Product Evaluation Report
January 8, 2009
Application Number. FL-6410 SCANNED
FLB Project Number. O6-FSC-0006 BY
St. Lucie County
Product Manufacturer. Folding Shutter Corporation
Manufacturer Address: 7089 Hemstreet Place
West Palm Beach, FL 33413
Product Name & Description: Titan II Folding (Accordion) Shutter
Scope of Evaluation:
This Product Evaluation Report is being issued in accordance with the requirements of the Florida
Department of Community Affairs (Florida Building Commission) Rule Chapter 913-72.070, F.A.C., for
statewide acceptance per Method 1(d). All products listed above have been tested and/or evaluated as
summarized herein to show compliance with the 2007 Florida Building Code and are, for the purpose
intended, at least equivalent to that required by the Code. Re-evaluation of this product shall be required
fallowing pertinent Florida Building Code modifications or revisions.
Substantiating Data:
FLB drawing #06-FSC-0006 titled "Titan II Folding Shutter', sheets 1-5, prepared by Frank L. Bennardo,
P.E., Inc., signed & sealed by Frank L Bernardo, P.E. is an integral part of this Evaluation Report
• TEST REPORTS
Uniform static structural performance has been tested in accordance with TAS 202 test standards per test
report(s) #0143-0408-02 & #0143-0903-01 by Hurricane Test Laboratory (HTL).
Large missile impact resistance and cyclic loading performance have been tested in accordance with TAB
201 & 203 test standards per test report(s) #0143-0408-02 & #0143-0903-01 by Hurricane Test
Laboratory (HTL).
Metal tensile capacity has been determined in accordance with ASTM E8 test standard per test report
#2KM-1334 by Q C Metallurgical, Inc..
• STRUCTURAL ENGINEERING CALCULATIONS
Structural engineering calculations have been prepared which
_evaluate the product based on comparative and/or rational
analysis to qualify the following design criteria:
1. Maximum Allowable Spans
2. Minimum Glass Separation
3. System Porosity
4. Anchor Spacing
No 33% increase in allowable stress has been used in the
design of each product
160 SW 12T" AVENUE #106 DEERFIELD BEACH, FL 33442
PHONE: 954-354-0660 FAX: 954-354-0443
for
WWW.ENGEXP.COM
2009
Page 2 of 2
Folding Shutter Corp. — Titan II Accordion Shutter
When installed outside the HVHZ, this system has been designed as a non -porous assembly as defined in
the ASTM E1996-02 standard. Therefore, a minimum separation between the shutter and any glazing
behind it is NOT required outside the HVHZ.
The 144" span shown in the glass separation note is the maximum span at which the product was tested
per test report #0143-0408-02, specimens #1, 2, & 4.
The separation from glass shown in the installation drawings (detail 1, sheet 5) of 3.25" is derived from
test report #0143-0408-02, specimen #2, section 18.1.1. This is the worst -case impact deflection
exhibited in testing at the 144" span. The worst case impact deflection at 99.5" slat span is based on test
report #0143-0408-02, specimen #5, section 18.1.
Impact Resistance:
Large Missile Impact Resistance has been demonstrated as evidenced in previously listed test reports,
and is accounted for in the engineering design of this product.
Slats with polycarbonate "windows" and perforated slats are qualified as impact -resistant per HTL test
report#0143-0903-01 listed above (Ref. sample#1).
The 2"x2"xl/8" comer post and end slat is qualified as an acceptable component of this impact resistant
system per Florida Product Approval4FL7288 (ASSA Accordion Shutter).
Wind Load Resistance
Each product has been designed to resist wind loads as indicated in the span schedule(s) on its
respective Product Evaluation Document (i.e. engineering drawing).
Installation
Each product listed above shall be installed in strict compliance with its respective Product Evaluation
Document (i.e. engineering drawing), along with all components noted therein.
Each product component shall be of the material specified in that product's respective Product Evaluation
Document (i.e. engineering drawing).
Limitations & Conditions of Use:
Use of each product shall be in strict accordance with its respective Product Evaluation Document (i.e.
engineering drawing) as noted herein.
All supporting host structures shall be designed to resist all superimposed loads and shall be of a material
listed in each product's respective anchor schedule. Host structure conditions which are not accounted
_ for in each product's respective anchor schedule shall be designed for on a site -specific basis by a
registered professional engineer.
