EVALUATION REPORT
r
Ifs_ COPY
EXTERIOR RESEARCH & DESIGN, I.I.C.
Q �s Certificate of Authorization #9503
C1 353 Certificate
STREET, UNIT#13
ST. LUCIE GbUNTY OXFORD, CT 06478
BUILDING DIVISION (203) 262-9245
REVIEWED Z I.
Owens Corning REVIEWED BY Evaluation Report 037940.02.12-118
One Owens Corning Parkway DATE F1.30674-11113
Toledo, OH 43659 PLANS AND PERK% Date of Issuance: 02/06/2012
(740) 404-7929 MUST BE KEPT ON JOB OR Revision 8: 10/09/2017
NO INSPECTION WILL BE MADE
SCOPE:
This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of
construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen,
P.E. for use of the product under the Florida Building Code and Florida Building Code, Residential Volume. The
products described herein have been evaluated for compliance with the 6t' Edition (2017) Florida Building Code
sections noted herein.
DESCRIPTION: Owens Corning AssphaliiiRoof in 1es
LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted
herein and FBC 1507.2.7.1 / R905.2.6.1.
CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the
referenced Quality Assurance documentation changes, or provisions of the Code that relate to the product change.
Acceptance of this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. if the
product changes or the referenced Quality Assurance documentation changes. TrinitylERD requires a complete
review of this Evaluation Report relative to updated Code requirements with each Code Cycle.
ADVERTISEMENT: The Evaluation Report number preceded by the words 'TrinityI ERD Evaluated" may be displayed in
advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety.
INSPEcrION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or
its distributors and shall be available for inspection at the job site at the request of the Building Official.
This Evaluation Report consists of pages 1 through 8.
Prepared by:
Robert J.M. Nieminen, P.E.
Florida Registration No. 59166, Florida DCA ANE1983
THESE PLANS AND ALL PROPOSED WORD
ARE SUBJECT TO ANY CORRECTIONS ;a
REQUIRED By FIELD INSPECTORS THAT,'
t``�; CIIAy BI; i�ECE3S:�Ry Ir l O�10EI1 :
CO"11PLY uViPH r:; L:'1'LICd `i GODES,I
The facsimile seal appearing was authorized by Robert
Nieminen, P.E. on 10/09/2017. This does not serve as an
electronically signed document
CERTIFICATION OF INDEPENDENCE:
1. Trinity IERD does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or
distributing products it evaluates.
2. Trinityl ERD is not owned, operated or controlled by any company manufacturing or distributing products it evaluates.
3. Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any company manufacturing or distributing products for
which the evaluation reports are being issued.
4. Robert Nieminen, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the
product.
5. This is a building code evaluation. Neither Trinity ERD nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any
project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained
specifically for that purpose.
Pm®I C®,�
�TRINITYJ ERD
ROOFING SYSTEMS EVALUATION:
1. SCOPE:
Product Category: Roofing
Sub -Category: Asphalt Shingles
Compliance Statement: Owens Corning Asphalt Roof Shingles, as produced by Owens Corning, have demonstrated
compliance with the following sections of the I `h Edition (2017) Florida Building Code and Florida Building Code,
Residential Volume through testing in accordance with the following Standards. Compliance is subject to the
Installation Requirements and Limitations/ Conditions of Use set forth herein.
