September 5, 2019
Project
Advantage Self Storage
Kitterman Road & US-1
Port St. Lucie, Florida
Architect
Frank G. Reif Architect
35 Pinelawn Road, Suite 207W
Melville, New York 11747
General Contractor
Welsh Construction
3845 W. Eau Gallie Blvd.
Melbourne, Florida 32934
Mechanical Engineer
PJV Engineering Inc.
7791 NW 46th Street #413
Doral, Florida
Mechanical Contractor
Meridian Mechanical Services
Cocoa, Florida
1 `7 12 -cal I
Kyle Stout
1029 Hornbeam Street
Oviedo, FL 32765
Main: (407) 402-3256
stout 1029@aol.com
www.AbsoluteTestandBalance.com
SCANNED
BY
St. Lucie Countv
AABC
Associated Air Balance Council
Annual Certificate
-' u ff elal to
Kyle Stout
Absolute Balance, Inc.
<</1. r'� ffzlt[OfG O}l1CrL'• �CILLIfZG'lltl!)fGL'•fG�' ar
�� �� Wiest czruG �rxla,�ace��i�,�u�
wider tfw iule� ritio/G� razrd r er�clr e//nutty pf ' tlzl
lssociatea� �i� 0a16ce loan - flu aGooe nwierz!zs f lGy
antlurimV to.lb ormto/a/,&,mem Gak1wvI iz aecorw1ance1
wffjb av ew&1"s1m'cd Gy tlzv ✓G/L' l <'rrnrd CGL'' rG
nzeirzGe. <oft�e %lrsociatca! r alaizcf C�oaizc�Gf r t1a� cW
��T�41w4lraLirm nzr/n/ter 0s-09-43rewyrnyl�zed
&, dw, G av and eizartcr q161u11,,ioam11 a� wr atioiz:
6'el f,-Az do rs -ewe mole, on, aiv ammmar Grori�, a
ei "Mha•Cioru lie. a� yeiu�� rrcoiWl or• lhe, 1 r eceV.,R
arar ri's ar/r�cle, ex�ire.f;ecFrnGer t�'/ ;�0/�.
7 • Benjiman J. Link, President
f
1 I I
Raymond R. Bert, Lxcwtive Director
t
AABCNational
Performance Guaranty
Pursuant to the agreement between
Absolute Balance, Inc., Orlando, Florida
AABC Certified Testing & Balancing Agency
Client
All systems shall be balanced in accordance with the plans and specifications and to the optimum performance capabilities of the
equipment and design. Testing and balancing shall be done in accordance with the standards published by the Associated Air Balance Council.
If for any reason, the Agency listed above fails to comply with the specifications, with the exception of termination of business by the
Agency, equipment malfunction or inadequacy, or improper design, which prevents proper balancing of the systems, the Associated Air
Balance Council will provide supervisory personnel to assist the Agency to perform the work in accordance with AABC Standards.
As part of the Performance Guaranty, the engineer or building owner may call upon AABC to assist him with any technical and/or field
problems pertaining to the final balanced condition of. systems. These services will be made available at no additional charge by the above
agency or by AABC National Headquarters.
Project Name Advantage Self Storage
Address Kitterman Road & US-1
Port St. Lucie, Florida
Name of Engineer Pablo J. Viteri
Engineering Firm PJV Engineering, Inc.
Address 7791 NW 46th Street. Suite #413
Dorla, Florida
Date 09-05-19
TBE # 06-09-43
By Kyle Stout
AABC Certified TBE
AABC
Associated Air
Balance Council
Absolute Balance, Inc.
Telephone: 407-402-3256 Date: 09-05-19
Email: stoutl029@aol.com Page: 1
Project: Advantage Self Storage
Kitterman Road & US-1
Port St. Lucie, Florida
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM
AHU-1
AHU-2
Equipment Location
Ceiling
Ceiling
Area Served
1 st Level Office
1 sl Floor Storage
Equipment Manufacturer
Carrier
Carrier
Model
FX4DNF019
FX4DNF049
Serial Number
0419F41245
5018FO8040
Specified
Actual
Specified
Actual
TotalCFM-Fan
600
635
1600
1567
Total CFM - Outlet
650
635
1600
1567
R/A CFM
550
536
1230
1201
O/A CFM
100
99
370
366
Total Static Pressure (Total/External)
—4.50
.37/.28
—4.50
.62/.32
Inlet Pressure
___
.20/.11
=-
.44/.14
Discharge Pressure
___
.17
-_
.18
Fan RPM
---
High
I Medium
Specified
Actual
Specified
Actual
Motor Manufacturer _
---
Gente
--
Gente
Motor HP
.33
.33
.75
.75
Phase
1
1
1
1
Voltage
208
214
208
214
Amperage
2.8
1.1
6.0
2.9
Motor RPM
3 Speed
I High
1 3 S eed
Medium
Motor Service Factor
1.0
1.0
1.0
1.0
Motor Sheave & Bore Size
D. D.
D.D.
