January 26, 2018
Work Prepared For:
Folding Shutter Corp. 1f;uno0
7089 Hemstreet Place A e IS
West Palm Beach, FL 33413 Q_RN
Regarding: Atrium on the Ocean
2900 N Hwy Al A
Hutchinson Island, FL 34949
Attention: Building Department Official
This office is the engineering evaluator of record for the Titan II Folding Shutter by Folding
Shutter Corp. (Florida Statewide Product Approval #FL7080.1-R2). We have been asked to
review the applicability for the above project of installing the product using Yd' stainless steel
CreteFlex (Elco) anchors into 3350 psi minimum concrete, with 2-1/2" minimum edge distance.
Anchor spacing shall be based on the following anchor schedule (Table 1). These anchors
shall be spaced as shown in the anchor schedule below for the maximum slat spans, wind loads
(provided per separate engineering), and connection types as indicated herein. Connection types
are depicted in Figure 1 on the following pages.
Please be advised that all information herein has been provided to us by our client and no
field investigation or verification of the applicability of the product, substrate, or requested spacing
has been performed. As a result, all information provided herein shall be verified by a qualified
professional on -site prior to construction. This information has been obtained by design only.
Except as expressly provided herein, no additional certifications or affirmations are intended. All
design criteria shall follow the product approval and engineering drawings noted above, as well as
the minimum requirements of the Florida Building Code sixth edition (2017). Thank you for your
attention to this matter.
N0/''',,
Respectfully, ; ���..•yoiao�y•SS�y,
30 31VIS
m cc
03d ON -77
Frank L. B , .6
ENGINEERIN>3� �•�,
#PI 0046549 1 Ce'tr ��88�
0I111i111I
10-FSC-0016
VENUE, SUITE 106, DEERFIELD BEACH, FLORIDA 33442
(954)354-0660
ENGINEERINGEXPRESS.COM
..n,�.1.11eM.�� �,E.�re� «,pa'P.. 1 of I
ENGINEEF':-j'G
l EXPRESS
Atrium on the Ocean
Table 1: Anchor Schedule
/luno0 a/on7
A8
03NNVOS
Page 2 of 3
105" Maximum Slat Span
Anchor Embedment Depth
Wind Loads, as provided by engineering
previously provided
Connection Type
C1
C2
1"
Interior Zone 4 ±57.4 psf
3.4"
5.1"
Exterior Zone 5 ±98.3 psf
1-1/2" '
Interior Zone 4 ±57.4 psf
8.1"
11.5"
Exterior Zone 5 ±98.3 psf
4.7"
6.6"
1-3/4"
Interior Zone 4 ±57.4 psf
10.4"
12.0"
Exterior Zone 5 ±98.3 psf
6.1"
1 8.4"
2"
Interior Zone 4 ±57.4 psf
10.6"
12.0"
Exterior Zone 5 ±98.3 psf
6.2"
8.6"
118" Maximum Slat Span
Anchor Embedment Depth
Wind Loads, as provided by separate
engineering
Connection Type
C1
C2
1"
Interior Zone 4 ±57.4 psf
3.0"
4.5"
Exterior Zone 5 ±98.3 psf
Interior Zone 4 ±57.4 psf
7.2"
10.2"
Exterior Zone 5 ±98.3 psf
4.2"
5.8"
1-3/4"
Interior Zone 4 ±57.4 psf
9.3"
12.0"
Exterior Zone 5 ±98.3 psf
5.4"
7.4"
2"
Interior Zone 4 ±57.4 psf
9.4"
12.0"
Exterior Zone 5 ±98.3 psf
5.5"
7.6"
*Note: Anchor capacities for 1" and 1-1/2" embedment obtained from Miami -Dade Notice of
Acceptance #13-0219.02 (by this engineer) and test reports #CTC 99-008, CTC 98-038, and
HETI 98-3023. Capacities for 1-1/2" embedment interpolated from above -referenced NOA. All
other anchor capacities obtained from current manufacturer published data, based on test report
HETI-98-3023, as stated by manufacturer:
160 SW 12T" AVENUE, SUITE 106, DEERFIELD BEACH, FLORIDA 3
(954) 354-0660
ENGIN EERINGEx PRESS. COM
smra�nr�xanw¢xunenwiavupom�omr�oaecm�e�rwuuox TMe«rwr�evu�mmn�remmm�sm�w:cmiemnru�rore mvcw cwrmca
, ENGINEEF'l_,11!13
EXPRESS®
Page 3 of 3
Atrium on the Ocean
%" x 1 WOME IEFLEX TAPCON 410 SS
OR
'%" x 1 Y"CAE )EFLEX TAPCON 410 SS C
TOR
%" x 2%"CRE IEFLEX TAPCON 410 SS
INTOCONCREIF
.
D-
P a,
/
�'W x 1 '/"CRE IEFCEX TAPCON 410 SS
_ - �+Z
OR—
W x 1 Y"CRE IEFLEX TAPCON 410 SS
OR
W x 2'/"CRE IEFLEX TAPCON 410 SS
INTO CONCREIf
Figure 1: Trap Mount Condition