HomeMy WebLinkAboutMISC LETTERSW. W. Schaefer Engineering & Consulting, 74801500i Court North Palm Beach Gardens, FL 33418 Phone(561)744-3424 May 9, 2018 SCANNED Hopes Windows, Inc. BY 84 Hopkins Ave. Wit. Lucie County Jamestown, NY 14702-0580 Attn: Ryan Carlson P.A. (CA #6809) RECEIVED MAY 1 1 2018 ST. Lucie County, Permitting Re: Window mullions for the St. Lucie Catholic Church, 280 SW Prima Vista Blvd., Port St. Lucie, Florida Issue: There has been a request for mullion back-up calculations and there is concern over the engineers mark-ups that exist on the previously certified window unit prints. Attached are the back-up calculations that show the mullions to be more than sufficient to support ,he windows and their pressures. Note that it is customary for an engineer to place hand written comments on a document prepared by others, copy that marked up document and then seal the copies. This.is acceptable by all FBP-E rules with respect to sealed documents. It is very easy to tell the difference between a signed dud sealed copied document and one that has been signed and sealed and then modified. The blue stamp and signature make it obvious that the document is the original sealed by the engineer and if the document were to be modified after the fact, it is easy to tell the difference between comments that are part of the copy and those that were penned in after being copied and sealed. Please know that the original sealed prints are those as marked up by the engineer who sealed the document (me). If there are any questions, please call. Sincerely, , P.E. i®,t�'b STA'rEnF �'4w o -ONAL SOW' fir ?A MAY 0 9 2018 MULLION FORMULAS E (psi) Fb (psi) MULLION LENGTH (L) (in.) LOAD WIDTH (W) (in.) Ix (in.4) Sx (in.3) ALLOWABLE MOMENT (M) (in. -lb.) ALLOWABLE DEFLECTION (D) (in.) LINIER LOAD W1 (lb./in.) PRESSURE P1 (psf) END REACTION R1 (Ibs.) LINIER LOAD W2 (Ib.fin.) PRESSURE P2 (psf) END REACTION R1 ((bs.) 2 SPAN BEAM E (psi) Fb (psi) MULLION SP\DEFLE LOAD WIDT Ix (in.4) Sx (in.3) ALLOWABLE (M) (in. -lb.) ALLOWABLEION (D) (in.) LINIER LOAD W1 (Ib./in.) PRESSURE P1 (psf) END REACTION R1 (Ibs.) LINIER LOAD W2 (lb./in.) PRESSURE P2 (psf) END REACTION R1 (Ibs.) Fb (psi) MULLION LE TH (L) (in.) Ix (in.4) Sx (in.3) ALLOWABLE MOMENT (M) (in.-Ib.) ALLOWABLE DEFLECTION (D) (in.) 29000000 23600 102.5 39.5 4.22 2.1 49560 0.569444444 48.48725159 176.7636514 2484.971644 3�- 137.5748191 1934.04878 / 66 28 0.108 0.171 3411.45 2.2 23.37732437 240.4524792 771.4517041 6.265289256 64.44297521 206.7545455 29500000 21600 100 0.766 0.766 16545.6 0.277777778 2xif srr-FL ,94LobJ90L� �.o'�. `se11111110 �>��v1.•SC j `� Q ,.•�pENSr•.,• 44135 STATE F ,0;'e. �iO P'ftic 9.2018 W.W. SCHAEFER ENGINEERING & CONSULTING, P.A. (CA #6809) PALM GMUDEENNS�LL3 418 IF MULLION FORMULAS E (psi) 29000000 Fb (psi) 23600 MULLION LENGTH (L) (in.) 102.5 LOAD WIDTH (W) (in.) 45.75 �Z X y Q y 2 Ix (in.4) 2.67 Sx (in.3) 1.333 /yJ uL4/ 0/-1 ALLOWABLE MOMENT (M) (in. -lb.) 31458.8 ALLOWABLE DEFLECTION (D) (in.) 0.569444444 LINIER LOAD W1 (Ib./in.) 30.67795302 PRESSURE P1 (pso 96.56011442 END REACTION RI (lb&) 1572.245092 LINIER LOAD W2 (lb./in.) 23.95435098 PRESSURE P2 (pso c5.39730145 ji GC.O �J Q. P END REACTION R1 (Ibs.) 1227.660488 E (psi) T28 0 Fb (psi) MULLION AN (L) (in.) LOAD WID (W) (in.) Ix (in.4) 0.108 Sx (in.3) 0.171 ALLOWABLE MO ENT (M) (in. -lb.) 3411.45 ALLOWABLE DEFL CTION (D) (in.) 2.2 LINIER LOAD W1 (lb.! ) 23.37732437 PRESSURE P1 (pso 240.4524792 END REACTION R1 (Ibs.) 771.4517041 LINIER LOAD W2 (lb./in.) 6.265289256 PRESSURE P2 (pso 64.44297521 END REACTION R1 (Ibs.) 206.7545455 t%%j%llllJjJyXY 09.2018 POINT LOAD AT DLE �� Q.•'�CGENS%- % E (psi) 29500000 a d' Fb (psi) 21600 NQ, 4Al 0 MULLION L GTH (L) (in.) 100 t Ix (in.4) 0.766 �90�; :, SETA �Op, •_�`� Sx (in 0.766 �i� FS,S�• . �� AL WABLE MOMENT (M) (in. -lb.) 16545.E 'oj/ r (I' y�� F� `- ALLOWABLE DEFLECTION (D) (In.) 0. 