Fan Sheave & Bore Size
D.D.
D.D.
Belts -- Quantity and Size
D. D.
D. D.
center to Center
D. D.
D. D.
D.D. = Direct Drive.
Absolute Balance, Inc.
Telephone: 407-402-3256 Date: 09-19
Email: stout1029@aol.com Page: 2
Project: Advantage Self Storage
, AIR MOVING EQUIPMENT TEST SHEET
SYSTEM
AHU-3
AHU-4
Equipment Location
Ceiling
Ceiling
Area served
1 st Floor Storage
2od Floor Storage
Equipment Manufacturer -
Carrier
. Carrier
Model
FX4DNF061
FX4DNF061
Serial Number
4918f24206
4818f18804
Specified
Actual
Specified
Actual
TotalCFM—Fan
2000
1887
2000
1853
TotalCFM— Outlet
2000
1887
2000
1853
RIA CFM
1630
1522
1630
1562
oiA CFM
370
365
370
291
Total Static Pressure (Total/External)
--4.50
.75/.33
---/.50
.81 /.35
inlet Pressure
---
.64/.22
---
.69/.23
Discharge Pressure
--
.11
--
.12
Fan RPM
---
HI h
---
High
Specified
Actual
Specified
Actual
Motor Manufacturer
---
Gente
---
Gente
Motor HP
.75
.75
.75
.75
Phase
1
1
1
1
Voltage
208
214
208
214
Amperage
6.0
4.1
6.0
4.2
Motor RPM
3 Speed
High
1 3 Speed
Hi h
Motor Service Factor
1.0
1.0
1.0
1-.0
Motor Sheave & Bore Size
D.D.
D.D.
Fan Sheave & Bore Size
D.D.
D.D.
Belts ---Quantity and Size
D.D.
-D-.D.
CentertoCenter .
D.D.
D.D.
D.D. = Direct Drive.
Absolute Balance, Inc.
Telephone: 407-402-3256 Date: 09-19
Email: stautl029@aol.com Page: 3
Project: Advantage Self Storage
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM
AHU-5
AHU-6
Equipment Location
Ceiling_
Ceiling
Area served
2nd Floor Storage
2nd Floor Storage
Equipment Manufacturer
Carrier
- Carrier
Model
FX4DNF061
FX4DNF061
Serial Number
3818G60723
4918F24208
Specified
Actual
Specified
Actual
Total CFM- Fan
2000
1902
2000
1876.
Total CFM - Outlet
2000
1962
2000
1876
R/ACFM
1630
1574
1630
1590
O/A CFM
370
328
370
286-
Total Static Pressure (TotallExtemal)
---/.50
.75/.36
-4.50
.921.40
Inlet Pressure
--=
.64/.25
---
.79/.27
Discharge Pressure
-_
.11
---
.13
Fan RPM
--
High
---
Hi h
Specified
Actual
Specified
Actual
Motor Manufacturer
---
Gente
---
Gente
Motor HP
.75
.75
.75
.75
Phase
1
1
1
1
Voltage
208
214
208
214
Amperage
6.0
4.61
6.0
3.93
Motor RPM
3 Speed
High
3 Speed
High
Motor Service Factor
1.0
1.0
1 1.0
1.0
Motor Sheave & Bore Size
D.D.
D.D.
Fan Sheave & Bore Size
D.D.
D.D.
Belts -- Quantity and Size
D.D.
D.D.
Center to Center
D.D.
D.D.
D.D. = Direct Drive.
Absolute Balance, Inc.
