HomeMy WebLinkAboutAPPLICATION FOR BUILDING PERMIT REVISIONSSCANNED
OFFICE USE ONLY: BY
DATE FILED: ��_ s St. Lucie County PERMIT# /�� _U%SS
REVISIONFEE: RECEIPT#
PLANNING & DEVELOPMENT SERVICES
BUILDING & CODE REGULATION DIVISION
2300 VIRGINIA AVENUE
GOA FORT P(772) 462 155382.5652
LOCATIONISITE
ADDRESS: --)A
APPLICATION FOR BUILDING PERMIT REVISIONS
PROJECT INFORMATION
DETAILED DESCRIPTION OF PROJECT
REVISIONS: ter„ X ,
CONTRACTOR INFORMATION:
STATE of FL REG./CERT. #: G
BUSINESS NAME: i+Aln b 5 UnF
QUALIFIERS NAME: /7 .
ADDRESS: D—�Tl✓��/l'tG
CITY: GE STATE:
PHONE (DAYTI
OWNER/BUILDER INFORMATION:
�I►/\37IDC
GT
ST. LUCIE CO CERT. #:
FAX:
ZIP:
CITY: STATE: ZI.P:
PHONE (DAYTIME: ? 72--W lj '-Z2 /i FAX:
ARCHITECT/ENGINEER INFORMATION:
NAME:
CITY: L' STATE: yG ZIP:
PHONE (DAYTIME): Ga Jr FAX:
SLCCC: 9123109
Revised 06/30/17 E v s' ® N
�F-
Architectonic Inc
April 12, 2018
f 3010 ;-
RECENED
Saint Lucie County Building Department APR 19 ?ojo
Attn: Roof Permit Plan Review PermRtfng Departmem
2300 Virginia Avenue St. Lucie county
Ft. Pierce, FL 34982
Re: Roofing specification prepared for the St. Lucie County Building Dept. for the structure
located at 3055 N US 1, Saint Lucie County, Florida
Manufacturer:
GAF
Profiles:
Modified Bitumen Roof System, NOA# 16-1206.02
Code:
FBC2017
Wind Speed:
170 MPH; Ultimate Design Wind Speeds Risk Category III
Exposure:
B
Mean Roof Height:
30' Maximum
Pitch:
Y4 /12
Required Design Pressure:
Zone1: -29.38 Zone 2: -46.33 Zone3:-64.41.
Maximum Uplift Pressure:
-90 psf
Roof Decking:
Existing 5/8" plywood sheathing to be nailed w 8d x 2" ring shank nails
@ 6" O.C. thru out Zone 1, 4" O.C. perimeter & 6" O.C. field Zone 2,
and 4" O.C. thru out Zone 3.
Base:
SBS-SV (self- adhering)
Ply Sheet:
(Optional) SBS-SA, SBS-TA, APP-TA (self -adhering)
Cap:
SBS-SA, SBS-SV, APP-SA, SBS-TA, APP-TA (self -adhering)
The above approved, as per Florida Building Code Compliance acceptances, 2017 Florida Building Code,
and the Manufacturer's recommendations.
806 Delaware Avenue Tel: 772 460 7751 www.architectonicinc.com
Fort Pierce, Florida 34950 Fax: 772 460 4244 FL Reg #AA26003348 1 of 1
RECEIVED
APR 13 1010
a�. 1
COUNTY J
Permitting Department
St. Lucie County
DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)
BOARD AND CODE ADMINISTRATION DIVISION
MIAMI-DADE COUNTY
PRODUCT CONTROL SECTION
11805 SW 26 Street, Room 208
Miami, Florida 33175-2474
T (786) 315-2590 F (786) 315-2599
NOTICE OF ACCEPTANCE (NOA) www.miamidade.gov/economv
GAF
1 Campus Drive
Parsippany, NJ 07054
SCOPE:
This NOA is being issued under the applicable rules and regulations governing the use of construction materials.
The documentation submitted has been reviewed and accepted by Miami -Dade County RER - Product Control
Section to be used in Miami -Dade County and other areas where allowed by the Authority Having Jurisdiction
(AHJ).
This NOA shall not be valid after the expiration date stated below. The Miami -Dade County Product Control
Section (in Miami -Dade County) and/or the AHJ (in areas other than Miami -Dade County) reserve the right to have
this product or material tested for quality assurance purposes. If this product or material fails to perform in the
accepted manner, the manufacturer will incur the expense of such testing and the AHJ may immediately revoke,
modify, or suspend the use of such product or material within their jurisdiction. RER reserves the right to revoke
this acceptance, if it is determined by Miami -Dade County Product Control Section that this product or material
fails to meet the requirements of the applicable building code.
This product is approved as described herein, and has been designed to comply with the Florida Building Code
including the High Velocity Hurricane Zone of the Florida Building Code.
DESCRIPTION: GAF Liberty'"' SBS Self -Adhering Modified Bitumen Roofing Systems Over Wood Decks.
LABELING: Each unit shall bear a permanent label with the manufacturer's name or logo, city, state and
following statement: "Miami -Dade County Product Control Approved", unless otherwise noted herein.
RENEWAL of this NOA shall be considered after a renewal application has been filed and there has been no
change in the applicable building code negatively affecting the performance of this product.
TERMINATION of this NOA will occur after the expiration date or if there has been a revision or change in the
materials, use, and/or manufacture of the product or process. Misuse of this NOA as an endorsement of any product,
for sales, advertising or any other purposes shall automatically terminate this NOA. Failure to comply with any
section of this NOA shall be cause for termination and removal of NOA.
ADVERTISEMENT: The NOA number preceded by the words Miami -Dade County, Florida, and followed by the
expiration date may be displayed in advertising literature. If any portion of the NOA is displayed, then it shall be
done in its entirety.
INSPECTION: A copy of this entire NOA shall be provided to the user by the manufacturer or its distributors and
shall be available for inspection at the job site at the request of the Building Official.