2. STANDARDS:
Section Pro a Standard Year
1507.2.5, R905.2.4 Physical Properties ASTM D3462 2010
1507.2.7.1, R905.2.6.1 Wind Resistance ASTM D3161 2016
1507.2.7.1, R905.2.6.1 Wind Resistance ASTM D7158 2011
3. REFERENCES:
Eathl Examination Reference Date
UL LLC (CER9626) Physicals & Wind Resistance File R2453, Vol. 3 02/15/2007
UL LLC (CER9626) Physicals & Wind Resistance 20120516-R2453 05/16/2012
UL LLC (TST9628) Physical Properties OGCA20263 04/18/2006
UL LLC (TST9628) Wind Resistance 11CA34308 02/18/2012
UL LLC (TST9628) Physicals & Wind Resistance 4786093137 02/01/2014
UL LLC (TST9628) Wind Resistance 4786126532 02/10/2014
UL LLC (TST9628) Physical Properties Classification letter 02/13/2014
UL LLC (TST9628) Physical Properties Classification letter 10/02/2015
Miami-Dade(CER1592) FBC HVHZ Compliance Various NOAs Various
ULLLC (QUA9625) Quality Control Service Confirmation Exp.05/16/2020
4. PRODUCT DESCRIPTION:
4.1 Asphalt Shineles:
4.1.1 Classic and Supreme are fiberglass reinforced, 3-tab asphalt roof shingles.
4.1.2 Berkshire are fiberglass reinforced, 4-tab asphalt roof shingles.
4.1.3 DevonshireTM are fiberglass reinforced, 5-tab asphalt roof shingles.
4.1.4 Duraattio�n TruDefinitioe Duration*, Duration Premium Cool, TruDefinitioe Duration Designer Color
Col ecl tion, TruDefinitioe Oakridge Oak , ridge.dand WeatherGuard HP are fiberglass reinforced, laminated
asphalt roof shingles.
4.2 Hip & Ridge Shingles:
4.2.1 Berkshire Hip & Ridge Shingles, High Ridge, WeatherGuard HP Hip & Ridge Shingles, Pro Edge Hip & Ridge
Shingles and DuraRidge' Hip & Ridge Shingles are fiberglass reinforced, hip and ridge asphalt roof shingles.
4.3 Accessory Starter Strips:
4.3.1 Starter Strip Shingle, Starter Strip Plus and Starter Shingle Roll are starter strips for asphalt roof shingles.
S. LIMITATIONS:
5.1 This is a building code evaluation. Neither TrinityiERD nor Robert Nieminen, P.E. are, in any way, the
Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used
for permitting or design guidance unless retained specifically for that purpose.
5.2 This Evaluation Report is not for use in FBC HVHZ jurisdictions.
5.3 Fire Classification is not part of this Evaluation Report; refer to current Approved Roofing Materials Directory
for fire ratings of this product.
Exterior Research and Design, LLC. Evaluation Report 037940.02.12-R8
CenificaN, fAUth dzgd.n#9303 6' EDITION(2017) FBC NON-HVHZ EVALUATION FL10674-R13
Owens Coming Asphalt Roof Shingles Revision 8. 10/09/2017
4age Z'of
�I I KINITY ERD
5.4 Wind Classification:
5.4.1 All Owens Corning asphalt shingles noted herein are Classified in accordance with FBC Tables 1507.2.7.1
and R905.2.6.1 to ASTM D3161, Class F and/or ASTM D7158, Class H, indicating the shingles are acceptable
for use in all wind zones up to Vasd = 150 mph (V„„ = 194 mph). Refer to Section 6 for installation
requirements to meet this wind rating.
5.4.2 All Owens Corning hip & ridge shingles, Starter Strip Shingle and Starter Strip Plus noted herein are
Classified in accordance with FBC Tables 1507.2.7.1 and R905.2.6.1 to ASTM D3161, Class F, indicating the
shingles are acceptable for use in all wind zones up to Va,d = 150 mph (Val, = 194 mph). Refer to Section 6 for
installation requirements to meet this wind rating.
5.4.3 Classification by ASTM D7158 applies to exposure category B or C, as defined in FBC 1609.4.3, and a mean
roof height of 60 feet or less. Calculations by a qualified design professional are required for conditions
outside these limitations. Contact the shingle manufacturer for data specific to each shingle.
5.4.4 Refer to Owens Corning published information on wind resistance and installation limitations.
5:5 All products in the roof assembly shall have quality assurance audit in accordance with F.A.C. Rule 61G20-3.
6. INSTALLATION:
5.1 Underlavment:
6.1.1 Underlayment shall be acceptable to Owens Corning and shall hold current Florida Statewide Product
Approval, or be Locally Approved per Rule 61G20-3, per FBC 1507.2.3,1507.2.4 or R905.2.3.