Telephone: 407-402-3256
Email: stoutl029@aol.com
Project: Advantage Self Storage
Date 09-19
Page. 4
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM
AHU-7
AHU-8
Equipment Location
Ceiling
Ceiling
Area served
2nd Floor'Stora a
3rd Floor Storage
Equipment Manufacturer
Carrier
Carrier
Model
FX4DN F061
FX4DN F049
Serial Number
3818F60720
5018FO8038
Specified
Actual
Specified
Actual
TotalCFM-Fan
2000
1891
1600
1623
Total CFM - Outlet
2000
1891
1600
1623
R/A CFM
1630
1530
1230
1265
O/A CFM
370
361
370
358
Total Static Pressure (Total/External)
—4.50
.89/.38
--4.50
.81 /.33
Inlet Pressure
---
.77/.26
---
' .71 /.23
Discharge Pressure
-
.12
-
10
Fan RPM
---
High
--1
' High
Specified
Actual
Specified
Actual
Motor Manufacturer
---
Gente
---
Gente
Motor HP
.75
.75
.75
:75
Phase
1
1
1
1
Voltage
208
214
208
•214
Amperage
6.0
3.8
6.0
3.97
Motor RPM
3 Speed
High
3 Speed
Hi h
Motor Service Factor
1.0
1 1.0
1.0
1.0
Motor Sheave & Bore Size
D.D.
D.D.
Fan Sheave & Bore Size
D.D.
D.D.
-Belts«Quantity. and Size.. _ __ _ _
_ _ ___—__ D.D. - - -- -
- -- -- ---D:D:- -- - -- -
Center to Center
D.D.
D.D.
D.D. = Direct Drive.
Absolute Balance, Inc.
Telephone: 407-402-3256 Date: 09-19
Email: stout1029@aol.com Page: 5
Project: Advantage Self Storage
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM
AHU-9
AHU-10
Equipment Location
Ceiling
Ceiling
Area Served
3rd Floor Storage
3rd Floor Storage
Equipment Manufacturer
Carrier
Carrier
Model
FX4DNF049
FX4DNF049
Serial Number
5018FO4768
5018FO8047
Specified
Actual
Specified
Actual
Total CFM- Fan
1600
1585
1600
1589
Total CFM - Outlet
1600
1585
1600
1589
R/A CFM
1230
1218
1230
1233
O/A CFM
370
367
370
356
Total static Pressure (Total/External)
—4.50
.83/.28
---/.50
.86/.43 .
Inlet Pressure
--
.73/.18
--
.75/.32
Discharge Pressure
-_
.10
___
.11
Fan RPM
—_
High
---
High
Specified
Actual
Specified
Actual
Motor Manufacturer
--
Gente
---
Gente
Motor HP
.75
.75
.75
.75
Phase
1
1
1
1
Voltage
208
214
208
214
Amperage
6.0
4.18
6.0
4.09
Motor RPM
3 Speed
I High
3 S eed
High
Motor Service Factor
1.0
1.0
1.0
1.0
Motor Sheave & Bore Size
D. D.
D.D.
Fan Sheave & Bore Size
D.D.
D.D.
Belts -- Quantity and Size
D.D.
D.D.
Center to Center
D.D.
D.D.
D.D. = Direct Drive.
Absolute Balance, Inc.
Telephone: 407-402-3256 Date: 09-19
Email: stoutl029@aol.com Page: 6
Project: Advantage Self Storage
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM
AHU-11
AHU-12
Equipment Location
Ceiling
Ceiling
Area served
3rd Floor Storage
31d Floor Storage
Equipment Manufacturer
Carrier
Carrier
Model
FX4DNF049
FX4DN F061
Serial Number
5018FO5011
4818F18801
Specified
Actual
Specified
Actual
TotalCFM—Fan
1600
1613
2000
1987
TotalCFM— Outlet
1600
1613
2000
1987
R/A CFM
1230
1257
2000
1987
CIA CFM
370
356
0
0
Total Static Pressure (Total/External)
--/.50
.86/.93
---/.50
.93/.35
Inlet Pressure
---
.69/.76
---
.83/.25
Discharge Pressure
---
.17
---
10
Fan RPM
---
High
--
High
Specified
Actual
Specified
Actual
Motor Manufacturer
---
Gente
--
Gente
Motor HP
.75
.75
.75
.75
Phase
1
1
1
1
Voltage
208
214
208
214
Amperage
6.0
3.9
6.0
4.07
Motor RPM
3 Speed
High
3 Speed
High
Motor Service Factor
1.0
1.0
1.0
1.0
Motor Sheave & Bore Size
D.D.
D.D.
Fan Sheave & Bore Size
D.D.
D.D.
Belts —Quantity and Size
D.D.
D.D.
Center to Center
D.D.
D.D.
D.D. = Direct Drive.
Absolute Balance, Inc.
Telephone:407-402-3256 Date: 09-19
Email: Stotitl029@aol.com Page: 7
Project: Advantage Self Storage
DUCT TRAVERSE ZONE TOTALS
System
Zone/Branch
Duct
Size
Area
S .Ft.
