Loading...
HomeMy WebLinkAboutMISC LETTER-EMAILSV Inspection Date: January 7, 2019 Saint Lucie County Planning & Development Services Building & Code Regulation Division 2300 Virginia Avenue Fort Pierce, FL 34982 REaMMI) AN 17 1919 Permitting Department St. Lucie County ax E N G IN E E R ING G R O UP Subject: Special Inspection Report 1 of 1 (Equipment Shelter Foundation) Permit: 1804-0141 FPL Site: St. Lucie Service Center Site Address: 3301 Orange Avenue, Fort Pierce, FL 34947 APX Project: 17-0149.07 Dear Building Official: APX Engineering Group, LLC (APX) performed observations of the FPL telecommunication equipment shelter foundation located at the above -referenced site. The purpose of these observations was to inspect the following in accordance with the Florida Building Code, 6t^ Edition (2017): 1. Removal of existing equipment shelter. 2. Removal of existing equipment shelter foundation. 3. Installation of foundation steel reinforcement. 4. Installation of foundation concrete. The installation of the above -mentioned items was visually inspected and compared with the approved construction drawings by APX Engineering Group, LLC dated October 5, 2018. Based on these observations and to the best of my knowledge and belief, the above -described construction of all structural load -bearing components complies with the permitted documents. Should you have any questions or wish to discuss any aspect of this letter, please do not hesitate to contact the undersigned. Sincerely, APX Engineering Group, LLC Michael A. Phillips, P.E. Chief Engineer Florida License #68312 SCANNED BY St. Lucie County C E &. No ST �O @ Is NAL E�G.�`. ,roneu�p��o N OVA August 30, 2018 St. Lucie County Building Department 2300 Virginia Avenue SCANNED Ft. Pierce, FL 34982 BY RE: FPL St. Lucie Telecommunications Site St. Lucie County 3301 Orange Ave. Ft. Pierce, FL PERMIT NO.: 1804-0141 STATEMENT OF COMPLIANCE MOISTURE/DENSITY TESTING SERVICES To Whom it may concern: In accordance with the Florida Building Code, NOVA Engineering and Environmental LLC has performed compaction testing at the above referenced project. As part of compaction testing, we performed modified proctor test in accordance with ASTM D- 6398 for the material used as backfill (fill) and field density testing to verify the compaction efforts. To the best of our knowledge compaction efforts for the foundation and building pad were performed in accordance with the approved construction documents and passed the 95% minimum compaction requirement as per the Florida Building Code and Geotechnical Report. Furthermore, it is our opinion that the compacted soils meet with the required design bearing capacity of 2,000 pounds per square foot, as detailed in APX Engineering's design drawings. We trust that you will find the information contained herein helpful and encourage you to contact us with an fliyglstions. LLC vi Lwpnez, P.E..' B eot ,n Yeer Sfat>�f• �Rla� • •'�Q�;� Profee �l �fui�er`'Number: 62162 ��Ilill�l PROFESSIONAL I PRACTICAL I PROVEN 4350 Oakes Road, Suite 518, Fort Lauderdale, Florida 33314 1. 954-424-2520 / f. 954-424-2580 / usanova.com -N OVA August 30, 2018 St. Lucie County Building Department 2300 Virginia Avenue Ft. Pierce, FL 34982 RE: FPL St. Lucie Telecommunications Site 3301 Orange Ave. Ft. Pierce, FL PERMIT NO.: 1804-0141 STATEMENT OF COMPLIANCE MOISTURE/DENSITY TESTING SERVICES To Whom it may concern: In accordance with the Florida Building Code, NOVA Engineering and Environmental LLC has performed compaction testing at the above referenced project. As part of compaction testing, we performed modified proctor test in accordance with ASTM D- 6398 for the material used as backfill (fill) and Feld density testing to verify the compaction efforts. To the)best of our knowledge compaction efforts for the foundation and building pad were performed in accordance with the approved construction documents and passed the 95% minimum compaction requirement as per the Florida Building Code and Geotechnical Report. Furthermore, it is our opinion that the compacted soils meet with the required design bearing capacity of 2,000 pounds per square foot, as detailed in APX Engineering's design drawings. will find the information contained herein helpful and encourage you to contact NN Environmental, LLC Number: 62162 PROFESSIONAL I PRACTICAL I PROVEN 4350 Oakes Road, Suite 518, Fort Lauderdale, Florida 33314 t. 954-424-2520 / f. 954-424-2580 / usanova.com 40 N OVA August 30, 2018 St. Lucie County Building Department 2300 Virginia Avenue Ft. Pierce, FL 34982 RE: FPL St. Lucie Telecommunications Site 3301 Orange Ave. Ft. Pierce, FL PERMIT NO.: 1804-0141 STATEMENT OF COMPLIANCE MOISTURE/DENSITY TESTING SERVICES To Whom it may concern: In accordance with the Florida Building Code, NOVA Engineering and Environmental LLC has performed compaction testing at the above referenced project. As part of compaction testing, we performed modified proctor test in accordance with ASTM D- 6398 for the material used as backfill (fill) and field density testing to verify the compaction efforts. To the best of our knowledge compaction efforts for the foundation and building pad were performed in accordance with the approved construction documents and passed the 95% minimum compaction requirement as per the Florida Building Code and Geotechnical Report. Furthermore, it is our opinion that the compacted soils meet with the required design bearing capacity of 2,000 pounds per square foot, as detailed in APX Engineering's design drawings. you will find the information contained herein helpful and encourage you to contact LLC Number: 62162 P R O F E SS IO N AL I PRACTICAL I PROVEN 4350 Oakes Road, Suite 518, Fort Lauderdale, Florida 33314 t. 954-424-2520 / f. 954-424-2580 / usanove.com OCT - 1 RECD Lydia Galbraith From: danault@olinwaynerompanies.com Sent: Wednesday, May 02,20182:58 PM To: Lydia Galbraith Subject: Zoning picture attached RE: Report_FL Review Comments_NoncomplianUrf.pdf, PE MIt11$04.01'4j Attachments: FPL Shelter pic 2018jpg Hi Lydia, This picture is the same shelter proposed for permit 1804-0141. The exterior finish is Aggregate. The trim color is Mesa Tan. Below is a photo of the shelter color. Note, we are not touching the tower. This is shelter only. If you need additional information, please advise, Thank you for all your help. SCANNED Thanks, BY Dan 239-776-5884 St. Lucie County -------- Original Message -------- Subject: Report_FL_Review_Comments_Noncompliant,rt.pdf, PERMIT 1804-0141 From: Lydia Galbraith <galbraithl@stludeco.org> Date: Tue, April 10, 2018 9:41 am To: °danault@olinwaynecompanles.com" <danault@olinwaynecompanies.com> Dan, Attached please find the Zoning review comments and list of missing documents. If you have any questions, please let me know. Thank you, Lydia Ga0raith, Zoning Specialist Building and Code Regulation (772) 462-1555 oalbraithl@stlucieco.org solo s?ep yBEST vlaces to wo)A Please Nnlo: Flmid� pax very Meadpebvc rveolm lem. Most vahlen eaminunfcalionx to or hom CounryolacluIs rsgardng Coma bacleaas ate public lec rds mallable Inaba pubGu and n Ele upan repueA It u No pMry of SL Wade C Loa, that an Cauntyreronb LmY be apaL but personal Inspedbn, CvaminaGanandtal Copying. Year -lmil mmmuni:agoM MO be aubbd le "bac d¢clwme unless an sadi inat applies to Its wmmunieallen. ltyou rettNed NIe emaJh en r,please lasp,tthe sender by reply a-mait and delate all nialerlala ham all computers. Joe Cicio 'From: Joe Cicio Sent: Tuesday, May 29, 2018 4:43 PM To: 'danault@olinwaynecompanies.com' 'Cc: Joe Cicio Subject: Review Comments for Permit Number 1804-0141 Attachments: Report -FL Review_Comments_Noncompliant-jrf.pdf Dear St Lucie County Permit Applicant, Thank You for choosing to do business and invest in St Lucie County. St Lucie County is committed in assisting you to navigate the building review process. Please know that county staff is committed to customer service and part of that service is providing assistance and guidance with our processes. Please do not hesitate to contact us further to discuss your building project as needed. Please see the attached plan review comments which have been generated for your permit. As soon as We receive the modified plans and any additional required documents back from the Design Professional, Contractor, Fire Department or Owner we will forward the permit package to our permitting department for issuance. Thank,You Jvupw 114. d4riv Pans Examiner II Standard Building Inspector Building Plans Examiner One and Two Family Dwelling Inspector One and Two Family Plans Examiner St. Lucie County PlanningandDevelopment Services 772-462-6453 2ws19L2W7,,;_, - MST places;•. • to work r Please Note: Florida has very broad public records laws. Most written communications to or from County officials regarding County business are public records available to the public and media upon request. It is the policy of St. Lucie County that all County records shall be open for personal inspection, examination and / or copying. Your e-mail communications will be subject to public disclosure unless an exemption applies to the communication. If you received this email in error, please notify the sender by reply e-mail and delete all materials from all computers. Joe Cicio From: Michael Phillips <mphillips@apxengineering.com> Sent: Tuesday, June 12, 2018 9:24 AM To: Joe Cicio Cc: Gutierrez, David; Dan Ault; Tony Mercer; Matt Abbey Subject: FW: FPL St Lucie shelter - Manufacture CD Shows 190mph *Contact Info* Mr. Cicio I appreciate your time to discuss the design requirements of this site this morning. As we spoke, the State of Florida DCA approved shelter specified for this site has been designed for a 190mph wind speed to allow it to be used throughout the state of Florida whereas the foundation has been designed for 169mph as required by the Florida Building Code for this specific site. The shelter design wind speed is in excess of the minimum design wind speed required per FBC Figure 1609.3(2), thus is also acceptable