Loading...
HomeMy WebLinkAboutCALCULATIONS1 � easyseals.com DESIGN CALCULATIONS FOR CORE S MAIN WALL -MOUNTED SIGNS 7374 Commcercial Circle — Ft Pierce GENERAL NOTES: 1. Design is in accordance with the Florida Building Code 6th Edition (2017) for use within and outside the High Velocity Hurricane Zone (HVHZ). 2. Wind loads have been calculated per the requirements of ASCE 7-10 as shown herein. 3. These engineering calculations pertain only to the structural integrity of those systems, components, and/or other construction explicitly specified herein and/or in accompanying engineering drawings. The existing host structure (if any) is assumed to be in good condition, capable of supporting the loaded system, subject to building department approval. No warranty, either expressed or implied, is contained herein. 4. System components shall be as noted herein. All references to named components and installation shall conform to manufacturer's or industry specifications as summarized herein. 5. Where site conditions deviate from those noted herein, revisions may be required or a separate site -specific engineering evaluation performed. 6. Aluminum components in contact with steel or embedded in concrete shall be protected as prescribed in the 2015 Aluminum Design Manual, Part 1. Steel components in contact with, but not encased in, concrete shall be coated, painted, or otherwise protected against corrosion. 7. Engineer seal affixed hereto validates structural design as shown only. Use of this specification by contractor, et. Al, indemnifies and saves harmless this engineer for all costs & damages including legal fees & apellate fees resulting from deviation from this design. Index: Pg 1 Cover Pg 2 Wind Loads Pg 3 Anchor Design Engineer's signature and seal valid .Po�npages 1'througlt`� • .L No.6738� ° � •° 5- ATE OF =�0� . F c 28 c� Chrlsfiaq;[41 9 V. • ct'a OE ff 67382 Easy SealS „,, ; , Cd Auth ft 31124 Federal Hwy, 71200 Easy Seals.com Page 1 Bocaoca Raton, FL 33432 Seats i evyual m Wall Sign Anchor Design Structure Dimensions & Loading Design wind pressure: Sign type Sign size CALCULATIONS IR WALL -MOUNTED SIGNS P = 46.0 psf Cabinet A= 60.9 sgft (entire cabinet) Wall material: Wood CDX or equiv, thickness to match Min Embed Anchor type/size: 3/8" Toggle Bolt (r) Ref: Powers Strap -Toggle, catalog Min Embedment: 0.5" Min edge dist: 3" Min Spacing: 1.5" Anchor tensile capacity: Tcap = 179.4 lb (per anchor) Check Anchors for Pullout Total Reaction: Rt = 2799 lb ... = P"A (entire cabinet) No. of anchors req'd: n = 15.6 total anchors ...= Rt/cap Total anchors required: 16 total anchors balanced over cabinet OK, typical anchor option shown. Ref anchor schedule for other anchor options. Page 3