HomeMy WebLinkAboutPLAN1 SETUP AND INSTALLATION OF SINGLE WIDE SHED 1. BUILDING IS PLACED IN REQUESTED LOCATION ON SCHEDULE 40 PVC TO ALLOW FOR MOVEMENT TO PLUM OR SQUARE UNIT TO HOUSE, FENCE, PROPERTY LINE, ETC. 2. ONCE UNIT IS SQUARE AND THE HIGH SPOT OF THE GROUND IS ESTABLISHED, THE BUILDING -OS BLOCKED ON THE HIGH SPOT AND LEVELED. THE OTHER END OF THE BUILDING IS BROUGHT UP TO LEVEL AND BLOCKED. THEN THE CENTER OF THE BUILDING ISP SUPPORTED TO LEVEL, BLOCKED. AND THEN SHIMMED. 3. AFTER THE BUILDING IS LEVEL, MORE BLOCKS ARE ADDED TO ACHIEVE THE CORRECT SPACING (SEE TABLE 3). 4. ANCHOR PLACEMENT IS ESTABLISHED BY THE WIDTH OF THE BUILDING. HOLES ARE DRILLED THRU THE 2"x4" BOTTOM PLATE WITH A 1/2" AUGER BIT. 1/2" EYEBOLT OR OPTIONAL 1/2" THREADED ROD (FOR A "HIGH SET") IS SECURED THRU THE HOLE. 5. ANCHORS ARE NOT REQUIRED IN THE BOTTOM PLATE FOR DOORS AND DOORWAYS WITH NO FOOTER (GARAGE DOORS FOR EXAMPLE). HEADER DESIGN TRANSFERS THESE LOADS. .6. IF THE .UNIT HAS A FLOOR, EITHER A HOLE IS DUG FOR THE 30" AUGER ANCHOR AND SACKFILLED AND SECURED AS PER THE DETAIL OR A 1/2" HOLE IS DRILLED INTO THE CONCRETE 1-1/2" OFF OF RIM JOIST. THE EYEBOLT IS FASTENED THRU THE BOTTOM PLATE AND A SIMPSON A-24 (OR EQUAL) IS SECURED TO THE CONCRETE WITH A 1/2" 7. IF THE UNIT IS A 'NO FLOOR' OPTION, ANCHOR WITH 1/2"x5" WEDGE ANCHOR THRU THE 2"x4" BOTTOM PLATE. TABLE 1 ANCHORING TO CONCRETE SHED WIDTH UPUFT (PLF) ANCHOR SPACING 20'-0" 400 S-6" 13'-8" 280 S-6" 11'-8" 240 V6" 10'-0" 200 S -6" 8,-0" 160 S-8" 6'-0" 120 S-6" TABLE 2 SKID RUNNER SPACING* SHED WIDTH X1 X2 X3 13'-8" P-103" 1'-1C3" I V-8" 2'-8" 6'-4" - 10'-0" P-7" C-10" - 8'-0" 0'-9" C-6" - 6'-0" 0'-10" 51" - -VALUES ARE FROM END OF JOIST TO CENTERS OF (2) 4'x4" SKIpB ONLY. 8' WIDE SHEDS HAVE (4) SETS OF SKIDS. SETUP AND INSTALLATION OF _JBLE WIDE SHED 1. BUILDING IS PLACED IN REQUESTED LOCATION. THE FIRST SECTION OF THE DOUBLE WIDE IS PLACED ON THE HIGHEST LOCATION OF GROUND AND IS LEVELED UP. 2. BLOCKS ARE THEN PLACED AT THE END, CENTER, AND OTHER END TO LEVEL. ONCE THE BUILDING IS LEVEL, BLOCKS ARE ADDED TO ACHIEVE THE CORRECT SPACING (SEE TABLE 3). 3. THE NEXT SECTION OF THE SHED IS BACKED INTO PLACE AND UNLOADED PARALLEL WITH THE FIRST SECTION. THE TWO SECTIONS ARE CONNECTED AT THE LOWER CORNER WITH (1)4"x44" BOLT AND NUT. THE SECOND SECTION IS THEN LEVELED AND THE OTHER BOLT HOLES ARE LINED UP AND BOLTED SECURE. THE REST OF THE BLOCKING IS THEN COMPLETED. THIS PROCEDURE IS REPEATED FOR MULTIPLE SECTION SHEDS UNTIL ALL SECTIONS ARE IN PLACE. 