DESIGN CALCULATIONS
FOR
CORE S MAIN
WALL -MOUNTED SIGNS
7374 Commcercial Circle — Ft Pierce
GENERAL NOTES:
1. Design is in accordance with the Florida Building Code 6th Edition (2017)
for use within and outside the High Velocity Hurricane Zone (HVHZ).
2. Wind loads have been calculated per the requirements of ASCE 7-10 as
shown herein.
3. These engineering calculations pertain only to the structural integrity of
those systems, components, and/or other construction explicitly
specified herein and/or in accompanying engineering drawings. The
existing host structure (if any) is assumed to be in good condition,
capable of supporting the loaded system, subject to building department
approval. No warranty, either expressed or implied, is contained herein.
4. System components shall be as noted herein. All references to named
components and installation shall conform to manufacturer's or industry
specifications as summarized herein.
5. Where site conditions deviate from those noted herein, revisions may be
required or a separate site -specific engineering evaluation performed.
6. Aluminum components in contact with steel or embedded in concrete
shall be protected as prescribed in the 2015 Aluminum Design Manual,
Part 1. Steel components in contact with, but not encased in, concrete
shall be coated, painted, or otherwise protected against corrosion.
7. Engineer seal affixed hereto validates structural design as shown only.
Use of this specification by contractor, et. Al, indemnifies and saves
harmless this engineer for all costs & damages including legal fees &
apellate fees resulting from deviation from this design.
Index:
Pg 1 Cover
Pg 2 Wind Loads
Pg 3 Anchor Design
Engineer's signature and seal valid
.Po�npages 1'througlt`�
• .L
No.6738� °
� •° 5- ATE OF
=�0� . F c 28 c�
Chrlsfiaq;[41 9 V. • ct'a OE ff 67382
Easy SealS „,, ; , Cd Auth ft 31124
Federal Hwy, 71200 Easy Seals.com Page 1
Bocaoca Raton, FL 33432
Seats
i evyual m
Wall Sign Anchor Design
Structure Dimensions & Loading
Design wind pressure:
Sign type
Sign size
CALCULATIONS IR WALL -MOUNTED SIGNS
P = 46.0 psf
Cabinet
A= 60.9 sgft (entire cabinet)
Wall material: Wood CDX or equiv, thickness to match Min Embed
Anchor type/size: 3/8" Toggle Bolt (r)
Ref: Powers Strap -Toggle, catalog
Min Embedment: 0.5"
Min edge dist: 3" Min Spacing: 1.5"
Anchor tensile capacity: Tcap = 179.4 lb (per anchor)
Check Anchors for Pullout
Total Reaction: Rt = 2799 lb ... = P"A (entire cabinet)
No. of anchors req'd: n = 15.6 total anchors ...= Rt/cap
Total anchors required: 16 total anchors balanced over cabinet
OK, typical anchor option shown.
Ref anchor schedule for other anchor options.