EVALUATION REPORT
CertainTeed Corporation Evaluation Report 3532.09.05-1113
20 Moores Road F15444-R12
Malvern, PA 19355 Date of Issuance: 09/22/2005
(610)651-5847 Revision 13:09/05/2017
SCOPE:
This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of
construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen, P.E. for
use of the product under the Florida Building Code "ft5"nVa`T-'u1Mffi o`$` , olume. The products described
herein have been evaluated for compliance with th 6th Edition (2017) Florida Building Code ections noted herein.
DESCRIPTION. CertainTeed Asphalt Roof Shingles. -�*^�
LABELING: Labeling shall be in accordance with the requirements of the Accredited Quality Assurance Agency noted herein
and FBC 1507.2.7.1 / R905.2.6.1
CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the referenced
Quality Assurance documentation changes, or provisions. of the Code that relate to the product change. Acceptance of this
Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. if the product changes or the
referenced Quality Assurance documentation changes. Trinity IERD requires a complete review of this Evaluation Report
relative to updated Code requirements with each Code Cycle.
ADVERTISEMENT: The Evaluation Report number preceded by the words "TrinitylERD Evaluated" may be displayed in
advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety.
INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or its
distributors and shall be available for inspection at the job site at the request of the Building Official.
This Evaluation Report consists of pages 1 through 12.
Prepared by:
Robert J.M. Nieminen, P.E.
Florida Registration No. 59166, Florida DCA ANE1983
CERTIFICATION OF INDEPENDENCE:
The facsimile seal appearing eras authorized by Robert Nieminen,
P.E. on 09/05/2017. Thu does not serve as an electroniwitysigned
dowment.
1. Trinityl ERD does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or
distributing products it evaluates.
2. Trinityl ERD is not owned, operated or controlled by any company manufacturing or distributing products it evaluates.
3. Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any company manufacturing or distributing products for
which the evaluation reports are being issued.
4. Robert Nieminen, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the
product.
5. This is a building code evaluation. Neither Trinityl ERD nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any
project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained
specificallyfor that purpose.
1 TRINITY ERD
ROOFING SYSTEMS EVALUATION:
1. SCOPE:
Product Category: Roofing
Sub -Category: Asphalt Shingles
Compliance Statement: CertainTeed Asphalt Roof Shingles, as produced by CertainTeed Corporation, have
demonstrated compliance with the following sections of the 6th Edition (2017) Florida Building Code and 6th Edition
(2017) Florida Building Code, Residential Volume through testing in accordance with the following Standards.
Compliance is subject to the Installation Requirements and Limitations / Conditions of Use set forth herein.
2. STANDARDS:
Section
Prooerty
Standard
Year
1507.2.5, R905.2.4
Physical Properties
ASTM D3462
2010
1507.2.7.1, R905.2.6.1
Wind Resistance
ASTM D3161
2016
1507.2.7.1, R905.2.6.1
Wind Resistance
ASTM D7158
2011
3. REFERENCES:
Entity
Examination
Reference
Date
UL(TST 1740)
ASTM
D3161
94NK9632
05/15/1998
UL(TST 1740)
ASTM
D3161
99NK26506
11/23/1999
UL(TST 1740)
ASTM
D3161
03CA12702
05/27/2003
UL(TST 1740)
ASTM
D3161
03CA12702
06/16/2003
UL(TST 1740)
ASTM
D3161
03NK29847
10/03/2003
UL(TST 1740)
ASTM
D3161
04CA11329
05/24/2004
UL(TST 1740)
ASTM
D3161
04CA32986
12/03/2004
UL(TST 1740)
ASTM
D3161
05NK07049
04/15/2005
UL(TST 1740)
ASTM
D3161
OSNK16778
05/12/2005
UL(TST 1740)
ASTM
D3161
05CA16778
05/12/2005
UL(TST 1740)
ASTM
D3161
05NK14836
05/22/2005
UL(TST 1740)
ASTM
D3161
OSNK22800
06/22/2005
UL(TST 1740)
ASTM
D3462
R684
09/21/2005
UL(TST 1740)
ASTM
D7158
OSNK08037
06/28/2006
UL(TST 1740)
ASTM
D3161 & D3462
09CA28873
07/23/2009
UL(TST 1740)
ASTM
D3462
