Inspection Date: January 7, 2019
Saint Lucie County
Planning & Development Services
Building & Code Regulation Division
2300 Virginia Avenue
Fort Pierce, FL 34982
REaMMI)
AN 17 1919
Permitting Department
St. Lucie County
ax
E N G IN E E R ING G R O UP
Subject:
Special Inspection Report 1 of 1 (Equipment Shelter Foundation)
Permit:
1804-0141
FPL Site:
St. Lucie Service Center
Site Address:
3301 Orange Avenue, Fort Pierce, FL 34947
APX Project:
17-0149.07
Dear Building Official:
APX Engineering Group, LLC (APX) performed observations of the FPL telecommunication equipment
shelter foundation located at the above -referenced site. The purpose of these observations was to inspect
the following in accordance with the Florida Building Code, 6t^ Edition (2017):
1. Removal of existing equipment shelter.
2. Removal of existing equipment shelter foundation.
3. Installation of foundation steel reinforcement.
4. Installation of foundation concrete.
The installation of the above -mentioned items was visually inspected and compared with the approved
construction drawings by APX Engineering Group, LLC dated October 5, 2018. Based on these
observations and to the best of my knowledge and belief, the above -described construction of all
structural load -bearing components complies with the permitted documents.
Should you have any questions or wish to discuss any aspect of this letter, please do not hesitate to
contact the undersigned.
Sincerely,
APX Engineering Group, LLC
Michael A. Phillips, P.E.
Chief Engineer
Florida License #68312
SCANNED
BY
St. Lucie County
C E &.
No
ST �O @
Is
NAL E�G.�`.
,roneu�p��o
N OVA
August 30, 2018
St. Lucie County Building Department
2300 Virginia Avenue SCANNED
Ft. Pierce, FL 34982 BY
RE: FPL St. Lucie Telecommunications Site St. Lucie County
3301 Orange Ave.
Ft. Pierce, FL
PERMIT NO.: 1804-0141
STATEMENT OF COMPLIANCE
MOISTURE/DENSITY TESTING SERVICES
To Whom it may concern:
In accordance with the Florida Building Code, NOVA Engineering and Environmental LLC has
performed compaction testing at the above referenced project.
As part of compaction testing, we performed modified proctor test in accordance with ASTM D-
6398 for the material used as backfill (fill) and field density testing to verify the compaction efforts.
To the best of our knowledge compaction efforts for the foundation and building pad were
performed in accordance with the approved construction documents and passed the 95%
minimum compaction requirement as per the Florida Building Code and Geotechnical Report.
Furthermore, it is our opinion that the compacted soils meet with the required design bearing
capacity of 2,000 pounds per square foot, as detailed in APX Engineering's design drawings.
We trust that you will find the information contained herein helpful and encourage you to contact
us with an fliyglstions.
LLC
vi Lwpnez, P.E..'
B eot ,n Yeer
Sfat>�f• �Rla� • •'�Q�;�
Profee �l �fui�er`'Number: 62162
��Ilill�l
PROFESSIONAL I PRACTICAL I PROVEN
4350 Oakes Road, Suite 518, Fort Lauderdale, Florida 33314
1. 954-424-2520 / f. 954-424-2580 / usanova.com
-N OVA
August 30, 2018
St. Lucie County Building Department
2300 Virginia Avenue
Ft. Pierce, FL 34982
RE: FPL St. Lucie Telecommunications Site
3301 Orange Ave.
Ft. Pierce, FL
PERMIT NO.: 1804-0141
STATEMENT OF COMPLIANCE
MOISTURE/DENSITY TESTING SERVICES
To Whom it may concern:
In accordance with the Florida Building Code, NOVA Engineering and Environmental LLC has
performed compaction testing at the above referenced project.
As part of compaction testing, we performed modified proctor test in accordance with ASTM D-
6398 for the material used as backfill (fill) and Feld density testing to verify the compaction efforts.
