Loading...
HomeMy WebLinkAboutEVALUATION REPORTSCANNED EXTERIOR RESEARCH & DESIGN, I.I.C. BY Certificate of Authorization tl9503 TRINITY ERD St. Lucie County 353 CHRISTIAN STREET, UNIT #13 OXFORD, CT 06478 (203)262-9245 EVALUATION REPORT TRI-BUILT Materials Group, LLC Evaluation Report A42960.10.12-R6 PO Box 70 FC160�8 R Rutherford, NJ07070 Date of Issuance:10/25/2012 (800) 516-1485 Revision 6: 09/25/2017 SCOPE: This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen, P.E. for use of the product under the Florida Building Code and Florida Building Code, Residential Volume. The products described herein have been evaluated for compliance with the 6"I Edition (2017) Florida Building Code sections noted herein. DESCRIPnoN:j TRI-BUILT Roof Underlavments LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted herein. CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the referenced Quality Assurance documentation changes, or provisions of the Code that relate to the product change. Acceptance of this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. if the product changes or the referenced Quality Assurance documentation changes. Trinityl ERD requires a complete review of this Evaluation Report relative to updated Code requirements with each Code Cycle. ADVERTISEMENT: The Evaluation Report number preceded by the words "Trinityi ERD Evaluated" may be displayed in advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety. INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or its distributors and shall be available for inspection at the job site at the request of the Building Official. This Evaluation Report consists of pages 1 through 6. Prepared by: yamrtna„ — gPS Robert J.M. Nieminen, P.E. F1s: ' The faamule seals i was autborhedb Robert Nieminen, „earns v Florida Registration No. 59166, Florida DCA ANE1983 P.E. an W/canon. Uls does not same as anelearonimlN signed doarnenc CEmIFICATION OF INDEPENDENCE: 1. Trinityl ERD does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or distributing products it evaluates. 2. Trinityl ERD is not owned, operated or controlled by any company manufacturing or distributingproducts it evaluates. 3. Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any company manufacturing or distributing products for which the evaluation reports are being issued. 4. Robert Nieminen, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the product. 5. This is a building code evaluation. Neither Trinity] ERD nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained specifically for that purpose. VTRINITYIERD ROOFING COMPONENT EVALUATION: 1. SCOPE: Product Category: Roofing Sub -Category: Underlayment Compliance Statement: TRI-BUILT Roof Underlayments, as produced by TRI-BUILT Materials Group, LLC, have demonstrated compliance with the following sections of the 6t6 Edition (2017) Florida Building Code through testing in accordance with the following Standards. Compliance is subject to the Installation Requirements and Limitations / Conditions of Use set forth herein. 2. STANDARDS: Section Property Standard Year 1504.3.1 Wind Resistance FM 4474 2011 1504.3.1 Wind Uplift UL 1897 2012 1504.6 Accelerated Weathering ASTM G155 2005 1507.2.4/ 1507.1.1, 1507.2.9.2 Physical Properties ASTM D1970 2015 1507.3.3 Physical Properties FRSA/TRI April 2012 (04-12) 2012 3. REFERENCES: Ent Examination Reference Date ERD (T5T6049) Physical Properties 540540.02.13-1 02/19/2013 ERD (TST6049) Physical Properties 540540.11.13 11/19/2013 ERD (TST6049) Physical Properties 540540.03.14 03/26/2014 ERD (TST6049) Physical Properties 544870.04.14-2 