Design
FPM CFM
TEST
Test 1 Test 2
FPM FPM CFM
Static or
Hertz or
Meter Type
AHU-1
O/A
8"
.35
285
100
284
99
Airfoil
AHU-2
O/A
8"
.35
1057
370
87
1046
366
Airfoil
AHU-3
O/A
8"
.35
1057
370
117
1043
365
Airfoil
AHU-4
R/A
24X12
2.0
815
1630
781
1562
Vel rid
AHU-5
R/A
24X12
2.0
815
1630
787
1574
Vel rid
AHU-6
R/A
24X12
2.0
815
1630
795
1590
Vel rid
AHU-7
O/A
8"
.35
1057
370
761
1032
361
Airfoil
AHU-8
O/A
10X8
.55
672
370
101
650
358
Airfoil
AHU-9
O/A
10X8
.55
672
370
144
667
367
Airfoil
AHU-10
O/A
10X8
.55
672
370
127
648
366
Airfoil
AHU-11
O/A
10X8
.55
672
370
87
648
356
Airfoil
Absolute Balance, Inc.
Telephone: 407-402-3256 Date: 09-19
Email: stoutl029@aol.com Page: 8
Project: Advantage Self Storage
ELECTRICAL DUCT HEATERS
No.
Area
Served
Mfg.
Desian
Volts Amps
Measured
Volts Amps
K. W.
Des. Meas.
1
AHU-1
Carrier
208
16.01
214
14.65
3.3
3.01
2
AHU-2
Carrier
208
16.01
214
13.86
3.3
2.85
3
AHU-3
Carrier
208
16.01
214
15.29
3.3
3.15
4
AHU-4
Carrier
208
16.01
214
14.62
3.3
3.01
5
AHU-5
Carrier 1
208
16.01
214
15.73
3.3
3.24
6
AHU-6
Carrier
208
16.01
214
13.95
3.3
2.87
7
AHU-7
Carrier
208
16.01
214
14.84
3.3
3.05
8
AHU-8
Carrier
208
16.01
214
15.41
3.3
3.17
9
AHU-9
Carrier
208
16.01
214
15.66
3.3
3.22
10
AHU-10
Carrier
208
16.01
214
14.59
3.3
3.0
11
AHU-11
Carrier
208
16.01
214
14.37
3.3
2.96
12
AHU-12
Carrier
208
16.01
214
15.71
3.3
3.23
Absolute Balance, Inc.
Telephone: 407-402-3256 Date: 09-19
Email: Stout1029@aol.com Page: 9
Project: Advantage Self Storage
DX COOLING COIL DATA
System
AHU-1
AHU-2
AHU-3
AHU-4
Location
Ceiling
Ceiling
Ceiling
Ceiling
Service
1st Floor Entry
1st Floor Storage
1st Floor Stora a
2nd Floor Stora e
ManufacturJer
Carrier
Carrier
I Carrier
Carrier
Design
Actual
Design
Actual
Design
Actual
Design
Actual
CFM
650
635
1600
1567
2000
1887
2000
1853
E.A.T., DB F
80.0
77.2
80.0
76.9
80.0
77.3
80.0
77.0
E.A.T., WB OF
67.0
62.5
67.0
63.0
67.0
63.4
67.0
62.8
L.A.T., DB OF
NS
56.5
NS
55.9
NS
56.3
NS
56.1
L.A.T., WB OF
NS
55.1
NS
55.4
NS
55.8
NS
55.5
O/A., DB OF
NS
96.2
NS
96.2
NS
96.2
NS
96.2
C/A., WB OF
NS
81.5
NS
81.5
NS
81.5
NS.
81.5
NS = None Specified.
Absolute Balance, Inc.
Telephone: 407402-3256 Date: 09-19
Email: Staut1029@aol.com Page: 10
Project: Advantage Self Storage
DX COOLING COIL DATA
System
AHU-5
AHU-6
AHU-7
AHU-8
Location
Ceiling
Ceiling
Ceiling
Ceiling
Service
2nd Floor Storage
2nd Floor Storage
2nd Floor Storage
3rd Floor Storage
Manufacturer
Carrier
Carrier
Carrier
Carrier
Design
Actual
Design
Actual
Design
Actual
Design
Actual
CFM
2000
1902
2000
1876
2000
1891
1600
1623
E.A.T., DB OF
80.0
76.9
80.0
77.1
80.0
76.5_
80.0
77.1
E.A.T., WB OF
67.0
63.3
67.0
64.0
67.0
62.4
67.0
63.8
L.A.T., DB OF
NS
56.1
NS
55.6
NS
56.6
NS
55.9
L.A.T., WB OF
NS
55.4
NS
55.0 '
NS
55.9
NS
55.4
O/A., DB OF
NS
96.2
NS
96.2
NS
96.2
NS
96.2
O/A., WB OF
NS
81.5
NS
81.5
NS
81.5
NS
81.5
NS = None Specified.