4. GROUND ANCHORS ARE THEN ADDED (SEE TABLE 4B). 5. ONCE THE BUILDING IS PROPERLY BLOCKED AND BOLTED TOGETHER, THE SUPPORT BRACING IS REMOVED. 6. ANCHORS ARE NOT REQUIRED IN THE BCRMIITE DOMNNOO Y�Wf,T„H NO _TOOTER (GARAGE DOORS FOR EXAMPL R N ��ittAANN143 I��PPy�p66 TABLE 3A PAD TYPES TYPE PAD DIMENSIONS MAX. LOAD' MATERIAL I 2"X8"x16" 1778LBS CONCRETE BLOCK QUALITY CEMENT AND SAND MIX p 4'X8"x16" 3500LBS CONCRETE BLOCK QUALITY CEMENT AND SAND MIX III 16"x16" 3950LBS ABS PLASTIC PADS IV B"X8"x16" 1900LBS CONCRETE BLOCK QUALITY CEMENT AND SAND MIX • BASED ON 2000PSF SOIL BEARING CAPACITY (2000PSF IS TYPICAL) NOTES 1. HOLLOW OR SOLID CONCRETE BLOCKS (8'x8'x16") MAY SE STACKED ON PADS FOR HIGH SETS UP TO 48' WITHOUT REINFORCING. 2. ADS PADS REQUIRED ON 11'-B" AND 13'-8' WIDE SHEDS ONLY. TABLE 3 SUPPORT FOOTING PAD SPACING FOR RUNNER BLOCKING FOR SINGLE & DOUBLE WIDE SHEDS SHED DESCRIPTION PAD MAXIMUM LOAD AND PAD TYPE SHED WIDTH TYPE LW-(PLF) END PAD MAX. SPACING END PAD SIDE RUNNER PAD TYPE INTERIOR PAD SIDE RUNNER PAD TYPE 13'-8" SW/DW 4.15/332 0" TO 6" 6'-0' 1936LB I, 11, III, OR IV 1879LB I, 11. 111. OR N 11'-8" SW/DW 5.00/480 0" TO 6" 6'-0" 2558LB I, II, III, OR IV 2558LB 1, II, Ill, OR N 10'-0" SW/DW 5.00/400 0• TO 6" 6'-0" 2400LB 1, 11, III, OR IV 2400LB I, 11. Ill, OR IV 8'-0' SW 4.00/320 O" TO C 6'-0" 2029LB 1, II, III, OR IV 2133L8 I, II, III, OR IV 6'-0" SW 3.00/240 0' TO 6" 6'-0' 1658LB I, 11, III, OR N 1866LB I, II, III, OR IV " LOAD WIDTH OF UPLIFT ON RUNNER NOTES 1. PAD SPACING IS END TO CENTER OF PAD. 2. PADS OTHER THAN END PADS SPACING IS CENTER TO CENTER. 3. USE SAME MAXIMUM SPACING FOR INTERIOR SPACING. SCANNED BY St. Lucie County 1. BUILDING ANCHORS SHALL BE "MOBILE HOME" TYPE HP-1 SINGLE HELIX EYE AUGER ANCHOR BY HOME PRIDE OF BRISTOL, VA. OR EQUAL. AVERAGE HOLDING STRENGTH IS NOT LESS THAN 4,900 LBS. 2. ANCHORING SYSTEM TO GROUND PER LOCAL BUILDING CODE (BY DEALER). LOCATE ANCHORS PER TABLE 4A OR 4B. 3. THREADED ROD WITH EYEBOLTS SHALL BE PLACED THRU THE BOTTOM PLATE (FLOOR SYSTEM) AND ATTACHED TO ANCHOR. TABLE 4A 30" AUGER ANCHOR SPACING - SINGLE WIDE SHED WIDTH LW" UPLIFT (PLF) END ANCHOR•" MAX. INTERIOR