To the)best of our knowledge compaction efforts for the foundation and building pad were
performed in accordance with the approved construction documents and passed the 95%
minimum compaction requirement as per the Florida Building Code and Geotechnical Report.
Furthermore, it is our opinion that the compacted soils meet with the required design bearing
capacity of 2,000 pounds per square foot, as detailed in APX Engineering's design drawings.
will find the information contained herein helpful and encourage you to contact
NN
Environmental, LLC
Number: 62162
PROFESSIONAL I PRACTICAL I PROVEN
4350 Oakes Road, Suite 518, Fort Lauderdale, Florida 33314
t. 954-424-2520 / f. 954-424-2580 / usanova.com
40
N OVA
August 30, 2018
St. Lucie County Building Department
2300 Virginia Avenue
Ft. Pierce, FL 34982
RE: FPL St. Lucie Telecommunications Site
3301 Orange Ave.
Ft. Pierce, FL
PERMIT NO.: 1804-0141
STATEMENT OF COMPLIANCE
MOISTURE/DENSITY TESTING SERVICES
To Whom it may concern:
In accordance with the Florida Building Code, NOVA Engineering and Environmental LLC has
performed compaction testing at the above referenced project.
As part of compaction testing, we performed modified proctor test in accordance with ASTM D-
6398 for the material used as backfill (fill) and field density testing to verify the compaction efforts.
To the best of our knowledge compaction efforts for the foundation and building pad were
performed in accordance with the approved construction documents and passed the 95%
minimum compaction requirement as per the Florida Building Code and Geotechnical Report.
Furthermore, it is our opinion that the compacted soils meet with the required design bearing
capacity of 2,000 pounds per square foot, as detailed in APX Engineering's design drawings.
you will find the information contained herein helpful and encourage you to contact
LLC
Number: 62162
P R O F E SS IO N AL I PRACTICAL I PROVEN
4350 Oakes Road, Suite 518, Fort Lauderdale, Florida 33314
t. 954-424-2520 / f. 954-424-2580 / usanove.com
OCT - 1 RECD
Lydia Galbraith
From:
danault@olinwaynerompanies.com
Sent:
Wednesday, May 02,20182:58 PM
To:
Lydia Galbraith
Subject:
Zoning picture attached RE: Report_FL Review Comments_NoncomplianUrf.pdf, PE MIt11$04.01'4j
Attachments:
FPL Shelter pic 2018jpg
Hi Lydia,
This picture is the same shelter proposed for permit 1804-0141.
The exterior finish is Aggregate. The trim color is Mesa Tan. Below is a photo of the shelter color. Note, we are not
touching the tower. This is shelter only.
If you need additional information, please advise,
Thank you for all your help. SCANNED
Thanks, BY
Dan
239-776-5884 St. Lucie County
-------- Original Message --------
Subject: Report_FL_Review_Comments_Noncompliant,rt.pdf, PERMIT
1804-0141
From: Lydia Galbraith <galbraithl@stludeco.org>
Date: Tue, April 10, 2018 9:41 am
To: °danault@olinwaynecompanles.com" <danault@olinwaynecompanies.com>
Dan,
Attached please find the Zoning review comments and list of missing documents. If you have any questions,
please let me know.
Thank you,
Lydia Ga0raith,
Zoning Specialist
Building and Code Regulation
(772) 462-1555
oalbraithl@stlucieco.org
solo s?ep
yBEST
vlaces
to wo)A
Please Nnlo: Flmid� pax very Meadpebvc rveolm lem. Most vahlen eaminunfcalionx to or hom CounryolacluIs rsgardng Coma bacleaas ate public lec rds mallable Inaba pubGu and n Ele upan
repueA It u No pMry of SL Wade C Loa, that an Cauntyreronb LmY be apaL but personal Inspedbn, CvaminaGanandtal Copying. Year -lmil mmmuni:agoM MO be aubbd le "bac d¢clwme
unless an sadi inat applies to Its wmmunieallen. ltyou rettNed NIe emaJh en r,please lasp,tthe sender by reply a-mait and delate all nialerlala ham all computers.
