HomeMy WebLinkAboutPROJECT INFORMATIONIT ABC AA8C Associated Air Balance Caandl INDEPENDENT TESTING ENGINEERS July 11, 2019 Sherry Polite Publix Supermarket Miami Facility - Refrigeration 100 NE 1831 Street Miami, FL 33179 RE: PUBLIX REMODEL #855; PORT ST LUCIE, FL Dear Ms Polite: JUL 2 3 2019 ST. Lucie County, Permitting Attached please find the Certified Final Report for the above referenced project. Hard copies are also being mailed to you. Please note the deficiency items are not included in the TAB report. They are listed in a separate letter, per your request. This report fulfills our contract for this project. If you have any questions, please feel free to contact us. Sincerely, TABC Sally Koether Project Assistant SCANNED Cc: John Caramalis, PE, Publix Super Markets, Inc. Shannon Fisk, Publix Super Markets, Inc. BY St. Lucie County Scott Gaskill, Publix Super Markets, Inc. Anthony Camilo, Publix Super Markets, Inc Anthony Clementi, Pubiix Super Markets, Inc Chris Cox, Publix Super Markets, Inc. Terry Abraham, Publix Super Markets, Inc. 1000 Holcomb Woods Parkway; Suite #290, Roswell GA 30076 •Telephone (678) 393-9401 •Facsimile (678) 366-2227 TABC AABC Ass doled Air Balance C~01 INDEEEY ENTTESTMG ENGINEERS CERTIFIED FINAL TEST AND BALANCE REPORT PUBLIX REMODEL #855 7576 South US 1 PORT ST LUCIE, FL 34952 ARCHITECT: ENGINEER: GENERAL CONTRACTOR: MECHANICAL CONTRACTOR: CERTIFICATION ATKINS ATKINS NIA N/A The HVAC systems described in this report have been tested, adjusted and balanced to their optimum performance capabilities, to the extent made possible by the installation and/or performance constraints which existed at the time of testing. All testing and balancing has been performed in accordance with the required standards and procedures of the Associated Air Balance Council, and all applicable test results have been recorded herein. PROJECT # FL18-222 TECHNICIAN: Eli Feliciano / Heny Abreu 0 DATE: July 11, 2019 Cw Achara Arnold, P.E., CEM, CxA, TBE (AABC Certification #01-05-53) 1000 Holcomb Woods Parkway; Suite #290, Roswell GA 30076 •Telephone (678) 393-9401 *Facsimile (678) 366-2227 I TAB C MEPENDENT TESTING ENGI.YEEM TABLE OF CONTENTS PUBLIX REMODEL #855 7576 South US 1 PORT ST LUCIE, FL 34952 FRONT SHEET AND CERTIFICATION NUMBER TABLE OF CONTENTS AABC NATIONAL PERFORMANCE GUARANTY GENERAL COMMENTS I. CERTIFICATION STATEMENT .......................................... INSTRUMENTATION LIST ................................................... NOMENCLATURE................................................................ FORMULAS.......................................................................... STORE PRESSURIZATION SHEET ..................................... AC-1 DATA SHEETS............................................................. AC-2 DATA SHEETS............................................................. AC-3 DATA SHEETS.... ......................................................... AC-4 DATA SHEETS............................................................. AC-5 DATA SHEETS............................................................. AC-6 DATA SHEETS............................................................. ERV-1 DATA SHEETS........................................................... HOOD TEST SHEETS........................................................... FAN DATA SHEETS... ............................................. ............. EXHAUST AIR DISTRIBUTION SHEET ................................ DRAWINGS............................................................................ A-48L ASSociatad Air Hot... Coaacil 1000 Holcomb Woods Parkway; Suite #290, Roswell GA 30076 *Telephone (678) 393-9401 •Facsimile (678) 366-2227 i Perfonnance Guaranty Pursuant to the agreement between Test and Balance Corporation AABC Certified Testing & Balancing Agency and Publix Super Markets, Inc. Client All systems shall be tested and balanced in accordance with the project plans and specifications and to the optimum performance capabilities of the equipment. Testing and balancing shall be done in accordance with the standards published by the Associated Air Balance Council. If the Agency listed above fails to comply with the specifications for any reason other than termination of business by the AABC agency or equipment malfunction or inadequacy which prevents proper balancing of the systems, AABC will investigate and, if warranted, will provide supervisory personnel to assist the member Agency to perform work in accordance with AABC Standards. This supervision will be provided at no additional cost to the building owner. This Guaranty is valid for one year from the date of submission of a test and balance report, provided the Agency is a current member of AABC, and may only be invoked in writing by the building owner, architect or engineer of record. The Guaranty is limited to the terms and conditions as stated herein. Project Name Publix #855 Address 7576 South US 1 Port St Lucie, FL 34952 Name of Engineer Pelayo J. Galante, PE Engineering Firm Atkins Email Address Address 2001 NW 107th Ave. Date TBE # I. Miami, FL 33172-2507 7/1112019 01-05-53 Achara Arnold, P.E., CEM, CxA, TBE AABC Certified TBE Associated Air Balance Council 1518 K Street, N.W. Washington, D.C. 20005 202-737-0202 - Fax 202-638-4833 info®aabc.com a ww ..aabc.com TABC AML MW AABc 4,soeL W"00.1. Cwr INDEPENDENT TESTING ENGINEERS PROJECT: PUBLIX REMODEL (STORE #855) PROJECT ID: FL18-222 LOCATION: 7576 SOUTH US 1: PORT ST. LUCIE, FL 34952 GENERAL COMMENTS CERTIFICATION STATEMENT A. All data contained in this final report has been compiled from the equipment and systems installed on the job. All values in this report are true and correct as of the date of test and are within the limits of field test error. All tests performed on this project meet or exceed the standards set forth by the Associated Air Balance Council (AABC) National Standards 71 edition, 2016. B. All supply air diffusers, return air and exhaust air registers/grilles were measured with a calibrated flow hood reading directly in cfm. Sidewall registers, grilles and exhaust hoods were measured with a direct reading instrument reading in velocity and then converted to cubic feet per minute. Pitot tube traverses were made at main ducts, where possible, in order to determine total system flow. With the above in mind, we believe that the following report should be self-explanatory; however, should any questions arise, please do not hesitate to contact us. TABC, ECi rFeticiano /.7fenyA6reu Eli Feliciano / Heny Abreu Reviewed by: Achara Arnold, P.E., CEM, CxA, TBE I TABC s AABC INDEPENDENT TESTING ENGINEERS PROJECT: PUBLIX REMODEL (STORE #855) PROJECT ID: FL18-222 LOCATION: 7576 SOUTH US 1: PORT ST. LUCIE, FL 34952 INSTRUMENTATION LIST I. AIRFLOW VOLUME/VELOCITY/STATIC PRESSURE MEASURING INSTRUMENTS 1. EVERGREEN TELEMETRY PIV MODULE; MODEL S-PVF-1 2. SHORTRIDGE MODEL ADM 870 AIR DATA MULTIMETER 3. SHORTRIDGE FLOWHOOD MODEL 860 4. ExTECH VANE THERMO-ANEMOMETER MODEL 45160 5. PITOT TUBE 1/8" x 12" 6. PrroT TUBE 5/16" x 12" 7. PrroT TUBE 5/16" x 18" 8. PITOT TUBE 5/16" x 24" 9. PITOT TUBE 5/16" x 36" 10. PITOT TUBE 5/16"x 48" 11. PrroT TUBE 5/16" x 60" TEMPERATURE MEASURING INSTRUMENTS 1. EXTECH MODEL RH390 THERMO-HYGROMETER 2. EXTECH MODEL 425421NFARED THERMOMETER III. CURRENT MEASURING DEVICES 1. AMPROBE MODEL ACD-14 TRMs PLUS IV. ROTATING EQUIPMENT SPEED INDICATORS 1. EXTECH MODEL 461893 NON -CONTACT PHOTO -TACHOMETER 2. SHIMPO MODEL DT-205L GENERAL: ALL INSTRUMENT CALIBRATION IS VERIFIED AND RECALIBRATED AND/OR REPLACED AS NECESSARY. CALIBRATION CERTIFICATES ARE AVAILABLE UPON REQUEST. i TAB C law r AABC ArseristW !U 8�r�,ke rumn INDEPENDENT TESTING ENGINEERS PROJECT: PUBLIX REMODEL (STORE #855) PROJECT ID: FL18-222 LOCATION: 7576 SOUTH US 1: PORT ST. LUCIE, FL 34952 NOMENCLATURE 1. AC/HR = ROOM TOTAL AIR VOLUME CHANGES PER HOUR. 2. Ada = Cross -sectional area of ductwork, square feet. 3. Ak = GRILLE NET AREA CORRECTION FACTOR, SQUARE FEET. 4. AMPS = MEASURED PUMP OR FAN MOTOR OPERATING CURRENT AT TEST CONDITIONS, AMPS. 5. AMPSHP = PUMP OR FAN MOTOR NAMEPLATE FULL LOAD CURRENT RATING AMPS. 6. BHP = CALCULATED PUMP OR FAN MOTOR BRAKE HORSEPOWER. 