Absolute Balance, Inc.
Telephone: 407-402-3256 Date: 09-19
Email: Stout1029@aol.com Page: 11
Project: Advantage Self Storage
DX COOLING COIL DATA
System
AHU-9
AHU-10
AHU-11
AHU-12
Location
Ceiling
Ceiling
Ceilin
Ceilin
Service
3rd Floor Storage
3rd Floor Storage
3'd Floor Storage
3rd Floor Storage
Manufacturer
Carrier
Carrier
Carrier
. Carrier
Design
Actual
Design
Actual
Design
Actual
Design
Actual
CFM
1600
1585
1600
1589
1600
1613
2000
1987
E.A.T., DB OF
80.0
76.5
80.0
77.1
80.0
76.8
80.0
76.5_
E.A.T., WB OF
67.0
62.9
67.0
63.6
67.0
61.9
67.0
62.6
L.A.T., DB OF
NS
56.1
NS
55.8
NS
55.4
NS
55.9
L.A.T., WB OF
NS
55.5
NS
55.2
NS
55.0
NS
55.4
O/A., DB OF
NS
96.2
NS
96.2
NS
96.2
NS
96.2
O/A., WB OF
NS
81.5
NS
81.5
NS
81.5
NS
81.5
NS = None Specified.
Absolute Balance, Inc.
Telephone:407-402-3256 Date: 09-19
Email: stout1029@aol.com Page: 12
Project: Advantage Self Storage
AIR DISTRIBUTION TEST SHEET
Absolute Balance, Inc.
Telephone:407-402-3256 Date: 09-19
Email: stoutl029@aol.com Page: 13
Project: Advantage Self Storage
AIR DISTRIBUTION TEST SHEET
M
• , '
®®
'
Absolute Balance, Inc.
Telephone: 407-402-3256 Date: 09-19
Email: stout1029@aol.com Page: 14
Project: Advantage Self Storage
AIR DISTRIBUTION TEST SHEET
Grill
Room
—Terml—nal
Design
I st Test
Final
etBenchmark Certificate Number 2018007556
Calibration
Laboratory
CERTIFICATE OF CALIBRATION
Customer Information:
instrument information:
ABSOLITE BALANCE
ID Number-
180a04737
1029 HORNBE:41I STREET
Description
461920 PHOTO TACHOMETER
OVIEDO,FL32765
Manufacturer
EXTECH
407402-3256
Model Number
461920
Serial Number
180894731
Size
Calibration information:
.Procedure NA17-20MX03
Cal Date 12106/2018
Temperblure
23-C
Next Cal Date` 1210612619
Humidity
50%
Technician JUSTIN RESCHKE
Accuracy
MANUFACTURER'S SPECIFICATIONS
Condition RECEIVED INTOLERANCE, LEFT AS FOUND
Stadl7ards Lased __ `" '-"�
Cal Standard Description Cal Date Cal Due
EL030 5500AMULTI-PRODUCT CALIBRATOR 08212017 08/31/2019
This rtpoa nuy not bemproduced. ezmpt in full, unless permission fin the publication ofan apptored abstract is obtained in waitingffons the calibration organization issuing dus report
Thismstrumrnthas bem calibrated using standards ith:accuracies uaccable through Nademl Institute ofStonduds and Toahnotogy in an Sl unit, derived from nation] physical coosmn,,
d<tised from ratio measmanents. or cmnparod to mnss¢us standards.
"i
Benchmark. Calibration Laboratory; Into calibration Control System complies with ISO Guide 17025. and ifrequested ANSVNCSLY,540-1-1904
A Test Unccminty tado ofat least 4:1 is m:dntaincd mless othgwim swell. /11 ,'-] /% / 0
QA Approval Dr.
Benchmark Calibration Laboratory, Inc.
2450 S. Laurel Avenue, Sanford, FL 32771
Ph. (407) 328-0772 Fax (407) 328-0747
www.benchmarkcallab.com
Page 1 of 1
EVERGREEN
TELEMETRY
Certificate of Calibratioln
Absolute Balance
Menufhcwm
Teteme
Calibration Environment
Tem erdmProduct
Module
Probe
Tem
75
of
Model
S-T-5
RMT=1
PR T-5
ReL H
51
%
SN
....
