HomeMy WebLinkAboutMISC LETTERMarch 9, 2018
Mr. Mike Fuggetta
Therma Seal Roof Systems, LLC
1421 Oglethorpe Road
West Palm Beach, FL 33405
Dear Mike,
Alk
r INSP2CT[ON seRVICe INC'
SCANNED
BY
St. Lucie County
Subject: Roof Moisture Survey
St. Lucie County — Logistics Center
3855 South US Highway One
Ft. Pierce, FL 34946
As requested, a Roof Moisture Survey was completed by Cleary Inspection Service, Inc. (CIS) on
the St. Lucie County — Logistic Center, located at 3855 South US Highway One, in Ft. Pierce, FL.
PURPOSE OF THE SURVEY: Obtain visual and isotopic inspection data, to provide a non-
destructive means to detect moisture by determining the amount of hydrogen within the layers of
the roof using a nuclear (isotopic) Roof Moisture Gauge. The gauge neutrons can penetrate up to
seven inches of roof and its coatings and the readings are of 7.5 seconds duration.
METHOD: Hydrogen readings were taken at approximately five-foot intervals and the data
recorded on the corresponding grid drawing.
HYDROGEN READINGS: The purpose of the moisture test is to try to identify areas with wet
roofing material. Following the field moisture tests, the customary procedure is for core samples to
be taken at locations corresponding to readings that range from "low" to "high", in order to
determine their moisture by weight content (gravimetric analysis).
CODE CRITERIA: According to Florida Building Code (FBC) 2014, Chapter 15, Section 1521.4,
not more than 25% of the total roof area or roof section of any existing building or structure shall be
repaired, replaced or recovered in any 12 month period unless the entire existing roofing system or
roof section is replaced or repaired to conform to requirements of this code.
CORE SAMPLES: Core cuts were made to determine their moisture content (percentage by
weight). Roof core samples, of a minimum of 2 inches in diameter, were taken down to the deck.
The core samples were then transported to the laboratory in air -tight compartments to determine the
type of roof components and percentage of moisture by weight. The detailed gravimetric results
sheet is included with this report.
FILE Uaupy
Mailing Address: P.O. Box 2471, Palm Beach, FL 33480
Office: 1017 North "H" Street, Lake Worth, FL 33460
Tel. (561) 722-9881 • Fax (561) 582-8039 0 Email: clearvinsoectionstMkmand.com • Website: KCWAND.com
Roof Moisture Survey
St. Lucie County — Logistics Center
3855 South US Highway One
Ft. Pierce, FL 34946
R`NSPBCT)ONseRVlce INC
Page -2-
ROOF GRAPH: The enclosed computerized graph was prepared from the data collected during
inspection and gravimetric test performed in accordance with TAS 126. This graph separates
moisture levels into four levels of dry to wet. The Florida Building Code sets allowable maximum
limit of moisture in the roof system as 5% in the roof membrane and 8% in the insulation. (See
chapter 15 section 1521.12)
TEST SUMMARY:
Top Gypsum Board Insulation: A total of 2415 nuclear field readings were recorded. The
nuclear field readings ranged from 3 to16. Of the 2415 readings, 100% readings were found
to be wet; over 8% moisture by weight content in the Top Gypsum Insulation (indicated in
red).
The Ton Gypsum Board does not meet current code for repair/recover.
Bottom ISO Insulation: A total of 2415 nuclear field readings were recorded. The nuclear
field readings ranged from 3 to16. Of the 2415 readings, III or 4.6% readings were found to
be wet; over 8% moisture by weight content in the Bottom ISO Insulation (indicated in red).
The Bottom ISO Insulation does meet current code for repair/recover.
However, all wet insulation to be removed
One Roof- Stele Ply Membrane over a Top Gypsum Board Insulation over a Bottom ISO
Insulation over a Steel Roof Deck
The test results presented here reflect the condition of the roof system at the time of the test. These
results are time and sample dependent since roof conditions are continuously changing due to
exposure to the elements and roof top traffic.
We appreciate the opportunity to be of service to you. Should you have any questions or need
additional information, please feel free to call at your convenience. Thank you.
Sincerely,
Cleary Inspection Service, Inc.
Kath ie I. eary
Metro -Dade County
Lab Certification #16.0211.02
Mailing Address: P.O. Box 2471, Palm Beach, Fl. 33480
Office: 1017 North "H" Street, Lake Worth, FL 33460
Tel. (561) 722-9881 • Fax (561) 582-8039 • Email: clearvinsoections@kcwand.com • Website: KCWAND.com
Forensic Engineering Consultants, Inc.
Cleary Inspection Services, Inc.
1017 North 'H' Street
Lake Worth, FL - 33460
Attention:
Dear Ms. Cleary:
Ms. Katherine Cleary
March 1, 2018
Re.: Gravimetric Tests
St. Lucie County Logistics Center
3855 South US Hwy-1
Ft. Pierce, FL - 34946
As requested, Forensic Engineering Consultants, Inc. (FEC) has completed gravimetric tests on
the six roof samples delivered to our office. The tests were done in accordance with TAS-126.
This report transmits the results of our laboratory tests.
The subject facility is located at 3855 South US Hwy-1 in Ft. Pierce, Florida. We understand
that eight core samples were obtained from the roof of the subject facility. In all, twenty four
samples from eight roof cores were delivered to our office in sealed plastic bags with notations
on the bags identifying the samples. We have used those same notations in our report.
The roof samples were removed from the bags and weighed. They were then placed in an
oven. The singe ply membrane samples were cooked at 150OF for over 24 hours, while the
insulation samples were cooked at 230°F for over 24 hours. The samples were then removed
from the oven, weighed again and the loss in moisture computed. The laboratory moisture
content test results are given in the attached sheet. The sheet also indicates the reported
sample locations.
We appreciate the opportunity to be of service. If you have any other questions, please call.
_ _ Sincerely,_ _-
Forensic Engineering Consultants, Inc.
u R. N. Sailappan, P. .3111
Principal Engineer
Florida Registration No. 46696
Forensic Engineering Consultants, Inc., P.O. Box 970034, Boca Raton, FL - 33497 Ph (561) 9018490 Fax (561)
Therma Seal Roof Systems, LLC
1421 Oglethorpe Rd.
West Palm Beach, FL 33405
ROOF SYSTEMS, LLC.
State License #CCC1325862
11/16/18
Permit# 1803-0339
Address: 3855 S US 1, Ft. Pierce, FL 34982
To whom this may concern,
Phone:(561) 223-2096
Fax: (561) 444-2272
SCANNED
BY
St. Lucie County
The roof hatch is located 15' 8" from the perimeter edge. Therefore, based on attached engineering, it falls into a
48.92 psf.
West Palm Beach, Florida 33405
Dwikel@thermasealroofs.com
1.561.223.2096 (p)
1.561.444.2272 (f)
1.561.719.2653 Cell
ROOF SYSTEMS. LLC.
RECEIVED
NOV 16 2018
.Permitting Department
St. Lucie County, FL
STATE OF FLO A - -- — - - --
COUNTY OF
Sworn to (or affirmed) and subscribed before me this � Yi day of I"A W .20 k by (name of person making statement).
Signature of Notam io
NamQyiye'rQ .
Personally Known OR Produced Identification +; ::�;�� JASMINE R I V E RA
Type ofIdentifica[ionProduced '�'° Commission sGGs46s7
�.•'
Ivly Commission Expires
January 22. 2021
FILE COPY
Solutions Driven. Customer Focused.