This NOA renews and revises NOA No. 15-0203.05 and consists of pages 1 through 18.
The submitted documentation was reviewed by Jorge L. Acebo.
NOA No.: 16-1206.02
Expiration Date: 02/22/22
Approval Date: 02/16/17
Page 1 of 18
ROOFING SYSTEM APPROVAL
Category
Roofing
Sub-Cateeorv:
Modified Bitumen
Material:
APP/SBS
Deck Type:
Wood
Maximum Design Pressure:
-60 psf.
TRADE NAMES OF PRODUCTS MANUFACTURED OR LABELED BY APPLICANT:
TABLE 1
Test, .
Product
Product
Dimensions
Specification
Description
LibertyV' SBS Self -Adhering
39.375" x 66'
ASTM D4601
Self -adhered, SBS modified base or
Base/Ply Sheet
ply sheet with glass reinforced mat.
Liberty' MA Mechanically
39.375" x 66'
ASTM D4601
SBS base sheet with a glass
Attached Base Sheet
reinforced mat coated with a
polymer -modified asphalt.
Liberty' SBS Self -Adhering
39.375" x 34'
ASTM D6164
Granule surfaced self -adhering SBS
Cap Sheet
modified membrane reinforced with
polyester mat, coated with polymer -
modified asphalt.
GAFGLAS' Ply 4
39.37"
ASTM D2178
Type IV asphalt impregnated glass
(1 meter) Wide
felt with asphalt coating.
Tri-Ply® Ply 4
39.37"
ASTM D2178
Type IV asphalt impregnated'glass
(1 meter) Wide
felt with asphalt coating.
GAFGLAS' FlexPly'' 6
39.37"
ASTM D2178
Type VI'aspbalt impregnated glass
(1 meter) Wide
felt with asphalt coating.
GAFGLAS' #75 Base Sheet
39.37"
ASTM D4601'
'Type 11, asphalt impregnated and
(1 meter) Wide
coated glass'mat base sheet.
Tri-Ply' #75 Base Sheet
39.37"
ASTM D4601
Type 11, asphalt impregnated and
(1 meter) Wide
coated glass mat base sheet.
GAFGLAS' #80 Ultima" Base
39.37"
ASTM D4601
Type II, asphalt impregnated and
Sheet
(1 meter) Wide
coated, fiberglass base sheet. ,
GAFGLAS' Stratavent'
39.37"
ASTM D4897
A nailable, fiberglass base sheet
Eliminator' Nailable Venting
(I meter) Wide
coated on both sides with asphalt.
Base Sheet
Surfaced on the bottom side with
mineral granules embedded in'
asphaltic coating.
Ruberoid'
39.37"
ASTM D6163
SBS modified asphalt base sheet
SBS Heat -Weld' 25
(1 meter) Wide
reinforced with a glass fiber mat and
smooth surfaced.
NOA No.: 16-1206.02
Expiration Date: 02/22/22
MIAMI•DAD, COUNTY Approval Date: 02/16/17
Page 2 of 18
Test
Product
Product
Dimensions
Specification
Description
Ruberoid®
39.37"
ASTM D6164
Non -woven polyester mat coated with
SBS Heat -Weld'"'
Smooth
(1 meter) Wide
SBS polymer -modified asphalt and
smooth surfaced.
Ruberoid®
39.37"
ASTM D6164
Non -woven polyester mat coated with
SBS Heat -Weld'
Granule
(1 meter) Wide
SBS polymer -modified asphalt and
surfaced with mineral granules.
Ruberoid®
39.37"
ASTM D6164
Non -woven polyester mat coated with
SBS Heat -Weld'
170 FR
(1 meter) Wide
fire retardant SBS polymer -modified
asphalt and surfaced with mineral
granules.
Ruberoid®
39.37"
ASTM D6164
Non -woven polyester mat coated with
SBS Heat -Weld'"'
Plus
(1 meter) Wide
SBS polymer -modified asphalt and
surfaced with mineral granules.
Ruberoid® 39.37" ASTM D6164 Non -woven polyester mat coated with
SBS Heat -Weld' Plus FR (1 meter) Wide fire retardant SBS polymer -modified
asphalt and surfaced with mineral
granules.
Ruberoid® EnergyCap' SBS 39.37"
Heat -Weld'"' Plus FR (1 meter) Wide
Ruberoid® Torch Smooth 39.37"
(1 meter) Wide
ASTM D6164 Non -woven polyester mat coated with
fire retardant SBS polymer -modified
asphalt and surfaced with mineral
granules with factory applied
EnergyCote''.
ASTM D6222 Non -woven polyester mat coated with
APP modified asphalt and smooth
surfaced.
Tri-Ply® TP-4
39.37"
ASTM D6222
Non -woven polyester mat coated with
(1 meter) Wide
APP modified asphalt and smooth
surfaced.
Ruberoid® Torch Granule
39.37"
ASTM D6222
Non -woven polyester mat coated with
(1 meter) Wide
APP modified asphalt and
surfaced with mineral granules.
Tri-Ply® TP-4G
39.37"
ASTM D6222
Non -woven polyester mat coated with
(1 meter) Wide
APP modified asphalt and
surfaced with mineral granules.
Ruberoid® Torch FR
39.37"
ASTM D6222
Non -woven polyester mat coated with
(1 meter) Wide
fire retardant APP modified asphalt
surfaced with mineral granules.
Ruberoid® EnergyCap` Torch
39.37"
ASTM D6222
APP modified cap membrane with a
Plus FR
(1 meter) Wide
torch grade bottom surface and a
mineral granular top surface coated
with factory applied EnergyCote'".