04/02/2014 ERD (TST6049) Physical Properties 544870.04.14-3 04/02/2014 ERD (TST6049) Physical Properties 544870.04.14-1 04/10/2014 ERD (TST6049) Physical Properties 544870.04.14-4 04/10/2014 ERD (TST6049) Physical Properties 543530.02.14-1-R1 05/14/2014 ERD (TST6049) Physical Properties 543530.05.14 05/28/2014 ERD (TST6049) Physical Properties 540540.30.14 10/31/2014 ERD (TST6049) Physical Properties SC7645.02.15 02/13/2015 ERD (TST6049) Accelerated Weathering SC8520.04.15 05/27/2015 ERD (T5T6049) Wind Resistance SC14045.05.17-R1 06/07/2017 UL, LLC. (QUA9625) Quality Control Multiple -Listing R16814 12/10/2015 UL, L-C. (QUA9625) Quality Control Service Confirmation Exp. 07/18/2020 4. PRODUCT DESCRIPTION: , 4.1 _ri9CT alit_Sand-VSK'S6 fg�yTQpderlaymeSt is a self -adhering, glass -mat reinforced, sand -surfaced, SBS modified bitumen roof underlayment, with a 36-inch sheet width; meets ASTM D1970. 4.2 Tri-Built S/A HT TU Underlayment is a self -adhering, non -woven polyester fabric surfaced, SBS modified bitumen roof underlayment; meets ASTM D197O and FRSA/TRI April 2012. 4.3 Tri-Built Smooth HT S/A Underlayment is a self -adhering, glass -mat reinforced, film -surfaced, SBS modified bitumen roof underlayment; meets ASTM D3970. S. LIMITATIONS: 5.1 This is a building code evaluation. Neither TrinitylERD nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained specifically for that purpose. 5.2 This Evaluation Report is not for use in FBC HVHZ jurisdictions. 5.3 Fire Classification is not part of this Evaluation Report; refer to current Approved Roofing Materials Directory for fire ratings of this product. Exterior Research and Design, I.I.C. Evaluation Report A42960.10.12-R6 Certificate of Authorization 09503 e EDITION (2017) FBC NON-HVHZ EVALUATION FL16048-RG TRI-BUILT Roof Underlayments; (800) 516-1485 Revision 6: 09/25/2017 Page 2 of 6 �I TRINITY ERD 5.4 TRI-BUILT Roof Underlayments may be used with any prepared roof cover where the product is specifically referenced within FBC approval documents. If not listed, a request may be made to the Authority Having Jurisdiction for approval based on this evaluation combined with supporting data for the prepared roof covering. 5.5 Allowable Roof Covers: TABLE.1: ROOF.. COVER OPTIONS Underlayment Asphalt Nail -On Tile Foam -On Tile Metal Wood Shakes Slate Shingles $ Shingles Tri-Built Sand-R SA Shingle Yes No No No Yes Yes Underlayment Tri-Built S/A HT TU Yes Underlayment Yes Yes See 5.5.1 Yes Yes Yes Tri-Built Smooth HTS/A Underlayment Yes No No Yes Yes Yes 5.5.1 "Foam -On Tile" is limited to use of the following Approved tile adhesives / underlayment combinations. TABLE IA: ALLOWABLE TILE ADHESIVE / UNDERLAYMENT COMBINATION51 Adhesive Florida Product Approval Underlayments ICP Adhesives Polyset® AH-160 FL6332 Tri-Built S/A HT TU Underlayment Dow TileBondT" FL22525 Tri-Built S/A HT TU Underlayment 5.6 Allowable Substrates: 5.6.1 'tDve - - on o ec : Tri-Built Sand-R SA Shingle Underlayment, Tri-Built S/A HT TU Underlayment or Tri-Built Smooth HT S/A Underlayment applied to: ➢ Plywood; ASTM D41 primed plywood; OSB; ASTM D41 primed OSB; Southern Yellow Pine; ASTM D41 primed Southern Yellow Pine; ASTM D41 primed structural concrete. While not required over plywood, OSB or Southern Yellow Pine substrates, TRI-BUILT Materials Group, LLC recommends priming the deck if the final roof cover is not slated for installation within 24 hours. Note: TRI-BUILT Materials Group, LLC requires tongue -and -groove board decking be covered with plywood or OSB prior to installation of the self -adhering underlayment. 