SPACING*" 13'-8" 7.00 243 0'-0" TO's-O" 10'-0" 11'-8" 6.00 208 0-0" To 3' 0" 10'-0" E1;0;=0 :_-5100i -174-'_ 0-0"'TO-3`-0:­ 8'-0" 4.00 138 U-0" TO 3'-0" 10'-0' 6'-0" 3.00 104 0•-0" TO S-0" 10'-0" TABLE B 30" AUGER ANCHOR SPACING - DOUBLE WIDE SHED WIDTH LW' UPLIFT (PLF) END ANCHOR"" MAX. INTERIOR SPACING••" 20'-0" 1 10.00 400 - 6-0" TO S-0" 5'-0" • LOAD WIDTH OF UPLIFT ON RUNNER LOCATION FROM END WALL OF AUGER ANCHOR ••• MAXIMUM SPACING BETWEEN ANCHORS 1..QANCH 1OR SPACING IS DESIGNED AS PER ASCE-7. 2. ALL MEASUREMENTS ARE CENTER -TO -CENTER. 3. THE MINIMUM NUMBER OF.ANCHORS PER SHED IS (4). (1) ANCHOR PER EACH CORNER. ADDITIONAL INTERIOR ANCHORS ARE REQUIRED IF SPACING IS MORE THAN 10'-0" BETWEEN ANCHORS.. 4. ANCHORS SHALL BE ON SIDE WALLS EXCEPT WHEN THE SHED IS PLACED NEXT TO AN EXISTING BUILDING; IN WHICH ANCHORS CAN BE PLACED ON THE END WALLS AS CLOSE TO THE SIDE AS POSSIBLE. ion-2-n/ ) s REVMXYBEID BY ` DATE PLANS AND r MU J, � ON JOB 2'X2' GALVANIZED WASHER OR NO INSPECTION NVML B MADE. 2'X2" GALVANIZED WASHER WITH 1/2- NUT 1/2" THREADED ROD WITH 1/2" NUT OPTIONAL FOR 'HIGH SEY NOTCH OR COUNTERSINK BOLT 1/2' THREADED ROD ^�� -� OPTIONAL FOR 'HIGH SET' i ,,,� EYES BOLTED TOGETHER WITH 1, BOLT & Nlli WITH (2)2'x2" GALVANIZED 1/2' COUPLER THRU 2'x4' BOTTOM PLATE 2'x4' BOTTOM PLATE NAILED 1/2' COUPLEIR� -^ F� WASHERS (2.000LB SHEAR CAPACIIY) :: xx 'x �4' MIN. 1/2'ED (4 N LOR CONCRETE WEDGE ANCHOR INTO SLAB TO 2'X6" P.T. BASE _ _ �4" MIN- 1/2'x12" FORGED EYEBOL" T" L THRU 2'X4' P.T. BOTTOM PLATE I EYES BOLTED TOGETHER Wfl`5 "/21xr2m" P _ I, OR N PAD WITH �- (SEE TABLE 1 FOR SPACING) L------- � BOLT h NUT WITH (2)2'x2' GALVANIZED BLOCK.IV REQUIRED (SEE TABLE 3). WASHERS (2.000LB SHEAR CAPACITY) 1/2'x3' (400 LBJ CONCRETE WEDGE ANCHOR SIMPSON A-24 CONCRETE SLAB BY OTHERS THROUGH CLIP OR EQUAL LOCAL CODES AND JURISDICTION CONCRETE SLAB BY OTHERS THROUGH LOCAL CODES AND JURISDICTION ,�XSj•IC�' i ..ii.= .+2 (SEE TABLE 1 FOR SPACING) 30" EARTH AUGER A 1L4 y� WIC r.,r (SEE TABLE 4 FOR SAC j4rr" 'NO _-- U.SHED'WlrSKID SHED WITH SKID SHED WITH FLOOR' OPTION TO�PADTr0R!BLOCKING ANCHORED TO CONCRETE ANCHORED TO CONCRETE TIE -DOWN DETAILS CODE VERSION Fee 2017 6N F l ASCE-7 :I MANUFACNRER BUPTApR s1¢DS BUILDING TYPEpy UyM"'E CONSTRUCTION TYPE V-B FIRE PROTECTION FIRE SUPPRESSION SYSTEM NONE OCCUPANCY