NOA No.: 16-1206.02
Expiration Date: 02/22/22
Approval Date: 02/16/17
Page 3 of 18
Test
Product
Product
Dimensions
Specification
Description
Ruberoid® EnergyCap' Torch
39.37"
ASTM D6222
APP modified cap membrane with a
Granule FR
(I meter) Wide
torch grade bottom surface and a
mineral granular top surface coated
with factory applied EnergyCote'.
Ruberoid® 20
39.37"
ASTM D6163
SBS polymer -modified asphalt base
(I meter) Wide
sheet reinforced with a glass fiber
mat.
Ruberoid' Mop Smooth
39.37"
ASTM D6164
Non -woven polyester mat coated with
(1 meter) Wide
SBS polymer -modified asphalt and
smooth surfaced.
Ruberoid® Mop Smooth 1.5 . 39.37"
(1 meter) Wide
Ruberoid' Mop Plus Smooth 39.37"
(1 meter) Wide
ASTM D6164 Non -woven polyester mat coated with
SBS polymer -modified asphalt and
smooth surfaced.
ASTM D6164 Non -woven polyester mat coated with
SBS polymer -modified asphalt and
smooth surfaced.
GAFGLAS' Mineral Surfaced
39.37"
ASTM D3909
Asphalt coated, glass fiber mat cap
Cap Sheet
(1 meter) Wide
sheet surfaced with mineral granules.
Tri-Ply' Mineral Surfaced
39.37"
ASTM D3909
Asphalt coated, glass fiber mat cap
Cap Sheet
(1 meter) Wide
sheet surfaced with mineral granules.
GAFGLAS' EnergyCap'
39.37"
ASTM D3909
Asphalt coated, glass fiber mat cap
BUR Mineral Surfaced Cap
(1 meter) Wide
sheet surfaced with mineral granules
Sheet
and factory applied EnergyCote ".
VersaShield' Fire -Resistant
42','„ X 100'
ASTM D 226
Non -Asphaltic fiberglass based
Roof Deck Protection
rolls
underlayment and/or fire barrier.
WeatherWatch' XT
36" x 50' rolls
ASTM D1970
Mat surfaced SBS modified,
36" x 66.7'
fiberglass reinforced, bituminous
rolls
sheet material used as a leak barrier
underlayment.
StormSafe" Anchor Sheet
40" Wide
ASTM D4601
Synthetic anchor sheet.
Topcoat® Surface Seal SB
5 or 55 gallons
ASTM D6083
Solvent based sprayable thermoplastic
rubber sealant designed to protect and
restore aged roof surfaces and to
increase roof reflectivity.
Topcoat' Membrane
1, 5 or 55
ASTM D6083
An acrylic, water based elastomeric
gallons
membrane system designed to protect
various types of roof surfaces.
Topcoat' MB Plus
5 or 55 gallons
Proprietary
Water based, low VOC primer used to
block asphalt bleed -through.
NOA No.: 16-1206.02
Expiration Date: 02/22/22
Approval Date: 02/16/17
Page 4 of 18
Product Dimensions
Topcoat® F1exSeal 1, 5 gallons or
I qt. tube
Topcoat® FireOut" Fire 5 or 55 gallons
Barrier Coating
APPROVED INSULATIONS:
Product Name
EnergyGuard' Polyiso Insulation
EnergyGuard' RA Polyiso Insulation
EnergyGuard' RH Polyiso Insulation
EnergyGuard' RN Polyiso Insulation
DensDeck"Roof Board
DensDeck' Prime® Roof Board
Securock' Gypsum -Fiber Roof Board
Test
Product
Specification
Description
Proprietary
Solvent based flashing compound for
gutters and other detailing.
ASTM D6083
Low VOC, water -based fire barrier
coating.
TABLE 2
Product Description
Polyisocyanurate foam insulation
Polyisocyanurate foam insulation
Polyisocyanurate foam insulation
Polyisocyanurate foam insulation
Gypsum board
Gypsum board
Gypsum board
Manufacturer
(With Current NOA)
GAF
GAF
GAF
GAF
Georgia-Pacific Gypsum LLC
Georgia-Pacific Gypsum LLC
United States Gypsum
Corporation
NOA No.: 16-1206.02
MIAMIExpiration Date: 02/22/22
[11 18 COUNTY • •., Approval Date: 02/16/17
Page 5 of 18
APPROVED FASTENERS:
TABLE3
Fastener Product Product
Number Name Description Dimensions
1. Drill-Tec' #12 Fastener Carbon steel fastener used Various
in steel or wood decks.
2. Drill-Tec'" #14 Fastener
Carbon steel fastener used
in steel, wood or concrete
decks.
3. Drill -Tee ASAPI 3S
Drill -Tee #12 fastener
with Drill-Tec'" 3"
Standard Steel Plate.
4. Drill-Tec'
Round galvalume plated
3" Steel Plates
steel stressplate with
reinforced ribs for use
with Drill-Tec" fasteners.
5. Drill -Tee
Round galvalume stress
3" Standard Steel Plates
plate used with Drill-
Tec'" fasteners.
6. Drill-Tec' AccuTrac®
Galvalume steel plate for
Recessed Plates
use with Drill -Tee
fasteners.
7. Drill -Tee AccuTrac®
AZ -SS aluminized steel
Flat Plates
plate for use with Drill -
Tee' #12 Fastener, Drill-
Tec'" #14 Fastener and
Drill -Tee XHD
Fastener.
8. Annular Ring Shank
Galvanized steel
Nails & Tin Caps
Ring shank roofing nails
with Galvanized steel tin
caps.
Various
.
Various
3" round
3" round
3" x 3"
3" x 3"
Nail: Minimum
12 Ga.
Various lengths
Tin Caps:
Minimum 32 Ga.
1%" Diameter
Manufacturer
(With Current NOA)
GAF
GAF
GAF
W.fi
GAF
GAF
Cef:VA
Generic
(Dade County Approved)
NOA No.: 16-1206.02
Expiration Date: 02/22/22
Approval Date: 02/16/17
Page 6 of 18
EVIDENCE SUBMITTED:
Test Agency
Name
Report Identifier
Date
IRT-ARCON, Inc.