5.6.2 Bond -to -Insulation: Tri-Built Sand-R SA Shingle Underlayment, Tri-Built S/A HT TU Underlayment or Tri-Built Smooth HT S/A Underlayment applied to: ➢ Dens Deck Prime; SECUROCK Gypsum -Fiber Roof Board. For installation under mechanically attached prepared roof coverings, insulation shall be attached per minimum requirements of the prepared roof covering manufacturer's Product Approval. For installations under foam -on tile systems (Tri-Built S/A HT TU Underlayment only), insulation attachment shall be designed by a qualified design professional and installed based on testing of the insulation/underlayment system in accordance with FM 4474, Appendix D orTAS 114, Appendix!. 1 Refer to Tile Manufacturer's or Adhesive Manufacturer's Florida Product Approval for Overturning Moment Resistance Performance. EMedor Research and Design, LLC. Evaluation Report A42960.30.12-R6 CertiJkate ofAuthorization p9503 rEDITION (2017)FBC NON-HVHZ EVALUATION FL16048-R6 TRI-BUILT Roof Underlayments; (800) 516-1485 Revision 6:09/25/2017 Page 3 of 6 QOTRINITYI ERD 5.6.3 Bond to Mechanically Attached Base Laver: Tri-Built Sand-R SA Shingle Underlayment, Tri-Built S/A HT TU Underlayment or Tri-Built Smooth HT S/A Underlayment applied to: ➢ ASTM D226, Type I or II felt. For installations under mechanically attached prepared roof coverings, base layer shall be attached per minimum codified requirements. For installations under foam -on tile systems (Tri-Built S/A HT TU Underlayment only), base layer shall be attached per minimum requirements of FRSA/TRI April 2012 (04- 12). 5.6.4 Wind Resistance for Underlayment Systems in Foam -On Tile Applications: FRSA/TRI April 2012 (04-12) does not address wind uplift resistance of all underlayment systems beneath foam -on tile systems, where the underlayment forms part of the load -path. The following wind uplift limitations apply to direct -deck underlayment systems that are not addressed in FRSA/TRI April 2012 (04-12) and are used in foam -on tile applications. Maximum Design Pressure is the result of testing for wind load resistance based on allowable wind loads, and reflects the ultimate passing pressure divided by 2 (the 2 to 1 margin of safety per FBC 1504.9 has already been applied). Refer to FRSA/TRI April 2012 (04-12), Appendix A, Table 3A or FBC 1609 for determination of design wind pressures. #1 Maximum Design Pressure =-45.0 osf: Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Primer: (Optional) ASTM D41 or RESISTO EXTERIOR PRIMER Underlayment: Tri-BuiltS/A HTTU Underlayment, self -adhered. #2 Maximum Design Pressure =-67.5 osf: Deck: Structural concrete to meet project requirements to satisfaction of Authority Having Jurisdiction. Primer: Soprema Elastocol 600c Underlayment: Tri-Built S/A HT TU Underlayment, self -adhered. #3 Maximum Design Pressure = -150.0 osf: Deck: Min. 15/32-inch APA-rated BCX plywood (may be installed C-side up) to meet project requirements to satisfaction of Authority Having Jurisdiction. Deck Preparation: Plywood shall be thoroughly cleaned to remove dust and debris that may inhibit adhesion. All sheathing fasteners shall be driven flush with the surface. All sharp splinters and wood projections shall be removed/sanded. Primer: (Optional) RESISTO EXTERIOR PRIMER Underlayment: Tri-Built S/A HT TU Underlayment, self -adhered, shall be thoroughly roll using hand roller and/or weighted roller to ensure there are no voids, and ensure there are no voids/bridging at side and end -laps. #4 Maximum Design Pressure = -60.0 osf: Deck: Min. 19/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Soprema Sopra-G or Modified