7. BTUH = HEATING OR COOLING ENERGY CAPACITY RATE, BRITISH THERMAL UNITS PER HOUR. 8. C = CONE OR FLOWHOOD READING. 9. CFM = AIR FLOW RATE, CUBIC FEET PER MINUTE. 10. CHW = CHILLED WATER. 11. EAT = ENTERING AIR DRY BULB TEMPERATURE, OF. 12. EFFm = PUMP OR FAN MOTOR OPERATING EFFICIENCY, PERCENT. 13. ESP = EXTERNAL STATIC PRESSURE, IN.WG. 14. EWB = ENTERING AIR WET BULB TEMPERATURE, OF. 15. EWT = ENTERING WATER TEMPERATURE, OF. 16. OF = TEMPERATURE IN DEGREES FAHRENHEIT. 17. FLA = FULL LOAD AMPERAGE RATING. 18. GPM = WATER FLOW RATE, GALLONS PER MINUTE. 19. HPnp = PUMP OR FAN MOTOR NAMEPLATE HORSEPOWER RATING. 20. HW = HOTWATER. 21. kW = ELECTRICAL ENERGY CAPACITY RATE, KILOWATTS. 22. LAT = LEAVING AIR DRY BULB TEMPERATURE, OF. 23. Lf = PUMP OR FAN MOTOR CURRENT LOAD FACTOR. 24. LWB = LEAVING AIR WET BULB TEMPERATURE, OF. TABCj%4eC A,.O aM.d All S f.Va l INDEPENDENT TESTING ENGINEERS PROJECT: PUBLIX REMODEL (STORE #855) PROJECT ID: FL18-222 LOCATION: 7576 SOUTH US 1: PORT ST. LUCIE, FL 34952 NOMENCLATURE (CONTINUED) 25. LWT = LEAVING WATER TEMPERATURE, OF. 26. % LOAD = CURRENT LOADING OF PUMP OR FAN MOTOR AT TEST CONDITIONS, PERCENT. 27. NA = NOT APPLICABLE OR NO ACCESS. 26. NG = NOT GIVEN. 29. NI = NOT INSTALLED. 30. CA = OUTSIDE AIR. 31. PF = PUMP OR FAN MOTOR CURRENT POWER FACTOR. 32. THENT = AIR ENTHALPY (OR TOTAL HEAT) AT COIL ENTERING CONDITIONS, BTU/LB. 33. TP = THERMALLY PROTECTED. 34. TSP = TOTAL STATIC PRESSURE, IN.WG. 35. THLVG = AIR ENTHALPY (OR TOTAL HEAT) AT COIL LEAVING CONDITION, BTU/LB. 36. TONS = REFRIGERATION RATE, 12,000 BTUH FOR COOLING & 15,000 BTUH FOR CONDENSING 37. VAVG = AIR VELOCITY, FEET PER MINUTE. 38. VFD = VARIABLE FREQUENCY DRIVE 39. VOLTS = MEASURED PUMP OR FAN MOTOR OPERATING VOLTAGE. 40. VOL. = ROOM TOTAL AIR VOLUME, CUBIC FEET. IV TAB C AAeC Axsnsa(W 449eteeeoC.H PROJECT: PUBLIX REMODEL (STORE #855) PROJECT ID: FL18-222 LOCATION: 7576 SOUTH US 1: PORT ST. LUCIE, FL 34952 FORMULAS USED ON TEST FORMS A. FOR CALCULATING PUMP/FAN BRAKE HORSEPOWER (THREE PHASE ONLY) 1. BHP = (1.732 X AMPS X VOLTS X EFFm X PF X LF) / (746) NOTE: L F OBTAINED FROM KAHOE FIELD MANUAL, TABLE 6.2 2. FULL LOADEFFM X PF = (HP X 746) / (1.732 X AMPSNP X VOLTSNP) NOTE: AT FULL LOAD, LF = 1.0. 3. % LOAD = [AMPS - (0.5 X AMPSNP)] / (0.5 X AMPSNP) X [VOLTS NOLTSNP] B. FOR CALCULATING ELECTRIC HEATER KW (THREE PHASE ONLY). 1. KW = (1.732 X AMPS X VOLTS) / (1000) C. FOR CALCULATING HEATING COIL CAPACITY. 1. BTUH = 1.085 X CFM X (LAT-EAT). D. FOR CALCULATING COOLING COIL CAPACITY. 1. AIRSIDE A. BTUH = 4.5 X CFM X(THENT-THLvG) 2. WATERSIDE A. BTUH = 500 X GPM X (LWT-EWT). E. FOR CALCULATING CHILLER TONNAGE. F G. 1. TONS = [500 XGPM X (LWT-EWT)]/(12,000). FOR CALCULATING AIR VOLUME. 1. FROMTRAVERSE. A. CFM = V AVG X ADucT 2. SIDEWALLGRILLES /UNIT HEATERS A. CFM = V AvG X Ak FOR CALCULATING ROOM AIR CHANGES 1. AC/HR = (CFM X60)/VOL. 2. CFM = [(AC/HR) X VOL.] / 60 u TAB C AABc INDEPENDENT TESTING ENGINEERS PROJECT: PUBLIX REMODEL (STORE #8551 PROJECT ID: FL18-222 LOCATION: 7576 SOUTH US 1: PORT ST LUCIE, FL 34952 STORE PRESSURIZATION UNIT # DESIGN (CFM) TEST CFM AC-1 OUTSIDE AIR SALES 2600 2759 AC-2 OUTSIDE AIR SALES 2600 2753 AC-3 OUTSIDE AIR SALES from ERV-1 800 0 AC4 OUTSIDE AIR REC/STORAGE) 500 460 AC-5 OUTSIDE AIR ADMIN 250 NO OUTSIDE AIR INTAKE AC-6 OUTSIDE AIR 250 NO OUTSIDE AIR INTAKE SF-1 SUPPLY FAN DELI HOOD, GH-1 1700 1744 TOTAL OUTSIDE AIR 8700 7716 F-1 EXHAUST AIR EMPLOYEE RR 180 228 F-4 EXHAUST AIR JANITOR 180 318 F-5 EXHAUST AIR DELI HOOD GH-1 2700 2464 F-6 EXHAUST AIR DELI HOOD, GH-2 1000 991 F-7 EXHAUST AIR SCULLERY, HR-1 750 VERIFIED OPERATION F-8 EXHAUST AIR BAKERY OVEN 1000 248 ERV-1 EXHAUST AIR PUBLIC RR 920 0 TOTAL EXHAUST AIR 6730 > 4249 NET PRESSURIZATION +1970 <+3445 BUILDING PRESSURIZATION IS POSITIVE Store should be positively pressurized. If the pressurization is not positive as indicated on this sheet, review the data in this report for corrective solutions that will allow adjustments in the HVAC equipment to correct this problem. SUMMARY OF MEASURED SUPPLY AIR AIRFLOW UNIT# MANUFACTURER/MODEL YEAR DESIGN SUPPLY AIRFLOW (CFM) MEASURED SUPPLY AIR CFM AC-1 MCQUAY / RPS025CSY 2002 13,000 12,219 AC-2 MCQUAY / RPSO45CSY 2002 14,300 13,550 AC-3 LENNOX / LCH120H4BJ3Y 2017 4380 03182 AC4 LENNOX / LCH120H4BJ2Y 2013 3560 2662 AC-5 LENNOX / LCH120H4BG3Y 2017 3800 3642 AC-6 LENNOX / LCH120H4BG3Y 2017 3800 3228 TOTAL I 42,840 > 38,483 Based upon 400 cfm per ton of cooling capacity, this total tested supply airflow equates to > 96.2 tons. 0 EXCLUDES SUPPLY OUTLET #s 1 & 10 TABC AA8C Ae"naetmP GY naeanro caunou INDEPENDENT TESTING ENGINEERS PROJECT: PUBLIX REMODEL (STORE #855) PROJECT ID: FL18-222 LOCATION: 7576 SOUTH US 1: PORT ST LUCIE, FL 34952 AC-1 DATA SHEET EXISTING MANUFACTURER: MCQUAY SERIAL: FB00020200885 MODEL: RPS025CSY DATE TESTED: 7-1-19 FAN SECTION COIL SECTION AHU DATA SPECIFIED DSN DATA FIELD TEST DATA AHU DATA SPECIFIED DSN DATA FIELD TEST DATA SUPPLY CFM (HIGH) 13,000 12,219 OA DB / WB,aF 90.0 / 82.0 SUPPLY CFM LOW T _ 5- 8187 RETURN CFM 10,400 9460 ROOM DB / WB ;F 75.0 / 63.0 OUTSIDE CFM 2600 02759 MIXED AP SP, "wq -0.32 COOLING CFM 13,000 12,219 FAN SUCTN SP, "w w,,,ilxa-,Y f.� ,r«• , .r. -0.93 EAT DB 71.6 FAN DISCH. SP, "w A ,-V +0.63 LAT DB 50.9 ESP / TSP, "wg 1.2 / 22 0.95 / 1.56 FAN RPM LOWIHIGH 5921 883 MOTOR HP 10.0 , -. ,. VOLTS / 208/3 HIGH SPEED MOTOR DATA NAMEPLATE DATA FIELD TEST DATA LOW SPEED MOTOR DATA NAMEPLATE DATA FIELD TEST DATA MOTOR MFR. AO SMITH �r., ` "�° ' , }4,14 MOTOR HP / BHP 10-0 / - 10.015.9 MOTOR HP / BHP 4.4 / - MOTOR RPM 1770 MOTOR RPM 1185 1st ,*ix {, �.,. VOLTAGE 200-230 204-206-201 VOLTAGE 200-230 204-206-201 AMPERAGE 28.0 15.7-18.5-20.4 AMPERAGE 17.5 10.7-11.3-12.4 SERVICE FACTOR 1.15'te r MISC. DATA AHU FIELD DATA HEATING SECTION LOW SPEED HIGH SPEED HEATER MODEL 3 FH47 3 FH53 HEATER RATING NO CHART NO CHART HEATER SETTING FAN SHEAVE 2135V94 X 2 7116" MOTOR SHEAVE 2 4 a/4" X 1 5/a" OT / C to C FIXED / 37 Yz" BELTS 1 2 @ BX93 NOTES: O MEASURED AT OUTSIDE AIR INTAKE; 6.3 FT2 X 438 FPM = 2759 CFM © COMPRESSOR WILL NOT ENGAGE FORM08-6-13 TAB C AABC Is+acl fu ul Qa(n"Co eo V INDEPENDENT TESTING ENGINEERS PROJECT: PUBLIX REMODEL (STORE #855) PROJECT ID: FL18-222 LOCATION: 7576 SOUTH US 1: PORT ST LUCIE, FL 34952 STATIC PRESSURE PROFILE UNIT NO: AC-1 DATE TESTED: 7-3-19 SPECIFIED DESIGN: CFM/TSP, "wg 13,000 / 2.2 FIELD TEST: CFM 12,219 TSP, "wg 1.56 FAN RPM 883 SP ENT FILTER, "wg = SP ENT COIL, "wg = SP ENT RECLAIMS, "wg= FAN SUCTION, "wg = FAN DISCHARGE, "wg = NOTES: FORM18-4-00 -0.32 -0.39 -0.68 -0.93 +0.63 3 TAB C AADC aswrinsq 61+Rnm�e carulmU INDEPENDENT