TAS 114
02-005
01/18/02
TAS 114
02-014
03/22/02
UL LLC
UL 790
R10689
03/14/13
UL 790
R1306
05/22/13
Factory Mutual Research Corp.
4470
3024805
11/20/06
4470
3036225
08/10/09
4470
3035140
08/10/09
4470
3040738
11/16/10
4470
3036980
08/14/09
4470
3044688
03/16/12
4470
3038278
11/18/11
4470
3032811
12/11/08
4470
797-03221-267
09/24/07
TrinitylERD
ASTMD4897
G34140.04.11-5-R3
06/04/15
ASTM D4601
G121110.12.08
12/02/08
ASTM D4601
G34140.04.11-4-R2
06/04/15
ASTM D6163
G34140.04.11-2
04/25/11
ASTM D6862
C8500SC.11.07
11/30/07
ASTM D6164
G33470.01.11
01/13/11
ASTMD6164
G31360.03.10
03/31/10
ASTM D6222
G43190.11.13-1
11/15/13
ASTM D6222
G43190.03.14-2
03/06/14
ASTM D6222
G43190.03.14-1
03/06/14
ASTM D6163
G40630.01.14-1
01/06/14
ASTMD6164
G40630.01.14-2A
01/07/14
ASTM D6164
G40630.01.14-2B-R1
01/16/15
ASTMD6164
G40630.01.14-2C
01/07/14
ASTMD6164
G46160.09.14-3B
09/09/14
ASTM D6164
G40630.03.14
03/06/14
ASTM D6164
G40630.01.14-2A-1-RI
04/10/14
ASTM D4601
G43180.01.14-1
01/10/14
ASTM D6164
G43180.03.14
03/03/14
ASTMD6164
G6850.08.08-R1
04/14/11
ASTM D6222
G6850.11.08
11/05/08
ASTM D6222
G6850.10.08
10/06/08
ASTM D3909
G43610.01.14
01/22/14
ASTM D3909
G30250.02.10-3-R2
06/03/15
ASTM D3909
SC6870.08.14-RI
09/04/14
ASTM D6222
G40620.07.12-2
07/17/12
ASTM D6163
G12210.06.09
08/03/09
ASTM D6222
G30250.02.10-2
05/11/10
Exterior Research and Design, LLC
TAS 114
18035.12.02-2
12/24/02
TAS 114
01501.04.03
04/03/03
TAS 114
01516.04.06
04/20/06
TAS 114
G4280LAB.10.06
10/20/06
NOA No.: 16-1206.02
MIAMI•DADE COUNTY
Expiration Date: 02/22/22
... , , Approval Date: 02/16/17
Page 7 of 18
/
EVIDENCE SUBMITTED: (CONTINUED)
Test Aaenev
Test Name
Report Identifier
Date
Atlantic & Caribbean Roof
TAS 114
07-079
12/13/07
Consulting, LLC
TAS 114
08-044
07/01/08
PRI Construction Material
ASTM E96
GAF-306-02-01
07/07/11
Technologies LLC
ASTM E2178
GAF-276-02-01
01/04/11
ASTM D2178
GAF-314-02-01
08/23/11
ASTM D2178
GAF-315-02-01
08/23/11
ASTM D226
GAF-270-02-02
11/15/10
ASTM D226
GAF-349-02-01
07/03/12
ASTMD1970
GAF-324-02-01
11/30/11
ASTM D6083
GAF-498-02-01
01/06/16
ASTM D6083
GAF-499-02-01
03/12/14
ASTM D6083
GAF-500-02-01
03/12/14
ASTM D6083
GAF-276-02-OIREV
O1/03/11
ASTM C1289
GAF-369-02-01
10/22/12
ASTM C1289
GAF-464-02-01
02/06/14
TAS 139
GAF-671-02-01
06/30/16
TAS 114
GAF-434-02-03
09/06/13
Momentum Technologies Inc.
ASTM D6162
AX04C9A
06/05/09
NOA No.: 16-1206.02
Expiration Date: 02/22/22
MIAMIDAD; COUNTY Approval Date: 02/16/17
Page 8 of 18
APPROVED ASSEMBLIES:
Membrane Type: APP/SBS
Deck Type 1I: Wood, Insulated
Deck Description: 19/32" or greater plywood or wood plank attached to -supports max. 24" o.c, with
8d common nails max. 6" o.c.
System Type A: All layers of insulation are adhered to a mechanically attached anchor sheet.
Membrane fully or partially adhered.
All Generaland System Limitations apply.
Fire Barrier: Topcoat® FireOut' Fire Barrier Coating, VersaShield' Fire -Resistant Roof
(Optional) Deck Protection, DensDeck' Roof Board or Securock® Gypsum -Fiber Roof Board.
Anchor sheet: GAFGLAS' Ply 4, Tri-Ply® Ply 4, GAFGLAS' FlexPly" 6, GAFGLAS' #75
Base Sheet, Tri-Ply® #75 Base Sheet, GAFGLAS' #80 Ultima' Base Sheet,
GAFGLAS' Stratavent® Eliminator'" Nailable Base Sheet, Ruberoid® 20,
Ruberoid' Mop Smooth, Ruberoid® Mop Smooth 1.5 or Ruberoid® Mop Plus
Smooth mechanically fastened to deck with Miami Dade approved annular ring
shank nails and tin caps at a fastener spacing of 9" o.c. in the 4" side lap and in
two staggered rows in the field of the sheet.
One or more layers of any of the following insulations.
