HomeMy WebLinkAboutFIELD WITHDRAWL RESISTANCE TEST RESULTSSCANNED TESTING APPLICATION STANDARD (TAS) No.105-11
BY
St. Lucie County APPENDIX TAS 105-A
FIELD WITHDRAWAL RESISTANCE TEST RESULTS
GENERAL INFORMATION:
Job Name: City of Fort Pierce - Facilities Administration Building
Job Address: 3071 Oleander Avenue
Job Site Contact:
Ft. Pierce, FL 34982
Therma Seal Roof Systems, LLC (561) 223-2096
TESTING AGENCY/EQUIPMENT INFORMATION:
Note: The undersigned acknowledges that all testing has been conducted and
results have been reported in compliance with TAS 105 Appendix T105-A
Testing Agency:
Address:
Telephone:
Fax:
Email:
Representative Name:
Title:
Cleary Inspection Services, Inc.
1017 North "H" Street
Lake Worth, FL 33460
(561) 722 - 9881
(561) 582 - 8039
clearyinspections@kcwand.com
Katherine I. Cleary
Inspector
Test Apparatus: COMTEN MODEL # DFG2W2000, SERIAL # 21710015
BUILDING/ROOF SYSTEM INFORMATION:
Approx.
Roof Area Height: Height: =
15 ft.
Roof Area Dimensions: Length: =
101 ft.
Second largest dim.: =
75 ft.
Total roof area: =
6141 ft 2
Perimeter width: =
6 ft.
Perimeter area: =
1572 ft.2
Corner area: =
528 R.2
Parapet Height: =
N/A ft.
FASTENER INSTALLATION INFORMATION:
Is the fastener a self driller? Yes
Tool: Rigid 18v 0-1800 rpm's
Fastener type: # 14
Fastener Manufacturer: OMG
TEST INFORMATION:
Test Date: 1/17/2018
Number of Test Conducted 20
*Note the Location of all tests on 'Building Information', attached.
FIELD WITHDRAWAL RESISTANCE TEST RECORDING SHEET
Deck:* See TAS 105-11 to determine number of tests Steel
i. i
City of Fort Pierce - Facilities Administration Building
3071 Oleander Avenue
Ft. Pierce, FL 34982
Cleary Inspection Service, Inc.
Tel. (561) 722-9881, Fax (561) 582-8039
Email: clearyinspections@kcwand.com
SAMPLE NO.
PLAN IDENTIFIER
INITIAL FAILURE
LOAD
FIELD
PERIMETER
CORNER
1
Tl
350
X
2
T2
295
X
3
T3
285
X
4
T4
350
X
5
T5
275
X
6
T6
250
X
7
T7
350
X
8
T8
315
X
9
T9
300
X
10
T10
290
X
11
T11
325
X
12
T12
285
X
13
T13
275
X
14
T14
295
X
15
T15
345
X
16
T16
305
X
17
T17
340
X
18
T18
295
X
19
T19
330
X
20
T20
325
X
Recommend steel deck be examined at test location #6 where a low reading of 250 lbs was measured.
STATISTICAL ANALYSIS:
No. of Tests
T Estimator
Mean Failure Load:
Sample Standard Deviation:
Minimum -Characteristic Resistance Force:
Sincerely,
Cleary Inspections Service, Inc.
at e- eI.
Miami -Dade Certification No. 16.0211.02
n =
20
t' =
2.093
F=
309lbf
SF=
28.61bf
F'=
295.61bf
eky- I8
R.N. Sailappan,
Florida Registration No. 46696
V
2
Cleary Inspection Service, Inc.
Telephone (561) 722-9881
Fax (561) 582-8039
Email: kc@kcwand.com
Notes:
1. Use of the results herein to determine the required number of
fasteners for insulation attachment or an acceptable anchor or base
sheet fastener spacing, as outlined in TAS 117, shall utilize the
minimum characteristic resistance for (F') determined in compliance
with Section 9 of TAS 105. No margin of safety shall be applied to
field withdrawal resistance test results determined in compliance with
TAS 105.
2. A safety factor of 2 to 1 shall be applied to all results of laboratory
testing.
3. The following pages shall be completed for each roof area and
included with all Field Withdrawal Resistance Test Recording Sheets.
ffti�,r °atfeFro..rt
,,,h; tlties Atlmlnise1t/ar1aP(7,t�lelo2rnc0U �eBdr
d.
, m.
g
070Aveuem3er� ort P;FL
T®e1sx
Roof Area Building and Parapet Heights.
(If no parapet exists, "N/A")
NIA
15,
Ground
Level
Page 3
N
31'
32'
T1
T2
T3
31'
T5
Canopy T6 '
11'
T8
Recommend that steel deck
be examine at test location
Ty ;
#T6, where a low resistance
of 250 Ibs was measured.
70' T11
T12
T13
T14
T15
T16
T17
T18
20'
32'
T10
Cleary Inspection Service, Inc.
Tel. (561) 722-988, Fax (561) 582-8039
Email: clearyinspections@kcwand.com
12'
T7
12'
11'
T19
Cnoy16'
11'
NOT DRAWN TO SCALE
Drawings & measurements are approximate representation of field layout
Page 4
CERTIFICATE OF CALIBRATION
TRACEABLE TO THE UNITED STATES NATIONAL INSTITUTE OF STANDARDS AND TECHNOLOGY
AND PERFORMED IN ACCORDANCE WITH IS010012-2003
THIS DEVICE IS CERTIFIED TO BE WITHIN +/- 0.5% OF FULL SCALE READING AT EACH TEST POINT AT
THE TIME OF SHIPMENT
CERTIFICATE NUMBER: 24634 CALIBRATION DATE: 10/1812017
PART AND CUSTOMER INFORMATION
MODEL* DFG2W2000 SERIAL#: 21710015
CUSTOMER: CLEARY INSPECTION SERVICE, INC. CUSTOMER #: CLE33460 i
CALIBRATION
APPLIED
VALUE
(LB)
DATA
EXPECTED I
VALUE
(LB)
11 RUN1
I I (LB)
AVERAGE
(LB)
FULL
SCALE
ERROR
0.00
0.00
-
i 0.000
0.000
0.000%
100.00
400.00
400.00
393.000
393.000
-0.350%
600.00
800.00
800.00
{
795.000
795.000
-0.250%
1000.00
1200.00
1200.00
1199.000
1199.000
-0.050%
1400.00
16D0.00
1600.00
f
1602.000
1602.000
0.100%
1800.00
2000.00
2000.00
I 2004.000
2004.000
0.200%
CALIBRATION EQUIPMENT USED
SERIAL #1: 11706016
CAL EQUIP:
COMTEN INDUSTRIES load cell CNR EA, SIN
CNR EA
11706016 was calibrated at ComTen Industries
following to ASTM E-74. The uncertainty is 2
CAL DATE:
Lbf. Report No: 20300
611212017
SERIAL #2:
THIS EQUIPMENT IS CERTIFIED TRACEABLE TO THE UNITED STATES NATIONAL INSTITUTE OF STANDARDS AND TECHNOLOGY.
CONDITIONS
TEMPERATURE 76*F
RELATIVE HUMIDITY: 30%
AS FOUND NOTES: ( * Indicates that the partwas out of tolerance)
VALIDATION
CALIBRATION
PERFORMED
BY: CC
Calibration not valid without CERTIFIED stamp and initials
6405-49th Street North, Pinellas Park, FL 33781-5724 * 727-520-1200 * FAX 727-520-0299
E-Mail: sales@com-ten.com * Web: www.com-ten.com