IOCA41303
10/07/2010
UL(TST 1740)
ASTM
D3161
IOCA41303
10/08/2010
UL(TST 1740)
ASTM
D7158
IOCA41303
10/27/2010
UL(TST 1740)
ASTM
D3161 & D3462
10CA44960
11/11/2010
UL LLC(TST 9628)
ASTM
D3161, D3462 & D7158
13CA32897
11/21/2013
UL LLC(TST 9628)
ASTM
D3161, D3462
TFWZ.R684
04/22/2014
UL LLC (TST 9628)
ASTM
D7158
TGAH.11684
04/22/2014
UL LLC(TST 9628)
ASTM
D3161 & D3462
4786334434
09/16/2014
UL LLC(TST 9628)
ASTM
D3161 & D3462
4786570826
02/12/2015
UL LLC(TST 9628)
ASTM
D3161, D3462 & D7158
4786570717
12/16/2015
UL LLC(TST 9628)
ASTM
D3161 & D3462
4787195678
02/09/2016
UL LLC(TST 9628)
ASTM
D3161, D3462 & D7158
4787380356
10/26/2016
UL LLC(TST 9628)
ASTM
D3462
4787380357
10/13/2016
UL LLC(TST 9628)
ASTM
D7158
4787380357
11/08/2016
UL LLC(TST 9628)
ASTM
D3161
4787380357
11/09/2016
UL LLC(TST 9628)
ASTM
D3161, D3462 & D7158
4787586427
01/25/2017
UL LLC (QUA 9625)
Quality Control
Service Confirmation
Exp. 03/09/2020
Exterior Research and Design, U.C. Evaluation Report 3532.09.05-1113
CertiPcotc of Authorization#9503 6' EDITION (2017) FOC NON-HVHZ EVALUATION FL5444-R12
CertainTeed Asphalt Roof Shingles; (610) 651-5947 Revision 13: 09/05/2017
Page 2 of 12
TRINITY; ERD
4. PRODUCT DESCRIPTION:
4.1 CT2OT", XT" 25, XT" 30 and XT" 30 IR are fiberglass reinforced, 3-tab asphalt roof shingles.
4.2 Arcadia'", Belmont®, Belmont® IR, Carriage House Shangle®, Grand Manor Shangleo, Landmarks",
Landmark'" IR, Landmark'" Pro, Landmark'" Premium, Landmark'" TL, Landmark'" Solaris and
Landmarks" Solaris IR are fiberglass reinforced, laminated asphalt roof shingles.
4.3 NorthGate'" is a fiberglass reinforced, laminated, SBS modified bitumen roof shingle.
4.4 Presidential Shaker", Presidential Shaker" IR, Presidential Shake TLT" and Presidential Solaris'" are
fiberglass reinforced, architectural asphalt roof shingles.
4.5 Hatteras'", Highland Slate'" and Highland Slate"' IR are fiberglass reinforced, 4-tab asphalt roof shingles.
4.6 Patriot'" is a fiberglass reinforced asphalt roof strip -shingle (with no cut-outs) providing a laminated
appearance through an intermittent shadow line with contrasting blend drops for color definition.
4.7 Presidential Accessory, Accessory for Hatteras, Shangle Ridge TM, Shadow Ridge TM, Cedar Crests", Cedar
Crests" IR, NorthGate Ridge and NorthGate Accessory are fiberglass reinforced accessory shingles for hip
and ridge installation.
4.8 Any of the above listed shingles may be produced in AR (algae resistant) versions.
5. LIMITATIONS:
5.1 This is a building code evaluation. Neither TrinitylERD nor Robert Nieminen, P.E. are, in any way, the
Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was
used for permitting or design guidance unless retained specifically for that purpose.
5.2 This Evaluation Report is not for use within FBC HVHZ jurisdictions.
5.3 Fire Classification is not part of this Evaluation Report; refer to current Approved Roofing Materials
for fire ratings of this product.
5.4.1 All shingles noted herein are Classified in accordance with FBC Tables 1507.2.7.1 and R905.2.6.1 to ASTM
D3161, Class F and/or ASTM D7158, Class H, indicating the shingles are acceptable for us in all wind zones
up to Va:a = 150 mph (Valt = 194 mph). Refer to Section 6 for installation requirements to meet this wind
rating.„
5.4.2 Presidential Accessory, Accessory for Hatteras, Shangle Ridge, Shadow Ridge, Cedar Crest, NorthGate Ridge
and NorthGate Accessory hip & ridge shingles have been evaluated in accordance with ASTM D3161, Class
F. All except NorthGate Ridge and NorthGate Accessory require use of BASF Sonolastic NP 1 adhesive or
Henkel PLO Polyurethane Roof & Flashing Sealant, applied as specified in manufacturer's application
instructions, for use in wind zones up to V„d = 150 mph (Val, = 194 mph).
5.4.3 Classification by ASTM D7158 applies to exposure category B or C and a building height of 60 feet or less.
Calculations by a qualified design professional are required for conditions outside these limitations.
Contact the shingle manufacturer for data specific to each shingle.