TESTING ENGINEERS PROJECT: PUBLIX REMODEL (STORE #855) PROJECT ID: FL18-222 LOCATION: 7576 SOUTH US 1: PORT ST LUCIE, FL 34952 DUCT TRAVERSE SHEET DATE TESTED: 7-1-19 LOCATION AND SERVICE: AC-1 RETURN AIR SPEC CFM: 10,400 SPEC DUCT SIZE: TRAVERSE RPM: 883 TEST OPENING SIZE: 87" X 37" OPENING AREA: 22.3 TRAVERSE SP, "wg MEASURED BY: ❑ PITOT TUBE DUCT TRAVERSE ❑ COIL VELGRID TRAVERSE ❑ FILTERS VELGRID TRAVERSE fl \/FI rPin TPA\/FRCP AT fll ITCIf1F AIR OPPMIAlO ,l \/=I ! DTM TDA\/CDC= AT DCTI IDNI AID nD=nunln �saaaaaaaa� AVERAGE VELOCITY: 594 OPENING AREA: 22.3 TRAVERSE CFM = 13,246 DUCT LOCATION AND SERVICE: SPEC CFM: TEST DUCT SIZE: SPEC DUCT SIZE: DUCT AREA: MEASURED BY: ❑ PITOT TUBE DUCT TRAVERSE TRAVERSE RPM: TRAVERSE SP, "wg ❑ COIL VELGRID TRAVERSE ❑ FILTERS VELGRID TRAVERSE fl VFI f;Rlfl TRA\/FPCF AT nt ITCIIIF AIR nPPMIAIf- M \/PI ! Dln TDA\/cDeD AT DCTI IDAI AID nD=KIIAV] �aaaaaaaaa� AVERAGE VELOCITY: NOTES: FORM30-11-11 DUCT AREA: TRAVERSE CFM = 4 AVERAGE VELOCITY: 594 OPENING AREA: 22.3 TRAVERSE CFM = 13,246 DUCT LOCATION AND SERVICE: SPEC CFM: TEST DUCT SIZE: SPEC DUCT SIZE: DUCT AREA: MEASURED BY: ❑ PITOT TUBE DUCT TRAVERSE TRAVERSE RPM: TRAVERSE SP, "wg ❑ COIL VELGRID TRAVERSE ❑ FILTERS VELGRID TRAVERSE fl VFI f;Rlfl TRA\/FPCF AT nt ITCIIIF AIR nPPMIAIf- M \/PI ! Dln TDA\/cDeD AT DCTI IDAI AID nD=KIIAV] �aaaaaaaaa� AVERAGE VELOCITY: NOTES: FORM30-11-11 DUCT AREA: TRAVERSE CFM = 4 AVERAGE VELOCITY: NOTES: FORM30-11-11 DUCT AREA: TRAVERSE CFM = 4 "TABC AABC 4swisloC dU BatmM Cour�M INDEPENDENT TESTING ENGINEERS PROJECT: PUBLIX REMODEL (STORE #855) PROJECT ID: FL18-222 LOCATION: 7576 SOUTH US 1: PORT ST LUCIE, FL 34952 AC-1 SUPPLY AIR DISTRIBUTION SHEET DATE TESTED: 7-3-19 AREA SERVED SPECIFIED GRILLE SPECIFIED DESIGN PRELIM FIELD TEST PRELIM FIELD TEST FINAL FIELD TEST SIZE # TYPE/ SIZE NECK RUN- OUT Ak VEL CFM VEL CFM VEL CFM VEL CFM %OF DESIGN SUPPLY AIR SALES 1 ETR 25X6 C 855 1111 795 93% SALES 2 ETR 25X6 C 540 810 1 508 94% SALES 3 ETR 25X9 C 720 972 662 92% CHECKOUT/SALES 4 ETR 25X6 C 640 783 513 95% CHECKOUT/SALES 5 ETR 25X9 C 720 1116 677 94% CHECKOUT/SALES 6 ETR 25X6 C 540 783 502 93% CHECKOUT/SALES 7 ETR 25X9 C 720 504 669 93% SALES 8 ETR 18" C 1200 647 1116 93% SALES 9 ETR 14" C 850 468 808 95% SALES 10 ETR 25X6 C 500 300 475 95% SALES 11 ETR 25X9 C 720 396 659 92% SALES 12 ETR 25X9 C 535 321 492 92% CHECKOUT/SALES 13 ETR 25X9 C 720 418 698 97% CUSTOMER SVC 14 ETR 25X9 C 535 326 514 96% CHECKOUT/SALES 15 ETR 25X9 C 720 438 r 691 96% CUSTOMER SVC 16 ETR 25X9 C 535 326 519 97% SALES 17 ETR 18" C 1200 840 1121 93% SALES 18 ETR 14" 15" C 850 637 800 94% OUTLET TOTAL 13,000 12.219 94"/ NOTES: ETR = EXISTING TO REMAIN FORM40-08-07 TABC AAeC alftp +lalA Hal° C°°nrt/ INDEPENDENT TESTING ENGINEERS PROJECT: PUBLIX REMODEL (STORE #855) PROJECT ID: FL18-222 LOCATION: 7576 SOUTH US 1: PORT ST LUCIE, FL 34952 AC-1 RETURN AIR DISTRIBUTION SHEET DATE TESTED: 7-3-19 AREA SERVED SPECIFIED GRILLE SPECIFIED DESIGN PRELIM FIELD TEST PRELIM FIELD TEST FINAL FIELD TEST SIZE # TYPE/ SIZE NECK RUN- OUT Alk VEL CFM VEL CFM VEL CFM VEL CFM %OF DESIGN RETURN AIR SALES 1 ETR 36X20 20' C 1985 1388 1804 1885 95% SALES 2 20X10 14" 1.1 764 840 703 773 1 913 1004 733 806 96% SALES 3 ETR 16X10 14" 1.1 818 900 493 542 631 694 777 855 95% SALES 4 1 30X10 18" 1.8 722 1330 805 1449 909 1636 709 1277 1 96% SALES 5 18° 18" 1.8 722 1330 701 1262 876 1577 702 1263 95% SALES 6 25X10 16-4 1.4 714 1000 465 651 567 794 671 940 94% SALES 7 25X10 16" 1.4 714 1000 717 1004 882 1235 688 963 96% SALES 8 30X6 12"6 0.79 614 485 434 343 520 411 595 470 97% SALES 9 30X6 12-6 0.79 614 485 456 360 556 439 590 466 96% SALES 10 30X6 12-4 0.79 614 485 326 258 394 312 584 461 95% SALES 11 24X6 12" 0.79 709 560 282 223 339 268 666 526 94% INLETTOTAL 10,400 9912 95% NOTES: ETR = EXISTING TO REMAIN FORM40-08-07 TABC AAsc Aseoaialml AU @manor eanmm INDEPENDENT TESTING ENGINEERS PROJECT: PUBLIX REMODEL (STORE #855) PROJECT ID: FL18-222 LOCATION: 7576 SOUTH US 1: PORT ST LUCIE, FL 34952 AC-2 DATA SHEET EXISTING MANUFACTURER: MCQUAY SERIAL: FB00020200886 MODEL: RPSO45CSY DATE TESTED: 7-1-19 FAN SECTION COIL SECTION AHU DATA SPECIFIED DSN DATA FIELD TEST DATA AHU DATA SPECIFIED DSN DATA FIELD TEST DATA SUPPLY CFM HIGH 14,300 13,550 OA DB / WB; F 90.0 / 82.0 SUPPLY CFM LOW Xr t 9079 RETURN CFM 11,700 10,797 ROOM DB / WB °F 74.0 / 63.0 OUTSIDE CFM 2600 02753 MIXED AP SP, "w wte ," -0.62 COOLING CFM 14,300 13,550 FAN SUCT'N SP, "w -1.44 EAT DB 73.0 75.0 FAN DISCH. SP, "w TO +0.50 LAT DB 52.0 56.0 ESP/TSP,"w 1.2/2.2 1.12/1.94 FAN RPM LOW/HIGH - 624 932 MOTOR HP 10.0 s x VOLTS / 20813 `rafi`Z HIGH SPEED MOTOR DATA NAMEPLATE DATA FIELD TEST DATA LOW SPEED MOTOR DATA NAMEPLATE DATA FIELD TEST DATA MOTOR MFR. MAGNETEK MOTORHP/BHP 10.0/- 10.0/7.53 MOTOR HPlBHP 4.4/- :° ` MOTOR RPM 1770 arx MOTOR RPM 1185 VOLTAGE 200-230 205-203-200 VOLTAGE 200-230 205-203-200 AMPERAGE 30.0-28.0 24.6-21.9-25.3 AMPERAGE 17.0-17.5 13.9-13.5-15.3 SERVICE FACTOR 1.15Y x MISC. DATA AHU FIELD DATA HEATING SECTION LOW SPEED HIGH SPEED HEATER MODEL 3 FH47 3 FH53 HEATER RATING NO CHART NO CHART HEATER SETTING - FAN SHEAVE 2B5V124 X 2 7/16" MOTOR SHEAVE 2 U 7" X 1 5/a" OT / C to C FIXED / 38'/z" BELTS 2 @ BX103 NOTES: O MEASURED AT OUTSIDE AIR INTAKE; 6.3 FT2 X 437 FPM = 2753 CFM FORM08-6-13 TABC AMIL 0 AARC INDEPENDENT TESTING ENGINEERS PROJECT: PUBLIX REMODEL (STORE #855) PROJECT ID: FL18-222 LOCATION: 7576 SOUTH US 1: PORT ST LUCIE, FL 34952 STATIC PRESSURE PROFILE UNIT NO: AC-2 DATE TESTED: 7-3-19 SPECIFIED DESIGN: CFM/TSP, "wg 14,300 / 2.2 FIELD TEST: CFM 13,550 TSP, "wg 1.94 FAN RPM 932 NOTES: FORM18-4-00 SP ENT FILTER, "wg = -0.62 SP ENT COIL, "wg = -0.75 SP ENT RECLAIMS, "wg= -1.13 FAN SUCTION, "wg = -1.44 FAN DISCHARGE, "wg = +0.50 El TAB C AADC As�odslW 6U @utonro CauMli PROJECT: PUBLIX REMODEL (STORE #855) PROJECT ID: FL18-222 LOCATION: 7576 SOUTH US 1: PORT ST LUCIE, FL 34952 DUCT TRAVERSE SHEET DATE TESTED: 7-1-19 LOCATION AND SERVICE: AC-2 RETURN AIR SPEC CFM: 11.700 SPEC DUCT SIZE: TRAVERSE RPM: 932 TEST OPENING SIZE: 87" X 37" OPENING AREA: 22.3 TRAVERSE SP, "wg MEASURED BY: ❑ PITOT TUBE DUCT TRAVERSE ❑ COIL VELGRID TRAVERSE ❑ FILTERS VELGRID TRAVERSE ❑ VELGRID TRAVERSE AT OI ITSIDF AIR OPENING J VFI (:Rill TRAVFRRF AT RFTI IRN AIR nPFNINr �saaaaaaaa� AVERAGE VELOCITY: 555 OPENING AREA: 22.3 TRAVERSE CFM = 12.377 DUCT LOCATION AND SERVICE: SPEC CFM: TEST DUCT SIZE: SPEC DUCT SIZE: DUCT AREA: MEASURED BY: ❑ PITOT TUBE DUCT TRAVERSE ❑ VELGRID TRAVERSE AT OUTSIDE AIR OPENING TRAVERSE RPM: TRAVERSE SP, "wg ❑ COIL VELGRID TRAVERSE ❑ FILTERS VELGRID TRAVERSE O VFI GRID TRAVFRSF AT RFTI IRN AIR OPFNINC7 -�aaaaaaaaa� AVERAGE VELOCITY: NOTES: FORM30-11-11 DUCT AREA: TRAVERSE CFM = i) AVERAGE VELOCITY: 555 OPENING AREA: 22.3 TRAVERSE CFM = 12.377 DUCT LOCATION AND SERVICE: SPEC CFM: TEST DUCT SIZE: SPEC DUCT SIZE: DUCT AREA: MEASURED BY: ❑ PITOT TUBE DUCT TRAVERSE ❑ VELGRID TRAVERSE AT OUTSIDE AIR OPENING TRAVERSE RPM: TRAVERSE SP, "wg ❑ COIL VELGRID TRAVERSE ❑ FILTERS VELGRID TRAVERSE O VFI GRID TRAVFRSF AT RFTI IRN AIR OPFNINC7 -�aaaaaaaaa� AVERAGE VELOCITY: NOTES: FORM30-11-11 DUCT AREA: TRAVERSE CFM = i) AVERAGE VELOCITY: NOTES: FORM30-11-11 DUCT AREA: TRAVERSE CFM = i) TABC AABC INDEPENDENT TESTING ENGINEERS PROJECT: PUBLIX REMODEL (STORE #855) PROJECT ID: FL18-222 LOCATION: 7576 SOUTH US 1: PORT ST LUCIE FL 34952 AC-2 SUPPLY AIR DISTRIBUTION SHEET DATE TESTED: 7-3-19 AREA