Base Insulation Layer (Optional) Insulation Fasteners Fastener
(Table 3) Density/ft2
EnergyGuard' Polyiso Insulation, EnergyGuard'°' RA Polyiso Insulation,
EnergyGuard' RH Polyiso Insulation, EnergyGuard'" RN Polyiso Insulation
Minimum 1" thick N/A N/A
Top Insulation Layer Insulation Fasteners Fastener
(Table 3) Density/ft2
DensDeck' Prime' Roof Board, Securock® Gypsum -Fiber Roof Board
Minimum 1/4" thick N/A N/A
Note: All layers of insulation shall be adhered to the anchor sheet in full mopping of approved hot
asphalt within the EVT range at a rate of 20-40 lbs./100 sq. ft. or in 3/4" to 1" wide beads 6"
o.c. of OlyBond 500' Adhesive or Olybond 500' Green applied in serpentine pattern with
minimum 3/4" wide ribbons or OlyBond' Adhesive Fastener at a rate of 1 gal./100 ft2.
Please refer to Roofing Application Standard RAS 117 for insulation attachment.
Ply Sheet: One or more layers of Liberty"" SBS Self -Adhering Base/Ply Sheet self -adhered
(Optional) with minimum 3" wide laps and rolled with a weighted roller in accordance with
manufacturer's instructions.
Or
One layer of WeatherWatch' XT self -adhered with minimum 3" wide laps and
rolled with a weighted roller in accordance with manufacturer's instructions.
Note: WeatherWatch'XT may only be used with a torch adhered cap.
NOA No.: 16-1206.02
MIAMI-DADE COUN7Y Expiration Date: 02/22/22
Approval Date: 02/16/17
Page 9 of 18
Membrane: One layer of Liberty' SBS Self -Adhering Cap Sheet self -adhered with minimum
4" wide laps and rolled with a weighted roller in accordance'with manufacturer's
instructions. (Not for use with WeatherWatchlXT)
OR
One or more layers of Ruberoid® SBS Heat -Weld' 25, Ruberoido SBS Heat -
Weld' Smooth, Ruberoid® SBS Heat -Weld' Granule, Ruberoid® SBS Heat -
Weld' 170 FR, Ruberoid® SBS Heat -Weld' Plus, Ruberoid® SBS Heat -Weld'
Plus FR or Ruberoid® EnergyCap' SBS Heat -Weld' Plus FR heat welded to the
self -adhering base/ply sheet in accordance with manufacturer's instructions.
OR
Ruberoid® Torch Smooth, Tri-Ply® TP4, Ruberoid® Torch Granule, Tri-Ply® TP-
4G, Ruberoid® Torch FR, Ruberoid®EnergyCap" Torch Plus FR or Ruberoid®
EnergyCap' Torch Granule FR with minimum 3" wide laps and torch applied to
the self -adhering base/ply in accordance with manufacturer's instructions.
Surfacing: Optional on granular surfaced membranes; required for smooth membranes.
Chosen components must be listed in a current NOA Approval and applied in
accordance with manufacturer's instructions.
1. Gravel or slag applied at 400 lbs./sq. and 3001bs./sq. respectively in a flood coat of
approved asphalt at 60 lbs./sq.
2. GAFGLAS® Mineral Surfaced Cap Sheet, Tri-Ply® Mineral Surfaced Cap Sheet or
GAFGLAS® EnergyCap" BUR Mineral Surfaced Cap Sheet adhered in a full mopping of
approved asphalt applied within the EVT range and at a rate of 2040 lbs./sq.
3. Topcoat® Membrane, Topcoat' MB Plus (to be used as a primer with Topcoat Membrane)
or Topcoat® Surface Seal SB applied at 1 to 1.5 gal./sq.
4. Fibered Aluminum Roof Coating.
Maximum Design
Pressure: -45 psf. (See General Limitation #7)
NOA No.: 16-1206.02
Expiration Date: 02/22/22
Approval Date: 02/16/17
Page 10 of 18
Membrane Type:
Deck Type 1I:
APP/SBS
Wood, Insulated
Deck Description: Min. 15/32" plywood attached to supports max. 24" o.c. with Sd common nails
max. 6" o.c.
System Type C(1): Top layer of insulation is simultaneously mechanically attached with optional layer
of base insulation to the deck. Membrane fully or partially adhered.
All General and System Limitations apply.
Fire Barrier: Topcoat® FireOut' Fire Barrier Coating, VersaShield® Fire -Resistant Roof Deck
(Optional) Protection, DensDeck® Roof Board or Securock' Gypsum -Fiber Roof Board.
One or more layers of any of the following insulations.
Base Insulation Layer (Optional) Insulation Fasteners Fastener
(Table 3) Density/ft'
EnergyGuard' Polyiso Insulation, EnergyGuard'a' RA Polyiso Insulation, EnergyGuard"' RH'
Polyiso Insulation, EnergyGuard'" RN Polyiso Insulation '
Minimum 1" thick (Loose laid) N/A N/A
Top Insulation Layer Insulation Fasteners Fastener
(Table 3) Density/ft2
EnergyGuard' Polyiso Insulation, EnergyGuard"' RH Polyiso Insulation
Minimum 1.5" thick 1 & 4,5 1:2
Note: All layers of insulation shall be mechanically attached using the fastener density listed
above. The insulation panels listed are minimum sizes and dimensions; if larger panels are
used, the number of fasteners shall be increased maintaining the same fastener density.
Please refer to Roofing Application Standard RAS 117 for insulation attachment.
Base Sheet: One layer of Liberty' SBS Self -Adhering Base/Ply Sheet self -adhered with
minimum 3" wide laps and rolled with a weighted roller in accordance with
manufacturer's instructions.
Or
One layer of WeatherWatcha XT self -adhered with minimum 3" wide laps and rolled
with a weighted roller in accordance with manufacturer's instructions.
Note: WeatherWatch"XT may only be used with a torch adhered cap.