1800143
1800143
Bar. Pressure
26:6
in H
d..t AS Found
LO�
® In Tolerance Q Out Tolerance
Calibration Data
�_��_�_�IIIIIIIIIII'
lfxrmtn ant Oftobfww Mdf n- —t
Calibration Standard SN & Dates
Variable
1D
CaMration Last
Caftelion Due
Temperature
15171149
11,Jan 17
11,1an 19
Statement of Traceability
This instrument has been dredged faraccuracy..gfibrated to nmubckuees spewcatlam, mW W tube
wilhm the spedW tolerance unless otherwise state& it hasee been calibrated using measurement standards
traceable tothe Nabonat insbtue'of Standards a!m TeBmoTogy. cr accepbd izibii [c standards of ineasuremgi3.
or derived by the ratio Type ofseif calibrated techniques.
15 Aug-2018 15-Aug-2020
Calibration Date Date Due
■ 624
t
EVERGREEN
1'ELEIMETRY
Certificate of Calibration
A$SOI-UTF, CaRtLAWLE
Module
W:
As Found 0 As left ® In Tolerance out of Tolerance
Calibration Data
SpecithilIbn
Cal
Sensori
Cal
Sensor2
41- 2%;!- last `
Std
Olaf Pms
Diffemtce
ad
Ga Lo
Drii
Approx Set Poirt
%
%
PSI
ftwa
ftvYc
flan
tbA�
0.13
0:3
03
0
0.3
0.3
0
0.434
1.d
1.0
0
10
10
0
0.857
20
20
0
2.0 _
20
0
2.168
5.0'
50
0
5.0
50
0
PSI -
psi
PSI,
PSI
10
10.0
10.0
- 0
--- 10.0
10.0
0
40
40.0
40.0
0
40.0
40.0
0
80,
86.0
80.4
0.3
80.0
80.5
0.3
120
120.0:
120.5.
- 0
120.0
121.0
d
240
240.0
2403
0.1
240!0
240.4
0.2
Conversion
PSI fto Ir m
1.00 Z307 27.60
0434 1.001200
OXWOhm OUtcftob n m card ioe T
NIST-Traceable Calibration Lab Standards
Variablesystem
ID
Cammadon Last
Cahbra6on Due
PMS5um
3015172
10,)an-17
10%lan-19
Tempemtum
15171149
11-1an-17
11-Jan-19
Statement of Traceabil tX
Ttds Ir ha eflt bas bcan dm*W for aearaey, ca6bretad to manaff4ue s gMCft Faris, and found to be
within the GPeoiHedtoterartae uniess'othe>wiae dated. it Ism been calibrated using aeaerrement standards
traoeabb to the Nabowl In W4m of StwK%ff ds and Teduwbgy, or accepted 1Mfl,&lcstartd3rda of nmweme
or derived bytlte raft type of wffeaftrated tadulques:
20-11u9-2d18 20 Aug-2019
alibra]Dd By Calibration Date Due
Gr
amazon CERTIFICATE OF CALIBRATION
',�Wl
Customer: AMAZON.COM.DEDC LLC
550 OAK RIDGE ROAD
HAZLETON, PA 18202
PO Number: 47V4RNIV
Certificate/SO Number: I-EW15X-30-4 Revision 0
As Left Data
0
Description Setpoints Accuracy Low Limit High Limit As Left 0 T TUR
Function Check
Display Test
P p
p
AC Volts Measure
501-lz
MY
4 . . ..... .
6: ...... . 998...
600HZ
DC Volts Measure
5'
1 0.0V i(1% Rdg + 5 LSD)
9.4 10.6
9.9 V
Resistance 2 Wire Comp Measure
-Resistance 0.00hm +(l% Rdg + 5 LSD) 0.0 0.5 0.0 Ohm
350.00hm ±(l%Rdg+SLSD) 346.0 354.0 350.0 ON
AC Current Measure
400 A Range
6.OA ±(2% Rdq + 5 LSD)
5.4
6.6
BOA
24.0A t(2.6% Rog + 6 LSD)
22.9
25.1
24.2 A
21 O.OA ±(2% Rdq + 5 LSD)
2053.