SERVED SPECIFIED GRILLE SPECIFIED DESIGN PRELIM FIELD TEST PRELIM FIELD TEST FINAL FIELD TEST SIZE TYPE/ SRE NECK RUN- OUT Ak VEL CFM VEL CFM VEL CFM VEL I CFM % OF I DESIGN SUPPLY AIR SALES 1 ETR 18" - C 1200 1296 1296 108% SALES 2 ETR 14" 13" C 850 901 901 106% SALES 3 ETR 25X9 - C 900 982 982 109% SALES 4 ETR - C 900 367 367 0 41% SALES 5 ETR - C 900 393 393 0 44% SALES 6 ETR - C 900 991 990 110% ENTRY/EXIT VEST 7 ETR 449X9 - C 1400 980 1263 90% ENTRY/EXITVEST 8 ETR - C 1400 1558 1261 90% SALES 9 ETR C NG 1017 101SALES 10 ETR 13"6 C 850 935 935 110% SALES 11 ETR 25X9 - C 960 1036 1036 108% SALES 12 ETR 25X9 - C 930 1013 1013 109% SALES 13 ETR 25X9 - C 960 1056 1056 110% SALES 14 ETR 25X9 - C 950 1040 1040 109% OUTLET TOTAL 013,100 13 550 103% NOTES: CS: ETR R = EAS I ING TO REMAIN O SCHEDULED SUPPLY AIRFLOW = 14,300 CFM 0 GRILLE IS INSTALLED BACKWARDS FORM40-08-07 10 TABC s AABC 4,+o 41W 4b".. Caortrn INDEPENDENT TESTING ENGINEERS PROJECT: PUBLIX REMODEL (STORE #855) PROJECT ID: FL18-222 LOCATION: 7576 SOUTH US 1: PORT ST LUCIE, FL 34952 AC-2 RETURN AIR DISTRIBUTION SHEET DATE TESTED: 7-2-19 AREASERVED SPECIFIED GRILLE SPECIFIED DESIGN PRELIM FIELD TEST PRELIM FIELD TEST FINAL FIELD TEST SIZE # TYPE/ SIZE NECK RUN- I OUT Ak VEL CFM VEL CFM VEL CFM VEL CFM %OF DESIGN RETURN AIR SALES 1 ETR 44X20 24" C 3980 3288 3662 92% SALES 2 30X6 14" 1.1 909 1000 539 593 827 910 91% SALES 3 30X6 14"4 1.1 1 909 1000 788 867 837 921 92% SALES 4 30X6 14° 1.1 909 1000 716 788 821 903 90% SALES 5 30X6 14-0 909 1000 728 801 1 1 829 912 91% SALES 6 26X6 14" 1.1 600 660 687 756 570 627 95% SALES 7 30X6 I 14° 1.1 NG 693 763 664 620 SALES 8 26X6 14-6 1.1 600 660 626 687 561 617 93% SALES 9 30X6 14-6 1.1 727 800 358 394 663 729 91% SALES 10 30X6 14-$ 1.1 727 800 827 910 675 742 93% INLET TOTAL 010,900 10,643 98% NOTES: ETR = EXISTING TO REMAIN O SCHEDULED RETURN AIRFLOW = 11,700 CFM FORM40-08-07 11 TABC ANIL AABC INDEPENDENT TESTING ENGINEERS PROJECT: PUBLIX REMODEL (STORE #855) PROJECT ID: FL18-222 LOCATION. 7576 SOUTH US 1: PORT ST LUCIE, FL 34952 AC-3 DATA SHEET EXISTING MANUFACTURER: LENNOX SERIAL: 5617B06390 MODEL: LCH120H4BJ3Y DATE TESTED: 74-1-19 FAN SECTION COIL SECTION AHU DATA SPECIFIED DSN DATA FIELD TEST DATA AHU DATA SPECIFIED DSN DATA FIELD TEST DATA SUPPLY CFM 4380 03182 CA DB / WB °F 90.0 / 82.0 RETURN CFM 3580 3182 OUTSIDE CFM 0 800 00 ROOM DB / WB,°F 79.0 / 66.0 MIXED AP SP, "w } -0.44 FAN SUCT'N SP, "w �" -1.12 FAN DISCH. SP, "wq +0.42 ESP / TSP, -wg 0.9 / 1.1 0.86 / 154 FAN RPM - 959 MOTOR HP 3.0 mr w COOLING CFM 4380 3182 VOLTS / 208/3 - ` EAT DB 76.0 79.0 MOTOR DATA NAMEPLATE DATA FIELD TEST DATA LAT DB 55.5 60.0 MOTOR MFR. INTERLINK MOTOR HP / BHP 3.0 /- 3.012.68 MOTOR RPM 1745 VOLTAGE 200-230 202-204-203 AMPERAGE 7.4-7.8 6.6-7.4-7.4 SERVICE FACTOR 1.15 a ',, HEATING AMPS STAGE 1 31.6 MISC. DATA AHU FIELD DATA STAGE 2 31.2 HEATER MODEL THERMALLY PROTECTED STAGE 3 - HEATER RATING THERMALLY PROTECTED HTG VOLTS / 208/3 204 / 3 HEATER SETTING THERMALLY PROTECTED # OF STAGES - 2 FAN SHEAVE 8" X 1" HEATING kW 30.0 22.2 MOTOR SHEAVE 5 Y<" X 7/8" ITOTALBTUH - 75,769 OT/CtoC 4'/:/24-/<" BELTS BX69 NOTES: O EXCLUDES SUPPLY OUTLET #s 1 & 10 0 FROM ERV-1 0 ERV-1 IS NOT OPERATIONAL FORM08-6-13 12 TABC AABC INDEPENDENT TESTING ENGINEERS PROJECT: PUBLIX REMODEL (STORE #855) PROJECT ID: FL18-222 LOCATION: 7576 SOUTH US 1: PORT ST LUCIE FL 34952 STATIC PRESSURE PROFILE UNIT NO: AC-3 DATE TESTED: 7-3-19 SPECIFIED DESIGN: CFM/TSP, "wg 4380 / 1.1 FIELD TEST: CFM 3182 O TSP, "wg 1.54 FAN RPM 959 SP ENT FILTER, "wg SP ENT COIL, "wg = -0.44 = NO ACCESS FAN SUCTION, "wg = -1.12 FAN DISCHARGE, "wg = +0.42 NOTES: O EXCLUDES SUPPLY OUTLET #s 1 & 10 FORM18-4-00 13 °TABC INDEPENDENT TESTING ENGINEERS PROJECT: _PUBLIX REMODEL (STORE #855) PROJECT ID: FL18-222 LOCATION: 7576 SOUTH US 1: PORT ST LUCIE, FL 34952 AC-3 SUPPLY & RETURN AIR DISTRIBUTION SHEET DATE TESTED: 7-2-19 AREASERVED SPECIFIED GRILLE SPECIFIED PRELIM FIELD TEST PRELIM FIELD TEST FINAL FIELD TEST SIZEDESIGN # TYPE/ SIZE NECK RUN- OUT Ak VEL CFM VEL CFM VEL CFM VEL CFM %OF DESIGN SUPPLY AIR RECEIVING/STORAGE 1 ETR 30X10 9" C 575 O O TRAINING 2 ETR 6" C 150 1 115 115 77% TRAINING 1 3 ETR 6" C 150 113 113 75% RECEIVING/STORAGE 4 ETR 30X10 12" C 575 640 640 111% LOUNGE-B 5 ETR 6° C 150 1 101 1 1 101 67% DEPT. MANAGER 6 ETR 6" C 150 115 115 77% DEPT. MANAGER 7 ETR 6" C 150 112 112 76 RECEIVING/STORAGE 8 ETR 30X10 11-6 C 565 450 450 80% MEN'S RESTROOM 9 ETR 9X9 C 120 65 65 54% WMN'S RESTROOM 10 ETR 9X9 C 120 0 0 PASSAGE-B 11 ETR 6" C 100 124 124 124% PRODUCE WRKRM 12 ETR 10" C 350 300 300 86% RECEIVING/STORAGE 13 ETR 30X10 11-6 C 575 373 373 65% PRODUCE WRKRM 14 ETR 10" C 350 294 294 84% ELECT.AREA 15 ETR 20X8 9" C 300 380 380 127% OUTLETTOTAL 4380 0 3182 RETURN AIR TRAINING 1 ETR 14X14 9"6 C 200 332 332 0166% PASSAGE-C 2 ETR 4SX24 24-6 C 3180 2498 249E 79% DEPT. MANAGER 3 ETR 14X14 9-6 C 200 308 308 0 154% INLET TOTAL 3580 1 3138 88% NOTES: ETR = EXISTING TO REMAIN O BLOCKED BY PRODUCT © DUCTWORK IS BROKEN O EXCLUDES OUTLET #s 1 & 10 O THE OPPOSED BLADE DAMPER IS NOT OPERATIONAL; NO MANUAL DAMPER INSTALLED 0 NO OPPOSED BLADE DAMPER OR MANUAL VOLUME DAMPER INSTALLED FORM40-08-07 14 TABC ,dW s AADC aefernearel. BNAnm CnwKn INDEPENDENT TESTING ENGINEERS PROJECT: PUBLIX REMODEL (STORE #855) PROJECT ID: FL18-222 LOCATION: 7576 SOUTH US 1: PORT ST LUCIE FL 34952 AC-4 DATA SHEET EXISTING MANUFACTURER: LENNOX SERIAL: 5613M00798 MODEL: LCH120H4BJ2Y DATETESTED: 7-1-19 FAN SECTION COIL SECTION AHU DATA SPECIFIED DSN DATA FIELD TEST DATA AHU DATA SPECIFIED DSN DATA FIELD TEST DATA SUPPLY CFM 3560 2662 OA DB / WB; F 90.0 / 82.0 RETURN CFM 3060 2202 OUTSIDE CFM 500 0460 ROOM DB / WB; F 75.0 / 63.0 MIXED AP SP, "w r W -0.22 FAN SUCT'N SP, "w ,., . -0.53 FAN DISCH. SP, "w9 +0.76 ESP /TSP,"w 0.9/1.11 0.98/1.29 FAN RPM 840 MOTOR HP 2.0 COOLING CFM 3560 2662 VOLTS / 208/3 mr EAT DB 88.0 77.0 MOTOR DATA NAMEPLATE DATA FIELD TEST DATA LAT DB 57.7 61.0 MOTOR MFR. INTERLINK MOTOR HP/BHP 2.0/- 2.0/1.65 MOTOR RPM 1755 VOLTAGE 200-230 202-204-200 AMPERAGE 5.6-5.8 4.5-5.3-5.5 SERVICE FACTOR 1.15 '�,� HEATING AMPS STAGE 1 32.1 MISC. DATA AHU FIELD DATA STAGE 2 30.6 HEATER MODEL THERMALLY PROTECTED STAGE 3 - HEATER RATING THERMALLY PROTECTED HTG VOLTS ! 208/3 204 / 3 HEATER SETTING THERMALLY PROTECTED # OF STAGES 2 FAN SHEAVE 6" X 1" HEATING kW 30.0 22.1 MOTOR SHEAVE 3 1/a" X 7/s" I TOTAL BTUH - 75,427 OT/CtoC 1/24'/a" BELTS A63 NOTES: O MEASURED AT OUTSIDE AIR INTAKE; 23" X 14" = 2.2 FT2 X 209 FPM = 460 CFM FORM08-6-13 15 TABC low AABC INDEPENDENT TESTING ENGINEERS PROJECT: PUBLIX REMODEL (STORE #855) PROJECT ID: FL18-222 LOCATION: 7576 SOUTH US 1: PORT ST LUCIE, FL 34952 STATIC PRESSURE PROFILE UNIT NO: AC-4 DATE TESTED: 7-3-19 SPECIFIED DESIGN: CFM/TSP, "wg 3560 / 1.11 FIELD TEST: CFM 2662 TSP, "wg 1.29 FAN RPM 840 NOTES: FORM18-4-00 SP ENT FILTER, "wg SP ENT COIL, "wg = -0.22 = NO ACCESS FAN SUCTION, "wg = -0.53 FAN DISCHARGE, "wg = +0.76 16 TABC AABC PaMCiNI W NI @dlb�Cp COUMU INDEPENDENT TESTING ENGINEERS PROJECT: PUBLIX REMODEL (STORE #855) PROJECT ID: FL18-222 LOCATION: 7576 SOUTH US 1: PORT ST LUCIE, FL 34952 AC-4 AIR TERMINAL UNIT DATA SHEET DATE TESTED: 7-2-19 TERMINAL SPECIFIED DESIGN DATA FIELD TEST DATA UNIT TYPE/ SIZE MIN CFM MAX CFM MIN CFM MAX CFM COMMENTS V-1 EXISTING 408 METALAIRE 75 O 510 / 500 ® 463 V-2 EXISTING 406 METALAIRE 40 O 165 / 200 © 0 V-3 EXISTING 406 METALAIRE 60 O 