GENERA— , JOTES
I. REFERENCE MATERIALS: FLORIDA BUILDING CODE, 2017,5TH EDITION WITH REVISIONS AND
SUPPLEMENTARY CODES AND STANDARDS REFERENCED THEREIN.
2. REFER TO THE CONCRETE AND WATERPROOFING REPAIR SPECIFICATIONS, THE OCFANA II
CONDOMINIUM. FOR DETAILS OF SCOPE OF WORK, MATERIALS, AND GENERAL REPAIR
PROCEDURES.
3. REPAIRS SHALL BE IN ACORDANCE WITH REPAIR SPECIFICATIONS AND STANDARDS SET FORTH BY
THE INTERNATIONAL CONCRETE REPAIR INSTITUTE (ICRI) AND APPLICABLE AMERICAN CONCRETE
INSTITUTE (ACI-14).
PREPARED
CONCRETE 3/4• MIN.
SURFACES OXIDIZED (CORRODED) BARS UNOXIDIZED
TO RECENE /A1�\ CLEARANCE I� & TIGHTLY
PATCH / 1 \ NOTg5 II BONDED BARS
SECTION THROUGH I REFER TO
CONCRETE MEMBER NOTE #7
APPUCABLE TO HYDRODEMOLITON, HYDROMILLING, PNEUMATC, HYDRAUUC
AND ELECTRIC BREAKERS. APPUCABLE TO HORZ.. VERT AND OVERHEAD
LOCATIONS
4. REMOVE LOOSE OR DELAMINATED CONCRETE ABOVE DAMAGED OR OXIDIZED REINFORCING STEEL
ONCE INITIAL REMOVALS ARE MADE, PROCEED WITH THE UNDERCUTTING OF ALL EXPOSED
OXIDIZED (CORRODED) BARS. UNDERCUTTING WILL PROVIDE CLEARANCE FOR UNDER BAR
CLEANING, FULL BAR CIRCUMFERENCE BONDING TO SURROUNDINGS CONCRETE, AND WILL SECURE
THE PATCH STRUCTURALLY.
5. PROVIDE MINIMUM 3/4' CLEARANCE BETWEEN EXPOSED REPARS AND SURROUNDING CONCRETE
OR 1/4' LARGER THAN LARGEST AGGREGATE IN REPAIR MORTAR; WHICH EVER IS GREATER.
6. CONCRETE REMOVAL SHALL EXTEND ALONG THE BARS TO LOCATIONS ALONG THE BAR FREE
OF BOND INHIBITING C_OROSION, AND WHERE THE BAR IS WELL BONDED TO SURROUNDING
CONCRETE. MINIMUM EXPOSURE OF CLEAN STEEL IS 2. OF BAR.
7. IF UNOXIDIZED REINFORCING STEEL IS EXPOSED DURING.THE UNDERCUTTING PROCESS, CARE
SHALL BE TAKEN NOT TO DAMAGE THE BAR'S BOND TO SURROUNDING CONCRETE. IF BOND
BETWEEN BAR AND CONCRETE IS BROKEN,UNDERCUTTING OF THE BAR SHALL BE REQUIRED.
8. ANY REINFORCMENT WHICH IS LOOSE SHALL BE SECURED IN PLACE BY TYING TO OTHER
SECURED BARS OR BY OTHER APPROVED METHODS.
SEAL
APPROVED BY:
00
DAVM CDLSVN,, P.F.
FL REG #55507 .
DATE:: 11711�K
CAUTION! BEFORE STARTING CONCRETE REMOVALS, REVIEW EFFECT OF
REMOVALS ON STRUCTURAL INTEGRITY. PROVIDE SHORING OF MEMBER(S) Ell 99
AS NECESSARY. PARTICULAR CARE SHALL BE EXERCISED AT SLAB/BEAM
CONNECTIONS TO COLUMNS AND AT COLUMN EXCAVATIONS. /:-IFILE LOW
METHOD PREPARED SURFACE
RECEIVE1/2- SAVICUT MAX OR TO
LESS AS NECSSARY TO MATERIAL
CUTTING
;
REINFORCINGAVOID
:::❖:•:":❖:❖:❖:❖:•:❖:•:::•:❖.•.❖.❖.•.•.❖.❖.•.!.•.❖.•.:L❖
:❖.❖.❖.❖.❖.❖.L•.
