated August 8, 2016
Dear Mr. Sommer:
GFA International, Inc. (GFA) has completed testing services during the site preparation phase for
the above referenced project. A review of GFA's field density test report indicates the soils placed
as fill within the building pad achieved a minimum of 95 percent of the maximum dry density as
determined by the modified Proctor test (ASTM D1557).
Based on the test results, the soils have been prepared in general accordance with the
recommendations presented in the referenced Tierra South Florida report dated August 8, 2016.
The soils upon which the referenced structure will rest are capable of providing a safe bearing
capacity of 3,000 psf.
We appreciate the opportunity to be of service to you during this project. Please contact the
undersigned if you have any questions or comments, or if we may further assist you.
Res pe ttdtl� Sty 1w",
GF/,dP7 i 6NP,/JfdC.
FIQMa e'rtj -R&6 ofi Auth&r zation No. 4930
No.83278 * _
Florida
OF
;$ �r
ion No..63218
607 NW
Cove • Port St. Lucie, Florida 34986 - (772) 924.3575 • (772) 924-3580
OFFICES THROUGHOUT
... 17/2— 00/1?
Page 1 of 4
rj
DESIGN OF HAPCO ALUMINUM LIGHTING POLES
CATALOG No. RTA20136131)
PROJECT: ADVANTAGE SELF STORAGE
St. Lucie County, Florida 3/19/20 EJW
DESIGN CRITERIA: FLORIDA BUILDING CODE 2017
170 MPH (max with Gust) Using ASCE7-10, Per Section 1601 & 1819
Date: 2-20-2020
References:
ASCE 7-I0 — Minimum Design Loads for Buildings & Other Structures
Florida Building Code 2017 Chapter 16 for Structures and 18 for Foundations Cat.I
AASHTO Standard Specifications for Highway Signs, Luminaries and Traffic Signals
1994 & 2014
FDOT Standard Specifications
Catalog Cut Sheets
Prepared By: James E. Wild, P.E.
592 Lancaster Gate SE
North Canton Ohio 44709
Submitted By: Precision Outdoor Lighting, Inc.
3832 Shipping Ave
Miami, Fl 33146
e9,9991BIB19BY)0o/
eee`eP�ES E
e t\o 43 39
';y e
P� ENGINEERING, INC.
Mechanical & Electrical Engineers
April 8.2020
Building Department
City of Port Saint Lucie
Permit Numbers: SLC 1712-0019
Address: 605 Kitterman Rd, Port St. Lucie, FL
Subject: Building compliance pith Energy Calculations
To Whom It May Concern.
This letter is to inform you that during the construction the have reviewed the product data of the materials and
equipment installed in this building, therefore, this building complies %Ath the energy calculations submitted during the
permit.
Please contact me if any questions on this matter.
Thank you for your time.
t t
Pablovitcri, R.E. 59535-- _
Principal
7791 NW 466 St, Suite 413, Doral, FL 33166 Plc 786-334-5683 info t pieeng.com Al4"W.PICLng.COnt
PJV
ENGINEERING, INC.
Mechanical & Electrical Engineers
April 8, 2020
Building Department
City of Port Saint Lucie
Permit Numbers: SLC 1712-0019
Address: 605 Kitterman Rd, Port St. Lucie, FL
Subject: Building compliance with Energy Calculations
To Whom It May Concern,
This letter is to inform you that during the construction we have reviewed the product data of the materials and
equipment installed in this building, therefore, this building complies with the energy calculations submitted during the
permit.
Please contact me if any questions on this matter.
Thank you for your time.
n J. Vi;
*�• N0.59535
STATE OF
Pablo Viteri, P.E. 59535
Principal
7791 NW 46" St, Suite 413, Dora], FL 33166 Ph: 786-334-5683 info@pjveng.cont vrnw.pjveng.com
Andrew Armbruster
From: Andrew Armbruster
Sent: Friday, June 7, 2019 8:58 AM
To: JPlinc
Cc: Tom Knight
Subject: Permit # 1712-0019 Deferred Submittals
Attachments: AV-37 STAIRS CALCS REV JAN 2019 s+s-AAN.pdf, J#85317-Truss-Placement-Diagram-
(AAN).pdf
Andrew,
Permit # 1712-0019 Deferred Submittals
Steel stair calcs and metal truss placement drawings are attached.