Ply Sheet: One layer of Liberty' SBS Self -Adhering Base/Ply Sheet self -adhered with
(Optional) minimum 3" wide laps and rolled with a weighted roller in accordance with
manufacturer's instructions. (Not for use with WeatherWatch®XT)
NOA No.: 16-1206.02
Expiration Date: 02/22/22
nwwHoaoecourm Approval Date: 02/16/17
Page 11 of 18
Membrane: One layer of Liberty"' SBS Self -Adhering Cap Sheet self -adhered with minimum 4"
wide laps and rolled with a weighted roller in accordance with manufacturer's
instructions. (Not for use with WeatherWatch'XT)
OR
One or more layers of Ruberoid' SBS Heat -Weld'" 25, Ruberoid' SBS Heat -Weld'
Smooth, Ruberoid' SBS Heat -Weld' Granule, Ruberoid' SBS Heat -Weld' 170 FR,
Ruberoid' SBS Heat -Weld' Plus, Ruberoid' SBS Heat -Weld' Plus FR or
Ruberoid® EnergyCap'' SBS Heat -Weld' Plus FR heat welded to the self -adhering
base/ply sheet in accordance with manufacturer's instructions.
OR
Ruberoid' Torch Smooth, Tri-Ply® TP4, Ruberoid' Torch Granule, Tri-Ply' TP-
4G, Ruberoid' Torch FR, Ruberoid' EnergyCap" Torch Plus FR or Ruberoid'
EnergyCap' Torch Granule FR with minimum 3" wide laps and torch applied to the
self -adhering base/ply sheet in accordance with manufacturer's instructions.
Surfacing: Optional on granular surfaced membranes; required for smooth membranes.
Chosen components must be listed in a current NOA Approval and applied in
accordance with manufacturer's instructions.
1. Gravel or slag applied at 400 lbs./sq. and 300 lbs./sq. respectively in a flood coat of
approved asphalt at 60 lbs./sq.
2. GAFGLAS' Mineral Surfaced Cap Sheet, Tri-Ply® Mineral Surfaced Cap Sheet or.
GAFGLAS' EnergyCap'°' BUR Mineral Surfaced Cap Sheet adhered in a full mopping of
approved asphalt applied within the EVT range and at a rate of 2040 lbs./sq.
3. Topcoat' Membrane, Topcoat' MB Plus (to be used as a primer with Topcoat' Membrane)
or Topcoat' Surface Seal SB applied at 1 to 1.5 gal./sq.
4. Fibered Aluminum Roof Coating.
Maximum Design
Pressure: -45 psf. (See General Limitation # 7)
NOA No.: 16-1206.02
Expiration Date: 02/22/22
Approval Date: 02/16/17
Page 12 of 18
Membrane Type: APP/SBS
Deck Type 1I: Wood, Insulated
Deck Description: Min. 15132" plywood attached to supports max. 24" o.c. with 8d common nails
max. 6" o.c.
System Type C(2): Top layer of insulation is simultaneously mechanically attached with optional layer
of base insulation to the deck. Membrane fully or partially adhered.
All General and System Limitations apply.
Fire Barrier: Topcoat' FireOut' Fire Barrier Coating, VersaShield' Fire -Resistant Roof Deck
(Optional) Protection, DensDeck' Roof Board or Securock' Gypsum -Fiber Roof Board.
One or more layers of any of the following insulations.
Base Insulation Layer (Optional) Insulation Fasteners Fastener
(Table 3) Density/ft2
EnergyGuard'" Polyiso Insulation, EnergyGuard"' RA Polyiso Insulation, EnergyGuard' RH
Polyiso Insulation, EnergyGuard'" RN Polyiso Insulation
(Loose laid) N/A N/A
Top Insulation Layer Insulation Fasteners Fastener
(Table 3) Density/fF
Securock' Gypsum -Fiber Roof Board
Minimum 1/2" thick 1 & 4,5 1:2
Note: All layers of insulation shall be mechanically attached using the fastener density listed
above. The insulation panels listed are minimum sizes and dimensions; if larger panels are
used, the number of fasteners shall be increased maintaining the same fastener density.
Please refer to Roofing Application Standard RAS 117 for insulation attachment.
Base Sheet: One layer of Liberty'' SBS Self -Adhering Base/Ply Sheet self -adhered in accordance
with manufacturer's instructions.
OR
One layer of WeatherWatch' XT self -adhered with minimum 3" wide laps and rolled
with a weighted roller in accordance with manufacturer's instructions.
Note: WeatherWatch®XT may only be used with a torch adhered cap.
Ply Sheet: One layer of Liberty' SBS Self -Adhering Base/Ply Sheet self -adhered with
(Optional) minimum 3" wide laps and rolled with a weighted roller in accordance with
manufacturer's instructions. (Not for use with WeatherWatch'XT)
Membrane: One layer of Liberty'" SBS Self -Adhering Cap Sheet self -adhered with minimum 4"
wide side laps and rolled with a weighted roller in accordance with manufacturer's
instructions. (Not for use with WeatherWatch'XT)
OR
Ruberoid' Torch Smooth, Tri-Ply' TP-4, Ruberoid' Torch Granule, Tri-Ply' TP-
4G, Ruberoid' Torch FR, Ruberoid' EnergyCap" Torch Plus FR or Ruberoid'
EnergyCap' Torch Granule FR with minimum 3" wide laps and torch applied to the
self -adhering base/ply sheet in accordance with manufacturer's instructions.
NOA No.: 16-1206.02
MIAMFDADE COUExpiration Date: 02/22/22
NTY
• • • . , Approval Date: 02/16/17
Page 13 of 18
Surfacing: Optional on granular surfaced membranes; required for smooth membranes.
Chosen components must be listed in a current NOA Approval and applied in
accordance with manufacturer's instructions.
1. Gravel or slag applied at 400 lbs./sq. and 300 lbs./sq. respectively in a flood coat of
approved asphalt at 60 lbs./sq.