OF a «
SECIRON THROUGH
CONCRETE MEMBER
APPLICABLE TO HYDRODEMOUrON. HYDROMILUNG. PNEUMATIC. HYDRAULIC AND
ELECTRIC a-& APPIEUCABLE TO HORZ.. VERT AND OVERHEAD
9.
SANDBLAST STEEL REINFORCEMENT TO REMOVE BOND INHIBITING MATa- RUST.
REINFORCEMENT BEEN DIMINISHED BY 15% OR MORE.
THE BAR WILL REPLACEMENT.
DIAMETER. WHERE• UNABLE TO LAP THE FULL DISTANCE, -rA- MAY BE DOWLEDv
OF 4" INTO SOUND CONCRETE WITH EPDXY.
AT EDGE LOCATIONS PROVIDE APPROVED fflGHT' MGLE CUTS AVOID FEATHERED EDGES.
GUIDELINES10.
EDGE PREPERATION PATCH CONFIGUR47IONS SHOULD BE KEPT AS SIMPLE AS
POSSIBLE
FOR a
r i• iS'i � is i 4 i JOO�!
dbm
a r mPREFERED
•
AFTER11. REMOVALS AND v • u • •MATERIALS
- - a BONDED' a. «a.AFTER
CLEANING TO ENSURE aADDITIONAL LOOSE AGGREGATE. OR THAT
ADDITIONAL DELAMINATIONS ARE NOT PRESEKT.
12.
PRIME AREAS TO RECEIVE REPAIR MORTAR WITH BONDING ACENT PER SPECIFICATION.
13.
PATCHING MATERIAL M BE POLYMER MODIFIED REPAIR
CAUTION! BEFORE STARTING REMOVALS, REVIEW EFFECT OF REMOVALS ON
STRUCTURAL INTEGRITY. PROVIDE SHORING OF MEMBER AS NECESSARY.
PARTICULAR CARE SHALL BE EXERCISED AT SLAB/BEAM CONNECTIONS TO
COLUMNS.
THESE kL NS AfdD ALL PROPOSED WOK
ARE SUBJECT TO ANY CORRECTIONS
;T
REQUIRED BY FIELD INSPECTORS THAT
,/
R TAAY BE NECESMaRy-IN ORDER T0,
COMPLYWftH'P'-L xAXICAA CODES."I
I
/ WAR
WEW1F/a�
� L•{���
TYPICAL SECTION THRU SLAB REPAIR
SEE raven � ran maul
MUM! "' Irtr CsION, r OJJ rIi11Ir r
2 01$ PROJAE� 01 J
GENERAL REPAIR PROCEDURE
9900 S OCEAN DR
AND SHORING JENSEN BEACH, FL 34957
SHORING POST
INSTALLATION
9
AVATON TO 15%
AN CROSS NON
UNLESS I alRI
BY ENGINEER WALL
MAX S I
POST
INSTALL
—ATION I
•
• I
I
.SHORING POST
EXCAVATED • INSTALLATION
CONCRETE
12^ MAX
COLUMN EXCAVATION LIMITS II
L
TYPICAL SHORING PLAN
CONSTRUCTION SHORING
1. SHORING REQUIRED AT THE ENGINEER'S DISCRETION AND DIRECTION OR WHERE
EXCAVATED DECK EXCEEDS 25% OR 50 SFT.
2. ALL SHORES TO BE TELESCOPING STEEL SCREW JACKS WITH A RATED LOAD OF
5000 LETS MIN. WHEN EXTENDED TO 8' UNLESS OTHERWISE NOTED.
3. ALL SHORING TO BE PLACED AS DIRECTED BY THE ENGINEER AND PRIOR TO
EXCAVATION.