375 / 350 © 254 V4 EXISTING 406 METALAIRE 45 300 © 205 V-5 EXISTING 408 METALAIRE 75 565 © 50 NOTES: O OUTLET TOTAL AIRFLOW / SCHEDULED AIRFLOW © NO KMC MODEL MEP-5001 ACTUATOR INSTALLED; UNABLE TO SET MINIMUM AIRFLOW FORM314-00 17 TABC RABC 4�eoridteJ AL t1Yup{o Coun[!I INDEPENDENT TESTING ENGINEERS PROJECT: PUBLIX REMODEL (STORE #855) PROJECT ID: FL18-222 LOCATION: 7576 SOUTH US 1: PORT ST LUCIE FL 34952 AC-4 SUPPLY AIR DISTRIBUTION SHEET DATE TESTED: 7-2-19 AREA SERVED SPECIFIED GRILLE SPECIFIED DESIGN PRETTESTFIELD FIELD ELIM TEST FINAL FIELD TEST SIZE # TYPE/ SIZE NECK RUN- OUT 'k VEL CFM VEL CFM VEL CFM %OF DESIGN SUPPLY AIR V-4 CASH ROOM 1 ETR 12X12 9" C 300 205 205 68% TOTAL MINIMAX 45/ 1 300 205 68% SALES 2 8" 8" C 300 1 125 125 42% SALES 3 8" 8" C 300 148 148 49% V-3 GENERAL OFFICE 4 ETR 12X12 - C 375 254 254 O 68% TOTAL MIN/MAX 60/ 375 254 68% V-2 MGR'S OFFICE 5 ETR 9X9 - C 165 0 0 0% TOTAL MIN/MAX 40/1 165 0 00% FROM BY PASS 110 110 BYPASS COMM. ROOM 6 ETR 9X9 - C 120 110 110 1 92% V-1 LOUNGE -A 7 ETR 10° 10° C 255 238 238 93% LOUNGE -A 8 ETR 10" 10° C 255 225 225 88% TOTAL MIN/MAX 751 510 463 91% V-5 PHARMACY 9 9X9 8" C 280 0 0 0% PHARMACY 10 9X9 8" C 285 50 50 18% TOTAL MINIMAX 751 565 50 0 9% FROM BY PASS 250 250 BYPASS NUTes: E I R = EXISTING TO REMAIN O NO FINISH GRILLE © ACTUATOR IS NOT OPERATIONAL © ACTUATOR IS NOT CONNECTED TO THE VAV FORM40-08-07 18 TABC AAeC 4.10 4 Q� CaunNi INDEPENDENT TESTING ENGINEERS PROJECT: PUBLIX REMODEL (STORE #855) PROJECT ID: FL18-222 LOCATION: 7576 SOUTH US 1: PORT ST LUCIE, FL 34952 AC-4 SUPPLY & RETURN AIR DISTRIBUTION SHEET DATE TESTED: 7-2-19 OUTLETTOTAL NOTES: ETR = EXISTING TO REMAIN O NO OPPOSED BLADE DAMPER OR MANUAL VOLUME DAMPER INSTALLED FORM40-08-07 19 TABC MOIL s j"ac A,,Q .9i "Bar. CauncO INDEPENDENT TESTING ENGINEERS PROJECT: PUBLIX REMODEL (STORE #855) PROJECT ID: FL18-222 LOCATION: 7576 SOUTH US 1: PORT ST LUCIE, FL 34952 AC-5 DATA SHEET EXISTING MANUFACTURER: LENNOX SERIAL: 5617BO6167 MODEL: LCH120H4BG3Y DATE TESTED: 7-1-19 FAN SECTION COIL SECTION AHU DATA SPECIFIED DSN DATA FIELD TEST DATA AHU DATA SPECIFIED DSN DATA FIELD TEST DATA SUPPLY CFM 3800 3642 OA DB / WB °F 90.0 / 82.0 RETURN CFM 3550 3642 OUTSIDE CFM 250 00 ROOM DB / WB; F 78.0 / 64.0 MIXED AP SP, "w 'fir -0.46 FAN SUCT'N SP, "w .; -1.14 FAN DISCH. SP, "w r,>g +0.26 ESP / TSP, "wg 0.9 / 1.13 0.72 / 1.40 FAN RPM - 948 MOTOR HP 3.0 _.._�=; COOLING CFM 3800 3642 VOLTS / 208/3 `-j EAT DB 75.6 77.0 MOTOR DATA NAMEPLATE DATA FIELD TEST DATA LAT DB 53.4 51.0 MOTOR MFR. INTERLINK MOTOR HP/BHP 3.0/- 3.0/2.84 MOTOR RPM 1745 VOLTAGE 200-230 204-207-201 AMPERAGE 7.8-7.4 6.9-7.4-7.8 SERVICE FACTOR 1.15 r HEATING AMPS STAGE 1 31.0 MISC. DATA AHU FIELD DATA STAGE 2 13.4 HEATER MODEL THERMALLY PROTECTED STAGE 3 HEATER RATING THERMALLY PROTECTED HTG VOLTS / 208/3 207 / 3 HEATER SETTING THERMALLY PROTECTED # OF STAGES 2 FAN SHEAVE 71/2" X 1" HEATING kW 22.5 15.9 MOTOR SHEAVE 4 Y<" X 7/s" TOTAL BTUH 54,266 OT/CtoC 1/24%- BELTS BX66 NOTES: O NO OUTSIDE AIR INTAKE INSTALLED FORM08-6-13 20 TAB C AA8C d>wciAfegdU ff.v .Cuuicfl INDEPENDENT TESTING ENGINEERS PROJECT: PUBLIX REMODEL (STORE #855) PROJECT ID: FL18-222 LOCATION: 7576 SOUTH US 1: PORT ST LUCIE, FL 34952 STATIC PRESSURE PROFILE UNIT NO: AC-5 DATE TESTED: 7-3-19 SPECIFIED DESIGN: CFM/TSP, "wg 3800 / 1.13 FIELD TEST: CFM 3642 TSP, "wg 1.40 FAN RPM 948 NOTES: FORM18-4.00 SP ENT FILTER, "wg SP ENT COIL, "wg = -0.46 = NO ACCESS FAN SUCTION, "wg = -1.14 FAN DISCHARGE, "wg = +0.26 21 TABC AABC 4,,padW4 lfalmpo Co H INDEPENDENT TESTING ENGINEERS PROJECT: _PUBLIX REMODEL (STORE #855) PROJECT ID: FL18-222 LOCATION: 7576 SOUTH US 1: PORT ST LUCIE, FL 34952 AC-5 SUPPLY & RETURN AIR DISTRIBUTION SHEET DATE TESTED: 7-2-19 AREA SERVED SPECIFIED GRILLE SPECIFIED DESIGN PRELIM FIELD TEST PRELIM FIELD TEST FINAL FIELD TEST SIZE # TYPE/ SIZE NECK RUN- OUT 'k VEL CFM VEL CFM VEL CFM VEL CFM % OF DESIGN SUPPLY AIR DELI DEPARTMENT 1 ETR 14" C 605 400 420 449 O 74% DELI KITCHEN 2 ETR 8° 8" C 200 1 163 166 178 O 89% DELI DEPARTMENT 1 3 ETR 14' C 605 490 1 530 567 94% DELISCULLERY 4 1 9X9 8" C 130 257 130 139 107% DELI DEPARTMENT 5 ETR 14° C 400 410 410 439 110% SF-1 6 10"6 410 390 390 417 102% DELI DEPARTMENT 7 ETR 14" C 400 422 422 452 113% SCULLERY 8 ETR 12' 12' C 430 300 300 321 75% DELI DEPARTMENT 9 ETR 14"6 C 620 425 425 455 73% 10 C NG 210 210 225 O OUTLET TOTAL 3800 3642 96% RETURN AIR DELISUPPLY 1 48X24 C 3450 1 3614 3614 3866 112% DELISCULLERY 2 1OX10 7-6 C 100 210 110 110 110% INLET TOTAL 3550 3976 112% NOTES: ETR = EXISTING TO REMAIN O OPPOSED BLADE DAMPER IS NOT OPERATIONAL © TAPPED OFF THE WRONG SIZE OF DUCT; TAPPED OFF 20"� DUCT INSTEAD OF 17"� DUCT © EXTRA OUTLET NOT SHOWN ON DRAWINGS FORM40-08-07 22 TABC s AABC A,fo�A ff m". Cau INDEPENDENT TESTING ENGINEERS PROJECT: PUBLIX REMODEL (STORE #855) PROJECT ID: FL18-222 LOCATION: 7576 SOUTH US 1: PORT ST LUCIE, FL 34952 AC-6 DATA SHEET EXISTING MANUFACTURER: LENNOX SERIAL: 5617BO6166 MODEL: LCH120H4BG3Y DATE TESTED: 7-1-19 FAN SECTION COIL SECTION AHU DATA SPECIFIED DSN DATA FIELD TEST DATA AHU DATA SPECIFIED DSN DATA FIELD TEST DATA SUPPLY CFM 3800 3228 OA DB / WB,°F 95.0 / 88.0 RETURN CFM 3550 3228 OUTSIDE CFM 250 00 ROOM DB / WB °F MIXED AP SP, "w M -0.67 FAN SUCT'N SP, "w g, x" -1.23 FAN DISCH. SP, "w $- "* +0.43 ESP / TSP, "wg 0.9 / 1.13 1.10 / 1.66 FAN RPM 951 MOTOR HP 3.0 ,• t COOLING CFM 3800 3228 VOLTS / 20813a EAT DB 76.3 75.0 MOTOR DATA NAMEPLATE DATA FIELD TEST DATA LAT DB 54.0 51.0 MOTOR MFR. INTERLINK MOTOR HP/BHP 3.0/- 3.0/2.82 MOTOR RPM 1745 VOLTAGE 200-230 205-207-200 AMPERAGE 7.4-7.8 77.6-6.6-7.8 SERVICE FACTOR 1.15E HEATING AMPS STAGE 1 31.7 MISC. DATA AHU FIELD DATA STAGE 2 16.3 HEATER MODEL THERMALLY PROTECTED STAGE 3 HEATER RATING THERMALLY PROTECTED HTG VOLTS / 208/3 204 / 3 HEATER SETTING THERMALLY PROTECTED # OF STAGES - 2 FAN SHEAVE 7'/" X 1" HEATING kW 22.5 17.0 MOTOR SHEAVE 4'/4" X 7/s" TOTAL BTUH - 58,021 OT/CtoC 1/24'/2" BELTS L BX66 NOTES: O NO OUTSIDE AIR INTAKE INSTALLED FORM08-6-13 23 TABC INDEPENDENT TESTING ENGINEERS PROJECT: PUBLIX REMODEL (STORE #855) PROJECT ID: FL18-222 LOCATION: 7576 SOUTH US 1: PORT ST LUCIE, FL 34952 STATIC PRESSURE PROFILE UNIT NO: AC-6 DATE TESTED: 7-3-19 SPECIFIED DESIGN: CFM/TSP, "wg 3800 / 1.13 FIELD TEST: CFM 3228 TSP, "wg 1.66 FAN RPM 951 NOTES: FORM18-4-00 SP ENT FILTER, "wg SP ENT COIL, "wg = -0.67 = NO ACCESS FAN SUCTION, "wg = -1.23 FAN DISCHARGE, "wg = +0.43 24 TABC INDEPENDENT TESTING ENGINEERS PROJECT: PUBLIX REMODEL (STORE #855) PROJECT ID: FL18-222 LOCATION: 7576 SOUTH US 1: PORT ST LUCIE, FL 34952 AC-6 SUPPLY & RETURN AIR DISTRIBUTION SHEET DATE TESTED: 7-2-19 SPECIFIED GRILLE FINAL FIELD TEST ammmommmmmmmm DESIGN �=___m__ ______OUTLETTOTAL - NOTES: ETR = EXISTING TO REMAIN FORM40-08-07 25 TABC s AABC INDEPENDENT TESTING ENGINEERS PROJECT: PUBLIX REMODEL (STORE #855) PROJECT ID: FL18-222 LOCATION: 7576 SOUTH US 1: PORT ST LUCIE, FL 34952 ERV-1 DATA SHEET EXISTING FAN DATA SPECIFIED DESIGN DATA FAN # ERV-1 ERV-1 LOCATION/SERVES SUPPLY EXHAUST CFM 800 920 STATIC PRESSURE, "wq 0.5 0.5 HP/BHP 0.5/- 0.5/- FAN RPM FIELD TEST DATA DATE TESTED 7-1-19 7-1-19 MANUFACTURER GREENHECK MODEL # ERV-20-30LB SERIAL # 130199955 MOTOR MFR MARATHON MARATHON MOTOR HP/BHP %/- 1/2/- MOTOR RPM 1725 1725 NP AMPERAGE 9.714.8 9.7 / 4.8 NP VOLTAGE 115 / 230 115 / 230 SERVICE FACTOR 1.0 1.0 TEST AMPERAGE 0 0 TEST VOLTAGE/PHASE 201/3 201/3 HEATER SIZE THERMALLY PROTECTED THERMALLY PROTECTED HEATER RATING THERMALLY PROTECTED THERMALLY PROTECTED FAN SHEAVE THERMALLY PROTECTED THERMALLY PROTECTED MOTOR SHEAVE DIRECT DRIVE DIRECT DRIVE OT / C to C DIRECT DRIVE DIRECT DRIVE BELTS DIRECT DRIVE DIRECT DRIVE FAN RPM DIRECT DRIVE DIRECT DRIVE SP ENT FILTER "w FAN SUCTION SP "w AP, "wq O FAN CFM MOTOR SEIZED MOTOR SEIZED NOTES: O PRESSURE DROP ACROSS FILTER AND ENERGY WHEEL FORM17-4-00 26 TAB C AABC d,rod•IM 41a eaeanen cunen INDEPENDENT TESTING ENGINEERS PROJECT: PUBLIX REMODEL (STORE #855) PROJECT ID: FL18-222 LOCATION: 7576 SOUTH US 1: PORT ST LUCIE, FL 34952 ERV-1 SUPPLY & EXHAUST AIR DISTRIBUTION SHEET DATE TESTED: 7-3-19 SPECIFIED GRILLE %OF DESIGN' .