TESTING -ADJUSTING -BALANCING
TESTING, ADJUSTING & BALANCING REPORT
for
STAN WEEKS & ASSOCIATES
EDWARDS LANDING
BUILDING 14 —
X96, 3188, MOO, 319$ MM, 3196 MOMIH-gDOWLane
FortPlerce, FL 34982
RECEIVED
JUL 15 2019
Permitting Department
St. Lucie County, FL
July 9, 2019
+++ALL BALANCING WORK PERFORMED IN ACCORDANCE WITH NCI STANDARDS AND PROCEDURES..
��CeKI(Ied�CAPPR
C)VEL)
BPI
Pro -Duct Services, 1915 Rio Vista Rit Fort Pierce, FL 34949
772.528.2076 pro-ductservicesfl@gmaii.com
A
�
,
y
�
K
m
�
� d
�
�
�
�
�
�
�
z
"�4_2rt4k
PRO -DUCT
SERVICES
BLOWERDOOR& DUCTLEAKAGETESTING
TESTING -ADJUSTING -BALANCING
TEST & BALANCE INSTRUMENTS
Evergreen Telemetry Capture Hood 15D:
Range: 100-2500 CFM
Accuracy: +/- 3%
Calibration: May 17, 2019
Evergreen Telemetry Capture Hood 813-14:
Range: 15-200 CFM
Accuracy: +/- 3%
Calibration: May 29, 2019
Evergreen Pressure/Velocity/Flow Sensing Module —Model S-PVF-1:
Range: 1-2, 14-32 inches HG, 32° - 158° F
Accuracy: +/- 3%
Calibration: June 5, 2019
Evergreen Wrist Reporter WR-401
Pro -Duct Services Technician:
Michael Faurot
Certified -NCI Contractor/Supervisor/Technician
NCI Commercial Certification ID: 19-229-03
— Equipment re -calibration is performed as required by testing guidelines. —
Pro -Duct Services, 1915 Rio Vista Rd, Fort Pierce, FL 34949
772.528.2076 pro-ductservicesJl@gmail.com
I
MICHAEL FAUROT
Has successfully completed the required training and passed
the written exam by the
Notf o� cou(ort ['solute, Ivor
to perform HVAC commercial system balancing up to 20 tons
according to NO practical standards and procedures.
R1fo Certified Since
►� . �d%&
May9,2019
Certifieas administered and recognized by
tamnmrlY/h2u4Ttf r�i!
Gar11ff9�3 i�
Egia�:wQOtt
��mm�ssO' na +�++b+++++■ .++� Rob Falke, President
Pro -Duct Services, 1915 Rio Vista At Fort Pierce, FL 34949
772.528.2076 pro-ductservicesjl@gmail.com
",4_244k
PRO -DUCT
SERVICES
BLOWERDOOR&DUCTLEAKAGETESTING
TESTING -ADJUSTING -BALANCING
AIR OUTLET CHARACTERIZATION
for
STAN WEEKS & ASSOCIATES
Edwards Landing —BUILDING 14
3186 Morning Dew Lane, Fort Pierce, FL 34982
Description
Outlet
Number
Type
file
Design
CFM
Pre Test
CFM
FINAL
CFM
Entrance
1
CD
8 x 4
30
32
35
Kitchen/Living Rm
2
CD
30 x 10
160
183
175
Bathroom
3
CD
8 x 4
15
31
30
Bedroom 1
4
CD
12 x 8
180
180
180
Bedroom 2 Vent 1
5
CD
10 x 10
125
112
115
Bedroom 2 Vent 2
6
CD
10 x 10
225
113
122
TOTAL
635
657
Mechanical components working as designed and match plan
COMMENTS requirements.
+++ ALL BALANCING WORK PERFORMED IN ACCORDANCE WITH NCI STANDARDS AND PROCEDURES if i
Pro -Duct Services, 1915 Rio Vista Rd, Fort Pierce, FL 34949
772.528.2076 pro-ductservicesflQagmail.com
63
Yi
PRO -DUCT
SERVICES
BLOWERDOOR & DUCTLEAKAGETESTING
TESTING -ADJUSTING -BALANCING
AIR OUTLET CHARACTERIZATION
for
STAN WEEKS & ASSOCIATES
Edwards Landing —BUILDING 14
3188 Morning Dew Lane, Fort Pierce, FL 34982
Description
Outlet
Number
Type
file
Design
CFM
Pro Test
CFM
FINAL
CFM
Entrance
1
CD
8 x 4
30
35
35
Kitchen/Living Rm
2
CD
10 x 30
160
.170
175
Bathroom
3
CD
8 x 4
i5
30
22
Bedroom 1
4
CD
12 x 8
280
167
170
Bedroom 2 Vent 1
5
CD
30 x 30
125
119
119
Bedroom 2 Vent 2
6
CD
30 x 10
125
119
117
TOTAL
635
638
FAN DATA Panasonic_Whispergreen Model_.EV-05-11USK1 Vent Fan___
Mechanical components working as designed and match plan
COMMENTS requirements.