Link to pre-engineered metal truss design drawings:
https://app.box.com/s/SOiSbpigfcgc68zgdf547tivhuvxgsia
Andrew Armbruster
Project Manager
321-427-9012
WELSH-1
C..O NSTrZ❑CTIC
Andrew Armbruster
From:
Andrew Armbruster
Sent:
Friday, June 7, 2019 8:58 AM
To:
JPlinc
Cc:
Tom Knight
Subject
Permit # 1712-0019 Deferred Submittals
Attachments:
AV-37 STAIRS CALCS REV JAN 2019 s+s-AAN.pdf, J#85317-Truss-Placement-Diagram-
(AAN).pdf
Andrew,
Permit # 1712-0019 Deferred Submittals
Steel stair calcs and metal truss placement drawings are attached.
Link to pre-engineered metal truss design drawings:
https://app.box.com/s/50i8bpigfc8c68zgdf547t]vhuvxgsla
Andrew Armbruster
Project Manager
321-427-9012
byl--
H. ELS
t OJJTe213C.T10\I
1
Andrew Armbruster
To: JPI inc
Subject: Permit # 1712-0019 Deferred Submittals
Attachments: Farrell Advantage Storage - Canopy shop drawing.pdf
Andrew,
Permit # 1712-0019 Deferred Submittal for aluminum canopy.
Andrew Armbruster
Project Manager
321-427-9012
r7 .1_
,c�rJ^Tr«arrr^n
gq
mi—yo,
°
Andrew Armbruster
From:
Andrew Armbruster
Sent:
Wednesday, July 10, 2019 3:05 PM
To:
JPI inc
Cc
Tom Knight
Subject:
Permit # 1712-0019
Attachments:
SD-01-15700 Aluminum Stand-Rev4 PJV Revised.pdf
Andrew
HVAC roof stand deferred submittal was submitted back in March. The pdf is attached. Let me know if this is enough
information or if more is required. Thank you
Andrew Armbruster
Project Manager
32�1-4227-9012
G!7 WSTa21!.^^.T IDK
Andrew Armbruster
To: JPI inc
Subject: Permit # 1712-0019 Deferred Submittals
Attachments: Farrell Advantage Storage - Canopy shop drawing.pdf
Andrew,
Permit # 1712-0019 Deferred Submittal foraluminum canopy.
Andrew Armbruster
Project Manager
321-427-9012
WELSH
LOW^TRU^.T IUL
Andrew Armbruster
From:
Andrew Armbruster
Sent:
Wednesday, July 10, 2019 3:05 PM
To:
JPI inc
Cc:
Tom Knight
Subject:
Permit # 1712-0019
Attachments:
SD-01-15700 Aluminum Stand-Rev4 PJV Revised.pdf
Andrew
HVAC roof stand deferred submittal was submitted back in March. The pdf is attached. Let me know if this is enough
information or if more is required. Thank you
Andrew Armbruster
Project Manager
321-427-9012
WELS .-
CONSTRUCT IQ
Andrew Armbruster
From:
Sent: SCANNED
To: BY
Cc: St. Lucie County
Subject:
Eric Price <ericprice@wildblue.net>
Monday, January 7, 2019 4:01 PM
Andrew Armbruster
Sha-ron Roslin; Phil Godoy
Re: Welder certification
&It"Z,0 /ti l
Eric Price
Florida Atlantic Ironworks, Inc.
Safety Director
/-7 -ace/C?
CF'?ZT( /-rC4 J
RECEIVED
1AN 3 - 1019
Permitting Department
St. Lucie County
From: "Andrew Armbruster" <andrew@welshci.com>
To: "Eric Price" <ericpdce@wildblue. net>, "Sha-ron Roslin" <SRoslin@hmbsteel.com>
Cc: "Phil Godoy" <godoypgss1@gmail.com>
Sent: Monday, January 7, 2019 3:49:54 PM
Subject: RE: Welder certification
I1 NJ Ya o rt o "_ ri o i of 0 4 - O O e 0`O o U &O I &'-@W o 0_OD8 @==Mo �
Andrew Armbruster
Project Manager
321-427-9012
WEL-SH-
CON57HUCTION
From: Eric Price <ericprice@wiIdblue. net> -
Sent: Monday, January 7, 2019 2:57 PM
To: Sha-ron Roslin <SRoslin@hmbsteel.com>
Cc: Phil Godoy <4odoypgss1 @gmail.com>; Andrew Armbruster <andrew@welshci.com>
Subject: Re: Welder certification
r
Here you go
Eric Price
Florida Atlantic Ironworks, Inc.