__---------__ OUTLETTOTAL �m___m__ ______- _ _ • • m� r I S-_m ______� O MOTOR SEIZED © NO MANUAL VOLUME DAMPER OR OPPOSED BLADE DAMPER INSTALLED FORM40-06-07 27 TABC s AAeC Ax+d+alwl ey aaeenco CorweD INDEPENDENT TESTING ENGINEERS PROJECT: PUBLIX REMODEL (STORE #855) PROJECT ID: FL18-222 LOCATION: 7576 SOUTH US 1: PORT ST LUCIE, FL 34952 HOOD TEST SHEET DATE TESTED 7-2-19 FAN # (EXHAUST / SUPPLY) F-5 / SF-1 SERVES GH-1 EXHAUST SECTION SPECIFIED EXHAUST CFM: 2700 FILTER# 1 2 3 4 5 6 7 8 FILTER SIZE i 20X20 20X20 20X16 20X16 20X16 20X16 20X20 20X20 AVERAGE VELOGTY.FPM 114 130 120 125 136 126 87 110 CONVERSION FACTOR 3.0 3.0 2.25 2.25 2.25 2.25 j 3.0 3.0 CALCULATED CFM 342 390 270 281 306 284 261 330 TOTAL AIRFLOW = 2464 CFM SUPPLY SECTION SPECIFIED MUA CFM: 02110 MAKE-UP OPENING: 5 fad 27" X 12" TEST FACE VELOCITIES (FPM) 254 181 1 246 234 238 187 173 288 216 254 i AVG. VELOCITY (FPM) 226 X OPENING AREA (FT2) 11.25 X AREA FACTOR 0.85 = 2161 CFM HOOD MANUFACTURER GREENHECK MODEL# GXEW144.00S HOOD SIZE: 145' X 60" SPEC. EXHAUST CFM 2700 SPECIFIED MUA CFM 2110 00 PERCENTAGE 78% TEST EXHAUST CFM 2464 TEST MUA CFM 2161 00 PERCENTAGE 88% NOTES:O ADDITIONAL MAKE-UP AIR COMES FROM ADJACENT SPACES AND IS INTRODUCED VIA AIR CONDITIONING UNITS 0 410 CFM MAKE-UP AIR COMES FROM AC-5 (DESIGN) 0 417 CFM MAKE-UP AIR COMES FROM AC-5 (ACTUAL); SF-1 = 2161-417 = 1744 CFM 28 TABC AdmL AABC GaresialN dU aae-.o< Cou,rp INDEPENDENT TESTING ENGINEERS PROJECT: PUBLIX REMODEL (STORE #855) PROJECT ID: FL18-222 LOCATION: 7576 SOUTH US 1: PORT ST LUCIE, FL 34952 HOOD TEST SHEET DATE TESTED 7-2-19 FAN # (EXHAUST / SUPPLY) F-6 / - SERVES GH-2 EXHAUST SECTION SPECIFIED EXHAUST CFM: 1000 FILTER # 1 FILTER SIZE 20X16 2 20X16 3 20X20 - -�-- AVERAGE VELOCITY, FPM 137 105 149 CONVERSION FACTOR 2.25 2.25 3.0 CALCULATED CFM 306 236 447 TOTAL AIRFLOW = 991 CFM SPECIFIED MUA CFM: TEST FACE VELOCITIES (FPM) SUPPLY SECTION MAKE-UP OPENING: AVG. VELOCITY (FPM) X OPENING AREA (FT') _ X AREA FACTOR = CFM HOOD MANUFACTURER GREENHECK MODEL # GXEW54.00-S HOOD SIZE: 51" X 55' SPEC. EXHAUST CFM 1000 SPECIFIED MUA CFM O PERCENTAGE - TEST EXHAUST CFM 991 TEST MUA CFM O PERCENTAGE - NOTES: O MAKE-UP AIR COMES FROM ADJACENT SPACES AND IS INTRODUCED VIA AIR CONDITIONING UNITS FORM59-6-13 29 -TABC AABC 4„orisi�AU B��Mof uxl� INDEPENDENT TESTING ENGINEERS PROJECT: PUBLIX REMODEL (STORE #855) PROJECT ID: FL18-222 LOCATION: 7576 SOUTH US 1: PORT ST LUCIE, FL 34952 FAN DATA SHEET FAN DATA SPECIFIED DESIGN DATA FAN # EXISTING F-1 EXISTING F-4 F-5 F-6 LOCATION/SERVES EMPLOYEE RR JANITOR DELI HOOD, GH-1 DELI HOOD GH-2 CFM 180 180 2700 1000 STATIC PRESSURE "wq 0.25 0.25 0.79 0.84 HP/BHP 1/30/- 1/30/- Y,/- 1/3/- FAN RPM - 718 1156 FIELD TEST DATA DATE TESTED 7-1-19 7-1-19 7-1-19 7-1-19 MANUFACTURER GREENHECK GREENHECK GREENHECK GREENHECK MODEL# G-070-D-X G-070-D-X CUBE-220-HP-7-G CUBE-141-3-G SERIAL # 1581608 15616110 15770023 15770029 MOTOR MFR GREENHECK GREENHECK MARATHON MARATHON MOTOR HP/BHP 1/30/- 1/30/- %/'% '/,/'/. MOTOR RPM 1550-1300-1050 1550-1300-1050 1725 - 1425 1725 - 1425 NP AMPERAGE 1.1 1.1 2.7-2.6 / 1.4 1.6-1.6 / 0.8 NP VOLTAGE 115 115 208-230/460 203-230/460 SERVICE FACTOR NOT GIVEN NOT GIVEN 1.15 1.15 TEST AMPERAGE 0.8 0.8 1.9 1.2 TEST VOLTAGE / PHASE 117 / 1 117 / 1 NO ACCESS 208 / 3 HEATER MODEL THERMALLY PROTECTED THERMALLY PROTECTED THERMALLY PROTECTED THERMALLY PROTECTED HEATER RATING THERMALLY PROTECTED THERMALLY PROTECTED THERMALLY PROTECTED THERMALLY PROTECTED HEATER SETTING THERMALLY PROTECTED THERMALLY PROTECTED THERMALLY PROTECTED THERMALLY PROTECTED FAN SHEAVE DIRECT DRIVE DIRECT DRIVE O AK46 X W MOTOR SHEAVE DIRECT DRIVE DIRECT DRIVE O 3 Yz" X Sls" OT / C to C DIRECT DRIVE DIRECT DRIVE © 2 / 5 3/s" BELTS DIRECT DRIVE DIRECT DRIVE © 41-230R RPM DIRECT DRIVE DIRECT DRIVE 702 1164 SUCTION SP, °w DISCH. SP, "w TSP,"w CFM O 228 O 318 2464 991 NOTES: O NO SPEED CONTROLLER INSTALLED © WIRED DIRECT; NO MEANS TO STOP THE FAN TO GATHER DRIVE PACKAGE INFORMATION FORM17-6-13 30 TABC AAHC As!edsfwdls 8a+aece cme�Il INDEPENDENT TESTING ENGINEERS PROJECT: PUBLIX REMODEL (STORE #855) PROJECT ID: FL18-222 LOCATION: 7576 SOUTH US 1: PORT ST LUCIE FL 34952 FAN DATA SHEET FAN DATA SPECIFIED DESIGN DATA FAN # EXISTING F-7 EXISTING F-8 SF-1 LOCATION/SERVES SCULLERY HR-1 BAKERY OVEN DELI HOOD GH-1 CFM 750 1000 1700 STATIC PRESSURE "wq 0.375 0.73 0.64 HP/BHP '/./- '/:/- ''%/- FAN RPM _ _ loll FIELD TEST DATA DATE TESTED 7-1-19 7-1-19 7-1-19 MANUFACTURER GREENHECK GREENHECK GREENHECK MODEL# G-123-VG-5-X CUE-121-VG-4-G KSFB-109-H15-01 SERIAL # 12359443 13524539 15770000 MOTOR MFR VARI GREEN VARI GREEN MARATHON MOTOR HP/BHP y,/_ y,/_ %/y MOTOR RPM 300-1725 300-1725 1725 - 1425 NP AMPERAGE 6.2 3.9 2.7-2.8 / 1.4 NP VOLTAGE 110/120 110/120 208-2301460 SERVICE FACTOR NOT GIVEN NOT GIVEN 1.15 TEST AMPERAGE 5.1 2.5 2.3 TEST VOLTAGE / PHASE 117 / 1 .117 / 1 NO ACCESS HEATER MODEL THERMALLY PROTECTED THERMALLY PROTECTED THERMALLY PROTECTED HEATER RATING THERMALLY PROTECTED THERMALLY PROTECTED THERMALLY PROTECTED HEATER SETTING THERMALLY PROTECTED THERMALLY PROTECTED THERMALLY PROTECTED FAN SHEAVE DIRECT DRIVE DIRECT DRIVE 4 3/<" X %" MOTOR SHEAVE DIRECT DRIVE DIRECT DRIVE 3%" X Y" OT / C to C DIRECT DRIVE DIRECT DRIVE 2'/2 / 15 %" BELTS DIRECT DRIVE DIRECT DRIVE AP41 RPM DIRECT DRIVE DIRECT DRIVE 1022 SUCTION SP, "w -0.72 DISCH. SP, °w TSP "w CFM VERIFIED OPERATION 0248 1744 NOT tom: o U.bb F 12 X 4bU FHM = 248 GFM (AT MAXIMUM SPEED) FORM17-6-13 31 TABC ,iL4BC A..oe+atMA 9afa Caa p INDEPENDENT TESTING ENGINEERS PROJECT: PUBLIX REMODEL (STORE #855) PROJECT ID: FL18-222 LOCATION: 7576 SOUTH US 11 PORT ST LUCIE. FL 34952 EXISTING F-1 EXHAUST AIR DISTRIBUTION SHEET DATE TESTED: 7-3-19 im SPEC ,IFIED DESIGN FINAL FIELD TEST ©®®�©®®®®®®®® OF �=___-__ ______- NU I r,: t I K= LA151 ING I O KEMAIN O NO OPPOSED BLADE DAMPERS OR MANUAL VOLUME DAMPERS INSTALLED FORM40-08-07 32 TABC INDEPENDENT TESTING ENGINEERS Observation and Deficiency Report for Publix Remodel #855 Port St July 1-3, 2019 1000 Holcomb Woods Pkwy Bldg. 200, Suite 290 • Roswell, Georgia 300760 Phone: 678-393-9401 0 Fax: 678-366-2227 aasc Ansoclalud AL 041a n Coumll TABC e Observations, Comments &Deficiencies asac aa.