+++ ALL BALANCING WORK PERFORMED IN ACCORDANCE WITH NCI STANDARDS AND PROCEDURES+++
Pro -Duct Services, 1915 Rio Vista Rd, Fort Pierce, FL 34949
772.528.2076 pro-ductservicesJl@gmailcom
•
y{
s
t
v
g
� Ify
t
f ✓)
f P
i
..,
i t
.�
r Sl �
•+
Lm
4
Y
y
MEN "�4_v,4k
PRO -DUCT
SERVICES
BLOWERDOOR&DUCTLEAKAGETESTING
TESTING -ADJUSTING -BALANCING
AIR OUTLET CHARACTERIZATION
for
STAN WEEKS & ASSOCIATES
Edwards Landing —BUILDING 14
3190 Morning Dew Lane, Fort Pierce, FL 34982
Description
Outiet
Number
Type
Size
Design
CFM
Dee Test
CFM
FINAL
CFM
Entrance
1
CD
8 x 4
30
32
32
Kitchen/Living Rm
2
CD
10 x 10
160
189
162
Bathroom
3
CD
8 x 4
15
37
30
Bedroom 1
4
CD
12 x 8
180
174
.174
Bedroom 2 Vent 1
5
CD
10 x 30
125
112
121
Bedroom 2 Vent 2
6
CD
10 x 10
125
110
118
TOTAL
635
637
Mechanical components working as designed and match plan -
COMMENTS requirements.
+++ ALL BALANCING WORK PERFORMED IN ACCORDANCE WITH NCI STANDARDS AND PROCEDURES...
Pro -Duct Services, 1915 Rio Vista Rd, Fort Pierce, FL 34949
772.528.2076 pro-ductservicesj!@gmaii.com
, A
1� J,
It
a
",4_e04,k
PRO-OUCT
SERVICES
BLOWERDOOR&DUCTLEAKAGETESTING
TESTING -ADJUSTING -BALANCING
AIR OUTLET CHARACTERIZATION
for
STAN WEEKS & ASSOCIATES
Edwards Landing —BUILDING 14
3192 Morning Dew Lane, Fort Pierce, FL 34982
Description
Outlet
Number
Type
Size
Design
CFM
Pre Test
CFM
FINAL
CFM
Entrance
i
CD
8 x 4
30
41
38
Kitchen/Living Rm
2
CD
10 x 30
160
162
162
Bathroom
3
CD
8 x 4
15
30
27
Bedroom 1
4
CD
12 x 8
180
179
179
Bedroom 2 Vent 1
5
CD
10 x 10
125
113
118
Bedroom 2 Vent 2
6
CD
10 x 10
125
110
117
TOTAL
635
641
FAN DATA
Mechanical components working as -designed and -match plan
COMMENTS requirements.
+++ ALL BALANCING WORK PERFORMED IN ACCORDANCE WITH NCI STANDARDS AND PROCEDURES +++
Pro -Duct Services, 1915 Rio Vista Rd, Fort Pierce, FL 34949
772.528.2076 pro-ductservicesfl@gmail.com
4
v
Y
u
P , e
mi
ii
s
a
a b
'
Lj
F
Y
,
3
k
A
'x
r
x
,
ni.
ZIA
s:
vY
y
f"
rvx
m Y
;y
,y
n
a
�4zrp,
%4±
ti;i
n
PRO -DUCT
SERVICES
BLOWERDOOR&DUCTLEAKAOETESTINO
TESTING -ADJUSTING -BALANCING
AIR OUTLET CHARACTERIZATION
for
STAN WEEKS & ASSOCIATES
Edwards Landing —BUILDING 14
3194 Morning Dew Lane, Fort Pierce, FL 34982
Description
Outlet
Number
Type
file
Design
CFM
Pre Test
CFM
FINAL
CFM
Entrance
1
CD
8 x 4
30
42
38
Kitchen/Living Rm
2
CD
30 x 10
160
180
170
Bathroom
3
CD
8 x 4
15
35
35
Bedroom 1
4
CD
12 x 8
180
175
179
Bedroom 2 Vent 1
5
CD
10 x 10
125
117
117
Bedroom 2 Vent 2
6
CD
30 x 30
125
119
120
TOTAL
635
659
FAN DATA Panasonic Whispergreen Model FV-05-11USK1 Vent Fan _
Mechanical components working as designed and match plan
COMMENTS requirements. ,
+++ ALL BALANCING, WORK PERFORMED IN ACCORDANCE WITH NCI STANDARDS AND PROCEDURES ; # i
Pro -Duct Services, 1915 Rio Vista Rd Fort Pierce FL 34949
772.528.2076 pro-ductservicesJl@gmail.com
',;
-�
��
,
B
Y
,
S
�
S
� A �
Fm
'
t
d � ti
t
!