214.7
210.OA
t mm
390.OA 1(2% Rdg + 5 LSD)
381.7
398.3
3931 A
1.8:1
N,-
390.OA ±(2.5% Rdg + 5 LSD)
379.7
400.3
390.6 A
2.3:1
Function Check
Continuity Test
E47f P
p p 0222
Date Received: November 19, 2018 Cdrtificate - Page 2 of 3 Customer Number: 1-619842-026
Service Level: S6
OPS-F20-013R101123/2017 FP003RO 1011412016
u
amazon CERTIFICATE OF CALIBRATION
N%4MM00011
Customer: AMAZON.COM.DEDC LLC
650 OAK RIDGE ROAD
HAZLETON, PA 10202
PO Number: 47V4RN1V
Certificate/SO Number: I-EW15X-30-4 Revision 0
Traceable Standards
Asset Manufacturer Model Number Description Cal Date Due Date
Traceability Number Use
10015 Fluke Corporation 5520A Multifunction Calibrator 15-Nov-18 30-Nov-19
5410016-2021-1 ARAL
The use of the standard Is defined as: AF -used for as -found readings, AL- used for as4eft readings.
Environmental Data
Temperature Relative Humidity
Tempt RH Asset
71.69°F 122.05°C 37.400A
3133E
LaWnIMLEga
amazon
Facility Responsible,
35 Vantage Point of
Rochester, MY 14624
800-828-1470
Unit Barcolle: 109111MINIT
09DIB272819
DateRecelved: November '19.20118
Service Level : 86
Calibrated By, Ravlowed BY:
eioctroniuiiy signed By: Electronically Signed By:
Rajkurnar K Frederick Tank
Rajkumar K Nov 10. 2018 FreclorickTank Nov 19, 2018
Calibration Technician 12:20:44 -05:00 Lab Manager 16A6:55 -05.00
Certificate - Page 3 of 3 customer Number: 1-619842-026
OPS-F20-013R10=312017 FP003RO 1011V2016
Certificate of Calibration
Absolute Balance
Manufacturer
Ever reen Telemetry
Calibration Environment
Product
Capture Hood,
Temperature
82
OF
Model
CH-813
Rel. Humidity
64
-
%
SN
1800144
Bar. Pressure
28.7
in H
® As Found ® As Left 0 In Tolerance ❑ Out of Tolerance
Calibration Data
Measurement
Variable
Test
Point
Cal
Standard
Allowable
Range
Test
Instrument
Min
Max
Airflow (CFM)
Spec
-3%-7
+3%-7
1
_151
150
2
52
52
3
16
15
4
-32
-33
5
83
82
6
Indicates out of tolerance condition
MIST -Traceable Calibration Lab Standards
Variable
System ID
Calibration Last
Calibration Due
Pressure
4693940
7/10/2017
7/10/2019
Pressure
1208000080
7IM017
7/6/2019
Velocity
1600344
1/26/2017
1/26/2019
Statement of Traceability
This instrument has been checked for accuracy, calibrated to manufacturers specifications, and found to be
within the specified tolerance unless otherwise stated. It has been calibrated using measurement standards
traceable to the National Institue of Standards and Technology, or accepted intrinsic standards of measurement,
or derived by the ratio type of self calibrated techniques.
Calibrated By
624 S. Perry Ln. #102, Tempe AZ 85281 • 602-574-6192
October 3, 2018
Calibration Date
EVERGREEN
TEIEMEIRY
Certificate of Calibration
ikRAOLUT'F RAIL-4mr—G
Manufachner
Evergreen T
Calibration Emritvnment
Product
Ca tune Hood
Temperature
89
OF
Model
CH-15D
ReL Humid"
38
y,
SN
1800205
Bar. Pressure
28.7
in
Q As Found
® As Left M In Tolerance r7 nid nrTntc.nne
Calibration Data
Measurement
Variable
Test
Point
Cal
Standard
AMR
elianae
Test
Instrument
mini
max
Airflow(CFM)
S ec
-3%-7
+396 7
1
2047
2040
2
1021
1Q17
3
157
157
4
-537
-532
5
trtdca Out afWAMtosaonditbn
NIST-Traceable Calibration Lab Standards
Variable
ID
Calibration Last
Calibration Due
Pressure
4693940
711020t7
i 71102019
Pressure
1208000M
7152017
7152019
vebw
1600344
1262017
1=019
Statement of TraceabtTdv
This arstrument has been checked fur accuracy, calibrated to manubatu&s spedkofons, andfound to be
withinthe sper�ied Werance unless odmnwse stated a has beencaffirated using measurement standards
traceable to the Nabonai Inslitue of Standards and Technology, or accepted Intrinsic standards of measummenk
or derived by the ratio type of seftw6brated Wmques.