777777E / • • r '' W.W. SCHAEFER ENGINEERING & CONSULTING, P-A. (CA,86809) 7480 RTH PALM13EACHGAR DENS, 33418 W. W. Schaefer Engineering & Consulting, P.A. 7480 1500Court North Palm Beach Gardens, FI, 33418 Phone (561)744-3424 May 9, 2018 Hopes Windows, Inc. 84 Hopkins Ave. Jamestown, NY 14702-0580 Attn: Ryan Carlson (CA #6809) RECEIVED MAY 1 1 2018 Sr. Lucie County, Permitting Re: Window mullions for the St. Lucie Catholic Church, 280 SW Prima Vista Blvd., Port St. Lucie, Florida Issue: There. has been a request for mullion back-up calculations and there is concern over the engineers mark-ups that exist on the previously certified window unit prints. Attached are the back-up calculations that show the mullions to be more than sufficient to support the windows and their pressures. Note that it is customary for an engineer to place hand written comments on a document prepared by others, copy that marked up document and then seal the copies. This is acceptable by all FBPE rules with respect to sealed documents. It is very easy to tell the difference between a signed and sealed copied document and one that has been signed and sealed and then modified. The blue stamp and signature make it obvious that the document is the original sealed by the engineer and if the document were to be modified after the fact, it is easy to tell the difference between comments that are part of the copy and those that were penned in after being copied and sealed. Please know that the original sealed prints are those as marked up by the engineer who sealed the document (me). If there are any questions, please call. Sincerely, .E. � ' srA'r; nF Q: r`r'A;ytegWN MAY 0 9-2018 i MULLION FORMULAS E (psi) Fb (psi) MULLION LENGTH (L) (in.) LOAD WIDTH (W) (in.) Ix (in.4) Sx (in.3) ALLOWABLE MOMENT (M) (in: Ib.) ALLOWABLE DEFLECTION (D) (in.) LINIER LOAD W1 (Ib.An.) PRESSURE P1 (pso END REACTION R1 (Ibs.) LINIER LOAD W2 (Ib.fin.) PRESSURE P2 (pso END REACTION R1 (Ibs.) 2 SPAN BEAM E (psi) Fb (psi) - MULLION SP\DEFLE LOAD WIDTH Ix (in.4) Sx (in.3) ALLOWABLE ALLOWABLE LINIER LOAD W1 (Ibdin.)\ PRESSURE P1 (psf END REACTION R1 (Ibs.) LINIER LOAD W2 (Ib./in.) PRESSURE P2 (pso END REACTION R1 (Ibs.) E (psi) Fb (psi) MULLION LE TH (L) (in.) (in: Ib.) (D) (in.) Ix (in.4) Sx (in.3) ALLOWABLE MOMENT (M) (in -1b.) ALLOWABLE DEFLECTION (D) (in.) 29000000 23600 102.5 39.5 4.22 2.1 ?Kv srFt 49560 ua,E lhvcL./O,✓ 0.569444444 48.48725159 176.7636514 2484.971644 37�` 137.5748191 ,4 o L 0 W 9 C3 L�E 10, 06• 1934.04878 101 / 66 28 0.108 0.171 3411.45 2.2 23.37732437 240.4524792 771.4517041 6.265289256 64,44297521 206.7545455 29500000 21600 100 0.766 0.766 16545.6 0.277777778 ``�N4 dS Cp _ gyp• 44135 sue. r0 STATE F 4e0FS,�' o,.F"ti 2018 W-W. SCHAEFER ENGINEERING & CONSULTING, P.A, (CA 416809) PALM BEACH GARDENS,FL333418 MULLION FORMULAS E (psi) 29000000 Fb (psi) 23600 MULLION LENGTH (L) (in.) 102.5 LOAD WIDTH (W) (in.) 45.75 Ix (in.4) 2.67 Sx (in.3) 1.333 ALLOWABLE MOMENT (M) (in. -lb.) 31458.8 ALLOWABLE DEFLECTION (D) (in.) 0.569444444 LINIER LOAD W1 (lb./in.) 30.67795302 PRESSURE P1 (pso 96.56011442 END REACTION R1 (Ibs.) 1572.245092 LINIER LOAD W2 (lb./in.) 23.95435098 PRESSURE P2 (pso 5.39730145 END REACTION R1 (Ibs.) 1227.660488 E (psi) 101009lf0 Fb (psi) 19 50 ) (in.) MULLIONVn3 66 LOAD WID (in.) 28 Ix (in.4)0.108 Sx (in.3)0.171 ALLOWABENT (M) (in. -lb.) 3411.45 ALLOWABL CTION (D) (in.) 2.2 LINIER LO(Ib.T ) 23.37732437 PRESSURo 240.4524792 END REAC1 (Ibs.) 771.4517041 LINIER LO(Ib.fin.) 6.265289256 PRESSURo 64.44297621 END REAC1 (Ibs.) 206.7545456 E (psi) 29500000 Fb (psi) 21600 MULLION LF.NIGTH (L) (in.) 100 Ix (in.4) 0.766 Sx (in 0.766 AL WABLE MOMENT (M) (in. -lb.) \0. 545.6 ALLOWABLE DEFLECTION (D) (in.) 77777 A )c N %92 4c.Lo�/ 'o'A 110 Q�•••%CCN,.• a s t No. 441 0 9.2018 i*OZ `cc= i9'• $TA F ;Iwo IAA- .0 %