DATE: 3/01118 St. Lucie County JOB ORDER #: 18-911
CLIENT: Onshore Roofing
ADDRESS: 4401 S.E. Commerce Avenue Stuart. Florida 34997
PROJECT: Island Dunes Country Clubhouse — Entegra Bella High "S"
ADDRESS: 8735 S Ocean Drive Jensen Beach, Florida
2017 FBC/ASCE-7 DESIGN PRESSURE CALCULATIONS
Proiect Information:
Mean Roof Height = 25' Exposure: D Basic/Ultimate Wind Speed: V it 170 mph
Length= 36'to 101' Category: 11 Nominal Wind Speed: V.d=Vint*40.6
Width = 23' to 85' Slope: 3/12 to 6/12 (asd = allowable strength design)
Parapet Wall: N/A Clubhouse & = 1.12, Kzt =1.0, Kd = 0.85
Note: The most conservative dimensions were utilized for the design calculations below.
Design Calculations:
Velocity Pressure: q = 0.00256*K KzXdV2
Velocity Pressure (,do: q=0.00256(1.12)(1.0)(0.85)(170)2] = 70.43 psf
Velocity Pressure (.d): q=0.00256(1.12)(1.0)(0.85)(170*40.6)2] = 42.26 psf
Width of Pressure Coefficient: 0.1(85') = 8.5'
0.4(25') = 10.0' } use: 8'6"
Effective Wind Area: <10ft2
For hip roofs with a roof slope of 25 degrees or less, zone three (3) shall be treated as
zone two (2).
External Pressure Coefficient:
1)
GCP1 =
-0.9
2)
GCP2 =
-1.7
3)
GCP3 =
-2.6
Internal Pressure Coefficient:
1) GCPi = 0.18
rig
Qualify Ae-�/.3sa��rance
Cn''
" Page 2, Job Order # 18-9 .`
Onshore Roofing
Island Dunes Country Clubhouse
Sloped Tile (Bella High "S") Roof
8735 S Ocean Drive; Jensen Beach, Florida:
Design Pressures Based on Vasd:
1) Field Pl = 42.26*[(-0.9) — (0.18)] = -45.6 psf
2) Perimeter P2 = 42.26* [(-1.7) — (0.18)] = -79.4 psf
3) Corners P3 = 42.26* [(-2.6) — (0.18)] = -117.5 psf
Attachment Requirements Per RAS 127 (Entegra Bella High "S" Tilel:
Tile System: Moment Based
Aerodynamic Multiplier: 0.378 f0 (Direct Deck Application - Table 1)
Restoring moment due to gravity: Mg = 6.51 ft. lb (Table 2)
Attachment resistance expressed as a moment: Mf= 94 ft-lb Polyset AH-160 Adhesive
Set (Table 4, Independent Large Paddy 63g)
1) Field : Mrl = ( 45.6*0.378) — 6.51 ft. lb =10.7 ft. lb. < 94 ft. lb = PASS
2) Perimeter: Mr2 = ( 79.4*0.378) — 6.51 ft. lb = 23.5 ft. lb. < 94 ft. lb = PASS
3) Comers : Mr3 = (117.5*0.378) — 6.51 ft. lb = 37.9 ft. lb. < 94 ft. lb = PASS
System is acceptable as approved with single independent large paddy (63g) placement of
Polyset AH-160 (by ICP Adhesives and Sealants) based on the requirements of Florida
Product Approval FL7804-R10.
Notes: Corners and perimeter area dimension shall not be less than a = 8'6"
Contractor to verify that the fastening patterns meet manufacturer's
requirements for issuance of a warranty (as applicable).
All work shall be in compliance with the local building code product
control notice of acceptance and manufacturer specifications and Florida
Building Code 2017 Edition.
Wind load calculations based on ASCE-7, 2017 FBC, and information
provided by client. Client is responsible for verifying existing/proposed
conditions/decks as it pertains to the above provided product approval.
All work shall be inspected by our field engineer (or authorized
representative) or a building department inspector to verify X\�jVVUbn?j/////
with specifications. _g�CAly �j
Sincerely, \�� LiceN
BF Sim'
No
n
2 'O=
/�P = o * —
n Szg�_
Mark A. Mesiano, '•,,c oR : Q-
Florida Engineering . thk • ��`��
Florida Reg. No. 4820�1/j ENG��
Certificate of AuthorizatioX4QI