6.2 Asphalt Shingles:
6.2.1 Installation of asphalt shingles shall comply with the Owens Corning current published instructions, using
minimum four (4) nails per shingle in accordance with FBC 1507.2.7 or R905.2.6, with the following
exceptions:
➢ Berkshire shingles require minimum five (5) nails per shingle.
➢ WeatherGuard HP shingles require minimum six (6) nails per shingle.
➢ Devonshirem shingles require minimum six (6) nails per shingle.
➢ Starter Strip Shingle and Starter Strip Plus require minimum five (5) nails per strip.
Refer to Owens Corning published information on wind resistance and installation limitations.
6.2.2 Fasteners shall be in accordance with the manufacturer's published requirements, buf not less than FBC
1507.2.6 or R905.2.5. Staples are not permitted.
6.2.4 Where the roof slope exceeds 21 units vertical in 12 units horizontal, special methods of fastening are
required. See figures below for details.
6.2.5 Minimum Nailing —Starter Strip Shingle and Starter Strip Plus:
Exterior Research and Design, LLC. Evaluation Report 037940.02.12-R8
Certificate ofAuthcrkadon 09503 e EDITION (2017) FBC NON-HVHZ EVALUATION F1.10674-1133
Owens Corning Asphalt Roof shingles Revision 8: 10/09/2017
Page 3 of 8
6.2.6 Minimum Nailing — Classics' &Supreme:
Normal Mansard or Area pars
wind Ames High Wind dmvenes y
Aran par, vienros normales Arms vientos .%.
tr n•
E•E40mra
Esposleidn
6.2.7 Minimum Nailing — Berkshire®:
r
ow- I 9Yf I 9Yf ' HYft
i'
Standard Fastening Pattern
Exterior Research and Design, I.I.C.
Certificate of Authadpolian 09503
�1 I j�ININ I ERD
Normal Mansard or Area papa
Wind Aram High Wind dasvanas y
Area papa vionnas nonnales Areas rionros /uertes
t: IAI s t t' t' x' IBI x. ^'
6 6/8' Exposure
Erposiei6a
6-Nail Fastening Pattern
Seahlastrip _
• OdndeselWdor '
aYf SYf 89f 9Yf
r
t
Z, - Asphah roaring cement
CuxnbdetrsDadoadaso
Mansard or Steep Slope Fastening Pattern
EDITION (2017) FBC NON-HVHZ EVALUA
Owens Coming Asphalt Roof Shingles
Evaluation Report 037940.02.12-R8
FL10674-R13
Revision 8: 10/09/2017
Page 4 of 8
6.2.8 Minimum Nailing— Devonshire:
= 7" 8" 8" 8" 7" I �"
N
58/8, exposure Sealant location
Exposid6n de 5.5l8 pulg Ubiaaddn del sellador
Standard 6-Nail Fastening Pattern
zw
\ TRINITY ERD
Mansard or Steep Slope Fastening Pattern
6.2.9 Minimum Nailing -Duration®, TruDefinition® Duration, Duration® Premium Cool & TruDefinition
Duration Designer Color Col en:
4-Nal Fastening Pattern
aveNav9raRnmewvlmn
F� F� FL
Nan,lypim
1• 1S 1Y 1•
•��aw" • s Wa -• m.0 rive... •.
6 T
Standard Fastening Pattern
6-Nall Fastening Patter
siuM+au®famni!R yxc ONeM1
F1 F�
Nan IYW W
t• lY tY
6 n•
Mansard or Steep Slope Fastening Pattern
Exterior Research and Design, U.C. Evaluation Report 037940.02.12-Rg
Certi)imte of Authorization Q9503 6rvEDITION (2017)FBC NON-HVHZ EVALUATION FL10674-R13
Owens Corning Asphalt Roof shingles Revision 8: 0/091201
Pag S oLg
6.2.1 Minimum Nailing—TruDefinition OakridgeO,Oakridge�:
4 Nail Pattem
Esquema wn 4 claws;
r r
IF ,z —►1 I<— tz
554 E*pm m Nass 551r ExpMM
apm Won de 65/8pli& Crams Expostrinnh 6618pulg.