Safety Director
From: "Sha-ron Roslin" <SRoslin(cDhmbsteel.com>
To: "Eric Price" <ericpriceRwildblue. net>, "Phil Godoy" <godovpgss1 ng.gmail.com>
Cc: "Andrew Armbruster" <andrewCilwelshci.com>
Sent: Monday, January 7, 2019 2:54:15 PM
Subject: FW: Welder certification
Eric,
We need the teams weld certs for the Advantage storage project. Mike Morris crew and the decking
crew.
Thank you,
Sha-Ron Roslin
Project Manager
HMB Steel Corp
4080 Pines Industrial Avenue
Rockledge, FL 32955
321-636-6511
321-698-0700 (cell)
sroslin(@hmbsteel.com
2
From: Andrew Armbruster fmailto:andrew(cDwelshci.coml
Sent: Monday, January 7, 2019 2:34 PM
To: Sha-ron Roslin <SRoslinna.hmbsteel.com>
Subject: Welder certification
Sha-Ron,
St Lucie County requires proof of welder's certification, please forward so we can submit. Thank you
Andrew Armbruster
Project Manager
321-427-9012
WELSH
CONSTRUCTION
0
PPL
April 10, 2018
ERIK SOMMER
266 E. Jericho Turnpike
Huntington Station, N.Y. 11746
Re: Farrell Storage at 605 Kitterman Road, Port Saint Lucie
Dear Erik:
Florida Power & Light Company
RECEIVED
JUL 2 3 2018
ST. Lucie County, Permitting
This is to confirm that, at the present time, FPL has sufficient capacity to provide electric service to the above
captioned property. This service will be furnished in accordance with applicable rates, rules and regulations.
Preliminary analysis of your request has indicated that a line extension will be required and will most likely
require a Contribution in Aid of Construction to be paid in order to provide service.
Please provide the final site plan, site survey and electrical load data as soon as possible so the necessary
engineering can begin.
Early contact with FPL is essential so that resources may be scheduled to facilitate availability of service
when required.
Sincerely,
Diana Villegas
Engineer I
a NEXTera ENERGY Company
Piv
ENGINEERING, INC.
Mechanical & Electrical Engineers
Shop Drawing / Submittal Review
❑ APPROVED ❑ REJECTED
® APPROVEDAS NOTED ❑ RESUBMIT
SUBMITTAL WAS REVIEWED FOR CONFORMANCE WITH THE
DESIGN CONCEPT AND INTENT AND GENERAL COMPLIANCE
WITH THE CONTRACT DOCUMENTS. THE CONTRACTOR IS
RESPONSIBLE FOR CONFIRMING AND CORRELATING ALL
QUANTITIES AND DIMENSIONS, FABRICATION AND CONSTRUCTION
METHODS COORDINATION OF THIS TRADE WITH ALL OTHER
APPLICABLE TRADES AND FOR PERFORMING HIS WORK IN ASAFE
AND SATISFACTORY MANNER.
BY Pablo Viteri DATE 07-19-18
Elevator Submittal
SUBMITTAL#
PJV Engineering, Inc.
7791 NW 46th Street, SUlte 413 - Dora], FL 33166
1. Provide one Sump Pump rated at 6,000 GPH or 100GPM for Elevator Shaft.
2. Provide lighting to the Fire Elevator Shaft.
3. Provide lighting to top of shaft for machine in each shaft
4. Increase Circuit breaker in panel MOP from (2)175A-3PH to (2)200A-3PH, wiring 3#4/0& #2gnd
(AL) IN 2-1/2"C for each elevator, from panel MDP to elevator. Elevators circuit breakers with shunt
trip capabilities, provide back up relay auxiliary connection. Coordinate with Fire Alarm Contractor and
elevator vendor on plans for details.