Joe Cicio
'From:
Joe Cicio
Sent:
Tuesday, May 29, 2018 4:43 PM
To:
'danault@olinwaynecompanies.com'
'Cc:
Joe Cicio
Subject:
Review Comments for Permit Number 1804-0141
Attachments:
Report -FL Review_Comments_Noncompliant-jrf.pdf
Dear St Lucie County Permit Applicant,
Thank You for choosing to do business and invest in St Lucie County. St Lucie County is committed in
assisting you to navigate the building review process. Please know that county staff is committed to customer service
and part of that service is providing assistance and guidance with our processes. Please do not hesitate to contact us
further to discuss your building project as needed.
Please see the attached plan review comments which have been generated for your permit. As soon as
We receive the modified plans and any additional required documents back from the Design Professional, Contractor,
Fire Department or Owner we will forward the permit package to our permitting department for issuance.
Thank,You
Jvupw 114. d4riv
Pans Examiner II
Standard Building Inspector
Building Plans Examiner
One and Two Family Dwelling Inspector
One and Two Family Plans Examiner
St. Lucie County PlanningandDevelopment Services
772-462-6453
2ws19L2W7,,;_,
- MST
places;•.
• to work
r
Please Note: Florida has very broad public records laws. Most written communications to or from County officials regarding County business are public records
available to the public and media upon request. It is the policy of St. Lucie County that all County records shall be open for personal inspection, examination and /
or copying. Your e-mail communications will be subject to public disclosure unless an exemption applies to the communication. If you received this email in error,
please notify the sender by reply e-mail and delete all materials from all computers.
Joe Cicio
From: Michael Phillips <mphillips@apxengineering.com>
Sent: Tuesday, June 12, 2018 9:24 AM
To: Joe Cicio
Cc: Gutierrez, David; Dan Ault; Tony Mercer; Matt Abbey
Subject: FW: FPL St Lucie shelter - Manufacture CD Shows 190mph *Contact Info*
Mr. Cicio
I appreciate your time to discuss the design requirements of this site this morning. As we spoke, the State of Florida DCA
approved shelter specified for this site has been designed for a 190mph wind speed to allow it to be used throughout the
state of Florida whereas the foundation has been designed for 169mph as required by the Florida Building Code for this
specific site. The shelter design wind speed is in excess of the minimum design wind speed required per FBC Figure
1609.3(2), thus is also acceptable and no changes are needed in our drawings.
Thank you,
Michael A. Phillips, PE, SE
Chief Engineer
APX Engineering Group, LLC
3400 Lakeside Drive, Suite 525
Miramar, FL 33027
Phone: (964) 744-1538, Ext 103
Email: mohillios(aaoxenaineerina.com
Web: www,aoxenoineering.com
From: Gutierrez, David <David.Gutierrez@fpl.com>
Sent: Monday, June 11, 2018 2:48 PM
To: Matt Abbey <mabbey@apxengineering.com>
Cc: Dan Ault <danault@olinwaynecompanies.com>; Tony Mercer <AMercer@glotel.com>; Sandy Bringas
<sbringas@apxengineering.com>; Michael Phillips <mphillips@apxengineering.com>
Subject: RE: FPL St Lucie shelter - Manufacture CD Shows 190mph *Contact Info*
Matt,
That will be great.
Contact info below.
J03i7- kx Cicciv
Plans M-aminerH
Standard Buddrnglnspectnr
Bud&—g-Plans F1=1i7er
One and Two FamilyLhve&g,-Inspector
One and Two FamilyPlans Examiner
St Lucie CouniyPlannirgaudDevelopmeut-1; cmces
�w 20�o a soar .
a0sr
s®n to.wlQik
David Gutierrez
Construction Manager I Office: 954-327-3110 1 Cell: 954-658-22621 Email: David.Gutierrez@FPL.com
Joe Cicio
From:
Joe Cicio
Sent:
Wednesday, May 09, 2018 9:09 AM
To:
'danault@olinwaynecompanies.com'
Cc:
Joe Cicio
Subject: Review Comments for Permit Number 1804-0141
Attachments: Report -FL Review_Comments_Noncompliantjrf.pdf
Dear St Lucie County Permit Applicant,
Thank You for choosing to do business and invest in St Lucie County. St Lucie County is committed in
assisting you to navigate the building review process. Please know that county staff is committed to customer service
and part of that service is providing assistance and guidance with our processes. Please do not hesitate to contact us
further to discuss your building project as needed.