5.4.3.1 Analysis in accordance with ASTM D7158 indicates the measured uplift resistance (R,) for the CertainTeed
asphalt Roof shingles listed in Section 4.1 through 4.6 (except Presidential Solarisr") exceeds the calculated
uplift force (FT) at a maximum design wind speed Of Va,d = 150 mph (Vul, = 194 mph) for residential
buildings located in Exposure D conditions with no topographical variations (flat terrain) having a mean
roof height less than or equal to 60 feet. The shingles are permissible under Code for installation in these
conditions using the installation procedures detailed in this Evaluation Report and CertainTeed minimum
requirements, subject to minimum codified fastening requirements established within any local
jurisdiction, which shall take precedence.
5.5 All products in the roof assembly shall have quality assurance audits in accordance with F.A.C. Rule 61G20-
3.
Exterior Research and Design, LLC. Evaluation Report 3532.09.05-R13
Certificate ofAuthorizaaon N9503 6'"EDITION (2017)FBC NON-HVH2 EVALUATION FL5444-R32
CertainTeed Asphalt Roof Shingles; (610) 651-SS47 Revision 13: 09/0512017
Page 3 of 12
r �
xr
' TRINITY, ERD
STEEP SLOPE
Use six nails andfonr spots of asphalt regime cement for erely fill LANDMARK TL
lanifiraterl shingle. Sec helow. Asp r t rem ing eemenl should meet
ASTNI D4586 Type U. Apply I' spots of asphalt roofing cement undo 131/2 f-13" 131/2"—�
each coiner and at above 12' to 13" in from each edge. (343 mm) (330 mm) (343 mm)
METRI(DIMENSIONS�I"(25mm)
(305 mm) ( (375. mm) 1 1305 mm)
M PER M
(25mm) I-�--
Figure 13-5: Use six nails andfoar spots of
asput ro0fnigoement on steep slopm
1V 14-3146 12"
05 mm)—. -~~ (375 mm)-- —(305 n
( ) Nailing l units
1' 25 mm behvBaq at 1' 25 mm
K nay
(25 mm)
I
ltoofing�am"�ent
Nailing areas for sleep slopes (greater than 21.12)
and "Storm -Nailing"
Nail between lower 2 nal Ines as shown above.
6.8.1 Hip & Ridge for Landmark•". Landmark'" IR, Landmark•" Pro, Landmark'"" Premium, Landmark'" TL,
Landmark" Solarts, LandmarkTM Solaris IR. NorthGate:
6.8.1.1 Option 1: Shadow Ridge'"" or NothGate Accessory
12' 1_ 97,1' J
— 6' 1 6' —
(150mm) I (150mm)
Centering
12 . i 7
15mm) Notches for Afignment to
the Top Edge of the Pn:vbus T
Cap for5'(125rmi) Exposure (19on
English Dimension
Shadow Ridge^'
Exterior Research and Design, U.C.
Certificate of Authorization N9503 6'"EDITION (2017)FBC NON-HVH2 EVALUATION
CertainTeed Asphalt Roof Shingles; (610) 651-5847
(250mm)
_415/1G'—415/16'-
025mm) 1 (125mm)
LlheT
edng1/4'/mmjAllgnmeM to 5.tthe Pmvbus7B1mm) Exposure (i m)
Metric Dimension
Shadow RidgeTM
Evaluation Report 3532.09.05-1113
FL5444-R12
Revision 13:09/05/2017
Page 8 of 12
r
6.8.1.2
6.8.1.3
��. TRINITY ERD
92717
4 i'Ll6' (125 rom}
—+—{393 mm)—s
(ktdemp Notch I rti S/Bvlt-6 m
(188 mm 168mmm)
)
13 /4'
(337 mm) ` Nron / Centering
MIGteL'Atep 75.6' 13114' Notch
14,
prNau9a4aurS¢ ( mm I (a37 nontign ) �Ai(hose
194 7� .
notches to top (�mm)
edge of
previous rmvrse.
NorthGate Ridge NorthGate Accessory
12" J
�(s05mm)— ILaying Notch
I � I
Figure 13-7M (Ise latqngno(ebas to centersbinglis on hips and
ridges, and to /oen(a Me correct arposum..
For ASTM D3161, Class F performance use BASF "Sonolastic® NPIm" adhesive or Henkel "PLO
Polyurethane Roof & Flashing Sealant", in accordance with CertainTeed requirements.
Option 2: Refer to instructions herein for Cedar Crest'"', Cedar Crest'" IR hip and ridge shingles.
Exterior Research and Design, I.I.C. Evaluation Report 3532.09.05-R13
Certificate of Authadratlon#9503 6t"EDrrION(2017)FBC NON-HVHZ EVALUATION FL5444-1312
CertainTeed Asphalt Roof Shingles; (610) 651-5847 Revision 13:09/05/2017
Page 9 of 12