STORALE ALLOWABLE-NUMBEIZOESiORIESI - -_--- - - BASIC WIND SPEED V+-teOmpn EXPOSURE C ENCLOSURE FNCLOsm INTERNAL PRESSURE COEFFICIENT +/- 0.18 ILIPORTANCE FACTOR 1.15 ROOF DEAD LOAD tOP3F ROOF LIVE LOAD 20PSF OR 3oolbs FIDOR DEAD LOAD 8n1` FLOOR LIVE LOAD sue. 75PSF - 125PSF On. "R' RATING OF WALLS, FLOOR, ROOF N/A MODULES PER BUILDING t HURRICANE PROTECTION USAGE No HURRICANE SHELTER USAGE No SQUARE FOOTAGE L65 T no So.FT. ' (n MTB p Dar<: LEJ 4/26/16 = S,tmc (n N/A o0el LLJ ALL GENERAL NOTES 1. FOUNDATION PLANS ARE NOT PART OF THIS PLAN SET AND ARE GOVERNED BY LOCAL JURISDICTION. LEJ 2. THIS BUILDING IS EXEMPT FROM THE FSC ENERGY CONSERVATION CODE PER SECTION J 1015.22. m 3. REFER TO TIE -DOWN DETAILS FOR PROPER INSTALLATION REQUIREMENTS TO MEET CODE. O \` ` 1111111/// T /LLJ /i CD L/ \ Ljj Q i CD °., STATE OF 44/ ZO ��s•FLORIDP::G�Z``� Q // /DNA `N`�� J Matt ew 7. SOidN'IR P_E. Q'" FinriCo License .64608 Cn Z Sheet: AD-1 OF 1 O 2N END PSI APPROVAL 261b-01-18 1 ALUMINUM ROOF SHEATHING ROOF FRAMING PLAN ELEVATION CROSS-SECTION TYPICAL ARCH FRAME END ELEVATION WITH GARAGE DOOR (ON", ON Onow Side Wall Header Schedule (180C) Size dl BgWide Upp to to 14! ' Wide Fasteners vrl strap (each end) Max. Span NJ@} 1-4'x4' 6'-P 0 3 -3'x 0.131' nails 4'k4"v25E4' e'-0' 1 8-3•x 0.131'nails a. Tabulated values are for No. 2 gade Spruce -Pine -Fir lumber. b. NJ - Number of lack studs required to support each and. c. Windex header for window openings that have more than 50% combined stud wall abou, and below, otherwise use door header schedule. d. See header details for alternate layouts, i.e. 2-2X4' or 4 x4' P.T. a. The header can be attached to the top plate and thus have the combined strength equivalent and use the maximum span stated. Max. Span I N.kb1 b. NJ- Number otlecx studs DOuirad 10 supper each end. c. Laid Bat d ND.eck studs, but NO studs led Alal. *I — 1. ACE FASIm. Be ... M 1. NARD aEgPRE4FNIS 2 SF NF1pat g.1YLUl£ ZY "M aeI wNmAAMN 1 McDW 0. OTH INK CREF RFp WX pR YORE WUE f1411wc IBNE AND eanW. onIDASE REFORM DoOR Names WNE sFuOs 'I i 4NGIE 244• HF�t I I I SNEk". II II _ (2L3-M•Wfw 1(3 0.414 O, W -PaeiWFR:aRT+i414'c _ 1211Y' 0R IV"' BmaIIe SNpS VFm E'SET]JRED m 6NFAlInN4 As Pw f0 MAX. WNVFIGNRFAE P6lRI1CRON6 HYDROVENT DETAIL SIDE WALL WINDOWS END WALLS WINDOWS & (OPTIONAL) & DOORS DOOR 6' WIDE OR LESS