Sopra-G mechanically attached with nails (FBC 1517.5.1) and tin caps (FBC 1517.5.2) spaced 6-inch o.c. at the 4-inch laps and 6-inch o.c. in three, equally spaced rows in the center of the sheet. Underlayment: Tri-Built S/A HT TU Underlayment, self -adhered. Exterior Research and Design, I.I.C. Evaluation Report A42960.10.12-R6 CerOJlcote ofAuthorization 09503 6'" EDITION 120171 FBC NON-HVHZ EVALUATION FL36048-R6 TRI-BUILT Roof Underlayments; (900) 516-1485 Revision 6: 09/25/2017 Page 4 of 6 \, TRINITY ERD 5.6.4.1 For mechanically attached Base Sheet, the maximum design pressure for the selected assembly shall meet or exceed that required under FRSA/TRI April 2012 (04-12), Appendix A, Table 3A. Alternatively, the maximum design pressure for the selected assembly shall meet or exceed the Zone 1 design pressure determined in accordance with FBC 1609. In this case, Zones 2 and 3 shall employ an attachment density designed by a qualified design professional to resist the elevated pressure criteria. Commonly used methods are ANSI/SPRI WD3, FM Loss Prevention Data Sheet 1-29 and Roofing Application Standard RAS 117. Assemblies marked with an asterisk* carry the limitations set forth in Section 2.2.10.1 of FM Loss Prevention Data Sheet 1-29 (January 2016) for Zone 2/3 enhancements. 5.7 Exposure Limitations: Tri-Built Sand-R SA Shingle Underlayment or Tri-Built Smooth HT S/A Underlayment shall not be left exposed for longer than 30-days after installation Tri-Built S/A HT TU Underlayment shall not be left exposed for longer than 180-days after installation. 5.8 Tile Slippage Limitations RAS 103 per FRSA/TRI April 2012 (04-12)): When loading roof tiles on the underlayment in direct -deck tile assemblies, the maximum roof slope shall be as follows. These slope limitations can only be exceeded by using battens during loading of the roof tiles. TABLE 2: TILE SLIPPAGE LIMITATIONS FOR DIRER -DECK TILE INSTALLATIONS Underlayment Tile Profile Staging Method Maximum Slope Flat Max. 10-tile stack 6:12 Lugged Max. 10-tile stack 5:12 Max. 30-tile stack (bottom 2-tile stack shall be inverted, followed by 8 tiles high 6:12 on slope, as shown below) A oil Tri-Built S/A HT TU Underlayment -, Lugged i s Exterior Research and Design, U.C. Evaluation Report A42960.10.12-R6 Certificate of Authorization H9503 6'"EDITION (2017)FBC NON-HVHZ EVALUATION FL36048-R6 TRI-BUILT Roof Underlayments, (900) S16-1485 Revision 6:09/25/2017 Page S of 6 VTRINITYIERD 6. INSTALLATION: 6.1 TRI-BUILT Roof Underlayments shall be installed in accordance with TRI-BUILT Materials Group, LLC published installation requirements subject to the Limitations set forth in Section 5 herein and the specifics noted below. 6.2 Re -fasten any loose decking panels, and check for protruding nail heads. Sweep the substrate thoroughly to remove any dust and debris prior to application, and prime the substrate (if applicable). 6.3 Tri-Built Sand-R SA Shingle Underlavment, Tri-Built S/A HT TU Underlavment or Tri-Built Smooth HT S/A Underlavment: 6.3.1 Shall be installed in compliance with the requirements for ASTM D2970 underlayment in FBC Table 1507.1.1 for the type of prepared roof covering to be installed. 