and no changes are needed in our drawings. Thank you, Michael A. Phillips, PE, SE Chief Engineer APX Engineering Group, LLC 3400 Lakeside Drive, Suite 525 Miramar, FL 33027 Phone: (964) 744-1538, Ext 103 Email: mohillios(aaoxenaineerina.com Web: www,aoxenoineering.com From: Gutierrez, David <David.Gutierrez@fpl.com> Sent: Monday, June 11, 2018 2:48 PM To: Matt Abbey <mabbey@apxengineering.com> Cc: Dan Ault <danault@olinwaynecompanies.com>; Tony Mercer <AMercer@glotel.com>; Sandy Bringas <sbringas@apxengineering.com>; Michael Phillips <mphillips@apxengineering.com> Subject: RE: FPL St Lucie shelter - Manufacture CD Shows 190mph *Contact Info* Matt, That will be great. Contact info below. J03i7- kx Cicciv Plans M-aminerH Standard Buddrnglnspectnr Bud&—g-Plans F1=1i7er One and Two FamilyLhve&g,-Inspector One and Two FamilyPlans Examiner St Lucie CouniyPlannirgaudDevelopmeut-1; cmces �w 20�o a soar . a0sr s®n to.wlQik David Gutierrez Construction Manager I Office: 954-327-3110 1 Cell: 954-658-22621 Email: David.Gutierrez@FPL.com Joe Cicio From: Joe Cicio Sent: Wednesday, May 09, 2018 9:09 AM To: 'danault@olinwaynecompanies.com' Cc: Joe Cicio Subject: Review Comments for Permit Number 1804-0141 Attachments: Report -FL Review_Comments_Noncompliantjrf.pdf Dear St Lucie County Permit Applicant, Thank You for choosing to do business and invest in St Lucie County. St Lucie County is committed in assisting you to navigate the building review process. Please know that county staff is committed to customer service and part of that service is providing assistance and guidance with our processes. Please do not hesitate to contact us further to discuss your building project as needed. Please see the attached plan review comments which have been generated for your permit. As soon as we receive the modified plans and any additional required documents back from the Design Professional, Contractor, Fire Department or Owner we will forward the permit package to our permitting department for issuance. Josepk n &icio Plans Examiner II Standard Building Inspector Building Plans Examiner One and Two Family Dwelling Inspector One and Two Family Plans Examiner St. Lucie County Plannngand Development Services 772-462-6450 ii�f�i ,;usoia n. Moir 0 Places r,...r.�., to woe, � Please Note: Florida has very broad public records laws. Most written communications to or from County officials regarding County business are public records Available to the public and inedia upon request. It is the policy of St. Lucie County that all County records shall be open for personal inspection, examination and f or copying. Your a -mail communications will be subject to public disclosure unless an exemption applies to the communication. If you received this email in error, please notify the sender by reply e-mail and delete all materials from all computers. J Joe Cicio From: Gary Santora <garysantora@outlook.com> Sent: Tuesday, June 19, 2018 1:48 PM To: Joe Cicio Subject: RE: Permit Number: 1804-0141 - Requested Construction Cost Breakdown Hi Joe, Here's the shelter breakdown requested: The cost for Port St. Lucie shelter project: 1. New 12'x25' shelter with indoor 60kw generator: $9,19S.Otl 2. Construction labor/material 53 385:0'Q� 'Thanks, Gary From: Joe Cicio <cicioj@stlucieco.org> Sent: Tuesday, June 19, 2018 11:35 AM To:'Gary Santora' <garysantora@outlook.com> Cc: Joe Cicio <cicioj@stlucieco.org> Subject: RE: Permit Number: 1804-0141 - Requested Construction Cost Breakdown Gary, I z Please include the cost of the building and the generator Thanks Ime Joseph M. Cicio Plans Examiner Standard Building Inspector Building Plans Examiner One.and Two Family Dwelling Inspector One and Two Family Plans Examiner St Lwci,e. C¢u.whj PL&mft Kg aid. De wed o m vF Sery U e - Hots- wwY your wv, ce, today ** PUast, cz, h C"b Pefer-sovv, Ciu,i,edi,Kg Off ai,ad, of @sFLrticizco org to•s of your Wggey�, eovwwte.Yviy-"-d, feedback. � 1 S From: Gary Santora[mailto:aarysantora@outlook.com] Sent: Tuesday, June 19, 2018 11:32 AM To: Joe Cicio <cicioi@stlucieco.ore> Subject: Permit Number: 1804-0141- Requested Construction Cost Breakdown Hi Joe, Here's the cost breakdown that you requested last week to secure final approval, please let me know if this meets your approval. Construction breakdown: Labor- $39,299.45 Materials- $14,535.55 Total= $ 53,835.00 Thanks, r Gary Santora Site Acquisition Consultant On behalf of T-Mobile 516-782-8872 Please Note: Florida has very broad public records laws. Most written communications to or from County officials regarding County business are public records available to the public and media upon request. It is the policy of St. Lucie County that all County records shall be open for personal inspection, examination and or copying. Your e-mail communications will be subject to public disclosure unless an exemption applies to the communication. If you received this email in error, please notify the sender by reply e-mail and delete all materials from all computers. O i i 2