Standard Fastening Pattern
6 Nail Pattom
Esquema con 6 claws
i
551a" Bfpmm
Erposiu6nde55/6prdg
Mansard or Steep Slope Fastening Pattern
6.2.1 Minimum Nailing—WeatherGuard®HP:
:tip :{•}: a•' •:.t}
1 NTINITYIERD
$Ingle 61ty VbW
Vhb Ltdnl
ilmill�Cbwmub ftwdslfli1
lir�aai111�6flj�dir
u
5519"Exposure '
Exposabnde 65/6D&dg
Exterior Research and Design, U.C. Evaluation Report 037940.02.12-Rg
Certificate oJAuthorizotion 49503 6"' EDITION (2017) FBC NON-HVH2 EVALUATION FL10674-1113
Owens Corning Asphalt Roof Shingles Revision 8: 10/09/2017
,Page 5 of B
NTINrryj ERD
6.3 Hip & Ridge Shingles:
6.3.1 Installation of Berkshire Hip and Ridge Shingles, High Ridge, WeatherGuard HP Hip and Ridge Shingles
and ProEdge Hip & Ridge Shingles shall comply with the Owens Corning current published instructions,
using four (4) nails per shingle. Installation of DuraRidge' Hip & Ridge Shingles shall comply with the
Owens Corning current published instructions, using two (2) nails per shingle. Refer to Owens Corning
published information on wind resistance and installation limitations, including the use of hand -sealing for
wind warranties.
6.3.2 Fasteners shall be in accordance with the manufacturer's published requirements, but not less than FBC
1507.2.6 or R905.2.5. Staples are not permitted.
6.3.3 Minimum Nailing— Berkshire® Hip & Ridge and High Ridge:
Fig. i 4
r o,erddwmwna
ptreCNn P
aaYf�� P
4
\\\L I I
P I I
I I
P
4 I I I I
A I I I I
I I
P I I I
6.3.4 Minimum Nailing— WeatherGuard® HP Hip and Ridge:
Fig. A 4 4
Plbauum
�—olMbn A
A
nalb �—y44
A I I
p I I
I i
Fig. C Hip & Ridge Shingle Fastening
ToPVb
MI6 Mlh
T
1' 1'
5^ �Omin
1
12
Exterior Research and Design, U.C. Evaluation Report 037940.02.12-RS
Certiflrore cfauthori:atlon 09503 (P EDMON (2017) FBC NON-HVHZ EVALUATION FL10674-1113
Owens Coming Asphalt Roof Shingles Revision 8: 10/09/2017
Page 7 of 8
6.3.5 Minimum Nailing - ProEdge Hip & Ridge Shingles:
Prevailing
Wind Direction Sealant Stdp
.—` 6'Expasure
Fasten 7%'
Cover Exposed
Fasteners with
Roof Cement
'� I TRINITY ERD
Standard-11•
Fastening
Pattern
12' I Sealant
7r!' 6'Exposr
I�17. 11
6.3.6 Minimum Nailing— DuraRidgeT" Hip & Ridge Shingles:
Note: The drawings below pertain to minimum, as -tested attachment requirements. Refer to Owens Corning
published installation instructions for their minimum requirements.
Nib —
eia
7. LABELING:
DinDY;.In d Direction
aieoWad
U=0dimt
Dinrdandddmm prrdmdmam
7.1 Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted
herein.
7.2 Asphalt shingle wrappers shall indicate compliance with one of the required classifications detailed in FBC
Table 1507.2.7.1 / R905.2.6.1.
8. BUILDING PERMIT REQUIREMENTS:
As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of
this product.
9. MANUFACFURING PLANTS:
Contact the named QA entity for information on which plants produce products covered by Florida Rule 9N-3 QA
requirements.
10. QUALiTy AssuRANCEENTITy:
ULLLC—QUA9625;(631)546-2458;Kanchi.Agrawala-Dokania@ul.com
- END OF EVALUATION REPORT -
Exterior Research and Design, I.I.C. Evaluation Report 037990.02.12-118
rertilicote of Authorization#9503 6TM EDITION (2017) FBC NON-HVHZ EVALUATION FL106741113
Owens Coming Asphalt Roof Shingles Revision 8: 10/09/2017
Page 8 of 8
_ALE COPY
r ^—
SCANNED EXTERIOR RESEARCH 9, DESIGN, L-C.
