HomeMy WebLinkAboutCALCULATIONSUNITED REFRIGERATION INC. Trenton Refrigeration Products 11401 Roosevelt Boulevard Philadelphia, Pennsylvania USA, 19154 Contact Name: Telephone: (215) 698-9100 Ext Fax:(215)-673.5411 Email: Internet: wwwhentonrefrigeration.00m JOB INFO Reference: Description: Ambient Temp: 90 °F Box Temp: 35 °F Box Location Indoors WALLLOAD trgleERp1/� ARE- TO t. 4ll `` t T:If ' 0 j1 t RECEIVED FEB 2 2 2018 ST. Lucie County, Permitting Length: 10 It Width: 6 it Height 8 It System Run -Time: hrs See tleteils onpaga 2. _ Total Wall Load: t 1272 BTUa1 PRODUCTLOAD See details on page 2. Total Product Load: 1 676 BTUrh INFILTRATION LOAD Average Infiltrating Air Temperature. ESTIMATED INFILTRATION Usage Heavy Infiltration Load 1: 2721 BTUIh ESTIMATED BY DOOR OPENINGS. Number Of Doors: i Average Door Width: 3 ft Average Door Height - 6 ft Hours Open Per 24 Hours: 1 his Ventilation RH: 55 % Infiltration Load 2: 1070. BTUrh ESTIMATED BY VENTILATION RATE Ventilation Rate: 0 cfm _ Ventilation. RH: 55 % - - Infiltration Load-3: —_ -----. - -0 -- -BTUfn Number Of Giass Doors: 0 Load: 0 eTUfP. -" - - Number Of Dock Dons: 0 Load: 0 BTUh Total Infiltration Load: 2721 j BTUrh Estimated from volume and temperatures. CUSTOMER INFO RECEIVED FEB 2 2 2018 ST, Lucie County, Permitting Telephone: Fax: Contact Ext E-Mail: MISCELLANEOUS LOAD LIGHTING 1 Wisq.ft. 60 W 24 his MOTORS 1 0.05 Hp 24 his PERSONNEL 0 0 his FORKLIFTS OTHER LOADS 0 W 0 hrs 0 W 0 hrs a W 0 his Total Miscellaneous Load: 84�J BTUIn REQUIREMENT SUMMARY Load Requirement+ 10 %; 5957 BTUIh i Cond. UnitAmb: 105 °F Bar Temp: 35 °F Design TO: 10 °F Refrigerant Type: R-404AI R-507 Cond. Unit Location: Outdoors CONDENSING UNIT SELECTION Number Of Condensing Units: Condensing Unit Type: °F UNIT COOLER SELECTION Number of Unit Coolers: Unit Cooler (Evaporator) Type: Low Profile -TLP Unit Cooler Voltage: 115I 1 160 Unit Cooler Model No: TLP107MASlB 6861 BTUIh SYSTEM BALANCE Total System Capacity: i 6833 BTU/h TD: I 10 °F S.S.T.: Equipment selection Is sized to meet capacity requirement solely from data and conditions provided by the user Copyright@2013 National Refrigeration -All rights reserved. Page 1 of 2 V2512010 2:29:12 PM Page 2 of 2 -• Reference: 1e ®1 ! ltl I l ksY Description: I ***MOOD � i WALLLOAD SHAPE Rectangular 3 4I Volume: 480 K' 2 Total Wall Load: ---- 1272 ! i BTU/1 Type Length Height! Section Thickness Insulation K- Factor Extemal i Wall Load Temp Width Area -F j BTU/h it ft fP in 1 Wall 10 8 80 4 Urethane (aid panels) 0.14 90 231 90 231 j 2 I Wall 10 8 80 4 Urethane (std panels) 0.14 0.14 90 138 3 I Wall 6 8 48 4 4 Urethane (std panels) Urethane (std panels) 0.14 90 138 i 4 Wall 6 10 8 6 48 60 6 Poured Concrete (sand 8: gravel) 12 360 66 173 5 6 i Floor Ceiling 10 6 60 4 Urethane (std panels) 0.14 90 nn I �rpduct �'Pe Weight Enuring Final Temp I Temo Pull-DomeTpc. Time Heat I Product . elow `Load Ib 'F . I °F 15 him 24 0.96 !b. BTUIh 0.48 676 Produce, Vegetables Lebucer rceoery i Total Product Weight: 660 b Total Product Load 676 i BTUin 11251,2018 2:29:12 Ptd