All components which are permanently installed shall be protected against corrosion, contamination, and
other such damage at all times.
Each product has been designed for use within the High Velocity Hurricane Zone (HVHZ).
160 SW 12T" AvENUE #106 DEERFIELD BEACH, FL 33442
PHONE: 954-354-0660 FAX: 954-354-0443
WWW.ENGEXP.COM
ENGINEERING
EXPRESSO
Product Evaluation Report
January 8, 2009 SCA
LBAppIIcation PrroNumber. St C Project Number: 06-FSC-0007 Ft0e COU17
Product Manufacturer. Folding Shutter Corporation
Manufacturer Address: 7089 Hemstreet Place
West Palm Beach, FL 33413
Product Name & Description: Titan 0.060" Aluminum Storm Panels
Scope of Evaluation:
This Product Evaluation Report is being issued in accordance with the requirements of the Florida
Department of Community Affairs (Florida Building Commission) Rule Chapter 913-72.070, F.A.C., for
statewide acceptance per Method 1(d). All products listed above have been tested and/or evaluated as
summarized herein to show compliance with the 2007 Florida Building Code and are, for the purpose
intended, at least equivalent to that required by the Code. Re-evaluation of this product shall be required
following pertinent Florida Building Code modifications or revisions.
Substantiating Data:
• PRODUCT EVALUATION DOCUMENTS
FLB drawing #06-FSC-0007 titled "Titan 0.060" Aluminum Storm Panels", sheets 1-5, prepared by Frank
L. Bernardo, P.E., Inc., signed & sealed by Frank L. Bernardo, P.E. is an integral part of this Evaluation
Report.
TEST REPORTS
Uniform static structural performance has been tested in accordance with TAS 202 test standards per test
report(s) #94-85 by Hurricane Engineering & Testing, Inc. (HETI) and per test report(s) #0143-0805-97 &
40143-1217-97 by Hurricane Test Laboratory (HTL).
Large missile impact resistance and cyclic loading performance have been tested in accordance with TAS
201 & 203 test standards per test report(s) #94-86 & #98-723 by Hurricane Engineering & Testing, Inc.
(HETI) and per test report(s) #0143-0805-97 & #0143-1217-97 by Hurricane Test Laboratory (HTL).
Metal tensile capacity has been determined in accordance with ASTM E8 test standard per test report
#95-T88 by Hurricane Engineering & Testing, Inc. (HETI).
STRUCTURAL ENGINEERING CALCULATIONS
Structural engineering calculations have been prepared which
evaluate the product based on comparative and/or rational
analysis to qualify the following design criteria:
1. Maximum Allowable Spans
2. Minimum Glass Separation
3. Anchor Spacing
160 SW 12TH AVENUE #106 DEERFIELD BEACH, FL 33442
PHONE: 954-354-0660 FAX: 954-354-0443
WWW.ENGEXP.COM
,F
C
Folding Shutter Corp. — Titan 0.060" Aluminum Storm Panels
No 33% increase in allowable stress has been used in the design of each product
Impact Resistance:
2009
Page 2 of 2
Large Missile Impact Resistance has been demonstrated as evidenced in previously listed test reports,
and is accounted for in the engineering design of this product.
Wind Load Resistance
Each product has been designed to resist wind loads as indicated in the span schedule(s) on its
respective Product Evaluation Document (i.e. engineering drawing).
Installation
Each product listed above shall be installed in strict compliance with its respective Product Evaluation
Document (i.e. engineering drawing), along with all components noted therein.
Each product component shall be of the material specified in that product's respective Product Evaluation
Document (i.e. engineering drawing).
Limitations & Conditions of Use:
Use of each product shall be in strict accordance with its respective Product Evaluation Document (i.e.
engineering drawing) as noted herein.
All supporting host structures shall be designed to resist all superimposed loads and shall be of a material
listed in each products respective anchor schedule. Host structure conditions which are not accounted
for in each product's respective anchor schedule shall be designed for on a site -specific basis by a
registered professional engineer.
All components which are permanently installed shall be protected against corrosion, contamination, and
other such damage at all times.
Each product has been designed for use within and outside the High Velocity Hurricane Zone (HVHZ).