6.3.2 Non -Tile applications: While priming is optional, TRI-BUILT Materials Group, LLC recommends priming the deck if the final roof cover is not slated for installation within 24 hours. Apply sheet parallel to the roof edge. Roll out approximately 10 It of membrane and peel back the first 3 ft of release film. Adhere the exposed part to the substrate and unroll the remaining membrane as far as possible. Once the entire length of membrane is in place, peel -off the release film diagonally while holding the membrane tight. Firmly roll, broom or hand -press the membrane into place to achieve a bond. Horizontal seams should be minimum 3-inches, configured to shed water. Vertical seams should be 6- inches and staggered not less than 2-ft from vertical seams in the course below, sealed in accordance with TRI-BUILT Materials Group, LLC requirements. When installing at slopes above 8:12, TRI-BUILT Materials Group, LLC recommends back -nailing in the overlap area at the top of the sheet at 12-inch o.c. For Valleys and Ridges: Cut underlayment into 4 to 6 foot lengths. Peel the release paper and center sheet over valley or ridge. Drape and press sheet into place, working from the center of the valley or ridge in each direction. For valleys, apply the sheet starting at the lowest point and work upward. 6.3.3 Tile Applications (Tri-Built S/A HT TU Underlavment only): Reference is made to FRSA/TRI April 2012 (04-12) Installation Manual and Table 1 herein, using the instructions noted above as a guideline. For foam -on tile applications, reference is made to Section 5.6.4 herein for wind resistance limitations that fall outside the scope of FRSA/TRI April 2012 (04-12). Tile shall be loaded and staged in a manner that prevents tile slippage and/or damage to the underlayment. See Table 2 herein, and TRI-BUILT Materials Group, LLC published requirements for tile staging. 7. BUILDING PERMIT REQUIREMENTS: As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of this product. S. MANUFACTURING PLANTS: Gulfport, MS 9. QUALITY ASSURANCE ENTITY: UL, LLC —QUA9625; (314) 578-3406; k.chancellor@us.ul.com - END OF EVALUATION REPORT - Exterior Research and Design, LLC. Evaluation Report A42960.10.12-116 Certificate of Authorization p9S03 r EDITION (2017) FBC NON-HVH2 EVALUATION FL16048-RG TRI-BUILT Roof Underlayments; (800) 516-1485 Revision 6:09/25/2017 Page 6 of 6 t F TRINITY I ERD EVALUATION REPORT Owens Corning One Owens Corning Parkway Toledo, OH 43659 (740)404-7829 SCANNED BY St. Lucie County EXTERIOR RESEARCH & DESIGN, I.I.C. Certificate afAuthorization N9503 353 CHRISTIAN STREET, UNIT #13 OXFORD, CT 06478 (203)262-9245 ition Report 037940.02.12-RS i 1.10674-R13' Date of Issuance: 02/06/2012 Revision 8: 10/09/2017 SCOPE: This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen, P.E. for use of the product under the Florida Building Code and Florida Building Code, Residential Volume. The products described herein have been evaluated for compliance with the 6th Edition (2017) Florida Building Code sections noted herein. DESCRIPTION: O-- C-orning Asphalt-R6nfSh'Ing e's LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted herein and FBC 1507.2.7.1 / R905.2.6.1. CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the referenced Quality Assurance documentation changes, or provisions of the Code that relate to the product change. Acceptance of this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. if the product changes or the referenced Quality Assurance documentation changes. TrinityJERD requires a complete review of this Evaluation Report relative to updated Code requirements with each Code Cycle. ADVERTISEMENT: The Evaluation Report number preceded by the words "Trinityl ERD Evaluated" may be displayed in advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety. INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or its distributors and shall be available for inspection at the jab site at the request of the Building Official. This Evaluation Report consists of pages 1 through 8. Prepared by: Robert J.M. Nieminen, P.E. Florida Registration No. 59166, Florida DCA ANE1983 The facsimile seal appearing was authorized by Robert Nieminen, P.E. an 10/0912017. This does not serve as an electronically signed document. CERTIFICATION OF INDEPENDENCE: 1. Trinityl ERD does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or distributing products it evaluates. 