HomeMy WebLinkAboutMISC LETTERSPAUL WELCH INC. Mechanical * Electrical * Civil Engineering 1984 S.W. Biltmore St. Suite#114 Port Saint Lucie, FL 34984 Phone (772) 785 - 9888 August 9, 2018 Email pwelchinc@aol.com Re: Re -Roof 900 Rock Rd. Fort Pierce, FL FILE C0 0v To Whom It May Concern: SCANNED By St. Lucie County Our office has calculated the required design pressure in accordance with ASCE 7-10 and FBC 2017 (61 Edition) for the roof replacement at the above referenced address. Wind speed: V it: 170mph, V,,d: 132 mph Exposure: C Enclosure Type: Enclosed Risk Category: End Zone Width (a): III 3'-0" p 1� R t «a �- D 3 f v Mean Roof Height: 12'-4" C-t P-%.kC orb Roof Slope: 0.5 / 12 ST. LUCIE COUNTY BUILDING D ?SION REVIEWED FOR COMPLIANCE „„ . i / n. A Required Design Pressure: Zone l: -37.3 PSF Zone 2: -58.8 PSF Zone 3: -83.9 PSF ruirva .vrvu FLKMIT MUST BE K T N JOB SITE OR NO INSPECTION(S) KLVIBE MADE Roofing to be installed shall be equal to, or exceed the required design pressures as listed above. All installations shall be in accordance with FBC 2017, Product Approval and manufacturer's installation instructions. Proposed Roof: Gulf Coast Supply & Manufacturing, LLC 24ga. GulfPBR Roof Panel (FL# 11650.2) Design Pressure -150 PSF (purlins 2'-0" O.C.) Design Pressure - 60 PSF (purlins 5'-0" O.C.) CONCEALED FASTENERS OR ATTACHMENTS Submitted by: ARE EERRES�PONSIIRBI �R THE PAUL ftIE C'H INC. ARTANR CORK ARE THESE Y COETIO S REQUIRED BY FIELD INSPECTORS THAT MAY BE NECESSARY IN ORDER TO Paul 1 , P.E. COMPLY WITH ALL APPLICABLE CODES. Reg. N 9945 Attach: Roof Zone / Purlin Spacing Plan; Windload, and Product Approval