BY Certificate of Authorization N9503
p {�'NI 1 1 ��/ ERD St. Lucie Count 353 CHRISTIAN STREET, UNIT#13
U ,Y OXFORD, CT 06478
PHONE: (203) 262-9245
FAX: (203) 262-9243
EVALUATION REPORT
Interwrap, Inc. Evaluation Report 140510.02.12-R3
32923 Mission Way FL15216-113
Mission, BC V2V-6E4 Canada Date of Issuance: 02/17/2012
(5S1) 574-2939 Revision 3:10/10/2017
SCOPE:
This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of
construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen,
P.E. for use of the product under the Florida Building Code and Florida Building Code, Residential Volume. The
I products described herein have been evaluated for compliance with the 6" Edition (2017) Florida Building Code
I sections noted herein.
DESCRIPTION: RhinoR000f,Underlayments�
LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted
herein.
CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the referenced
Quality Assurance documentation changes, or provisions of the Code that relate to the product change. Acceptance of
this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. if the product
changes or the referenced Quality Assurance documentation changes. Trinity ERD requires a complete review of this
Evaluation Report relative to updated Code requirements with each Code Cycle.
ADVERTISEMENT: The Evaluation Report number preceded by the words "Trinity) ERD Evaluated" may be displayed in
advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety.
INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or
its distributors and shall be available for inspection at the job site at the request of the Building Official.
This Evaluation Report consists of pages 1 through 3.
Prepared by:
Robert J.M. Nieminen, P.E.
Florida Registration No. 59166, Florida DCA ANE1983
THESE PLANS AND ALL PROPOSED WORK
ARE SUBJECT TO ANY CORRECTIONS
REQUIRED By FIELD INSPECTORS THAT
`-"AAY On NECEVARy IN ORDER TO Off,`
The facsimile seal appearing was authorized by Robert
Nieminen, P.E. on 10/1012017. This does not serve as an
electronically signed document
CERTIFICATION OF INDEPENDENCE:
1. TrinitylERD does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or
distributing products it evaluates.
2. Trinityl ERD is not owned, operated or controlled by any company manufacturing or distributing products it evaluates.
3. Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any company manufacturing or distributing products for
which the evaluation reports are being issued.
4. Robert Nieminen, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the
product
S. This Is a building code evaluation. Neither Trinityl ERD nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any
project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained
specifically for that purpose.
� � opv
"',JTPJN1TY1 ERD
ROOFING COMPONENT EVALUATION:
1. SCOPE:
Product Category: Roofing
Sub -Category: Underlayment
Compliance Statement: RhinoRoof Underlayments, as produced by Interwrap, Inc., has demonstrated compliance
with the following sections of the a Edition (2017) Florida Building Code through testing in accordance with
applicable sections of the following Standards. Compliance is subject to the Installation Requirements and
Limitations / Conditions of Use set forth herein.
2. STANDARDS:
Section Properties Standard Year
1507.1.1, T1507.1.1 Unrolling, Breaking Strength, Pliability ASTM D226 2009
1507.1.1 Tear Strength ASTM D1970 2015
3. REFERENCES:
Entity Examination Reference Date
ITS(TST1509) Physical Properties 100539395COQ-006 10/27/2011
ITS (TST1509) Physical Properties 100539395COQ 002 10/27/2011
ITS (TST1509) Physical Properties 100539395COQ-006 03/14/2014
PRI(TSTSB7R) ASTM D1970;Tear strength OCF-330-02-02 10/03/2017
ITS (QUA1673) Quality Control Service Confirmation 09/30/2017
4. PRODUCTDEsCRipriON:
4.1* RhincRoof U20 is a multilayered polymer woven coated synthetic roof underlayment available in 42-inch
wide rolls, and can be produced in various other sizes; meets FBC 1507.1.1 (Exception).