2. Trinityl ERD is not owned, operated or controlled by any company manufacturing or distributing products It evaluates. 3. Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any company manufacturing or distributing products for which the evaluation reports are being issued. 4. Robert Nieminen, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the product. S. This is a building code evaluation. Neither Trinityl ERD nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained specifically for that purpose. TRINITY ERD ROOFING SYSTEMS EVALUATION: 1. SCOPE: Product Category: Roofing Sub -Category: Asphalt Shingles Compliance Statement: Owens Coining Asphalt Roof Shingles, as produced by Owens Corning, have demonstrated compliance with the fallowing sections of the 6" Edition (2017) Florida Building Code and Florida Building Code, Residential Volume through testing in accordance with the following Standards. Compliance is subject to the Installation Requirements and Limitations / Conditions of Use set forth herein. 2. STANDARDS: Section Property Standard Year 1S07.2.S, R905.2.4 Physical Properties ASTM D3462 2010 1507.2.7.1, R905.2.6.1 Wind Resistance ASTM D3161 2016 1507.2.7.1, R90S.2.6.1 Wind Resistance ASTM D7158 2011 3. REFERENCES: Entity Examination Reference Date UL LLC (CER9626) Physicals & Wind Resistance File R2453, Vol. 3 02/15/2007 UL LLC(CER9626) Physicals& Wind Resistance 20120516-R2453 05/16/2012 UL LLC (TST9628) Physical Properties 06CA20263 04/18/2006 UL LLC(TST9628) Wind Resistance 11CA34308 02/18/2012 UL LLC (TST9628) Physicals& Wind Resistance 4786093137 02/01/2014 UL LLC (TST9628) Wind Resistance 4786126532 02/10/2014 UL LLC (TST9628) Physical Properties Classification letter 02/13/2014 UL LLC (TST9628) Physical Properties Classification letter 10/02/2015 Miami -Dade (CER1592) FBC HVHZ Compliance Various NOAs Various ULLLC (QUA9625) Quality Control Service Confirmation Exp. 05/16/2020 4. PRODUCT DESCRIPTION: 4.1 Asphalt Shingles: 4.1.1 Classic and Supreme are fiberglass reinforced, 3-tab asphalt roof shingles. 4.1.2 Berkshire are fiberglass reinforced, 4-tab asphalt roof shingles. 4.1.3 Devonshire'" are fiberglass reinforced, S-tab asphalt roof shingles. 4.1.4 Duration, Tru Definition Duration*, Duration Premium Cool, TruDefinition Duration Designer Color Collection, TruDefinition0akridge, Oakridge and WeatherGuard HP are fiberglass reinforced, laminated asphalt roof shingles. 4.2 Hip & Ridge Shingles: 4.2.1 Berkshire Hip & Ridge Shingles, High Ridge, WeatherGuard HP Hip & Ridge Shingles, ProEdge Hip & Ridge Shingles and DuraRidge' Hip & Ridge Shingles are fiberglass reinforced, hip and ridge asphalt roof shingles. 4.3 Accessory Starter Strips: 4.3.1 Starter5trip Shingle, Starter Strip Plus and Starter Shingle Roll are starter strips for asphalt roof shingles. S. LIMITATIONS: 5.1 This is a building code evaluation. Neither TrinityJERD nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained specifically for that purpose. 5.2 This Evaluation Report is not for use in FBC HVHZ jurisdictions. 