HomeMy WebLinkAboutREVIEW COMMENTSPlanning & Development Services
Building& Code Regulation Division
2300 Virginia Avenue
Fort Pierce, FL 34982
Phone:(772)462.2172 Fax:(772)462-6443
Address: 605 Kitterman Rd Building C
City / State / Zip: Port St Lucie , FI 34981
Parcel#: 3415-707-0001-000/0
Zoning: CG
APPLICATION INFORMATION
REVIEW COMMENTSSCANNED
BY
St. Lucie County
Page 1
Owner(s):
Farrell Advantage Pt St Lucie Holding Llc
Jurisdiction: SAINT LUCIE COUNTY
Lot#: I Block:
Permit Number: 1712-0019 Stories:
Automatic Sprinkler System? No
Permit Type: BUILDING COMMERCIAL
CONTRACTOR INFORMATION
Contractor Name: Kim R Welsh
Fax Number: 321-362-2582
Business Name: Welsh Construction Llc
Email: Ken@Welshci.Com
Business Addr: 3845 W Eau Gallie Blvd Ste 101
City / State / Zip: Melbourne, FI 32934
REVIEWS AND COMMENTS
Review Type Status Reviewed By
Date Started Date Comoleted Date Released
ADDRESSING ASSIGNMENT COMPLETE Lori Bander
1211912017 1212012017 1212012017
Comment:
DOCUMENTS MISSING
PENDING Lashahna Ingram
12/1/2017
Comment:
NEEDS ELECTICAL SUB
12/1/2017
Comment:
NEEDS PLUMBING SUB
12/1/2017
Comment:
NEEDS ROOFING SUB
C t'
NEEDS HVAC/MECH SUB
12/1/2017 ommen.
12/19/2017 Comment:
A COPY OF THE PAID UTILITY SERVICE RECEIPT FOR ELECTRIC SERVICE OR A LETTER FROM THE
ELECTRICAL UTILITY PROVIDER THAT ELECTRIC WILL BE AVAILABLE TO THE LOCATION.
12/28/2017 Comment:
VEG PERMIT FILED UNDER (F) FOR FARRELL ADVANTAGE FOR PERMITS 1712-0015, 1712-0018, 1712-0019
AND 1712-0020. FEE POSTED ON PERMIT 1712-0015.
3/30/2018 Comment:
RECORDED NOC LISTING WELSH CONST. AS CONTRACTOR.
ENVIRONMENTAL REVIEW
COMPLETE Lynn Swartzel 12121/2017 12127/2017 12/2712017
Comment:
FIRE DEPARTMENT REVIEW
PENDING Tony Jerger
Comment:
FRONT COUNTER REVIEW
COMPLETE Lashahna Ingram 12/112017 121112017
Comment:
y
.J�.f�uGti (i0crm.�
Planning & Development Services
Building &Code Regulation Division
2300 Virginia Avenue
Fort Pierce, FL 34982
Phone:(772)462.2172 Fax:(772)462-6443
REVIEW COMMENTS
PE REVIEW COMMENTS (2) INCOMPLETE Joe Ciclo 511512018
2/14/2018
2114/2018
2/20/2018
2/20/2018
2/20/2018
2/20/2018
2120/2018
2/22/2018
Comment: CONTRACTOR TO SUBMIT [ 41 ORIGINAL, SIGNED, SEALED AND DATED SOIL TESTS FROM TIERRA SOUTH
ALL OF THE TESTS SUBMITTED ARE COPIES AND ARE FOR A 2 STORY BUILDING' PLEASE IDENTIFY IN
THE TEST REPORTS THAT THERE ARE [ 31 INDIVIDUAL SINGLE STORY BUILDINGS AND [ 1 ] 3 STORY
BUILDING' SEPARATE THE REPORTS FOR EACH BUILDING ••'• SECOND REVIEW "'• RECEIVED [ 3 ] STILL
NEED[1]
Comment: THE TEST CRITERIA ON SHEET 5001.0 [ 02300 EARTHWORK ] IS NOT WHAT HAS BEEN SUBMITTED FOR
REVIEW'•" NOT REVISED TO CURRENT REVISED TESTING'•••
Comment: SUBMIT AN ORIGINAL, SIGNED, SEALED AND DATED STRUCTURAL INSPECTION PLAN IN TRIPLICATE,
GENERATED BY THE DESIGN PROFESSIONAL OF RECORD TO BE USED BY THE THRESHOLD INSPECTOR'
SEE FBC 110.8.1 'THIS IS NOTED WITHIN SECTION III I NOTE 4 /// SHEET S001.0 "" SECOND REVIEW'•"
5001.0 PLAN STILL CALLING FOR THRESHOLD ENGINEER INSPECTIONS'•"
Comment: SUBMIT A NOTARIZED, ORIGINAL LETTER FROM THE FEE OWNER OF THE BUILDING AS TO HIS/HER
SELECTION OF HIRING THE SPECIAL INSPECTOR AND PAYING ALL COSTS •' SEE FBC 110.8.3 FOR THE
REQUIREMENTS ••'• PLANS STILL CALLING FOR THRESHOLD INSPECTIONS —
Comment:
Comment:
Comment:
Co[rimenf.. .