«raenear Hvwrea souxn INDEPENDENT TESTING ENGINEERS PROJECT: PUBLIX REMODEL (STORE #855) PROJECT ID: FL18-222 LOCATION: 7576 South US 1; Port St. Lucie, FL 34952 DATE: 7/1-3/2019 GENERAL COMMENTS I. CERTIFICATION STATEMENT A. All data contained in this report has been compiled from the equipment and systems installed on the job. All values in this report are true and correct as of the date of test and are within the limits of field test error. All tests performed on this project meet or exceed the standards set forth by the Associated Air Balance Council (AABC) National Standards 7th edition, 2016. B. All supply air diffusers, return air and exhaust air registers/grilles were measured with a calibrated flow hood reading directly in cfm. Sidewall registers, grilles and exhaust hoods were measured with a direct reading instrument reading in velocity and then converted to cubic feet per minute. Pitot tube traverses were made at main ducts, where possible, in order to determine total system flow. II. OBSERVATIONS, COMMENTS & DEFICIENCIES A. The priority coding for Observations and / or Deficiencies included herein is as follows: H = High Priority: Items to be corrected for proper system balance and operation. M = Medium Priority: Items not critical for system operation, but must be corrected. L = Low Priority: Items to be reviewed for future course of action. FYI = For Your Information B. Once the "Responsible Party" is identified, the responsible contractor should take the appropriate corrective action(s) to correct the deficiency items listed herein. Once all deficiency items have been corrected, TABC must be notified in "writing" in order to schedule a retest of the deficient item(s). Retesting of deficient items, if necessary, may be subject to additional charges depending upon the contract agreement. C. Only outstanding deficiency items are listed in this report. Please see the attached field punch report for the complete list of all deficiency items found during our testing. 1000 Holcomb Woods Pkwy Bldg. 200, Suite 290 • Roswell, Georgia 30076 • Phone: 678-366-2108 . Fax: 678-366-2227 TABC INDEPENDENT TESTING ENGINEERS Observations, Comments & Deficiencies PROJECT: PUBLIX REMODEL (STORE #855) LOCATION: 7576 South US 1; Port St. Lucie, FL 34952 s AABC Abe =N dAU"N Cai,mtll PROJECT ID: FL18-222 DATE: 7/1-3/2019 Nest Date Item # Observations, Comments & Deficiencies Priority Responsible Comments / Photo Status Party Existing AC-1 7/1-3/2019 1. There is noticeable air leakage around the control section of the H unit. Existing AC-1 7/1-3/2019 2. Both of the compressors will not engage. H Existing AC-2 The supply grilles for outlet #s 4 and 5 are installed backwards. 7/1-312019 3. These 2 outlets are low on airflow (41% and 44% of design airflow, H respectively). Existing AC-3 7/1-3/2019 4. The ductwork for supply air outlet #10, serving Women's H Restroom, is broken and it is discharging air above the ceiling. Existing AC-3 The opposed blade damper for return air inlet #1 is not operational 7/1-3/2019 5. and there is no manual volume damper installed. The measured H airflow is 332 cfm or 166% of the specified design airflow of 200 cfm. 1000 Holcomb Woods Pkwy Bldg. 200, Suite 290 • Roswell, Georgia 30076 • Phone: 678-366-2108 • Fax: 678-366-2227 TABC Observations, Comments & Deficiencies INDEPENDENT TESTING ENGINEERS PROJECT: PUBLDf REMODEL (STORE #855) LOCATION: 7576 South US 1; Port St. Lucie, FL 34952 AABC As,ai W.d All Ba .C.0 l PROJECT ID: FL18-222 DATE: 7/1-3/2019 Test Date Item # Observations, Comments & Deficiencies Priority Responsible Comments / Photo Status Party Existing AC-3 7/1-3/2019 6. There is no opposed blade damper or manual volume damper H installed on return air inlet #3. The measured airflow is 308 cfm or 154% of the specified design airflow of 200 cfm. Existing AC-4 7/1-3/2019 7. The VAVs do not have KMC model MEP-5001 actuators installed. H There is no means to set minimum airflow. Existing AC-4 7/1-3/2019 8. The actuator for VAV-2, serving Manager's Office, is not H operational. It will not open the damper from the CPC board. Existing AC-4 7/1-3/2019 9. Supply air outlet #4, served by VAV-3, in the General Office has H no finish trim installed. 1000 Holcomb Woods Pkwy Bldg. 200, Suite 290 • Roswell, Georgia 30076 • Phone: 678-366-2108 e Fax: 678-366-2227 TABC INDEPENDENT TESTING ENGINEERS Observations, Comments & Deficiencies PROJECT: PUBLIX REMODEL (STORE #855) LOCATION: 7576 South US 1; Port St. Lucie, FL 34952 AABC A uxiaf<tl AL 9 W �rtce Caux4 PROJECT ID: FL18-222 DATE: 7/1-3/2019 Test Date Item # Observations, Comments & Deficiencies Priority Responsible Comments / Photo Status Part Existing AC-4 7/1-3/2019 10."'��"'' The actuator, for VAV-5, is not connected to the VAV box. H f Existing AC-4 7/1-3/2019 11. There is no opposed blade damper or manual volume damper H installed on supply air outlet #13, serving Floral. Existing AC-4 7/1-3/2019 12. There is no opposed blade damper or manual volume damper H installed on return air inlet #3, serving the Lounge. Existing AC-5 7/1-3/2019 13. This unit is scheduled for 250 cfm outside air; however, there is no H outside air intake and damper installed. Existing AC-5 7/1-3/2019 14. There is an extra supply air outlet installed on this unit that is not FYI shown on the drawing. rl 1000 Holcomb Woods Pkwy Bldg. 200, Suite 290 • Roswell, Georgia 30076 e Phone: 678-366-2108 • Fax: 678-366-2227 TABC INDEPENDENT TESTING ENGINEERS Observations, Comments & Deficiencies PROJECT: PUBLIX REMODEL (STORE #855) LOCATION: 7576 South US 1; Port St. Lucie, FL 34952 0 a AABC Awa I.Md/ W1. CO.W? PROJECT ID: FL18-222 DATE: 7/1-3/2019 Test Date Item # Observations, Comments &Deficiencies Priority Responsible Comments / Photo Status . Par Existing AC-5 7/1-3/2019 15. The opposed blade damper for supply air outlet #1 is not H operational. The measured airflow is 449 cfm or 74% of the specified design airflow of 605 cfm. Existing AC-5 7/1-3/2019 16. Supply air outlet #2 is tapped off the wrong duct size. Drawing M01.01 shows it is to be tapped off from a 17" Q duct; however, it is FYI tapped off from a 20"� duct. F•5 i 1NEn �;' Existing AC-5 7/1-3/2019 17. The existing duct has no duct sealer or insulation installed. H Existing AC-5 7/1-3/2019 18 The measured return airflow (3976 cfm) is higher than the H measured supply airflow (3642 cfm). TABC suspects duct leakage or that the curb adaptor is not compatible with the existing duct. 1000 Holcomb Woods Pkwy Bldg. 200, Suite 290 • Roswell, Georgia 30076 A Phone: 678-366-2108 • Fax: 678-366-2227 TABC INDEPENDENT TESTING ENGINEERS Observations, Comments & Deficiencies PROJECT: PUBLIX REMODEL (STORE #855) LOCATION: 7576 South US 1; Port St. Lucie, FL 34952 AABC Ast o=44nAbsel dCou ? PROJECT ID: FL18-222 DATE: 7/1-3/2019 Test Date Item # Observations, Comments & Deficiencies Priority Responsible Comments / Photo Status Party Existing AC-6 i I `1 7/1-3/2019 19. This unit is scheduled for 250 cfm outside air; however, there is no H k:^ ' = outside air intake and damper installed. 1 �- it � A Existing AC-6 7/1-3/2019 20 The measured return airflow (3228 cfm) is higher than the H measured supply airflow (3744 cfm). TABC suspects duct leakage or that the curb adaptor is not compatible with the existing duct. Existing ERV-1 7/1-3/2019 21. This unit is not operational. The motors for exhaust fan and supply H fan are seized. Existing ERV-1 7/1-3/2019 22. There is no opposed blade damper or manual volume damper H installed on any of the exhaust air inlets. 