5.3 Fire Classification is not part of this Evaluation Report; refer to current Approved Roofing Materials Directory for fire ratings of this product. Exterior Research and Design, U.C. Evaluation Report 037940.02.12-R8 certificate ofAutharrrotlan 49S03 6' EDITION (20171 FBC NON-HVHZ EVALUATION FL10674-R13 Owens Coming Asphalt Roof Shingles Revision 8: 10/09/2017 Page 2 of 8 TRINITY ERD 5.4 Wind Classification: 5.4.1 All Owens Corning shingles noted herein are Classified in accordance with FBC Tables 1507.2.7.1 and R905.2.6.1 to ASTM D3161, Class F and/or ASTM D7158, Class H, indicating the shingles are acceptable for use in all wind zones up to Vew = 150 mph (Vurt = 194 mph). Refer to Section 6 for installation requirements to meet this wind rating. 5.4.2 All Owens Corning hip & ridge shingles, Starter Strip Shingle and Starter Strip Plus noted herein are Classified in accordance with FBC Tables 1507.2.7.1 and R905.2.6.1 to ASTM D3161, Class F, indicating the shingles are acceptable for use in all wind zones up to Vs, = 150 mph (Vu, = 194 mph). Refer to Section 6 for installation requirements to meet this wind rating. 5.4.3 Classification by ASTM D7158 applies to exposure category B or C and a building height of 60 feet or less. Calculations by a qualified design professional are required for conditions outside these limitations. Contact the shingle manufacturer for data specific to each shingle. 5.4.4 Refer to Owens Corning published information on wind resistance and installation limitations. 5.5 All products in the roof assembly shall have quality assurance audit in accordance with the Florida Building Code and F.A.C. Rule 61G20-3. 6. INSTALLATION: 6.1 Underlavment: 6.1.1 Underlayment shall be acceptable to Owens Corning and shall hold current Florida Statewide Product Approval, or be Locally Approved per Rule 61G20-3, per FBC Sections 1507.2.3, 1507.2.4 or R905.2.3. 6_2 Asphalt Shingles: 6.2.1 Installation of asphalt shingles shall comply with the manufacturers current published instructions, using minimum four (4) nails per shingle in accordance with FBC Sections 1507.2 or R905.2, with the following exceptions: E > Berkshire shingles require minimum five (5) nails per shingle. > WeatherGuard' HP shingles require minimum six (6) nails per shingle. > Devonshire'" shingles require minimum six (6) nails per shingle. > Starter Strip Shingle and Starter Strip Plus require minimum five (5) nails per strip. Refer to Owens Corning published information on wind resistance and installation limitations. 6.2.2 Fasteners shall be in accordance with the manufacturer's published requirements, but not less than FBC 1507.2.6 or R905.2.5. Staples are not permitted. 6.2.4 Where the roof slope exceeds 21 units vertical in 12 units horizontal, special methods of fastening are required. See figures below for details. 6.2.5 Minimum Nailing— Starter Strip Shingle and Starter Strip Plus: Felt cnderuyneent Desk WeasherLuck• rKy mMetlaymmt Dej,_ ' 'y Drip edge edge ^Ndh bated r-3' from tare Imteuust .y Sell ses&n sdN.. Swtn=Up Pofrioned along tree sHetJasti Ctemcved Stann Strip shingle ombangs ems and raku li?f Exterior Research and Design, U.C. certificate ofAuthothotion 99503 Fekwavkymrm rDM 6drtl6Nsd Yh+UnMee[ 's.. uderhlmeat by tlae one— massesaw ✓ 4nmeeve Im:AMN 6tNtN 6tdp Poe 6,R�ee[mr edtaeve Padtloneddet9 rNe stMN SNP Plus Ile--Rv ovNhemusm Nd rakes Evaluation Report 037940.02.12-R7 FL10674-1112 Revision 7: 04/18/2016 Page 3 of 8 6.2.8 Minimum Nailing- Devonshire'": �" 1 811 8�� B" 7" 1 _Ta 64/8' Psposure 1 n del locahon E3posidbn de 5 -5/6 pul9 56 I@tcaclbdel sellador TRINITY ERD a Nails Ten I' Spots of Asphalt goal Cement Standard 6-Nail Fastening Pattern Mansard or Steep Slope Fastening Pattern 6.2.9 Minimum Nailing - Duration", TruDe_f_initionls.Duration, Duration" Premium Cool & TruDefinition Duration Designer Color Collection: ..