/
Go ent:
2/22/2018 - Y
5
Gommen'
2/22/2018
2/22/2018
M[CTffiffin"nn
91LLCOmmo E
2/22/2018
Comment:
2/22/2018
3/8/2018
THE SPECIAL INSPECTOR TO FILL OUT THE ST LUCIE COUNTY FORM FOR SPECIAL INSPECTORS AND
IDENTIFY WHO WILL BE MAKING THE FIELD INSPECTIONS WITH APPROPRIATE LICENSE NUMBERS
PLANS STILL CALLING FOR THRESHOLD INSPECTIONS ••••
SUBMIT [ 3 ] ST LUCIE COUNTY "CERTIFICATION FOR DESIGN LOAD COMPLIANCE " SHEETS
COMPLETELY FILLED OUT IN ORIGINAL FORMAT, THEN SIGNED, SEALED AND DATED BY YOUR DESIGN
PROFESSIONAL" THESE ARE AVAILABLE ON OUR WEB -SITE — SECOND REVIEW •'•• SHEETS
INCORRECT OR INCOMPLETE " OCCUPANCY TYPE IS S-1, CONSTRUCTION TYPE IS 1113 AND 56 / NOT
BEARING WALL SYSTEM ?' WILL NEED [ 3 ] ORIGINAL, SIGNED,SEALED AND DATED SHEETS FOR EACH
BUILDING PERMIT A,B,C AND D WITH THE PERTINENT PRESSURES ETC FOR THAT SPECIFIC BUILDING'
BUILDING C IS 2B' BUILDING A,B AND D ARE 5B'
SUBMIT [ 3 ] ST LUCIE COUNTY " PRODUCT REVIEW AFFIDAVITS SIGNED, SEALED AND DATED IN
ORIGINAL FORMAT • BE SURE THAT THESE SHEETS ARE COMPLETELY FILLED OUT NOT "PER PRODUCT
APPROVAL— THESE ARE AVAILABLE ON OUR WEB -SITE — SECOND REVIEW "" SHEET A-321.00 AND A-
320.00 SPEC OVERHEAD DOORS BY JANUS AND PRODUCT AFFIDAVITS SPEC DCBI 690 SERIES ?? ,
PLEASE SUBMIT [ 31 ST LUCIE COUNTY " PRODUCT REVIEW AFFIDAVITS " NOT CITY OF PORT ST LUCIE I
SUBMIT [ 3 ] IF CLADDING REMANS THE SAME FOR ALL 4 BUILDINGS OTHERWISE WILL NEED [ 31 FOR
EACH BUILDING PERMIT [ BUILDING A,B,C AND D ]' BE SURE THAT THESE AFFIDAVITS CO-INCIDE WITH
ALL PLAN NOTES AND PRODUCT APPROVAL INFORMATION PROPOSED FOR USE
SUBMIT IN TRIPLICATE, ORIGINAL ENGINEERED SHOPS WITH CALCULATIONS FOR THE STAIRCASES,
LANDINGS, GUARDRAILS AND HANDRAILS W/ ALL CONNECTIONS / MUST BE REVIEWED AND APPROVED
BY P.E. MURRAY BRYNTESEN' SEE NOTES 5001.0 AND FRANK RELF [ SEE NOTES ARCHITECTURAL
DRAWINGS "' SECOND REVIEW*** NOT RECEIVED
SUBMIT IN TRIPLICATE ORIGINAL S.S.D. ENGINEED SHOPS FOR THE FABRICATION AND ASSEMBLY OF
THE STRUCTURAL STEEL ROOF SYSTEM PER AISC STANDARDS [ SEE 5001.0 ]' MUST INCLUDE ALL
CONNECTIONS AND WELD SPECS '• THESE SHOPS MUST BE REVIEWED AND APPROVED BY P.E. MURRAY