4. AFTER INSTALLING SHORES, TIGHTEN EACH SHORE TO HARD FIT PLUS 1/2 TURN.
5. SHORING POSTS SHALL NOT BE RELEASED UNTIL NEWLY INSTALLED REPAIRS
HAVE CURED TO 95% DESIGN STRENGTH OR FOR A MINIMUM OF 14 DAYS, AT
ENGINEER'S DIRECTION.
ESP
CA#8539
STRUCTURAL ENGINEERING
PROFESSIONALS, INC.
751 Northlake Blvd., Suite 2C Phone- (561) 844-4060
North Palm Beach, FL 33408 Fax: (561) 844-1001 '
$01 yw
DRAWN JC
CHECKED DC
SCALE NT
SK-21
SHEET 1 OF 1 1
Ya" Tapcon
12" on center, 11" Embed, repair all
fastener holes at the end of removal -
(TYP. Top & Bottom)
'"'Only for impending hurricanes
2X, 16d nails in
each 2"x4" stud
(TYP. Top & Bottom)
2"x4" Strongback brace to be
installed at half height of wall
1-12d nail in each 2"x4" stud
Kicker brace leg
16" on center
1-12d nail in each end
Kicker brace base 2"x4"
Y4" concrete tapcons at
12" on center
"Only for impending hurricanes
APPROVED BY:
r
1AVID CDLSTQR�, P,E.
FL RE G #5550.1
t DATE:
J , .
Top Section
View
Foam or carpet, secure to the
top cap of wind wall
(TYP. Top & Bottom)
1 x 2", used to secure
visqueen to wind wall
Visqueen—tape & staple visqueen
as needed to secure to wind wall
— (TYP. Top & Bottom)
Secure Y2" plywood to the 2"x4"
studs at 8" on center with 8d nails
(TYP. Top & Bottom)
Reinforce alternating stu
"ONLY for impending hurricanes
Y" Plywood
Visqueen (6 MIL THK)
over plywood
ottom Section View
See TYP. call —outs on
top section view.
WF HrE 00C, 'AANTOA pIr C� ��J� �JJJ31NIULINr
WEATHER WALL
DETAILS JENSEN BEACH FL
L34957
BA51C WIND SPEED
170 MPH
(A5CE 7 - 10)
WIND EXP05URE CATEGORY
D
INTERNAL PRE55URE COEFFICIENT
± 0.18
EDGE DISTANCE
8 Fr
BUILDING ENVELOPE CATEGORY
ENCL05ED
10 5Q FT E.W.A. COMPONENT AND CLADDING LOAD5:
WALL EDGE:
+GG, -105.5 P51'
WALL INTERIOR:
+GG, -59.4 P5F
NOTES:
1) Tapcons into ceiling and interior floor
shall be at the discretion of the FOR based
on existing weather conditions. Contractor
may normally substitute extension shoring
posts to compression fit weather wall
between each vertical stud for temporary
support.
2) In case of hurricane warning or watch,
FOR will issue an official letter at his
r L
discretion to have contractor install Tapcons
and weather kicker braces.
All 2" x 4" on 16" centers
Visqueen (6 MIL THK)
to cover entire wall
Caulk both sides of
wind wall top to bottom
THESE PLANS AND ALL PROPOSED (WORK
ARE SUBJECT TO ANY CORRECTIONS
REQUIRED BY FIELD INSPECTORS THAT
a k,AAY BC NECE$I>.�',RYIN ORDEF TO:
lJ®mPLY mH LLLL APPucAI;I�_; CODES
ESP
CA#8539
3) Weater wall in intended primarily for
moderate weather protection to prevent
normally encountered winds, rain, and some
micro dust. As with Hurricane rated doors
and windows, wind blown rain at hurricane
rated winds may result in some water
getting past the wall.
� Min
Ea. side
F�
SCANNED
BY
St. Lucie County
STRUCTURAL , ENG1NEE ING
PROFESSI0NALS, INC.
Weatherwall location
751 Northlake Blvd., Suite 2C Phone: (561) 844-4060
North Palm Beach, FL 33408 Fax: (561) 844-1001 '
Balcony
DRAWN JC
CHECKED DC
SCALE NTS
SK-1
SHEET 1 OF 2