2. GAFGLAS® Mineral Surfaced Cap Sheet, Tri-Ply® Mineral Surfaced Cap Sheet or
GAFGLAS® EnergyCap" BUR Mineral Surfaced Cap Sheet adhered in a full mopping of
approved asphalt applied within the EVT range and at a rate of 20-40 lbs./sq.
3. Topcoat® Membrane, Topcoat® MB Plus (to be used as a primer with Topcoat® Membrane)
or Topcoat® Surface Seal SB applied at 1 to 1.5 gal./sq.
4. Fibered Aluminum Roof Coating.
Maximum Design
Pressure: -52.5 psf. (See General Limitation # 7)
NOA No.: 16-1206.02
Expiration Date: 02/22/22
MIAMIFU COUNTY
• • • , , Approval Date: 02/16/17
Page 14 of 1S
Membrane Type: APP/SBS
Deck Type 1: Wood, Non -insulated
Deck Description: Min. 15/32" plywood attached to supports max. 24" o.c. with 8d common nails
max. 6" o.c.
System Type E(1):
Base Sheet is mechanically attached to the deck. Membrane fully or partially
adhered.
All General and System
Limitations shall apply.
Fire Barrier:
Topcoat® FireOute' Fire Barrier Coating, VersaShield®Fire-Resistant Roof Deck
(Optional)
Protection, DensDeck' Roof Board or Securock' Gypsum -Fiber Roof Board.
Base Sheet:
Liberty' MA Mechanically Attached Base Sheet in accordance with
manufacturer's instructions.
Fastening Options:
Base sheet is mechanically attached to the deck with Drill-Tec'" #14 Fasteners and
Drill-Tec' 3" Steel Plates 8" o.c. in the 3" laps and 8" o.c. in two staggered rows
in the field.
(Maximum Design Pressure —60 psf., See General Limitation #7)
Base sheet is mechanically attached to the deck with Miami Dade approved tin -
caps and nails at 8" o.c. in the 3" laps and 8" o.c. in three equally spaced,
staggered rows in the field of the sheet.
(Maximum Design Pressure —45 psf., See General Limitation #7)
Ply Sheet:
One or more layers of Liberty'" SBS Self -Adhering Base/Ply Sheet in accordance
(Optional)
with manufacturer's instructions.
OR
One layer of WeatherWatch'XT self -adhered with minimum 3" wide laps and
rolled with a weighted roller in accordance with manufacturer's instructions.
Note: WeatherWatch®XT may only be used with a torch adhered cap.
Membrane:
One layer of Liberty SBS Self -Adhering Cap Sheet self -adhered in accordance
with manufacturer's instructions. (Not for use with WeatherWatch® XT)
Or
One or more layers of Ruberoid' SBS Heat -Weld' 25, Ruberoid' SBS Heat-
Weld'Smooth, Ruberoid' SBS Heat -Weld"" Granule, Ruberoid' SBS Heat -
Weld' 170 FR, Ruberoid' SBS Heat -Weld"° Plus, Ruberoid' SBS Heat -Weld'
Plus FR or Ruberoid' EnergyCap' SBS Heat -Weld' Plus FR heat welded in
accordance with manufacturer's instructions.
OR
Ruberoid' Torch Smooth, Tri-Ply' TP4, Ruberoid' Torch Granule, Tri-Ply' TP-
4G, Ruberoid® Torch FR, Ruberoid' EnergyCar Torch Plus FR or Ruberoid'
EnergyCap' Torch Granule FR with minimum 3" wide laps and torch applied in
accordance with manufacturer's instructions.
NOA No.: 16-1206.02
Expiration Date: 02/22/22
Approval Date: 02/16/17
Page 15 of 18
Surfacing: Optional on granular surfaced membranes; required for smooth membranes.
Chosen components must be listed in a current NOA Approval and applied in
accordance with manufacturer's instructions.
1. Gravel or slag applied at 400 lbs./sq. and 300 lbs./sq. respectively in a flood coat of
approved asphalt at 60 lbs./sq.
2. GAFGLAS® Mineral Surfaced Cap Sheet, Tri-Ply® Mineral Surfaced Cap Sheet or
GAFGLAS® EnergyCap'" BUR Mineral Surfaced Cap Sheet adhered in a full mopping of
approved asphalt applied within the EVT range and at a rate of 20-401bs./sq.
3. Topcoat® Membrane, Topcoats MB Plus (to be used as a primer with Topcoat® Membrane)
or Topcoat® Surface Seal SB applied at 1 to 1.5 gal./sq.
4. Fibered Aluminum Roof Coating.
Maximum Design
Pressure: See fastening options above
NOA No.: 16-1206.02
Expiration Date: 02/22/22
Approval Date: 02/16/17
Page 16 of 18
Membrane Type: APP/SBS
Deck Type 1: Wood, Non -insulated
Deck Description: Min. 19/32" CDX plywood nailed to 6" o.c. at the field of the sheet with #8 ring
shank nails and 4" o.c. at the perimeter of the sheet with #10 ring shank nails.
Plywood installed over wood rafters spaced 24" o.c.
System Type E(2): Base sheet is mechanically attached, to the deck. Membrane fully or partially
adhered.
All General and System Limitations shall apply.
Fire Barrier: Topcoat® FircOut' Fire Barrier Coating, VersaShield® Fire -Resistant Roof Deck
(Optional) Protection, DensDeck, Roof Board or Securock" Gypsum -Fiber Roof Board.
Base Sheet: StormSafe"" Anchor Sheet is fastened to the plywood deck using Drill-Tec'" #12
Fasteners and 3" Drill-Tec' Accutrac® Flat Plates or Drill-Tec' AccuTrac,
Recessed Plates spaced 9" o.c. at the 4" side laps and 3 rows spaced 9" o.c. in the
field of the sheet.
Ply Sheet: One layer of Liberty`" SBS Self -Adhering Base/Ply Sheet self -adhered with
(Optional) minimum 3" wide laps and rolled with a weighted roller in accordance with
manufacturer's instructions.