—_,_.�V_—LN=thWNneanaMCN _ xatryeeal N }r Standard Fastening Pattern lshitl"N a,•.MA wtrypeu Mansard or Steep Slope Fastening Pattern 6J 311 Pastening Pattern Su'MalChitxOpa.aVMa I/I�wt*Iwt+l ..— i '.... 6-Nail Fastening Pattern Exterior Research and 0esign, LLC. Evaluation Report 037940.02.12-R7 Certificate o/AuthaArudon 999e3 FL10674-R12 Revision 7: 04/18/2016 Page 5 of 8 TRINITY ERE) 6.2.1 Minimum Nailing—TruDefinition Oakridge°, Oakridge°: 4 Nil Pollan, Esquema con 4 rla vs r r N-- rr —►I k— m --sl 5� Eapasure tlapa 55/a"Exposun� Fxyos(C4n da 65/6yu'& CGva £rpazRan@55/ayWp. Standard Fastening Pattern 6 Nall Panarn Esquama cm 6 darns r r 5 &pmun 1Lm 55w Expo Cbvo Erpos(Cbn A,55/6pW3 Espuslei5aN 55/6pd9. •l _ �...� • i N•4TISk' Mansard or Steep Slope Fastening Pattern 6.2.1 Minimum Nailing— WeatherGuard° HP: 6-Nail Fastening Pattern t• �� t alnvb b VC �•,• .. :i;{;• 'j' Fra4rrrhiz FMLILts eb...a bier �. q.a6r Exterior Research and Be sign, LLC. Evaluatlan Report 037940.02.12-R7 0vt1ficate oJAatAoriaolion 49503 F1.10674-R32 Revision 7:04/18/2016 Page 6 of 8 TRINITY ERD 6.3 Hip & Ridge Shingles: 6.3.1 Installation of Berkshire Hip and Ridge Shingles, High Ridge, WeatherGuard HP Hip and Ridge Shingles and ProEdge Hip & Ridge Shingles shall comply with the manufacturer's current published instructions, using Four (4) nails per shingle. Installation of DuraRidgeno Hip & Ridge Shingles shall comply with the manufacturer's current published instructions, using two (2) nails per shingle. Refer to Owens Corning published information on wind resistance and installation limitations, including the use of hand -sealing for wind warranties. 6.3.2 Fasteners shall be in accordance with the manufacturer's published requirements, but not less than FBC 1507.2.6 or R905.2.5. Staples are not permitted. 6.3.3 Minimum Nailing — Berkshire® Hip & Ridge and High Ridge: 6.3.4 Minimum Nailing — WeatherGuard° HP Hip and Ridge: Fig. A ss tf IbIL• AQY P j I \I j Y i • i rEIWNn N Exterior Research and Design, LLe. certiifimte o/Authorization p9503 Fig. C Hip & Ridge Shingle Fastening T,Vv, T Yl 101W • T 1' .T e• E Lomry uL - I ---- -- IIr — - - --�I Evaluation Report 037940.02.12-R7 F1.10674-1112 Revision 7: 04/18/2016 Page 7 of 8 6.3.5 Minimum Nailing - ProEdge Hip & Ridge Shingles: Prevailing Wind Direction stdant Strip 6- Expomn \ Finten Td' Cevv Exposed Fasten . wkh Rcaf Cement TRINITY ERD Standard--tt,-- Fastoning Pattern L111 1Sealant 6' EaPoaber 6.3.6 Minimum Nailing— Dura Ridge'" Hip & Ridge Shingles: Note: The drawings below pertain to minimum, as -tested attachment requirements. Refer to Owens Corning published installation instructions for their minimum requirements. � On+a'len ��wi�d�rs< p�n,amaddv,m pP\r.amin,er.�� I I 1 t vue: qm Vim ugtrbt 7. LABELING: 7.1 Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted herein. 7.2 Asphalt shingle wrappers shall indicate compliance with one of the required classifications detailed in FBC Table 1507.2.7.1 / R905.2.6.1. 8. BUILDING PERMIT REQUIREMENTS: As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of this product. 9. MANUFACTURING PLANTS: Contact the named CIA entity for information on which plants produce products covered by Florida Rule 9N-3 CA requirements. 10. QUALITY ASSURANCE ENTITY: UL LLC—QUA9625 ; (414) 248-6409; karen.buchmann@ul.com - END OF EVALUATION REPORT - Exterior Research and Design, U.C. Evaluation Report 037940.02.12-R7 Crrtlflaafe ofaothorimtion e9503 FL10674-R72 Revision 7: 04/28/2016 Page 8 of 8