HomeMy WebLinkAboutMISC LETTERPAUL WELCH INC.
echanical * Electrical * Civil Engineering
7RF-CEIV:ED 1984 S.W. Biltmore St. Suite#114
Port Saint Lucie, FL 34984
B Phone (772) 785 - 9888
t@rmK%i�e Email pwelchinc@aol.com N(GQ
N
March 23, 2018 SG 6� G0uX\,CA
St•�'�c�e
Re: UDT — Seal Museum Association Shutter Installation
3300 N Highway AlA
Fort Pierce, FL 34949
To Whom It May Concern:
Our office has calculated the required design pressures in accordance with ASCE 7-10
and Florida Building Code 2017 for the installation of the shutter at the above referenced
address.
Wind speed: V it: 165 mph, V.d: 128 mph
Exposure: D
Enclosure Type: Enclosed
Shutter Size: 183" WIDE X 97" HIGH
Shutter Location: (See Attached Sketch)
Required Design Pressure: +43.81-58.6 PSF
Shutters to be installed shall be equal to, or exceed the required design pressures as listed
above "Required Design Pressure".
Shutters shall be installed in accordance with the shutter manufacturer's installation
instructions and Florida Product Approval and Florida Building Code 2017.
Shutter shall be FL# 12246.1
Thank you for your attention to this matter.
Submitted by:
PAU WELCH INC.
_ Paul We ch, P.E.
Reg. No.29945
CONCEALED FASTENERS OR ATTACHMENTS
ARE THE RESPONSIBILITY OF THE
CONTRACTOR OR RECORD
FILE COPY