1000 Holcomb Woods Pkwy Bldg. 200, Suite 290 • Roswell, Georgia 30076 a Phone: 678-366-2108 a Fax: 678-366-2227 TABC INDEPENDENT TESTING ENGINEERS Observations, Comments & Deficiencies PROJECT: PUBLDC REMODEL (STORE #855) LOCATION: 7576 South US 1; Port St. Lucie, FL 34952 AAsc A.w WddAba8II.I CcU ll PROJECT ID: FL18-222 DATE: 7/1-3/2019 Test Date Item # Observations, Comments & Deficiencies priority Responsible Comments [ Photo Status Part Existing F-1 (Employee Restroom) 7/1-3/2019 23. There is no opposed blade damper or manual volume damper H installed for the two exhaust air inlets. Existing F-1 (Employee Restroom) 7/1-3/2019 24 The measured airflow is 228 cfm or 126% of the specified design H airflow of 180 cfm. There is no speed controller installed. Existing F-4 (Janitor) 7/1-3/2019 25 The measured airflow is 318 cfm or 177% of the specified design airflow of 180 cfm. There is no speed controller installed. H F-5 (Deli Hood; GH-1) 7/1-3/2019 26. This fan is wired direct (no disconnect switch installed). There is H no means to shut the fan down to gather drive package information. 1000 Holcomb Woods Pkwy Bldg. 200, Suite 290 9 Roswell, Georgia 30076 • Phone: 678-366-2108 • Fax: 678-366-2227 TABC INDEPENDENT TESTING ENGINEERS Observations, Comments & Deficiencies PROJECT: PUBLIX REMODEL (STORE #855) LOCATION: 7576 South US 1; Port St. Lucie, FL 34952, AA8G q wNMep Ab ue�anco Co,urcli PROJECT ID: FL18-222 DATE: 7/1-3/2019 Test Date Item # Observations, Comments & Deficiencies Priority Status Responsible Party Comments / Photo Existing F-8 (Bakery Oven) The measured airflow is 248 cfm or 25% of the specified design airflow of 1000 cfm with the fan set at maximum speed.. TABC 7/1-3/2019 27. did not locate any issues with ductwork. The measured static Fl pressure is 0.72 in.wg. The measured amperage draw is 2.5 compared to motor nameplate full load amperage of 3.9 amp. Further investigation should be conducted to identify the cause of low airflow so that corrective action can be taken. With the above in mind, we believe that our test and balance report should be self-explanatory; however, should any questions arise, please do not hesitate to contact us. TABC, E�' 1-sllmwllle�rao f46eeu Eli Feliciano / Aeny Abreu Reviewed by: Achara Arnold, P.E., CEM, CxA, TBE y, 1000 Holcomb Woods Pkwy Bldg. 200, Suite 290 • Roswell, Georgia 30076 • Phone: 678-366-2I08 • Fax: 678-366-2227 TABC do Aasoolaferl AfrBelanas toxncN txpetBNaurtrrr�s•t•avtz t;<vrtKt>tilts PACE #: PROJECTNAMEt IU it �� TABCTECHNICIAN: .40Jryot) PROJECT LOCATION: ZuY%F �� f+ L'� 1 � . �i. PROJECT #• it. CONTRACTOPU RECID Byl Dato oP ltetura 9 rl Item tt pate Tested Discipline Descriptlon arDaffalencles or Observations Cert•ceted Not Corrected 131 t r %t �} rk 3 rtr� Crrt, ?tl rl l /U iNt wit, LJAvL. 6Ae1vh 0,rf6v' will .00, fS &. 622— err fjjjd&kC 0 f Fa9U Zer e. Jikt4C 4e � �,�t�llt 1� ®r�.!•1e e�` � !ra �rct��t, r r.'��'rr'a��t - ;Okll r U A l 11 eIe, da QC'(iUfiin tln.l2 .* 3 WA) aer° Oy M4 ) 7 i/ s 4t�P rWrl' �t1t ,�rlUl l��s rJ 1tib�Wws �0 �' ,t+r1+i, rYy Vk1 C . ' Uuloofv WMek M Gek," I U }ze �t4J .kv Awl Test and balance Corporation hps.provided the above deiicicudics for your intbrtmmtion and hutleiive 11 should bo understood iimt linal balance cannot be completed until lhcse deticlencles me corrected and ` wr(&ni. nalifrcaliou" orsame lips been Meelved. 100011olcomb Woods Parkway 94tto 0290. Roswell GA 30076 *Telephono(678) 393-9401 ,pnesimik (678) 3W2227 TAB C c Amw1atod Air selenee Cauneg IN21TENUMT TRUING aNCINEMW PAGF. #: PROJF,CTNAME: },�Ui)I 1 S S TABCTF.CHNICIAN:_ PROJECT LOCATION': r i s' 1' f„„. ,, a :.' , i r_ . PRUJF.CT tF; CONTRACTOR: REC'D BY: Date of Return' S itemil Date Teijed Discipline Inscription ofDolklenclesorObservations Corrected Not Corrected vkl I/- d-. 4 GctA+w 1,5 jkve)/441?j 44rv'td'W" A04' y,�llyr—S� tY ✓ % GUd�d . )." ,U0 mvo ctr Oil . 11^t J" /18r,�1 r� rrc f� eft. r L crdd �t�te'V4r S rS tE U iG J ,j'r`, I + y +34- f L)Qc5 IY�fP �)tf1@�� s Ir'�i: U(ttC %IIL4{{ )v GV' Test and Balnnco Corporation lies ptovided the above dcftciencies: for yoni flitprtilation =d initiative..It sliould be uuderstood dial haul Iztliinceeannot be completed taitil Iliso der4leecics are corrocled and "IVIVen ito�imfign" of sanio iiea been received. 10OD Holcomb Wobda Parkway S.oilo ii2911, Roswotl QA 30076 u7'elepiloite (¢78) 393A401 wPacsbniie (678) 36(-2227 I TAB lNj)fv%NpEK-rTmj!2 Mwmm PROJECT NAME- — PROJECT LOCATION- CONTRAMOR.- — t m Anwalated Air Buena Coupoff PAGE #. LJ TABC TECHNICIAN: PROJECTM RJECD BY: Data of Return TrIa Item 0 Date Tested Discipline Description ofDaficlencles or Observations Corremod Not Corrected culf 1-11 /X#lpf, 41C evi, �wA st Je G A AV QV ALAI ,40XIMW t4 r, I NO <Oleet-1 C%%dllral 119M / 45�) "410 0 W arm 1% hat L4 Test and flakinco-Cotporation has provided the Move deficiencies for your hiform4 on And. initiative. It should be understood that fund b11101100 M1110t bO MWOodumill those deficiencies we corrected aw tri Y. tti tCtldlpli"ofsaluo 11% been repewed. 1000 Holcomb Woods Parkway Suito WO, Roswell (3A 30076 01'elphoue (67 $)393t941)1 *Vawlm9e(67S)36&2277 TAB C MrPENDBNTTFSTINC ENCtNAM AssaolaMdA& BalawaCoum# PROJGf PAVE: - '- -- --1�—V V- i PAGE a:: TABCTLCANICIAn I PROJECT LOCATION: lvG. kJ PROJPCI'M CONTRACTOR: RE CID BY. - Date of Return Trip Item 11 Date -tested Diselpllne Doserlptian of Detidenales or Observations Corrected Not Corrected Av k i �ufisi�i� fro ' A � AV!:tS rJ eoPE1f 1l �`l'&- andL 454't° 317 d" he rf�S�$ta d! ho- C104- l xryf 5, Tcst:pid Bulanee Corporation Ims ptovldcd the above deficiencies for your intbnantion and Initiative. It should be nurlcrstood tiwt fnml balance cannot beoompleled un0l thasa'tlaficicncics aie.eorreeted and'SPrillsn nollflcnllou" ofsanic lias bceo received: 1000 Holcomb Woods Parkway Suite A29% Roswell GA 3M6 *Telephone (678) 393-9401 #Facsimile (673) 366.2227 TABC INDEPENDENT TESTING GNr,INU S .rlABC a..acmrna ur amanco camrcu PROJECT: Publix Super Markets (Store 855) PROJECT ID: FL,18-222 LOCATION: 7576 S. US Highway 1; Port Saint Lucie, FL 34952 DATE: 2/6I2019 SUMMARY OF DEFICIENCY ITEMS / COMMENTS Below is a short summary of the issues identified during our sun e . It is recommended that the report he reviewed in its entiret . ITEM UNIT #/ DEFICIENCIES / COttIMENTS # DESCRIPTION I Building Pressurization ' Our test indicates that this store is operating under negative pressurization of 1132 cfin (3646 cfin outside air - 4778 cfin exhaust air = -1 132 cfin). • Only one stage of cooling is operational. 7 P- ''' l-l"n 2 AC-1 (Sales) • The high discharge static pressure (+2.38 in.wg.) indicates there is some restriction in the system. )�(b5 ca i'?:'r„ -. ',i 3 AC-2 (Salos) • This unit is operating in low speed. It will not go into high with the dip switch. • Ilie outside air damper is closed; it only opens in high speed. CV Me, f t, iv 4 AC-5 (Deli) The outside air intake and damper are not install,,A r r, J 5 AG6 (Bakery) • The outside air intake and damper are not installed. s i • VAV #s 1-4 do not have KMC model MEP-5001 actuator installed. G VAVs lri 't ' ' VAV #5, serving the Pharmacy, is not accessible at the time of this survey. • VAV 96, serving Floral, does not have a manual volume damper installed on the entering side of the VAV box. Also, there is no access to the actuator. 7 F-1 (Employee RR) • This fat is not operational. �12 r1rS 8 `4 (Mop Wash) • This fan is not operational. -2 l7/!S rc -, tf t 9 F-5 (Janitor) • This fan is not operational. 10 F-7 (FIR-1) • This fan is not operational. 1000 1 lolcomb Woods Parkway, Suite 290 • Roswell. Geoq& 30076 • Phone: 678-366-2103 • Fax: 673-366-2227 SNDIIV .I� • �_ �s Ike' n? 4 i ;TryUi E � . y{i 4 :1 I r MA ayYpyau lotlna YBCM►� ==a 'ai j i r ; 1� !N 2