G.F.I. �+ NOTES -OPTIONAL ELECTRIC OUTLET -ALL WIRING SHALL BE B GAGE 3-WIRE MC CABLE N " -ENCASE IN ALL METAL BOXES. SOURCE L " WIRING DIAGRAM (OPTIONAL) .SEE HEADER D.M. f.4 RuNND. ON INSUE 2a4 24• 4"x4" W/2"x4" CODE REVIEW pf<ssmeeTxNx<Im<:m<.. m< 17183n<4rL�nM1<eI llJ833N5 D, ReAeo.i0 rQAI 2239 PlainReview. N[fm GMarti,y PE RPEA2U]9.I6,T FIEM 16YCCL 1U0]N6. TN PF IIL1939 I4 xDMMM WAu SH"M aPRO15 END WAu L SOLE PUTE EEmR FRMIIND AND FLOOR FRAvND WUN OR.- (1m"').12• SNAP W/6-10d MIS STANDARD WALL DETAIL Nine WAu FRAMING MEMBERS ARE CONFIRMS FIMu ce EOLLLL WITH DOOR & WINDOW OPTIONS FOUNDAMN SA, TO ROOF AND ..am pISURE A COMMAS LOAD PAIN. W ON WALL MET1YeE.Rs ARE e F+OaR sxGk H NOT cONRMIWS ew MU& CIAVPS. TID. OR 3/4' RtWOpp - 3/4• P.T. PLwrT4p SNAM BE FORMED OF GLLwM>m sFED. OF NOT LEBS - 3/4• TkG IWN OMe NOWw TIICKNM P.T. T&O � 4M1C TABLE 2 ____ ____ ____ ____ ____ ____ ____ ____ 61® WL111 %1 # %1 Ir-r 1'-+d' r 'Gr +'-+N• +r-6 r-W W-4• - Iw-O 11 6-Ir - 0'-0'- 6'-0' tl 1V I. - Y I .NNAIGGG, aax miTD lnnvsrcm4r .1 Fa e.m wK EO an > mz 9 o r i I I I I � m b I , 2A6 P.T. 24 0.4 Fe'. g on NA. Imes, o IV O.C. TIP A 3/4• TAG PLYBOARD r r P.T. ATTACHED 'MM H24 OR EGMALEM. SD TARE 2 FOR ouunm AND I I sPADwG i U.. EUPEROR ANEXE tTPE Ur rvRED B REsmun_w.UONN_ mON TYPE V-e MOTION NONE 'RMSION SYSTEM NONE y - SIORRGE_ E NUMBER OF STORIES 1 ID SPEED V�-160mpn c IE NG n m PRESSURE COEFFICIENT +/- G18 GE FACTOR 11.15 WE LOAD 3OKF OR 305R KIM IM DEAD LOAD 1DEEF UME LOAD 3M 76PSF - 12EPSF OPT. MNG OF WALLS. FLOOR, ROOF N/A CS PER BUILDING 1 DJE PROTECTION USAGE NO N E SHELTER USAGE NO E FOOTAGE 719 SOST. OR I£4 w wmwn MTB z om J 12/12/17 Z Q Scale: H N/A (n LLJ vr,7F— = In SS-6-180CR1 0- W I. FUUNDATUA PVf3 IRE NOT PART OF Tm PIAN SET AND ME 0-WYaWED W IOfIL ,NRe01ClI0N. W J 2 WOE PERS CIpNE%IEIIEPT FROM RIC me EN. CONSENVAMN Qa S. fIFFM io jI -�µN DETAOS FOR PROPER WAUAMN fdONF4FN10 TO MEET COOS 4. ALL 6TUM sa a MuSSUS. ETC ARE b 02 SPF. E%CEi N 0 AU NGFED. () S. See MRD OVEP. 400 so. R. WILL NAVE AN DO' "Nuv MR. LU fl� 6. G�uTnRS M BE RERAVUE) OF SFIE RT or . THND MIN. es NQ >. NL WwU0W9 AND Game To MEET THE VNIMUM SPEG6FGRONs LL n As: IX nARIW Btt — sell- --."e— — UN1— _118 Q -.0 STATE ; .4, - 0 OF •... .......... C) Matthew T. BOIdWIn P.E. z Florida License #64608 F m Sheet: SSB-1 OF 1 MAR 21 2018 ST, Lucl�Y Remitting