BRYNTESEN "' SECOND REVIEW "' DID NOT RECEIVE
SUBMIT TRIPLICATE, ORIGINAL, ROOF TRUSS LAYOUTS W- ENGINEERS CUT SHEETS FROM THE
MANUFACTURER FOR THE LIGHT GAGE TRUSSES' THESE SHOPS MUST BE REVIEWED AND APPROVED
BY P.E. MURRAY BRYNTESEN •'• SECOND REVIEW*** DID NOT RECEIVE
SUBMIT TRIPLICATE PLANS WITH SPECIFICATIONS FOR THE PARKING LOT LIGHT POLES W/ FOUNDATION
DESIGN TO MEET 150 M.P.H. WIND LOADS, EXPOSURE C - SUBMIT IN TRIPLICATE [ SEE C-600 ] PLANS
MUST BE FOR THE POLE / FIXTURE AND BRACKET COMBINATION' PLANS MUST BE REVIEWED AND
APPROVED BY THE ENGINEER OF RECORD'•' SECOND REVIEW — DID NOT RECEIVE
SUBMIT TRIPLICATE, ENGINEERED S.S.D. SHOPS FOR THE STEEL FLOOR ASSEMBLIES' THESE MUST BE
REVIEWED AND APPROVED BY THE STRUCTURAL E.O.R.'•. SECOND REVIEW*** DID NOT RECEIVE
THE SQUARE FOOTAGE ON THE PLOT PLAN ON T-000.00 FOR BUILDING D IS INCORRECT "" SECOND
REVIEW STILL INCORRECT FOOTAGE'••' SHEET A-106.00 SHOWS DIFFERENT OUTSIDE DIMENSIONS AND
SHOWS THE BUILDING TO BE 155' LONG' PLOT PLANS ON T-000.00 IS 135' LONG AND SHOWS THE 15, AND
20' DIMENSION REVERSED' PLEASE CHECK ALL PLANS FOR CONSISTENCY
SUBMIT THE MANUFACTURERS SPECIFICATIONS IN TRIPLICATE FOR THE ELEVATOR SYSTEMS,
REVIEWED AND APPROVED BY THE DESIGN PROFESSIONAL OF RECORD ••• NOT RECEIVED "' SECOND
REVIEW
3/9/2018 Comment: CONTRACTOR TO PAY ALL CURRENT PLAN REVIEW FEES UPON RE -SUBMITTAL OF DOCUMENTS
Y
Planning & Development Services
Building 8 Code Regulation Division
2300 Virginia Avenue.
Fort Pierce, FL 34982
Phone:(772)462.2172 Fax:(772)462-6443
REVIEW COMMENTS
3
Comment:
PLEASE NOTE: (1) ALL REVIEW COMMENTS WHEN ANSWERED WILL REQUIRE A COVER LETTER
ADDRESSING WHERE THE CHANGES WERE MADE, (2) ALL CHANGES WILL BE REQUIRED TO BE CLOUDED
ON THE PLANS AND (3) THE CONTRACTOR WHEN RESUBMITTING WILL BE REQUIRED TO INSERT THE
NEW UPDATED PAGES INTO THE PLANS OR IF THE CONTRACTOR PREFERS, A REVISED COMPLETE SET
3/9/2018 OF PLANS CAN BE SUBMITTED
PLEASE NOTE THAT A SUBMITTAL CHECKLIST WILL BE REQUIRED STATING THE TYPE AND QUANTITY OF
DOCUMENTS SUBMITTED FOR RE -REVIEW SIGNED AND DATED BY THE CONTRACTOR
PLEASE NOTE ANY COMMENT NOT ADDRESED MAY BE SUBJECT TO AN ADDITIONAL REVIEW FEE PER ST.