5. Provide (2)200A-3PH disconnect with 200A time delay fuse instead of 175A time delay fuse located
at ground floor in elevator Machine Room.
6. Provide (2) disconnects 30A-1P for lighting elevator shaft and lighting car in each elevator,
7. Run (1) 3" and (1) 2" conduits from the electrical room to each elevator hoist way. Per NEC code,
there can be no more than (4) quarter bends between pull points and pull boxes are required every 100'.
Verify with elevator vendor for exact requirements.
8. Provide fire alarm connection to the elevator sump pumps to recall elevators as noted on sequence of
operation Alarm note #4 on sheet FA-2.00. Verify with plumbing contractor.
9. Provide fire alarm connections to elevator controller, coordinate with fire alarm contractor.
10. Provide phone wall jacks inside elevator for each cabinet. Coordinate with elevator contractor.
11. As per submitted heat rejection provide 2 Ton minisplit AC for Machine Room as per plans,
coordinate with mechanical and electrical contractor.
Pablo Viteri, P.E. 59535
Principal
7791 NW 40 St. Suite 413, Dorm, FL 33166 Pb: 786-334-5683 info@pjveng.com w .pjvengcom
Piv
ENGINEERING. INC.
Mechanical & Electrical Engineers
Shop Drawing / Submittal Review
❑ APPROVED ❑ REJECTED
® APPROVEDAS NOTED ❑ RESUBMIT
SUBMITTAL WAS REVIEWED FOR CONFORMANCE WITH THE
DESIGN CONCEPT AND INTENT AND GENERAL COMPLIANCE
WITH THE CONTRACT DOCUMENTS. THE CONTRACTOR IS
RESPONSIBLE FOR CONFIRMING AND CORRELATING ALL
QUANTITIES AND DIMENSIONS, FABRICATION AND CONSTRUCTION
METHODS COORDINATION OF THIS TRADE WITH ALL OTHER
APPLICABLE TRADES AND FOR PERFORMING HIS WORK IN ASAFE
AND SATISFACTORY MANNER.
BY Pablo Viteri DATE 07-19-18
Elevator Submittal
SUBMITTAL#
PJV Engineering, Inc.
7791 NW 46th Street, Suite 413 - Doral, FL 33166
1. Provide one Sump Pump rated at 6,000 GPH or 100GPM for Elevator Shaft.
2. Provide lighting to the Fire Elevator Shaft.
3. Provide lighting to top of shaft for machine in each shaft
4. Increase Circuit breaker in panel MEiP from (2)175A-3PH to (2)200A-3PH, wiring 3#4/0& #2gnd
(AL) IN 2-1/2"C for each elevator, from panel MDP to elevator. Elevators circuit breakers with shunt
trip capabilities, provide back up relay auxiliary connection. Coordinate with Fire Alarm Contractor and
elevator vendor on plans for details.
5. Provide (2)200A-3PH disconnect with 200A time delay fuse instead of 175A time delay fuse located
at ground floor in elevator Machine Room.
6. Provide (2) disconnects 30A-1P for lighting elevator shaft and lighting car in each elevator,
7. Run (1) 3" and (1) 2" conduits from the electrical room to each elevator hoist way. Per NEC code,
there can be no more than (4) quarter bends between pull points and pull boxes are required every 100'.
Verify with elevator vendor for exact requirements.
8. Provide fire alarm connection to the elevator sump pumps to recall elevators as noted on sequence of
operation Alarm note #4 on sheet FA-2.00. Verify with plumbing contractor.
9. Provide fire alarm connections to elevator controller, coordinate with fire alarm contractor.
10. Provide phone wall jacks inside elevator for each cabinet. Coordinate with elevator contractor.
11. As per submitted heat rejection provide 2 Ton minisplit AC for Machine Room as per plans,
coordinate with mechanical and electrical contractor.
Pablo Viteri, P.E. 59535
Principal
7791 NW 46' St, Suite 413, Dotal, FL 33166 Ph: 786-334-5683 info@pjveng.com �.pjveng.com
rivENGINEERING, INC.
