HomeMy WebLinkAboutTESTING, ADJUSTING, AND BALANCING REPORTpff
ulrg 1-11z - o(o8-9
)MEGA AIR SERVICES LLC
DBA OMEGA TEST AND BALANCE
---A CERTIFIED INDEPENDENT TESTAND BALANCE COMPANY—�
126 WISTERIA AVENUE, FORT PIERCE, FLORIDA 34982
CELL (772)216-7632 'QF
TABB CERTIFICATION NO. BB032001C
www.omegaairserviceslic.com
omegama niac532002@va hoo.com
TESTING, ADJUSTING, AND BALANCING REPORT
DOYLE MASONRY
P.O. BOX 12339
FORT PIERCE, FLORIDA 34949
MECHANICAL ENGINEER:
FORT PIERCE ENGINEERING
315 SOUTH 7TM STREET
FORT PIERCE, FLORIDA 34950
FEBRAURY 7, 2019
SCANNED
BY
St. Lucie County
--ALL WORK PERFORMED IN ACCORDANCE WITH TABB STANDARDSAND PROCEDURES—
HUGH GRIMES
TA88 TECHNICIAN
_8R183)6IDT MARCM ai )819
,v'ba:� R•
AU'
I1MEGA AIR SERVICES LLC
DBA OMEGA TEST AND BALANCE
---A CERTIFIED INDEPENDENT TESTAND BALANCE COMPANY——
126 WISTERIA AVENUE, FORT PIERCE, FLORIDA 34982
CELL(772)216-7632
TABB CERTIFICATION NO. BB032001C/BB0320025/BB1032610T
www.omegaairserviceslic.com
omega ma niac532002@va hoo.com
DOYLE MASONRY
TEST AND BALANCE INSTRUMENTS
SHORTRIDGE SERIES 8400 FLOWHOOD W/ADM860 AIR DATA MULTIMETER
RANGE: 0 TO 61 IN H.G
ACCURACY: 0.05% FS
CALIBRATION DATE: AUGUST 8, 2018
CHECK -IT DIGITAL PSYCHROMETER —MODEL #622
RANGE:
ACCURACY:
CALIBRATION DATE:
SHORTRIDGE ADT446 TEMPROBE
RANGE:
ACCURACY:
CALIBRATION DATE:
FLUKE 322 CLAMP METER
350 TO 2050 F, 50/o TO 1000/o RH
t20 *1 DIGIT f30/o
AUGUST 8, 2018
-200 TO 1800 F
t 0.50 FROM 320 TO 1580 F
AUGUST 8, 2018
HUGH A. GRIMES,
CERTIFIED T.A.B.B. CONTRACTOR/SUPERVISOR/TECHNICIAN
--ALL WORKPERFORMED INACCORDANCE WITH TABB STANDARDSAND PROCEDURES—
HUGH GRIMES
TABB TECHNICIAN
881032610T MARCH 31. 2019
NO
BYAC QPERIISE
')MEGA AIR SERVICES LLC
DBA OMEGA TEST AND BALANCE
...A CERTIFIED INDEPENDENT TES TAND BALANCE COMPA N Y---
126 WISTERIA AVENUE, FORT PIERCE, FLORIDA 34982
CELL(772)216-7632
TABB CERTIFICATION NO. BB032001C
www.omegaairserviceslic.com
omegamaniacS32002@yahoo.com
TESTING, ADJUSTING, AND BALANCING WARRANTY
DOYLE MASONRY
ALL TESTING, ADJUSTING, AND BALANCING PERFORMED ON THIS PROJECT BY
OMEGA AIR SERVICES LLC DBA OMEGA TEST AND BALANCE IS UNDER WARRANTY
FOR A PERIOD OF ONE YEAR FROM THE DATE OF COMPLETION OF THE TEST AND
BALANCE UNLESS OTHERWISE NOTED.
WARRANTY PERIOD SHALL BE: FEBRUARY 7, 2019 THROUGH FEBRUARY 7, 2020
--ALL WORKPERFORMED MACCORDANCE WITH TABB STANDARDSAND PROCEDURES
o.,QarPsiw:4ccc.
'Psuy...Q..rq Mt+4ti+YM0uv
J.tib']CI.
Ali
Hugh Grimes
Omega Air Services, LLC
TABB Supervisor
BB032002S
March 31, 2019
. cavemc�.m
HUGH GRIMEB
TABB TECHNICIAN
BB1032fi1OT MARCH 31, 2019
H GH A. GRIMES,
T.A.B.B. CONTRACTOR/SUPERVISOR/TECHNICIAN
PAC EIPMUSE
rg cerun�v o
o
-
HUGH GRIMES
TABB TECHNICV+N
BRIOiJ610T M4RfH 11 J01$
DOYLE MASONRY
AIR OUTLETS
AHU-1
ADDRESS
OUTLET
NUMBER
TYPE
SIZE
DESIGN
CFM
PRE.
CFM
FINAL
CFM
RESTROOM
1
CD
4
25
47
26
RESTROOM
2
CD
4
25
53
26
BREAK STORAGE
3
CD
8
175
190
179
DATA
4
CD
8
150
119
159
BREAK STORAGE
5
CD
10
250
268
259
BREAK STORAGE
6
CD
10
275
301
289
BREAK STORAGE
7
CD
10
250
259
267
BREAK STORAGE
8
CD
10
250
237
256
OFFICE
9
CD
10
275
261
291
RECEPT. WAITING
10
CD
8
150
163
157
1825
1909
REMARKS:
ALL WORKPERFORMED INACCORDANCE WITH TABB STANDARDSAND PROCEDURES
HHGH GRIMES
TABB TECHNICIAN
AR1032610T HAREM 31 2019
DOYLE MASONRY
FAN TEST SHEET
P. FAfthtAlW=
&MME82MEW,EF22
LOCATION
SIDEWALL
SIDEWALL
%
�y
SERVICE
EXHAUST
EXHAUST"
j
MANUFACTURER
GREENEHCK
GREENEHCK
MODEL NUMBER
SBE-1H24-S
SBE-LH24-5
SERIAL NUMBER
NA
NA
DESIGN CFM
2000
2000,
_F
W=MbTdRlUA,TAV=
MAKE I FRAME
DD
DD
HP(W)I RPM
1/2 11550
1i2 11560
VOLTS PHASE HERTZ
23011160
23011160m10,4�
FLA I S.F.
NA
NA
2R1a !v'y�yp�''
��BN�9�I�LW�iJr «
*eat T�krU
L� ✓< { dS i`RAR�2'S)
MOTOR SHEAVE SIZE
DD
DD
MW
FAN SHEAVE SIZE
DD
DD
�. ; WIL
BELTS
DD
DD
9f9Fw.%mm
CL DISTANCE
DD
DD
k
inm
;gym
TEST46ATA
a="'W"
TOTAL CFM
2113
2227
VOLTS
121
122
AMPS
7.1
7.3
SP SUCTION
NA
NA
SP DISCHARGE
Na
Na
EXT. SP
NA
NA
xs
y
REMARKS:
--ALL WORK PERFORMED IN ACCORDANCE WITH TA BB STANDARDS AND PROCEDURES,,