Membrane: One layer of Liberty' SBS Self -Adhering Cap Sheet self -adhered with
minimum 4" wide laps and rolled with a weighted roller in accordance with
manufacturer's instructions.
Or
One or more layers of Ruberoid® SBS Heat -Weld"' 25, Ruberoid® SBS Heat -Weld""
Smooth, Ruberoid® SBS Heat -Weld' Granule, Ruberoid® SBS Heat -Weld' 170
FR, Ruberoid® SBS Heat-Wcld' Plus, Ruberoid® SBS Heat-Weld'Plus FR or
Ruberoid® EnergyCap ' SBS Heat -Weld' Plus FR heat welded in accordance with
manufacturer's instructions.
OR
Ruberoid® Torch Smooth, Tri-Ply® TP-4, Ruberoid® Torch Granule, Tri-Ply® TP-
4G, Ruberoid® Torch FR, Ruberoid® EnergyCap' Torch Plus FR or Ruberoid®
EnergyCap"' Torch Granule FR with minimum 3" wide laps and torch applied in
accordance with manufacturer's instructions.
Surfacing: Optional on granular surfaced membranes; required for smooth membranes.
Chosen components must be listed in a current NOA Approval and applied in
accordance with manufacturer's instructions.
.1. Gravel or slag applied at 400 Ibs:/sq. and 3001bs./sq. respectively in a flood coat of
approved asphalt at 60 lbs./sq.
2. GAFGLASI Mineral Surfaced Cap Sheet, Tri-Ply® Mineral Surfaced Cap Sheet or
GAFGLASO EnergyCap'" BUR Mineral Surfaced Cap Sheet adhered in a full mopping of
approved asphalt applied within the EVT range and at a rate of 2040 lbs./sq.
3. Topcoat' Membrane, Topcoat® MB Plus (to be used as a primer with Topcoat, Membrane)
- or Topcoat, Surface Seal SB applied at 1 to 1.5 gal./sq.
4. Fibered Aluminum Roof Coating.
Maximum Design
-Pressure: -60 psf. (See General Limitation # 7)
NOA No.: 16-1206.02
MIAMI-DADE COUNTY Expiration Date: 02/22/22
..., , Approval Date: 02/16/17
Page 17 of 18
WOOD DECK SYSTEM LIMITATIONS:
A slip sheet is required with GAFGLAS® Ply 4, Tri-Ply® Ply 4 and, GAFGLAS® F1exPly 6 when used as
a mechanically fastened base or anchor sheet..
GENERAL LIMITATIONS:
1. Fire classification is not part of this acceptance; refer to a current Approved Roofing Materials Directory
for fire ratings of this product.
2. Insulation may be installed in multiple layers. The first layer shall be attached in compliance with
Product Control Approval guidelines. All other layers shall be adhered in a full mopping of approved
asphalt applied within the EVT range and at a rate of 20-40 lbs./sq., or mechanically attached using the
fastening pattern of the top layer
3. All standard'panel sizes are acceptable for mechanical attachment. When applied in approved asphalt,
panel size shall be 4' z 4" maximum.
4. An overlay and/or recovery board insulation panel is required on all applications over closed cell foam
insulations when the base sheet is fully mopped. If no recovery board is used the base sheet shall be
applied using spot mopping with approved asphalt, 12" diameter circles, 24" o.c.; or strip mopped 8"
ribbons in three rows, one at each side lap and one down the center of the sheet allowing a continuous
area of ventilation. Encircling of the strips is not acceptable. A 6' break shall be placed every 12' in
each ribbon to allow cross ventilation. Asphalt application of either system shall be at a minimum rate of
12 lbs./sq. '
Note: Spot attached'systems shall be limited to a` maximum design pressure of 45 psf.
5. Fastener spacing for insulation attachment is based on a Minimum Characteristic Force (F') value of 275
lbf., as tested in compliance with Testing Application Standard TAS 105. If the fastener value, as field-
tested, are below 275 lbf. insulation attachment shall not be acceptable: '
6. Fastener spacing for mechanical attachment of anchor/base sheet or ni6nibrarie attachment is based on a
minimum fastener resistance value in conjunction with the maximum design value listed within a specific
system. Should the fastener'resistance be less than that required, as determined by the Building Official,
a revised fastener spacing, prepared, signed and sealed by a Florida Registered Engineer, Architect, or
Registered Roof Consultant may be submitted. Said revised fastener spacing shall utilize the withdrawal
resistance value taken from Testing Application Standards TAS 105 and calculations in compliance with
Roofing Application Standard RAS 117. .
7. Perimeter and corner areas shall comply with the enhanced uplift pressure requirements of these areas.
Fastener densities shall be increased for both insulation and base sheet as calculated in compliance with
Roofing Application Standard,RAS 117. Calculations prepared, signed and sealed by a Florida registered
Professional Engineer, Registered Architect, or Registered Roof Consultant (When this limitation is
specifically referred within this NOA, General Limitation #9 will not be applicable.)
8. All attachment and sizing of perimeter nailers, metal profile, and/or flashing termination designs shall
conform with Roofing Application Standard RAS 111 and applicable wind load requirements.
9. The maximum designed pressure limitation listed shall be applicable to all roof pressure zones (i.e. field,
perimeters, and comers). Neither rational analysis, nor extrapolation shall be permitted for enhanced
fastening at enhanced pressure zones (i.e. perimeters, extended comers and comers). (When this
limitation is specifically referred within this NOA, General Limitation #7 will not be applicable.)
10. All products listed herein shall have a quality assurance audit in accordance with the Florida Building
Code and Rule 61 G20-3 of the Florida Administrative Code.
END OF THIS ACCEPTANCE
NOA No.: 16-1206.02
MIAMI•DADE COUNTY Expiration Date: 02/22/22
... � , Approval Date: 02/16l17
Page 18 of 18