Mechanical & Electrical Engineers
I Shop Drawing / Submittal Review I
❑ APPROVED ❑ REJECTED
® APPROVEDASNOTED ❑ RESUBMIT
SUBMITTAL WAS REVIEWED FOR CONFORMANCE WITH THE
DESIGN CONCEPT AND INTENT AND GENERAL COMPLIANCE
WITH THE CONTRACT DOCUMENTS. THE CONTRACTOR IS
RESPONSIBLE FOR CONFIRMING AND CORRELATING ALL
OUANTITIESAND DIMENSIONS, FABRICATION AND CONSTRUCTION
METHODS COORDINATION OF THIS TRADE WITH ALL OTHER
APPLICABLE TRADES AND FOR PERFORMING HIS WORN IN A SAFE
AND SATISFACTORY MANNER.
BY Pablo Viteri DATE 07-19-18
SUBMITTAL#
Elevator Submittal
PJV Engineering, Inc. -
7791 NW 46th Street, Suite 413 - Doral, FL 33166
1. Provide one Sump Pump rated at 6,000 GPH or 100GPM for Elevator Shaft.
2. Provide lighting to the Fire Elevator Shaft.
3. Provide lighting to top of shaft for machine in each shaft
4. Increase Circuit breaker in panel MDP from (2)175A-3PH to (2)200A-3PH, wiring 3#4/0& #2gnd
(AL) IN 2-1/2"C for each elevator, from panel MDP to elevator. Elevators circuit breakers with shunt
trip capapilities, provide back up relay auxiliary connection. Coordinate with Fire Alarm Contractor and
elevator vendor on plans for details.
5. Provide (2)200A-3PH disconnect with 200A time delay fuse instead of 175A time delay fuse located
at ground floor in elevator Machine Room.
6. Provide (2) disconnects 30A-1P for lighting elevator shaft and lighting car in each elevator,
7. Run (1) 3" and (1) 2" conduits from the electrical room to each elevator hoist way. Per NEC code,
there can be no more than (4) quarter bends between pull points and pull boxes are required every 100'.
Verify with elevator vendor for exact requirements.
8. Provide fire alarm connection to the elevator sump pumps to recall elevators as noted on sequence of
operation Alarm note #4 on sheet FA-2.00. Verify with plumbing contractor.
9. Provide fire alarm connections to elevator controller, coordinate with fire alarm contractor.
10. Provide phone wall jacks inside elevator for each cabinet. Coordinate with elevator contractor.
11. As per submitted heat rejection provide 2 Ton minisplit AC for Machine Room as per plans,
coordinate with mechanical and electrical contractor.
Pablo Viteri, P.E. 59535
Principal
7791 NW 46' S6 .Sn1IC 413. Dom1, FL 33166 Ph: 786-334-5693 info@,pjvcng.com www.pjycng.com
Piv
ENGINEERING, INC.
Mechanical & Electrical Engineers
Shop Drawing I Submittal Review
❑ APPROVED ❑ REJECTED
El APPROVEDASNOTED ❑ RESUBMIT
SUBMITTAL WAS REVIEWED FOR CONFORMANCE WITH THE
DESIGN CONCEPT AND INTENT AND GENERAL COMPLIANCE
WITH THE CONTRACT DOCUMENTS. THE CONTRACTOR IS
RESPONSIBLE FOR CONFIRMING AND CORRELATING ALL
QUANTITIES AND DIMENSIONS, FABRICATION AND CONSTRUCTION
METHODS COORDINATION OF THIS TRADE WITH ALL OTHER
APPLICABLE TRADES AND FOR PERFORMING HIS WORK IN A SAFE
AND SATISFACTORY MANNER.
BY Pabloyiteri DATE 07-19-18
Elevator Submittal
SUBMITTAL#
PJV Engineering, Inc.
7791 NW 46th Street, Suite 413 - Doral, FL 33166
1. Provide one Sump Pump rated at 6,000 GPH or 100GPM for Elevator Shaft.
2. Provide lighting to the Fire Elevator. Shaft.
3. Provide lighting to top of shaft for machine in each shaft
4. Increase Circuit breaker in panel MDP from (2)175A-3PH to (2)200A-3PH, wiring 3#4/0& #2gnd
(AL) IN 2-1/2"C for each elevator, from panel MDP to elevator. Elevators circuit breakers with shunt
trip capabilities, provide back up relay auxiliary connection. Coordinate with Fire Alarm Contractor and
elevator vendor on plans for details.