Please see the attached plan review comments which have been generated for your permit. As soon as
we receive the modified plans and any additional required documents back from the Design Professional, Contractor,
Fire Department or Owner we will forward the permit package to our permitting department for issuance.
Josepk n &icio
Plans Examiner II
Standard Building Inspector
Building Plans Examiner
One and Two Family Dwelling Inspector
One and Two Family Plans Examiner
St. Lucie County Plannngand Development Services
772-462-6450
ii�f�i ,;usoia n. Moir
0
Places
r,...r.�., to woe, �
Please Note: Florida has very broad public records laws. Most written communications to or from County officials regarding County business are public records
Available to the public and inedia upon request. It is the policy of St. Lucie County that all County records shall be open for personal inspection, examination and f
or copying. Your a -mail communications will be subject to public disclosure unless an exemption applies to the communication. If you received this email in error,
please notify the sender by reply e-mail and delete all materials from all computers.
J
Joe Cicio
From: Gary Santora <garysantora@outlook.com>
Sent: Tuesday, June 19, 2018 1:48 PM
To: Joe Cicio
Subject: RE: Permit Number: 1804-0141 - Requested Construction Cost Breakdown
Hi Joe,
Here's the shelter breakdown requested:
The cost for Port St. Lucie shelter project:
1. New 12'x25' shelter with indoor 60kw generator: $9,19S.Otl
2. Construction labor/material 53 385:0'Q�
'Thanks, Gary
From: Joe Cicio <cicioj@stlucieco.org>
Sent: Tuesday, June 19, 2018 11:35 AM
To:'Gary Santora' <garysantora@outlook.com>
Cc: Joe Cicio <cicioj@stlucieco.org>
Subject: RE: Permit Number: 1804-0141 - Requested Construction Cost Breakdown
Gary,
I z Please include the cost of the building and the generator
Thanks
Ime
Joseph M. Cicio
Plans Examiner
Standard Building Inspector
Building Plans Examiner
One.and Two Family Dwelling Inspector
One and Two Family Plans Examiner
St Lwci,e. C¢u.whj PL&mft Kg aid. De wed o m vF Sery U e -
Hots- wwY your wv, ce, today ** PUast, cz, h C"b Pefer-sovv, Ciu,i,edi,Kg Off ai,ad, of
@sFLrticizco org to•s of your Wggey�, eovwwte.Yviy-"-d, feedback.
� 1
S
From: Gary Santora[mailto:aarysantora@outlook.com]
Sent: Tuesday, June 19, 2018 11:32 AM
To: Joe Cicio <cicioi@stlucieco.ore>
Subject: Permit Number: 1804-0141- Requested Construction Cost Breakdown
Hi Joe,
Here's the cost breakdown that you requested last week to secure final approval, please let me know if this meets your
approval.
Construction breakdown:
Labor- $39,299.45
Materials- $14,535.55
Total= $ 53,835.00
Thanks,
r
Gary Santora
Site Acquisition Consultant
On behalf of T-Mobile
516-782-8872
Please Note: Florida has very broad public records laws. Most written communications to or from County officials regarding County business are public records
available to the public and media upon request. It is the policy of St. Lucie County that all County records shall be open for personal inspection, examination and
or copying. Your e-mail communications will be subject to public disclosure unless an exemption applies to the communication. If you received this email in error,
please notify the sender by reply e-mail and delete all materials from all computers.
O
i
i
2