Product Evaluation Report
Rule 61G20-3 F.A.C. I Report No. 2386, Rev. 1 I Project No. 417-1015 1 12/6/17 1 Page 1 of 2
Manufacturer
Kennedy Skylights
5294 Tower Way
Sanford, FL 32773
Code: Current Edition of the Florida Building Code
Product Series. Model and/or Description
ISFG4 Curb Mounted Glass Skylight
Large Missile Impact
Compliance Methods: Product Approval Rule 61G20-3.005(1)(a) —Certification Mark or Listing
Product Installation Instructions: FILE COPY
• KENN0004, Rev. B, dated 12/6/17, signed and sealed by Robert J. Amoruso, Kennedy Skylights "ISFG4" Curb
Mounted Self -Flashing Glass Skylight - LMI, Installation Anchorage Details
Engineering Analysis Et Product Evaluation: The following engineering and/or rational analysis/calculations have been
performed.
Anchorage and product verification has been substantiated by calculation (PTC Report. No. 2058-1 and 2058-2)
prepared, signed and sealed by RobertJ. Amoruso, P.E. in accordance with the current edition of the Florida
Building Code.
Design Pressure Evaluation/Product Evaluation
• Drawing No. KENN0004
o Product Name/Series: "ISFG4" Curb Mounted Self -Flashing Glass Skylight - LMI
o High Velocity Hurricane Zone (HVHZ): NO
o Outside High Velocity Hurricane Zone (HVHZ): YES
o Impact Resistant: YES
• Glazed laminated product using KurarayTrosifol PVB Glass Interlayer by Kuraray America, Inc.
Current Kuraray America NOA can be found here.
• National Certified Test Laboratory, Inc. Test Report No. NCTL-230-2959-1
• Design Pressure
• +/-52.5 psf
• Margin of Safety = 2 applied for positive and negative loading to Structural Design Pressure per
Sections 1504 and 1523 of the current edition of the FBC and MD FAQ
(http://www.miamidade.gov/building/products/skylights.aso .
• Performance and Testing Standards
Test Report No. NCTL-210-2959-1
o ASTM E330-90
o ASTM E331-93 SCANNED
o ASTM E283-91 BY
o ASTM E1886-99 St. Lucie County
o ASTM E1996-99
Performance Testing Standards:
• ASTM E330-90, Standard Test Method for Structural Performance of Exterior windows, Doors, Skylights and
Curtain Walls by Uniform Static Air Pressure Difference
• ASTM E331-93, Standard Test Method for Water Penetration of Exterior Windows, Skylights, Doors, and Curtain
Walls by Uniform Static Air Pressure Difference
• ASTM E283-91, Standard Test Method for Determining Rate of Air Leakage Through Exterior Windows, Curtain
Walls, and Doors Under Specified Pressure Differences Across the Specimen
�A�A� PTC Product Design Group, LLC I PO Box 520775 1 Longwood, FL 32752-0775
rsL 321-690-1788 1 FBPE Certification of Authorization No. 25935
Product Evaluation Report
Rule 61G20-3 F.A.C. I Report No. 2386, Rev. 1 I Project No. 417-1015 1 12/6/17 1 Page 2 of 2
• ASTM E1886-99, Standard Test Method for Performance of Exterior Windows, Curtain Walls, Doors, and Impact
Protective Systems Impacted by missile(s) and Exposed to Cyclic Pressure Differentials
• ASTM E3996-99, Standard Test Method for Performance of Exterior Windows, Curtain Walls, Doors, and Impact
Protective Systems Impacted by Windborne Debris in Hurricanes
Product Testing:
• NCTL-210-2959-1, dated 10/30/03, signed and sealed by Gerald J. Ferrara, P.E., testing to ASTM E283-91/E330-
90/E331-93 and ASTM E1886-99/1996-99 for "ISFG4" Curb Mounted Self -Flashing Glass Skylight
Material Certifications/Component Approvals:
• Laminated Glass Interlayer: See current Miami -Dade Notice of Acceptance (NOA) for component approval for
KurarayTrosifol (formally Butacite) PVB Glass Interlayer by Kuraray America, Inc. used in this product. Kuraray
America NOA can be found here.
Limitations f3 Conditions of Use:
• "ISFG4" Curb Mounted Self -Flashing Glass Skylight shown on KENN0004
o This product has not been evaluated for use inside the HVHZ (High Velocity Hurricane Zone)
o This product is Impact Resistance. Therefore, a protective impact -rated device is not required.
• Refer to Product Installation Instructions noted above for:
o Maximum allowable wind loads at related maximum allowable size(s).
o Overall dimensions and material/grade of main product components, accessories, etc.
o Illustrated diagrams of the attachment of the product to the structure.
o Anchor type(s), size(s), substrate(s), embedment, edge distance, and spacing/locations.
• Site wind pressures shall be determined by a licensed professional engineer in accordance with the current edition
of the Florida Building Code and/orASCE 7-10 for components and cladding based on allowable stress design.
• Site conditions not covered in this product evaluation document are subject to additional engineering analysis by a
licensed professional engineer or registered architect as required by the authority having jurisdiction.
• Adequacy of the existing structural substrates as a main wind force resisting system capable of withstanding and
transferring applied product loads to the foundation is the responsibility of the licensed professional engineer or
registered architect acting as the design professional of record for the project of installation.
Certificate of Independence per Product Approval
Rule 61G20-3.009
PTC Product Design Group, LLC and Robert J. Amoruso, P.E.
does not have, nor will acquire, any financial interest in the
company manufacturing or distributing product(s) covered
by this Product Evaluation Report. PTC Product Design
Group, LLC and RobertJ. Amoruso, P.E. do not have, nor
will acquire any financial interest in any other entity
involved in the approval process or testing of the
product(s) covered by this Product Evaluation Report.
Digitally signed
by Robert J
Amoruso
11:14:21-05'00'
Evaluated by:
Robert J. Amoruso, P.E.
FL PE License No. 49752
PTC Product Design Group, LLC I PO Box 520775 1 Longwood, FL 32752-0775
OWNaw 321-690-1788 1 FBPE Certification of Authorization No. 25935