5. Provide (2)200A-3PH disconnect with 200A time delay fuse instead of 175A time delay fuse located
at ground floor in elevator Machine Room.
6. Provide (2) disconnects 30A-1P for lighting elevator shaft and lighting car in each elevator,
7. Run (1) 3" and (1) 2" conduits from the electrical room to each elevator hoist way. Per NEC code,
there can be no more than (4) quarter bends between pull points and pull boxes are required every 100'.
Verify with elevator vendor for exact requirements.
8. Provide fire alarm connection to the elevator sump pumps to recall elevators as noted on sequence of
operation Alarm note #4 on sheet FA-2.00. Verify with plumbing contractor.
9. Provide fire alarm connections to elevator controller, coordinate with fire alarm contractor.
10. Provide phone wall jacks inside elevator for each cabinet. Coordinate with elevator contractor.
11. As per submitted heat rejection provide 2 Ton minisplit AC for Machine Room as per plans,
coordinate with mechanical and electrical contractor.
Pablo Viteri, P.E. 59535
Principal
7791 NW 4611' St. Suite 413. Dural, FL 33166 Pit: 786-334-5683 info,,pjvcng.com www.pjvcng.com
X;
PjV
ENGINEERING, INC.
Mechanical & Electrical Engineers
Shop Drawing / Submittal Review
❑ APPROVED ❑ REJECTED
® APPROVEDASNOTED ❑ RESUBMIT
SUBMITTAL WAS REVIEWED FOR CONFORMANCE WITH THE
DESIGN CONCEPT AND INTENT AND GENERAL COMPLIANCE
WITH THE CONTRACT DOCUMENTS. THE CONTRACTOR IS
RESPONSIBLE FOR CONFIRMING AND CORRELATING ALL
QUANTITIES AND DIMENSIONS, FABRICATIONAND CONSTRUCTION
METHODS COORDINATION OF THIS TRADE WITH ALL OTHER
APPLICABLE TRADES AND FOR PERFORMING HIS WORK IN A SAFE
AND SATISFACTORY MANNER Ft
BY Pablo viteri DATE 07-1! 18
SUBMITTAL# Elevator Submittal
PJV Engineering, Inc.
7791 NW 46th Street, Suite 413 - Doral, FL 33166
1. Provide one Sump Pump rated at 6,000 GPH or 100GPM for Elevator Shaft.
2. Provide lighting to the Fire Elevator Shaft.
3. Provide lighting to top of shaft for machine in each shaft
4. Increase Circuit breaker in panel MDP from (2)175A-3PH to (2)200A-3PH, wiring 3#4/0& #2gnd
(AL) IN 2-1/2"C for each elevator, from panel MDP to elevator. Elevators circuit breakers with shunt
trip capabilities, provide back up relay auxiliary connection. Coordinate with Fire Alarm Contractor and
elevator vendor on plans for details.
5. Provide (2)200A-3PH disconnect with 200A time delay fuse instead of 175A time delay fuse located
at ground floor in elevator Machine Room.
6. Provide (2) disconnects 30A-lP for lighting elevator shaft and lighting car in each elevator,
7. Run (1) 3" and (1) 2" conduits from the electrical room to each elevator hoist way. Per NEC code,
there can be no more than (4) quarter bends between pull points and pull boxes are required every 100'.
Verify with elevator vendor for exact requirements.
8. Provide fire alarm connection to the elevator sump pumps to recall elevators as noted on sequence of
operation Alarm note #4 on sheet FA-2.00. Verify with plumbing contractor.
9. Provide fire alarm connections to elevator controller, coordinate with fire alarm contractor.
10. Provide phone wall jacks inside elevator for each cabinet. Coordinate with elevator contractor.
11. As per submitted heat rejection provide 2 Ton minisplit AC for Machine Room as per plans,
coordinate with mechanical and electrical contractor.
Pablo Vitcri, P.E. 59535
Principal