August 12, 2018
Calibration Date
AZ 8%81
EVERGREEN.
TELEMETRY
Certificate of Calibration
Absolute Balance
Manuiaciurer
Evmreen Telemetry
Caflbra8on Environment
Product
Pressure IVelocity Module
Temperature
75
of
Model
S47VF-1
Rel. Humidity
54
%
SN
_
1800365
Bar. Pressure
28:5
in H
U As Found ® As Lett ® fn Tolerance 0 but of Tolerance
Calibration Data
Measurement
Variable-
Test
Point
Cal
Standard
Allowable
Ran a
Test
Instrument
Min
Max
Batometiid
Pressure (n Hg)
S
-2%-0:1
+2%+0.1
1
24.8
24.8
2 •
28.5
28.6
3
30.3
30A
Dillbrerdal
Pressure
(In WC)
(FPS
S c
-2%-A01
+2%+.001
1
10.00
10.01'
2 --
------20tf0
3
0.5000
0.5004.
4
- 0.0500
0.0505
5
-10.00
-10.04
6
S,
-0.0500
3%-7
+3g(,+7
-0.0503
103
105
2
W8
.
509
Airflow
°
S
-3%-7
+.3%+7
1
100
UPON
2
500
REQUEST
broiesadeftoknscowrrdiiwr T
NIST-Traceable Lab Calibration Standards
variableep
Pressure
SvSlem to
4693940
I Calleration Last
10-551-1�
CaHbrafion flue .
10,1ut-19
Pressure
1208000080
5Jul-17
5Ju4.19
Wocity
1600344
26Jan-17 ' -
26-Jan-19
Statement of Traceabil ft
This Instrument has been dmdwd for arruracy. cagmated to manufsd mi% spedficatimrs, and found to be
w" the specified toiamnca unless ctlt_emmie motes. -It has been calibrated using measurement standards
baoaaDla to the Naflorral hStkue of Standards and Tectmalogy, craccepted intringo standards of measurement,
or derives by cite ratio type of self cafibrated lachnicim.
Calibrated By
624'S. Perry Ln. $102. Temue AZ
„-Aug 2018 11-Aug 2020
Calibration Date Date Due
*V►IALMOR
CERTIFICATE OF CALIBRATION
TSI Incorporated, Alner Products, 500 Cardigan Road, Shoreview, AIN 55126 USA.
7111:1-800-874-2811 1-651490-2811 FAa: 1-651-490-3824 wwwalnorcom
ENVIRONMENT CONDITION
TEMPERATURE
72.8
°F.
RELATIVE Ht1MmnY
27.0
%RH
BARO&IECRICPRESSURE
28.89
inHg
Rotating Vane Anemometer
MODEL RVA801
SERIAL NO. A04658
CALIBRATION STANDARDS USED 0 AS LEFT 0 IN TOLERANCE
Wind Tunnel Calibration System 192 ❑ As FOUND 0 OUT OF TOLERANCE
CALIBRATION DATA
TESTINNG_
TEhiPERATuREMEASMI)INOF Tolerance: +Z0'F
POINTS
CALIBRATION STANDARD
INSTRUMENT OUTPUT
ALLOWABLE RANGE
1
73.9
TU
71.9 - 75.9
TESTING
VELOCITY MEAStfREDINsrAnN Tolerance. +(L0%ofreading td.OfNmin
POINTS
CALIBRATION STANDARD
INSTRDIFIENT OUTPUT
ALLOWABLE RANGE
1
10010
101
95.0 -105.0
2
149.9
151
1444-155.4
3
2%2
199
194.2-206.2
4
499.3
499
4903-508.3
5
1000.6
996
986.6-1014.6
6
15023.
-1494
1483.3-1521.3
7
3992.3
3998
3948.4 - 4036.2
8
6010.9
6OD9
5946.8 - 6075.0
Indicates ml of tolerance condition
Standard Conditions: AmbientTemperature =21.1. °C; Barometric Pressure= 760.0 mmHg
Measurement Variable
System ID .Number
Date Last Calibrated
Calibration Due Date
DC Voltage
E00$277
02-01-18
08-31-19
DC Voltage
E003276
02-01-I8
08-31-19
Barometric pressure
E003271
08-16-18
08-31-19
Temperature
E003270
08-22-18
0&31-19
Pressure
E002740
08-02-18
02-28-19
Calibration procedure used: IDOO0005936
Calibrated By
Oct. 26, 2018
Calibration Date