S. LIMITATIONS:
5.1 This is a building code evaluation. Neither Trinity IERD nor Robert Nieminen, P.E. are, in any way, the
Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was
used for permitting or design guidance unless retained specifically for that purpose.
5.2 This Evaluation Report is not for use in FBC HVHZ jurisdictions.
5.3 Fire Classification is not part of this Evaluation Report; refer to current Approved Roofing Materials
Directory or test report from accredited testing agency for fire ratings of this product.
5.4 RhinoRoof Underlayments may be used with any prepared roof cover where the product is specifically
referenced within FBC approval documents. If not listed, a request may be made to the Authority Having
Jurisdiction for approval based on this evaluation combined with supporting data for the prepared roof
covering.
5.5 Allowable Roof Covers:
- - TABLE I: ROOFfOVEROPTIONS _ -
Underlaym2Rnt
Asphalt
Shingles
Nail -On Tile
Foam -On Tile
Metal
Wood Shakes
&Shingles
Slate or
Simulated Slate
rRiriioofU20o
- No
Yes
'Yes
No
5.6 Exposure Limitations:
RhinoRoof U20 shall not be left exposed for longer than 30-days after installation.
Exterior Research and Design, LLC. Evaluation Report 140510.02.12-R3
Certificate ofAuthorizotion#9503 6'EOITION(20171 FBC NON-HVHZ EVALUATION FL35216-R3
RhinaRoof Underlayments Revision 3: 20/10/2017
Page 2 of 3
,, I KINIIY I ERD
6. INSTALLATION:
6.1 RhinoRDof Underlayments shall be installed in accordance with Interwrap, Inc. published installation
instructions subject to the Limitations set forth in Section 5 herein and the specifics noted below.
6.2 Re -fasten any loose decking panels, and check for protruding nail heads. Sweep the substrate thoroughly to
remove any dust and debris prior to application.
RhinoRoof U20:
6.3.1 -,_ Shall be installed in compliance with the requirements for ASTM D226, Type I or II underlayment in FBC
Table 1507.1.1 for the type of prepared roof covering to be installed, taking into account the wider sheet -
width for double -layer applications.
6.3.1 Fasteners:
For exposure < 24 hours, corrosion resistant fasteners may be 1-inch roofing nails with a 3/8-inch diameter
head, or those noted in 6.4.2. The use of staples is prohibited.
For exposure > 24 hours up to maximum 30 days, corrosion resistant fasteners shall be in 1-inch
diameter plastic or metal cap nails or FBC HVHZ nails & 1-5/8" diameter tin caps (with the rough edge facing
up). The use of staples is prohibited.
6.3.2 Single Laver: Roof Slope >4:12:
End (vertical) laps shall be minimum 6-inches and side (horizontal) laps shall be minimum 4-inches. Refer to
Interwrap, Inc. recommendations for alternate lap configurations and/or the use of sealant under certain
conditions.
For exposure < 24 hours, use of every -other fastening location printed on the surface is acceptable. For
exposure > 24 hours up to maximum 30-days, use of every fastening location printed on the surface is
required.
When batten systems are to be installed atop the underlayment, the underlayment need only be
preliminarily attached pending attachment of the battens on the same day. Battens shall not be positioned
over cap nails. If this occurs, remove the cap nail and patch the hole in accordance with Interwrap
published instructions.
6.4.3 Double Layer: 2:12< Roof Slope <4:12:
End (vertical) laps shall be minimum 12-inches and side (horizontal) laps shall be minimum half -sheet -width
plus 1-inch.
Double layer application; begin by fastening a half -width plus 1-inch starter strip along the eaves. Place a
full -width sheet over the starter, completely overlapping the starter course. Continue as noted in 6.5, but
maintaining minimum half -width plus 1-inch side (horizontal) laps, resulting In a double -layer application.
BUILDING PERMIT REQUIREMENTS:
As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of
this product.
8. MANUFACTURING PLANTS:
Qingdao, China
9. QUALITY ASSURANCE ENTITY:
Intertek Testing Services NA Inc. — QUA1673; (608) 836-4400
- END OF EVALUATION REPORT -