9 i
Y
•
a
�
�`
�
i
i
i
1
�� 1 �� i
7
�
+ r
S
s
4 � ..
.�-��
��:a
. �
'.'
i�..r�
'mod
— ..
�
-
.. i.�.-._�.-.,.3.. -..,j. _ 7
K
-�
��
b
Y
�
�''
Y
P�
i
�'r�
'
�
t
�
ti
'-
.,
.�
y �
� s
�
v
�
�
1
r
. �
t
d{ � �
r
..
ni't
.:
�,, . r , y
1.4
�
'
�
'3
Sr M,'
�
r �
h-.�...
. �
..je
1 1 s
.��.^? .�.� y'. x ..0..a. ..n
-i
err
v
� ..
'
.
Y �
�
a
. Y.
:x
��i
p�
� ..
..
i
v i
5
y
S '
t.
�
K._
rs
ii
n, i s
.��
'
'
i
'�
t
4
8
1 ,
.s
�
_
,-
r
k
� '
'
- ,
Q '-
..
�
�a
..,
a
C
(.
Y
� �
� 'i
r
t
... P
�
5
j
-
t
�
� U. f
� . �
_
4 �
PRO -DUCT
SERVICES
BLOWERDOOR&DUCTLEAKAGETESTING
TESTING -ADJUSTING -BALANCING
AIR OUTLET CHARACTERIZATION
for
STAN WEEKS & ASSOCIATES
Edwards Landing —BUILDING 14
3196 Morning Dew Lane, Fort Pierce, FL 34982
Description
Outlet
Number
Type
file
Design
CFM
Pre Test
CFM
FINAL
CFM
Entrance
i
CD
8 x 4
30
37
37
Kitchen/Living Rm
2
CD
10 x 30
160
161
161
Bathroom
3
CD
8 x 4
15
28
28
Bedroom 1
4
CD
12 x 8
180
176
176
Bedroom 2 Vent 1
5
CD
10 x 10
125
112
119
Bedroom 2 Vent 2
6
CD
30 x 30
125
114
124
TOTAL
635
645
FAN DATA Panasonic Whispergreen Model FV-05-11USK1 Vent Fan_
Mechanical components working as designed and match plan
COMMENTS requirements.
+++ ALL BALANCING WORK PERFORMED IN ACCORDANCE WITH NCI STANDARDS AND PROCEDURES...
Pro -Duct Services, 1915 Rio Vista R4 Fort Pierce, FL 34949
772.528.2076 pro-ductservicesfl@gmail.com
oil
OV
4
0
IT
I
I IT YI
'v
z a
8.4
PRO_ -DUCT
SERVICES
BLOWERDOOR& DUCT LEAKAGETESTING
TESTING -ADJUSTING -BALANCING
TESTING, ADJUSTING, & BALANCING WARRANTY
for
Don Weeks & Associates
Edwards Landing —BUILDING 14
All Testing, Adjusting, & Balancing performed on this project by Pro -Duct Services is under
warranty for a period of One Year from the date of completion of the Test & Balance, unless
otherwise noted. Warranty will be considered null and void if another TAB company is
brought in to evaluate the project without notifying Pro -Duct Services to be present at the
time of the additional testing.
Date of TAB Testing: 7/8/2019 Warranty Expiration Date: 7/31/2020
Pro -Duct Services Authorized Signature:
Pro -Duct Services Technician: Michael Faurot
Certified NCI Contractor/Supervisor/Technician
NCI Commercial Certification ID: 19-229-03
BPI Certification ID: 5059122
... ALL BALANCING WORK PERFORMED IN ACCORDANCE WITH NCI STANDARDS AND PROCEDURES...
Pro -Duct Services, 1915 Rio Vista R t Fort Pierce, FL 34949
772.528.2076 pro-ductservicesfl@gmail.com
71,
Ir
PRO -DUCT
SERVICES
BLOWERDOOR& DUCT LEAKAGETESTING
TESTING -ADJ U STI N G- BALAN C I N G
Pro -Duct Services, 1915 Rio Vista Rd, Fort Pierce, FL 34949
771.52&2076 pro-ductservicesJl@gmaii.com
Zip
41