LUCIE COUNTY RESOLUTION #13-196
3/9/2018
Comment:
COMMENTS E-MAILED AS OF THIS DATE •••'• END OF FIRST REVIEW ""'
Comment:
PER PLAN SHEET S001.0 THE BUILDINGS HAVE BEEN DESIGNED TO 160 M.P.H. EXPOSURE C / PER PLAN
5115/2018
SHEET S002.0 THE ULIFT AND SERVICE PRESSURES ARE DESIGNED TO 170 M.P.H. EXPOSURE C' THE
BUILDING, COMPONENTS AND CLADDING MUST MATCH "' DESIGN PROFESSIONAL TO SHOW ALL
WINDOW AND DOOR FLASHING ON PLANS PER FBC 1405.4
5/15/2018
Comment:
THE ENGINEER IS SPECIFYING 10 MIL VAPOR BARRIER AND THE ARCHITECT IS SPECIFYING GRACE
PREPRUFE WATERPROOFING MEMBRANE ?????
Comment:
THE DESIGN PRESSURE TABLES CALCULATED BY ENGINEER ON S002.0 MUST CO-INCIDE WITH THE
5116/2018
PRESSURES ON THE PRODUCT AFFIDAVITS BY FRANK RELF [ ARCHITECT ] "THE CARLISLE ROOF
COVERING PRESSURE IS TO LOW FOR THE ACTUAL PRESSURES' BE SURE THAT THE DESIGN
PROFESSIONALS STATE THE PRODUCT APPROVAL NUMBERS ON THE S.L.C. AFFIDAVITS
5/16/2018
Comment:
RE -REVIEW FEES DUE
Comment:
PLEASE NOTE: (1) ALL REVIEW COMMENTS WHEN ANSWERED WILL REQUIRE A COVER LETTER
ADDRESSING WHERE THE CHANGES WERE MADE, (2) ALL CHANGES WILL BE REQUIRED TO BE CLOUDED
ON THE PLANS AND (3) THE CONTRACTOR WHEN RESUBMITTING WILL BE REQUIRED TO INSERT THE
NEW UPDATED PAGES INTO THE PLANS OR IF THE CONTRACTOR PREFERS, A REVISED COMPLETE SET
OF PLANS CAN BE SUBMITTED
5/16/2018
PLEASE NOTE THAT A SUBMITTAL CHECKLIST WILL BE REQUIRED STATING THE TYPE AND QUANTITY OF
DOCUMENTS SUBMITTED FOR RE -REVIEW SIGNED AND DATED BY THE CONTRACTOR
PLEASE NOTE ANY COMMENT NOT ADDRESED MAY BE SUBJECT TO AN ADDITIONAL REVIEW FEE PER ST.
LUCIE COUNTY RESOLUTION #13-196
COMMENTS SENT
5/1612018
Comment:
COMMENTS E-MAILED AS OF THIS DATE
PLANS EXAMINER ELECTRIC
COMPLETE Walter Pride 211612018 212312018 212312018
Comment:
PLANS EXAMINER MECHANICAL
COMPLETE Carl Peterson 31212018 31212018 3l2/2018
Comment:
PLANS EXAMINER PLUMBING
INCOMPLETE Greg Smyth 2/1612018
5/21/2018
Comment:
MUST HAVE HI LO DRINKING FOUNTAINS PER SECTION 410.3 FPC
PLANS EXAMINER REVIEW
COMPLETE Joe Cicio 2/1412018 6115/2018 511512018
Comment:
ZONING REVIEW
COMPLETE Lydia Galbraith 12/1912017 3/2312018 3123/2018
Comment: