EVALUATION REPORT
Polyglass USA, Inc. Evaluation Report P12060.02.09-R24
1112 West Newport Center Drive FL52S9-R28
Deerfield Beach, FL 33442 Date of Issuance: 02/24/2009
(954) 233-1230 Revision 24-.01/24/2018
SCOPE:
This Evaluation Report is issued under Rule 61620-3 and the applicable rules and regulations governing the use of
construction materials In the State of Florida. The documentation submitted has been reviewed by Robert Nleminen, P.E.
for use of the product under the Florida Building Code and Florida Building Code, Residential Volume. The products
described herein have been evaluated foi compliance with the e Edition (2017) Florida Building Code sections noted
herein.
DESCRIPTION: Pollyglass Roof Underlayments;
LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted herein.
CoiTrINUED COMPLMNCE: This Evaluation Report is valid until such time as the named product(s) changes, the referenced
Quality Assurance documentation changes, or provisions of the Code that relate to the product change. Acceptance of this
Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. of any changes to the
product(s), the Quality Assurance or the production facility location(s). NEMO I etc. requires a complete review of this
Evaluation Report relative to updated Code requirements with each Code Cycle.
ADvEFrnSEMENT: The Evaluation Report number preceded by the words "NEMOJetc. Evaluated" may be displayed in
advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done In its entirety.
INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or its
distributors and shall be available for inspection at the job site at the request of the Building Official.
This Evaluation Report consists of pages I through 14.
Prepared by:
Robert J.M. Nieminen, P.E.
Florida Registration No. 59166, Florida DC4 ANE1983
The famimlle seal appearing was authorized by Robert Nlemlnen,
P.E. an OV24/2018. This does not some as an electronically
signed document.
CIEFITIFICATION OF INDEPENDENCE
1. NEMOJetc. does not have, nor does It intend to acquire or will It acquire, a financial interest in any company manufacturing or
distributing products it evaluates.
2. NEMO I etc. is not owned, operated or controlled by any company manufacturing or distributing products it evaluates.
3. Robert Nieminen, P.E. does not have nor will acquire, a financial interest In any company manufacturing or distributing products for
which the evaluation reports are being Issued.
4. Robert Merriman, P.E. does not have, nor will acquire, a financial Interest In any other entity involved in the approval process of the
product.
S. This is a building code evaluation. Neither NEW I etc. nor Robert Nleminen, P.E. are,, in any way, the Designer of Record for any
project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained
specifically for that purpose.
NNEMO I etc.
ROOFING COMPONENT EVALUATION:
1. SCOPE*
Product Category. Roofing
Sub-Categarlp UnderlayrrEnt
Compliance Statement: Roof Underlayments, as produced by Polyglass USA, Inc., have demonstrated compliance with the
following sections of the 6h Edition (2017) Florida Building Code through testing in accordance with the following Standards.
Compliance is subject to the Installation Requirements and Limitations / Conditions of Use set forth herein.
Z. STANDARDS:
Section
Property
Standard
Year
1504.3.1
Wind Uplift
FM 4474
2011
1504.3.1
Wind Uplift
UL 1897
2012
1507.2.3/1507.1.1
Physical Properties
ASTM D226
2009
1507.2.4 / IS07.1.1, 1507.2.9.2
Physical Properties
ASTIM D1970
2015
ISO7.3.3
Physical Properties
FRSAJTRI April 2012
2012
1507.11.2
Physical Properties
ASTM D6164
2011
1507.11.2
Physical Properties
ASTM D6222
2011
TAS110
Accelerated Weathering
ASIM D4798
2011
3. REFERENCES:
Entity
Examination
Reference
Date
FM Approvals (TST 1867)
Wind Uplift
30D4091
01/12/2DOO
PHI M 5878)
Physical Properties
PRIO1111
04/08/2002
PHI (TST 5878)
Physical Properties
PUSA-005-02-01
01/31/2002
PHI (TST 5878)
Physical Properties
PUSA-013-02-01
12/23/2002
PHI (TST 5878)
Physical Properties
PUSA-013-02-02
12123/2002
PHI (TST 5878)
Physical Properties
PUSA-013-02-03
12123/2002
PHI (TST 5878)
Physical Properties
PUSA-018-02-02
07/14/2003
PHI (TST 5878)
Physical Properties
PUSA-028-02-01
07/1312005
PHI (TST 5878)
Physical properties
PUSA-033-02-01
01/12/2006
PHI (TST 5878)
Physical Properties
PUSA-035-02-01
09/29/2006
PHI (TST 5878)
Physical Properties
PUSA-05"2-02
12/10/2007
PHI (TST 5878)
Physical Properties
PUSA-061-02-02
01/28/2008
PHI (TST 5878)
Physical Properties
PUSA-07"2-01
02/22,/2008
PHI (TST 58781
Physical Properties
PUSA-083-02-01
04/14/2008
PHI M 5878)
Physical Properties
PUSA-088-02-01
07/2.9/2009
MTI (TST 2508)
Physical Properties
JX20H7A
04/01/2008
MTI (TST 2508)
Physical Properties
RX14EBA
01/29/2009
ERD (TST 6049)
Physical Properties
11752.09.99-1
02/08/2000
ERD (TST 6049)
Wind Uplift
11757.08.01-1
08/23/2001
ERD tTST 6049)
Wind Uplift
11776.06.02
01/16/2003
ERD (TST 6049)
Physical Properties
02200.07.03
07/14/2003
ERD (TST 6049)
Wind Uplift
P1740.01.07
01/D4/2007
ERD (TST 6049)
Physical Properties
P5110.04.07-1
04/11/2007
ERD (TST 6049)
Wind Uplift
P9260.03.08
03/21/2008
ERD (TST 6049)
Physical Properties
P13450.08.09
08/1312009
ERD (TST 6049)
Wind Uplift
P30540.12.09-111
11/30/2009
ERD DST 6049)
Physical Properties
P11030.1-1.09-1
21/30/2009
ERD W 6049)
Wind Uplift
P11030.11.09-2
11/30/2009
ERD (TST 6049)
Physical Properties
P11030.11.09-3
11/30/2009
ERD (TST 6049)
Physical Properties
P33360.06.10
06/25/2010
ERD (TST 6049)
Physical Properties
P33370.03.11
03/02/2021
ERD (T57 6049)
Physical Properties
P33370.04.11
04/26/2011
ERD (TST 6049)
Physical Properties
P37300.10.11
10/19/2011
NEMOETC,LLC. Evaluation Report P12060.02.09-R24
Cer*� qfftdw�n #32455 e EDITION (2017) FBC NON4WHZ EVALUATION FLS2S9-RZB
Polv&w Rout Underlayntersts; (9S4) 233-1230 Revision 24:01/24/2018
Page 2 of 14
ONEMOletc.
gntipf
Examination
Reference
Date
ERD OW 6049)
Physical Properties
P40390.08.12-1
08/06/2012
ERD (TST 6G49)
Physical Properties
P40390.08,12-2
08/07/2012
ERD (M 6049)
Physical Properties
C41420.09.12-3
09/11/2012
ERD M 6049)
Wind Uplift
P39680.03.13
03/0412013
ERD (IST6049)
Physical Properties
P45370.04.13
04/26/2013
ERD W6049)
Wind Uplift
P1738.02.a7-R2
04/29/2013
ERD CM 6049)
Wind Uplift
117S7.04.01-2-RI
G4/30/2013
ERD (M 6049)
Wind Uplift
P41630.08.23
08/06/2013
ERD (TST 6049)
Wind Uplift
P12751.05.03-RI
31/26/2023
ERD (TST6049)
Wind Uplift
P11781.11.03-RI
11/26/2013
ERD (TST 6049)
Physical Properties
P45270.05.24
05/12/2014
ERD(W6049)
Physical Properties
6020.a7.14-1
09/08/2014
ERD CW 6049)
Physical Properties
6020.09.14-2
09/08/2014
ERD OW 6049)
Physical Properties
6020.09.14-3
09/08/2014
ERD (TST 6049)
Physical Properties
6020.09.14-4
09/08/2014
ERD UW 6049)
Physical Properties
6020.09.14-5
09/08/2014
ERD W 6049)
Physical Properties
6020.09.14-6
09/08/2014
ERD (T57 6049)
Physical Properties
P46520.10.14
10/03/2014
ERD (TST 6049)
Physical Properties
P43290.10.14
10/17/2014
ERD (TST 6049)
Physical Properties
PLYG-SC7550.03.15
03/24/2015
ERD M 6049)
Physical Properties
P40390.04.15
04/03/2015
ERD UST 6U49)
Physical Properties
P44360.10.14-RI
05/18/201S
ERD (TST 6049)
Physical Properties
PLYG-SCSOBO.05.15-1
05/20/2015
ERD M7 6049)
Wind Uplift
PLYG-SC8905.05.16-1
05/17/2016
ERD (TST 6049)
Physical Properties
PLYG-SC8080.07.16
07/16/2016
ERD (TST 6049)
Wind Uplift
PLYG-SC12025.10.26
10/12/2016
ERD (TST 6049)
Physical Properties
PLYG-SC13D40.12.16
12/27/2016
ERD (TST 6049)
Physical Properties
PLYG-5CII900.03.17
03/10/2017
ERD (TST 6049)
Physical Properties
PLYG-SC22115.08.17
08/08/2017
ICC-ES (EVL 2396)
IBCCompliance
ESR-1697
11/01/2014
Miami -Dade (CER 1592)
HVHZ Compliance
NOA 14,0717.08
01/22/2015
Polyglass USA
Manufacturing Affidavit
Products Current
02/18/2009
Polyglass USA
PILAfficlavit
Mule -Hide Crass Ltg
03/01/2008
Polyglass USA
Materials Affidavit
PoIVstIck SA Compound
08/18/2011
UL, LLC (QUA9625)
Quality Control
Service Confirmation
Exp.10/05/2018
4. PRODucr DESCRIFnON:
4.1.1 Elastobase is a fiberglass reinforced, SBS modified bitumen base sheet.
4.1.2 Elastobase P Is a polyester-relinforced, SBS modified bitumen base sheet.
4.1.3 Polyglass G2 Base is a fiberglass -reinforced, asphaltic base sheeL
4.1.4 Polyglass APP Base is a fiberglass -reinforced, APP modified bitumen base sheet.
4.2.1 Polystick IVM or Polystick MYS PLUS is a nominal 60-mil thick rubberized asphalt waterproofing membrane, glass
fiber reinforced, surfaced with polycleflnic film surface; meets FRSAITRI April 2012.
4.2.2 Polystick IR-Xe is a nominal 60-mll thick rubberized asphalt waterproofing membrane, glass fiber reinforced, with an
aggregate surface, meets ASTIVI D1970.
4.2.3 PoWck TU Plus Is a nominal 8D-mil thick rubberized asphalt waterproofing membrane, glass fiber reinforced, with a
polyester fabric surface; meets ASTIVI D1970 and FRS"I April 2012.
NEMO ETC, U.C. Evaluation Report P12060.02.09-R24
OareRWIv ofAuthoenthm #32455 ED171ON (2017) FOC NON-HVHZ EVALUAMON R5259-R28
Polyglass Roof Underlayments, (954) 233-1230 Ftevision 24: 61/24/2018
Page 3 of 14
ONEMO I etc.
4.2.4 Polystick TU P is a nominal 130-mil thick rubberized asphalt waterproofing membrane, glass-fiber/polyester
reinforced, with a granular surface; meets FRSA/TRI April 2012.
4.2.5 Polystick TU Max is a nominal 60-mil thick rubberized asphalt waterproofing membrane with a 190 g/m 2 polyester
fabric surface; meets ASTM D1970 and FRSAITRI April 2012.
4.2.6 Polyllex SAP, Polyllex: SAP FR, Mule -Hide SAAPP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR) are polyester
reinforced, APP modified bitumen cap sheets; meet FRSAfTRI April 2012.
4.2.7 PollystIck Dual PrW" Is a nominal 60-mil thick dual -layer rubberized asphalt waterproofing membrane, fiberglass
reinforced, with a polyester fabric surface; meets ASTM D1970.
4.2.8 Polystick rile Prdm is a nominal 60-mil thick dual -layer rubberized asphalt waterproofing membrane, fiberglass
reinforced, with a polyester fabric surface; meets ASTIVI D1970 and FRSA/TRI April 2012.
4.2.9 Polystick MIJ-X is a nominal 54-mil thick dual -layer rubberized asphalt waterproofing membrane, fiberglass
reinforced, with a polypropylene film surface; meets AC188 and physical requirements of ASTM D1970 (See Section
5.8).
4.3.1 Elastoflex G TU is a polyester reinforced, modified bitumen file underlayment composed of a sand -surfaced SBS
modified bitumen back-slde and granule -surfaced APP modified bitumen top -side. Elastaflex G TU Is for use as an
alternate to "Mineral Surface Roll Roofing" (ASTM D6380, Class M) in the "Single Ply System" from FRSA)TRI April
2012 (04-12) beneath mechanically fastened tile roof systems or Hot Asphalt applied "Cap Sheet' In the "Two Ply
System" from FRSA/rRI April 2012 (04-12) beneath mechanically fastened or adhered file roof systems.
4.3.2 Elastofiex S6 G and Elastaflex S6 G FR are polyester reinforced, SBS modified bitumen cap sheets; meet ASTM D6164.
Elastoflex S6 6 and Elastoflex: S6 6 FR are for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D6380,
Class M) in the "Single Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems.
Elastofiex S6 G is for use as an alternate to Hot Asphalt applied "Cap Sheer in the 'Two Ply System" from FRSA/TRI
April 2012 (04-12) beneath mechanically fastened or adhered tile roof systems. Elastoflex S6 G FR is for use as an
alternate to Hot Asphalt applied "Cap Sheer in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath
mechanically fastened tile roof systems.
4.3.3 PolVflex G and Polyflex G FR are polyester reinforced, APP modified bitumen cap sheets; meet ASTM D6222.
Polyflex G is for use as an alternate to Heat Applied aCap Sheer In the 'Two Ply System" from FRSA/TRI April 2012
(04-32) beneath mechanically fastened or adhered tile roof systems. Polyflex 6 FIR Is for use as an alternate to Heat
Applied 'Cap Sheer in the "Two Ply System" from FRSAITRI April 2012 (04-12) beneath mechanically fastened tile
roof systems.
S. UNIFTATIONS:
5.1 This is a building code evaluation. Neither NEMO I etc. nor Robert Nieminen, P.E. are, In any way, the Designer of
Record for any project an which this Evaluation Report, or previous versions thereof, is/was used for permitting or
design guidance unl� retained specifically for that purpose.
5.2 This Evaluation Report Is not for use In the HVHZ.
5.3 Fire Classification is not part of this Evaluatlion Report; refer to current Approved Roofing Materials Directory for fire
ratings of this product.
5.4 Polygiass Roof Underlayments may be used with any prepared roof cover where the product Is specifically referenced
within FBC approval documents. If not listed, a request may be made to the Authority Having Jurisdiction for
approval based an this evaluation combined with supporting data for the prepared roof covering.
NEMO ETC, Uc. Evaluation Report P12060.02.09-R2,4
Ce�rftwft �f A.11mrWtima #32455 e EDITION (2017) FBC NON-HVHZ EVALUATION FL52594t2B
P*g1ass Roof Underlaymnts, (954) 233-IMO Revision 24:01/24/2018
Page 4 of 24
ONEMOjetc.
5.5 Allowable Roof Covers.
Underlayment
Asphalt Shingles
N211-On Tile
Foam -On Tile
Metal
Wood Shakes
Slate
Sishingles
Elastabase
Yes
Yes
Yes
Yes
Yes
Yes
Mweshenin2-nywem)
(&mShenIn2-pIysy%mmj
Elastobase P
Yes
Yes
Yes
Yes
Yes
Yes
nsseDeeln2-ply�m)
(&=Sheetln2-ply��m)
Polyglass G2 Base
No
Yes
Yes
No
No
No
(�.SMWn2-ply,�.)
(Ba.Sh�eI.2-pIywM.)
Polyglass APP Base
No
Yes
Yes
No
No
No
(�Sheatln2-plysy�m)
(BawSheetIn2-plysy�m)
Polystick MTS or MTS PWS
Yes
Yes
No
Yes
Yes
Yes
PoWlck I R-Xe
Yes
No
No
No
Yes
Yes
Polystick TU P
No
Yes
Yes (See 5.5.1)
No
No
No
PoWlckTU Plus
Yes
yes
Yes (See 5.5.1)
Yes
Yes
Yes
Polystick TU Max
No
Yes
Yes (See S.5.1)
Yes
No
No
Polystick Dual Pro
Yes
No
No
Yes
Yes
Yes
Polystick Tlle Pro
Yes
Yes
Yes (See5.5.1)
Yes
Yes
yes
Polystick MU-X
Yes
No
No
Yes
Yes
yes
Elastoftex 56 G
Yes
Yes
Yes (See 5.5.1)
No
Yes
Yes
Elastollex SG G FR
Yes
yes
No
No
Yes
Yes
Elastoflex G TU
Yes
Yes
Yes (See 55.1)
No
Yes
Yes
Polyflex G
Yes
Yes
Yes (Sees.5.1)
No
Yes
Yes
Polyflex G FR
Yes
Yes
No
NZ
Yes
Yes
Polyflex SAP or SAP FR
Yes
yes
Yes (Sees.5.1)
No
Yes
Yes
Mule -Hide SA-APP Cap Sheet
Yes
Yes
Yes (See 55.1)
No
Yes
Yes
or SA-APP Cap Sheet (FR)
I
I
I
5.5.1 "Foam -On Tile is limited to use of the following Approved tile adhesives / underlayment combinations.
U
N
Adhesive
Florida Product
Undulaynnents
Approval
DAP Foam Touch 'n Seal Stormllond Roof
FL14506
Polystick TU Plus, PolystickTU Max
Tile Adhesive
Dow'rileBond—
FL22525
Polystick TU P, Polystick TU Plus, Polyfl" SAP arTle Pro
Polystick TU P, Polystick TU Plus, Polystick TU Max, Polystick Tile Pro,
ICP Adhesives PolysetO AH-160
FL6332
Elastoflex 6 TU, Elastoflex S6 G, Polyflex G, Polyflex SAP, Polyllm SA Cap FR,
Mule -Hide SA-APP Cap Sheet or Mule�Hlde SA-APP Cap Sheet (FR)
Polystick TU P, Polystick TU Plus, Polystick TU Max, Polystick Tile Pro,
ICP Adhesives Polysetm RTA-1
FL6276
Elastoflex G TU, Elastoflex 56 G, Polyflex G, Polyflex SAP, Polyflex SA Cap FR,
I
Mule -Hide SA-APP Cap Sheet or Mule�Hide SA-APP Cap Sheet (FR)
1 Refer to Tile Manufacturer's orAdhesive Manufacturer's Florida FroductApprovalfor Overturning Moment Resistance Performance.
NEMO ETC, I.I.C. Evaluation Report P12060.02.09-R24
csoo,te ofAuthorbofla. #32455 EDMON (2017) F13C NON4lVHZ EVAWAYION FLSZSS-RZB
Palyglass Roof Underlayments; (954) 233-1230 Revision 24:01/2412018
Page 5 of 14
NNEMO I etc.
5.6 Allowable Substrates;
5.6.1 Direct -Bond to Deck:
Polystick (all variations), Dual Pro, Tile Pro, Polyflex SAP or SAP FR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet
(FR) self -adhered to:
> New untreated plywood; ASTIVI D41 primed new untreated plywood; Existing plywood; ASTM D41 primed existing
plywood; New or existing, unprimed OSB; ASTM D41 primed OSB; Southern Yellow Pine; ASTIM D41 primed
Southern Yellow Pine; ASTM 041 primed structural concrete; Huber Engineered Woods "ZIP System" Panels
(designed and installed to meet wind loads for project).
Note., Polyglass does not require priming of new or existing plywood or CISB sheathing. New or existing plywood or
OSB sheathing should be cleaned of all dirt and debrils prior to application of Polystick membranes.
Elastoflex G TU, El astoflex S6 G or Elastofl ex S6 G FR in hot aspha It to:
> ASTM D41 primed structural concrete.
Polyflex G or Polyflex G FR torch -applied to:
> ASTM D41 primed structural concrete.
5.6.2 Bond -to -insulation;
Polystick (all variations), Polyflex SAP or SAP FR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) self -adhered
to:
> ASTM C1289, Type 11, Class I polylsocVanurate or Type V polylsocyanurate-composlte Insulation; Dens Deck
DuraGuard; Dens Deck Prime; or SECUROCK Gypsum -Fiber Roof Board.
Elastoflex G TU, Elastoflex S6 G or Elasboflex S6 G FR in hot asphalt to:
> Dens Deck PrlmecirSECUROCK Gypsum -Fiber Roof Board.
Polyflex G or Polyflex 6 FR torch -applied to:
> ASTM D43. primed structural concrete; Dens Deck Prime or SECUROCK Gypsum-Rber Roof Board.
For installation under mechanically attached prepared roof coverings, insulation shall be attached per minimum
requirements of the prepared roof covering manufacturer's Product Approval. For installations under foam -on tile
systems, insulation attachment shall be designed by a qualified design professional and Installed based an testing of
the insulation/underlayment system In accordance with FBC Section 1504.3.1.
5.6.3 Bond to Mechanically Attached Base Laver:
Polystick (all variations), Polyflex SAP or SAP FIR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) Dual Pro or
Tile Pro self -adhered to:
> ASTIVI D226, Type I or 11 felt; Elastabase; Elestabase P or Mule -Hide Nall Base.
Elastoflex G TU, Elastoflex S6 G or Elastoflex SIS G FR In hot asphalt to:
> ASTIVI D226, Type I or 11 felt; Elastobase; Elastobase P, Mule -Hide Nail Base or Polyglass G2 Base.
Polyflex G or Polyflex G FR torch -applied to:
> Elastobase; Elastobase P, Mule -Hide Nail Base, Polyglass G2 Base or Polyglass APP Base.
For installations under mechanically attached prepared roof coverings, base layer shall be attached per minimum
codified requirements. For Installations under foam -on tile systems, base layer shall be attached per minimum
requirements of FRSAJTRI April 2012 (04-12), Appendix A, Table 1, Or as listed in Section 5.6.4 herein, or as tested in
accordance with FBC Section 1504.3.1.
NEMO ETC, Ut Evaluation Report P12060.02.09-R24
Certlft� cf)kuthodwli� #32455 eH EDITION (M7) FBC NON-HVHZ EVALUATION FL5259-R28
Polinifass Roof Underlayments; 19541233-2230 Revision 24:01/24/2018
Page 6 of 24
ONEMO I etc.
5.6.4 Wind Resistance for Underlayment Systems in Foam -On Tile Applications: f.RSA/TRI April 2012 (04-12) does not
address wind uplift resistance of all underlayment systems beneath foam -on tile systems, where the underlayment
forms part of the load -path. The following wind uplift limitations apply to underlayment systems that are not
addressed in FRSA1TRI April 203.2 (04-12) and are used in foam -on tile applications. Maximum Design Pressure is the
result of testing for wind load resistance based on allowable wind loads, and reflects the ultimate passing pressure
divided by 2 (the 2 to I margin of safety per FBC 1504.9 has already been applied). Refer to FRSA/TRI April 2012 (04-
3.2), Appendix A, Table 1A or FBC 1609 for determination of design wind loads.
#1 Maximum Design Pressure � -90 cisf.
Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Havingluriscliction.
Primer: None
Base Ply: (Optional) Polystick IVITS or PolystIck MTS PLUS, self -adhered.
Underlayment. Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflax SAP FR, Mule -Hide SA-APP Cap Sheet and
Mule-Hicle SA-APP Cap Sheet (FR), self -adhered.
#2 Maximum Design Pressure = -97.S psf,.
Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Primer. PG100 or ASTM D41
Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered.
Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule-Hlde SA-APP Cap Sheet and
Mule -Hide SA-APP Cap Sheet (FR), self -adhered and back -nailed within the selvedge -edge side laps using 12 ga. x
1W ring shank nails through 32 ga., 1-5/9" diametertin caps spaced 12winch C.c.
#3 Maximum Design Pressure = -105 Psf.*
Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Primer: WB-3000
Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered.
Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FIL Mule -Hide SA-APP Cap Sheet and
Mule -Hide SA-APP Cap Sheet (FR), self -adhered and back -nailed within the selvedge -edge side laps using 22 Ca. x
1Y." ring shank nails through 32 ga., 1-5/8" diameter tin mps spaced 124nch c.c.
#4 Maximum Design Pressure = -235 P
Deck: Min. 15/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Primer: (Optional) PG100 or ASTM D41
Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, seff-adhered.
Joints; Min. 4-inch wide strips of Elastaflex SA-V over all plywood Joints.
Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and
Mule -Hide SA-APP Cap Sheet (FR), self -adhered.
#5 Maximum Design Pressure = -315 p
Deck: Structural concrete to meet project requirementsto satisfaction of Authority Having Jurisdiction.
Primer: PG100 or ASTM D41
Base Ply: (Optional) Polystick MTS or Polystick IVITS PLUS, self -adhered.
Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, 'nie Pro, Polyflex SAP, Polyflex SAP FR, Mule-Hlcle SA-APP Cap
Sheet and Mule-Hicle SA-APP Cap Sheet (ER), self -adhered.
#6 Maximum Design Pressure = -672.5 p
Deck: Structural concrete to meet project requirements to satisfaction of Authority Having Jurisdiction.
Primer: PG100 or ASTM D41
Underlayment: Elastaflex G TU or Elastoflex S6 G, applied In full mopping of hot asphalt or Polyflex G, torch -applied.
#7 Maximum Design Pressure = -30.0 psf*
Deck: Min. 15/32-inch OSI3 to meet project requirements to satisfaction olAuthority HavingJurisdiction.
Base Sheet: Elastobase or Mule -Hide Nall Base (poly -film top surface)
Fasteners: 21 Ca. x 1.25-inch long x 1-inch head diameter round metal cap nails
Spacing: 6-Inch o.c. at the 3-finch wide side laps and S-Inch o.c. at two (2) equally spaced staggered center rows.
Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered.
Underlayment: Poiystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and
Mule -Hide SA-APP Cap Sheet (FR), self -adhered.
NEW EVC, LLC. Ewluation Report P12060.02.09-R24
C,rtyk� vfA.Iho�tb. #M455 dn' EDITON (2017) FOC NON-HVHZ EVALUATION FL52594tW
Polyglass Rout Undeflayments; (9541 Z33-2230 Revision 24: 01/24/2019
Page 7 of 24
ONEMOletc.
#8 MaAmurn Design Pressure= -37.S Psf*
Deck: Min. 15/324nch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet'. Elastobase or Mule -Hide Nall Base (poly -film top surface)
Fasteners: 11 ga. x 1.25-Inch long x I -Inch head diameter round metal cap nails
Spacing: 6-Inch o.c. at the 3-Inch wide side laps and &Inch o.c. at two (2) equally spaced staggered center rows.
Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, seff�dhered.
Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FIR, Mule -Hide SA-APP Cap Sheet and
Mule�Hlde SA-APP Cap Sheet (FR), self -adhered.
#9 Maximum Design Pressure = -37.5 psf*:
Deck: Min. 19/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: one (1) or two (2) layers ASTM D225, Type 11 felt
Fasteners: 11 ga. x 1.25-inch long x 1-incb head diameter round metal cap nails
Spacing: 6-Inch o. c. at the 3-Inch wide side laps a nd 12-Inch o.c. at two (2) equally spaced staggered center rows.
Underlayment: Elastaflu G TU or Elastoflex S6 G, applied in full mopping of hot asphalt
#10 Maximum Design Pressure z -45 pd*:
Deck: Min. 19/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: One (1) layer ASTM D226, Type 11 felt
Fasteners: 11 ga. x 1.25-inch x 3/8-Inch head diameter annular ring shank roaring nails at 1-5/8-Inch diameter tin caps
Spacing: 4-Inch o.c. at the 24nch wide side laps and 44nch c.c. at two (2) equally spaced staggered center rows.
Base Ply: (Optional; for use with self -adhering underlayment only) Polystick MTS or Polystick MTS PLUS, self -adhered.
Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polynex SAP FIR, Mule -Hide SA-APP Cap Sheet and
Mule -Hide SA-APP Cap Sheet (FR), self -adhered or Elastallex G TU, applied In full mapping of hat asphalt
#11 Ma)dmum Design Pressure = -45 Psf*
Deck: Min. 29/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Two (2) layers ASTM D226, Type It felt
Fasteners: 11 ga. x 1.25-inch long x3/Mnch head diameter annular ring shank roofing nails at 1-5/8-inch diametertirimps
Spacing: 9-Inch o.c. at the 2-Inch wide side laps and 9-Inch o.c. at two (2) equally spaced staggered center rows.
Base Ply; (Optional; for use with self -adhering underlayment only) Polystick MTS or Polystick MTS PLUS, self -adhered.
Undeflayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FIR, Mule -Hide SA-APP Cap Sheet and
Mule -Hide SA-APP Cap Sheet (FR), self -adhered or Elastoflex G TU or Elastofi" 56 G, applied In full mopping of hot
asphalt.
#12 Ma)dmum Design Pressure = -45 nsf.,
Deck:
Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet:
Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap)
Fasteners:
Simplex MAXX Cap Fasteners
Spacing:
94nch o.c. at the 2-inch wilde side laps and 18-Inch o.c. attwo (2) equally spaced staggered center rows.
Underlayment: Elastoflex 6 TU or Elastoflex SIS G, applied in full mopping of hot asphalt or Polyflex 6, torch -applied.
#13 Maximum Design Pressure = -52.5
Deck:
Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet:
Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap)
Fasteners:
Simplex MAXX Cap Fasteners
Spacing:
S�Inch o.c. at the 24nch wide side laps and 12-inch o.c. at two (2) equally spaced staggered center rows.
Underlayment: Elastoflex G TU or Elastoflu S6 6, applied In full mapping of hot asphalt or Polyflex 6, torch -applied.
#14 Maximum Design Pressure -- -52.5 psf
Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Elastobase or Mule�Hlde Nall Base (poly -film top surface)
Fasteners: Simplex Original Cap Nails
Spacing: 64nch o.c. atthe 3-inch wide side laps and 6-inch o.c. at four (4) equally spaced staggered center rows.
Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered.
Underlayment: Polystick TU P, Polystick TU Plus, Potystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and
Mule�Hlde SA-APP Cap Sheet (FR), self -adhered.
NEMO ETC, I.W. Evaluation Report P12060.02.09-R24
GerQ7WW OTAUthar1raWn 032455 EDMON (ZD17) FBC NON-HVHZ EVALUA110N M259-RZB
Polyglass Roof thriderlayments; (954) 233-1230 RmIslon 24:01/24/2018
Page 8 of 24
ONEMOletc.
#15 Maximum Design Pressure= -52.5 P
Deck: Min. 15/324nch plywood to meet pmject requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap)
Fasteners: Simplex Original Cap Nails
Spacing: 6-Inch o.c at the 3-Inch wide side laps and 6-inch o.c. at four (4) equally spaced staggered center rows.
Underlayment: Elastaflex G TU or Elastaflex S6 G, applied In full mopping of hot asphalt or Polyflex G, torch -applied.
#15 Maximum Design Pressure = -60 p
Deck: Min. 19/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap)
Fasteners: 11 ga. x 1.25-Inch long x 3/9-Inch head diameter annular ring shank roofing nails at 1-5/84nch diameter tin caps
Spacing: 8-inch o.c. at the 4-Inch wide side laps and 8-inch o.c. at three (3) equally spaced staggered center rows.
Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or PolVflex G, torch -applied.
#17 Maximum Design Pressure = -60 P
Deck: Min. 19/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap)
Fasteners: OMG #12 Standard Roufgrip with OMG Flat Bottom Metal Plates
Spacing: 12-Inch o.c. at the 4which wide side laps and 12-Inch o.c. attwo (2) equally spaced staggered center rows.
Underlayment: Elastoflex G TU or Elastaflex SIS G, applied In full mopping of hot asphalt or Polyflex G, torch -applied.
#18 Maximum Design Pressure = -67.5 P
Deck: Min. 15/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Polyglass G2 Ham or Polyglass APP Base (requires use of torch-crpplied underloyment)
Fasteners: 12 ga. x L25-inch long x 3/8-Inch head diameter annular ring shank roofing nails at 1-5/8-inch diameter tin caps
Spacing; &-inch o.c. at the 4-Inch wide side laps and 8-Inch o.c. at four (4) equally spaced staggered center rows.
Underlayment: Elastaflex 6 TU or Elastoflex S6 G, applied In full mopping of hot asphalt or torch-appiled or Polyflex G, torch -
applied.
#19 Maximum Design Pressure = -75 a
Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet Polyglaw G2 Base or Polyglass APP Base (requines use of torch�pplied underlayment)
Fasteners: Dekfast #14 with Dekfast Hex Plates, 0MG #14 HD with OMG 3" Galvalume Steel Plates, OMG Roofkdp #14 with
CMG Flat Bottom Plates (AccuTrac), Trufast HO with Tmilast 34nch Insulation Plates or Simplex MAXX Cap
Fasteners
Spacing: INnch o.c. at the 4-inch wide side laps and 10-Inch c.c. at three (3) equally spaced staggered center rows.
Underlayment: Elastoflex G TU or Elastoff� S6 G, applied In full mopping of hot asphalt or torch -applied or Polyflex G, torch -
applied.
#20 Maximum Design Pressure = -90 p
Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet; ElaMbam (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap)
Fasteners: Simplex MAXX Cap Fasteners
Spacing: 6-Inch mc at the 2-inch Wide side laps and 6minch o.c. at two (2) equally spaced staggered center rows.
Underlayment: Elastoflex G TU or Elastollm S6 G, applied In full mopping of hot asphalt or Polyflex G, torch -applied.
#21 MaximurriDesign Pressure=-90p
Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Elastabase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap)
Fasteners: OMG #12 Standard Roolgrip or OMG #14 Heavy Duty with OMG 3' Round Metal Plates or OMG Flat Bottom Metal
Plates
Spacing: 6�lnch o.c. at the 4-inch wide side laps and 6-Inch o.c. at three (3) equally spaced staggered center rows.
Underlayment: Elastoflex G TU or Elastofiex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied.
#22 Maximum Design Pressure= -90
Deck: Min. 15/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Elastobase (sanded top surface)
Fasteners: Tmfest #12 DP or Trufast #14 HD with Trufast 3" Metal Insulation Plates
Spacing: 6-Inch o.c. at the 4-Inch wide side laps and 6-Inch o.c. at three (3) equally spaced staggered center rows.
Underlayment: Elastaflex G TU or Elastolleic S6 G, applied In full mapping of hat asphalt.
NEMO ETC, I.I.C. Evaluation Report PJL2060.02.09-R24
Auft,1kizU.. 0�455 6" ED111ON 12017) FBC NON.HVHZEVAWATION FL5259-RZB
PoWass Roof Underlayments; (9S4) Z33-1230 Revision 24:01/24/2018
Page 9 of 14
ONEMOletc.
#23 Maximum Design Pressure = -90 P
Deck: Min. 15/32-inch plywood to meet project requirements to Satisfaction of Authority Having Jurisdiction.
Base Sheet: Polyglass G2 Base or Palyglass APP Base (requires use of torch�pplled underlayment)
Fasteners: Dekfast #14 with Dekfast Hex plates, OMG #14 HD with OMG 3" Galvalume Steel Plates6 OMG Roafgrip #14 with
OMG Flat Bottom Plates (AccuTrac), Trufast HD With Trufast 34nch Insulation Plates or SImplex MAXX Cap
Fasteners
Spacing: 9-Inch o.c. at the 4-Inch wide side laps and 9-inch o.c. at four (4) equally spaced staggered center rows.
Underlayment Elastoflex G TU or Elastoflex SS G, applied In full mopping of hot asphalt or torch -applied or Polyflex G, torch -
applied.
#24 Maximum Design Pressure= -97.5p
Deck: Min. 19/324nch plywood to meet project requirements to satisfaction of AuthofrtV Having Jurisdiction.
Base Sheet: Elastobase or Mule -Hide Nall Base (poly -film top surface)
Fasteners: 12 ga. x 1.25-inch x 3/8-inch head diameter annular ring shank roofing nails at 1-5/8-Inch diameter tin caps
Spacing: 4-inch o.c. at the 4-1 nth wide side laps and 4-inch o.c. at four (4) equally spaced staggered center rows.
Base Ply: (Optional) Polystick NITS or Polystick MTS PLUS, self -adhered.
Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polynex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and
Mule,Hlde SA-APP Cap Sheet (Fill, self -adhered.
#25 Maximum Design Pressure = -105 P
Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority HavingJurlsdictlon.
Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap)
Fasteners; Simplex MA)D(C2p Fasteners
Spacing: G-Inch o.c. at the 2-inch wide side laps and 64nch o.c. at three (3) equally spaced staggered center rows.
Underlayment: Elastoflex G TU or Elastoflex SS G, applied In full mapping of hot asphalt or Polyflex G, torch -applied.
#26 Maximum Design Pressure = -112.5 p
Deck: Min. 19/32-Inch plywood to meet project requirements to Satisfaction of Authority Having Jurisdiction.
Base Sheet: Elastobase or Mule -Hide Nail Base (poly -film top surface)
Fasteners: 11 ga. x 1.25-inch x 3/82inch head diameter annular ring shank roofing nails at 1-5/8-Inch dlametertmcaps
Spacing: 6-Inch o.c. at the 4-inch wide side laps and 6-Inch o.c. at four (4) equally spaced staggered center rows.
Primer: PG100 orASTM D41 primer at all tin -caps
Base Ply: Polystick MTS or PolysVick MTS PLUS, self -adhered
Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, PolyflexSAP FR, Mule -Hide SA-APP Cap Sheet and
Mule -Hide SA-APP Cap Sheet (FR), self -adhered.
#27 Maximum Design Pressure = -120 p
Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority HavingJurisdiction.
Base Sheet: Elastobase (sanded top surFace for hot-asphaft or torch -applied cap or poly -film surface for torch -applied up)
Fasteners: OMG #12 Standard Roularlp or OMG #14 Heavy Duty with OMG 3" Round Metal Plates or OMG Flat Bottom Metal
Plates
Spacing: 6-inch o.c. at the 4-inch wide side laps -and 6-Inch o.c. at five (5) equally spaced staggered center rows.
Underlaynnent: Elastaflex 43 TU or Elastaflex S6 G, applied in full mopping of hot asphalt or Polyflex 6, torch -applied.
#28 Maximum Design Pressure = -220 p
Deck: Min. 25/32-Inch plywood to meet project requirements to Satisfaction of Authority Having Jurisdiction.
Base Sheet: Elastobase (sanded top surface)
Fasteners: Trufast #12 DP or Trufast #14 HD with Tnufast 3" Metal Insu lation Plates
Spacing: 6-incho.c at the 4winch wide side laps and 6-inch o.c. at five (5) equally spaced staggered center rows.
Underlayment: Elastoflex G TU or ElastafleXS6 G, applied in full mopping of hot asphatL
5.6.4.1 All other direct -deck, adhered Polyglass underlayment systems beneath foam -on tile systems carry a Maximum
Design Pressure of -45 psf.
NEW ETC, LLC. Evaluation Report P12060.02.09-R24
Certiliarte of AAhcdw� 032455 e EDITION (2017) FBC NON41VHZEVALUATION FL9259-RZB
Polyglass Root Underlaymerits; (954) 233-1230 Revision 24:01/24/2028
Page 10 of 14
ONEMOjetc.
5.6.4.2 For mechanically attached Base Sheet, the maximum design pressure for the selected assembly shall meet or exceed
that required under FRSAtrRI April 2012 (04-12), Appendix A, Table IA.
Alternatively, the maximum design pressure for the selected assembly shall meet or exceed the Zone I design
pressure determined in accordance with FBC 1609. in this case, Zones 2 and 3 shall employ an attachment density
designed by a qualified design professional to resist the elevated pressure criteria. Commonly used methods are
ANSI/SPRI WD1, FIVI Loss Prevention Data Sheet 2-29 and Roofing Application Standard RAS 117. Assemblies marked
with an asterisk* carry the limitations set forth in Section 2.2.10.1 of FM Loss Prevention Data Sheet 1-29 (January
2016) for Zone 2/3 enhancements.
5.7 Exposure Limitations:
Elastobase, Elastobase P, Polyglass G2 Base or Polyglass APP Base shall not be left exposed for longer than 30-days
after Installation.
Polystick IR-Xe or Polystick MU-X shall not be left exposed for longer than 90-days after installation.
Polystick MTS, MTS PLUS, TU P, TU Plus, TU May, Qual Pro, Tile Pro or Elastaflex G TU shall not be left exposed for
longer than 180-days after installation.
Polyflex SAP or SAP FR, or Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) does not have an exposure
limitation, unless the prepared roof covering is to be adhesive -set tile, in which case the maximum exposure is 30
days.
Elastoflex S6 G or Elastoflex S6 G FR or Polyflex G or Polyflex G Fit does not have an exposure limitation, unless the
prepared roof covering is to be adhesive -set file (Elastoflex S6 G or Polyflex 6 only), in which case the maximum
exposure is 180 days.
5.8 PoIVstIck MLI-X has been found through comparative testing to have a lesser coefficient of friction than ASTM D226
roofing felt in a dry condition, tested at standard laboratory conditions. Agreement between purchaser and seller, as
set forth in Section 4.3, Note 1 of ASTM D197G-15, should be established as to slip resistance.
5.9 Tile Slippage Limitations (FRSA/TRl April 203.2 (04-12)):
- When loading roof tiles an the underlayment In direct -deck tile assemblies, the maximum roof slope shall be as
follows. These slope limitations can only be exceeded by using battens during loading of the roof tiles.
Underlayment
Tile Profile
Staging Method
Maximum Slope
Elastoilex G TU
Flat
10-tile stack
7:12
Lugged
8-tile stack (6 over 2)
6:12
Elastoflex S6 G or S6 G FR
Flat or Lugged
6-tile stack (4 over 2)
4:22
Polystick MTS or MTS PWS
Flat
6-tile stack (4 over 2)
5:22
Lugged
6-tile stack (4 over 2)
4:12
Polystick Tile Pro
Flat or Lugged
6-tIle stack (4 over 2)
7:12
Polystick TU Max
Flat
6-tlle stack (4 over 2) or 20-tile stack
7:12
Lugged
6-ule stack (4 Over 2)
7:12
Lugged
20-tile stack
6:12
PolystickTU P
Flat
6-tile stack (4 over 2)
6:12
Lugged
&tile suck (4 over 2)
4:12
PolystickTU Plus
Flat or Lugged
6-tile stack (4 over 2)
7:12
Flat or Lugged
167tile stack
6:12
Polyflex G or 6 FR
Flat or Lugged
6-tile stack (4 over 2)
4:12
Polyflex SA P or SA P FR
Flat or Lugged
6-tile stack (4 over 2)
4:12
NEMO ETC, I.I.C. Evaluation Report P12060.02.09-R24
Gerbflc� QFAuthanw11vn#324S5 e EDITION (2017) FBC NON-HVHZ EVAILLIATION FL5259-RZS
Polatiass Rod Underlayments; j954) 233-2230 Revision 24; 01/24/2028
Page 11 of 14
ONEMOletc.
6. lNsTAuA'nON;
6.1 Pollyglass Roof Underlayments shall be installed In accordance with PoWass; published installation requirements
subjecitto the Limitations setfbrth in Section 5 herein and thespecifics noted below.
6.2 Re -fasten any loose decking panels, and check for protruding nail heads. Sweep the substrate thoroughly to remove
any dust and debris prior to application, and prime the substrate (if applicable).
6.3.1 Non -Tile Applications:
Shall be installed In compliance with the codified requirements for ASTM D226, Type 11 underlayment in FBC Table
1507.1.1 for the type of prepared roof covering to be installed.
Elastobase, Elastobase P or Mule -Hide Nail Base may be covered with a layer of PolVstIck, Polyfiex SAP, Polyflex SA
0 FR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR), self -adhered, Elastaflex 6 Tu, Elastaflex S6 G or
Elastoflex 36 6 FR In hot asphalt or Pohyflex G or Polyflex: G FR, torch applied. Roof cover limitations are those are
those associated with the top -layer underlayment, as set forth in Table 2.
6.3.2 Tile Applications:
- Elastobase, Elastobase P or Mule -Hide Nail Base are limited to use as a mechanically attached base Sheet in the "Two
Ply System" from FRSA/TRI April 2012 (04-12). Reference is made to Table I and Section 5.6.4 herein, coupled with
FRSA/TRI April 2012 104-12) installation Manual.
6.4.2
In FBC Table 1507.1.1 for the type of prepared roof covering to be installed.
Direct -to -Deck with Mechanically Fastened Roof Covers:
All self -adhering materials, with the exception of Polystick TU Plus, Polyflex SAP or SAP FR and Mule -Hide SA-APP
Cap Sheet or SA-APP Cap Sheet (FR) should be back -nailed In selvage edge seam in accordance with Polyglass / Mule -
Hide back nailing guidelines. Nails shall be corrosion resistant, 11 gauge ring -shank type with a minimum 1-inch
diameter metal disk or Simplex-tVpe metal cap nail, at a minimum rate of ir o.c. PoWck TU Plus should be back -
nailed using the above noted fasteners and spacin& In area marked "nail area, area pare clavar" an the face of
membrane. The head lap membrane is to cover the area being back -nailed.
All seal -lap seams (selvage laps) must be
firmly rolled with a minimum 28 lb. hand
roller to ensure full contact and adhesion. F
For Dual Pro and Tile Pro, align the edge of
the top sheet to the end of the glue pattern
(the sheet will overlap the fabric).
View of ovelap Sum of owl Pm andIlle Poo
All over -fabric and over -granule end -laps shall have a 64nch wide, uniform layer of Polyplus 50 Premium Modified
Wet/Dry Cement or Polyglass PGSW Modified Cement applied In between the application of the lap.
Polystick TU Plus, Dual Pro and THe Pro may not be used in any exposed application such as crickets, exposed valleys,
or exposed roof to wall details
NEMO ETC, U.C. Evaluation Report P12060.02.09-R24
0yofkate 01Au&u&at1=#32455 e"EDMON (2017) FBC NON-HVHZ EVALUATION FLSZ59-RZB
Polyglaw Rourf Underlayments; (9S4) 233-1230 Red%lon 24:01/24/2018
Page 12 of 14
ONEIVIOletc.
Repair of Polystick membranes is to be accomplished by applying Polyplus 50 Premium Modified Wet/Dry Cement or
Polyglass PGSUU Modified Cement to the area In need of repair, followed by a minimum 6 x 6 inch patch of the
Polystick material of like kind, set and hand rolled in place over the repair area. Patch laps, if needed, shall be
Installed in a water shedding manner.
All Polystick membranes shall be installed to ensure full contact with approved substrates. Polyglass requires a
minimum of 40-lb weighted -roller or, on steep slopes, use of a stiff broom with approximately 40-lbs of load applied
for the field membrane. Hand rollers are acceptable for rolling of patches, laps (min. 28 lb roller) or small areas of the
roof that are nut accessible to a large roller or broom.
6.4.3 Tile Applications (not allowLd for Polystick Dual Pro, IR-Xe or PbWck MU-XJ:
Reference is made to FRSA/TRI April 2012 (04-12) Installation Manual and Table 1 herein, using the instructions
noted above as a guideline.
For mechanically fastened tile roofing over 2-ply system, consisting of Base Sheet and self-adherling top sheet(s), Base
Sheet fastening shall be not less than FRSAfTRI April 2012 (04-12), Table 1.
For adhesive -set tile applications, refer to Section 5.6.4 herein.
6.4.4 Two (2) Ply Underlayment Systems:
Polystick MTS or MTS PLUS followed by Polystick MTS, MTS PLUS, TU P, TU Plus, TU Max, Tile Pro, MUX or Polyflex
SAP is allowable for use under mechanically attached prepared roof systems. Limits of use are those associated with
the top -layer material. This Is not a requirement, but is allowable if a 2-ply underlayment system is desired.
Polystick MTS or MTS PLUS followed by PoIVsdck TU P, TU Plus, TU Max, Tile Pro or Polyflex SAP is allowable for use
under foam -an tile systems. Limits of use are those associated with the top -layer material. This is not a requirement,
but is allowable if a 2-olv underlavinent system Is desired.
Elastuflex G TU, Elastoflex S6 G or Elastoflex S6 6 FR shall be installed in compliance with current Polyglass published
installation requirements. For use in tile applications:
Elastoflex G TU Is for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D6380, Class M) in the OSIngle
Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems or the Hot Asphalt
applied "Cap Sheet" in the 'rwo Ply System" from FRSAJTRI April 2012 (04-12) beneath mechanically fastened or
adhered tile roof systems.
Elastoflex S5 G is for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D6380, Class M) in the "Single Ply
System" from FRSA/TR1 April 2012 (04-1Z) beneath mechanically fastened tile roof systems or the Hot Asphalt
applied "Cap Sheee In the 'Two Ply System" from FRSA/TRI April 201Z (04-12) beneath mechanically fastened or
adhered tile roof systems.
Elastoflex S6 G FIR is for use as an alternate to 'Mineral Surface Roll Roofing" (ASTM D6380, Class M) in the "Single
Ply System" from FRSArFRI April 2012 (04-12) beneath mechanically fastened tile roof systems or the Hot Asphalt
applied "Cap Sheet" In the rwo Ply System' from FRSAfrRI April 2012 (04-12) beneath mechanically fastened tile
roof systems.
6.5.2 For hot -asphalt -applications, Elastoflex G TU, Elastaflex S6 6 or Elastoflex 56 G FR shall be fully asphalt -applied to the
substrates noted in Section 5.6. Side laps shall be minimum 3-inch and end -laps minimum 6-inch wide, off -set
minimum 3 feet from course to course. Side and end laps shall be fully adhered In a complete mopping of hot asphalt
with asphalt extending approximately 3/8-Inch beyond the lap edge.
6.6.1 Polyflex G or Polyflex 6 FR shall be installed in compliance with current Polyglass published installation requirements.
For use in tile applications:
V Polyflex G Is for use as an alternate to the Heat Applied "Cap SheeV in the "Two Ply System" from FRSA/TRI April
2012 (04-12) beneath mechanically fastened or adhered file roof systems (Base Sheet Limited perS.6.3).
-1 PoWex G FR Is for use as an alternate to the Heat Applied "Cap Sheet" in the "Two Ply Systemn from FRSA/TRI
April 2012 (04-12) beneath mechanically fastened tile roof systems (Base Sheet Limited per 5.6.3).
NEMO ETC, U.C. E�Iuatlon Report P12060.02.09-R24
�UflmteqfAuthvrk�ffa,155 EVITION (ZO171 FHC WON-HVHZ EVALUAMON F1.5159-R28
Polyglaw Roof Undarlayments; (954) 233-U30 Re"on 24:01/24/2018
Page 13 of 14
ONEMOletc.
6.6.2 Polyflex G or Polyflex 6 FR shall be fully torch -applied to the substrates noted In Section 5.6. Side laps shall be
minimum 3-Inch and end -laps minimum 64nch wide, off -set minimum 3 feet from course to course. Side and end
laps shall be fully heat -welded and inspected to ensure minimum 3/8-inch flow of modified compound beyond the lap
edge.
6.7 Tile Staginic
6.7.1 Tile shall be loaded and staged in a manner that prevents tile slippage and/or damage to the uncleflayment Referto
Table 2 herein, and Polyglass; published requirements for tile staging.
6.7.2 Battens and/or Counter -battens, as required by the tile manufacturer and FRSA/TFU April 2012 (04-12) must be used
on all roof slopes greater than 7:12. Precautions should be taken as needed, such as the use of battens or nall-
boards, to prevent tile sliding and/or damage to the underlayment during the loading process.
6.7.3 Polyglass specifies the minimum cure time after installation of self -adhering membranes and before loading of
roofing t1les Is forty-eight (48) hours.
7. BUILDING PERMIT REQUIREMENTS' .
As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of this product.
B. MANuFAcrURING PLANTS:
Contact the noted QA agency for information an product locations covered for F.A.C. GIG20-3 QA requirements. The following
plants have qualified products under their respective physical properties specifications.
Fernley, NV, Hazleton, PA & Winter Haven, FL
ASTM D2970
Polystick MU-X
Hazleton, PA
M-D 13-0004
Elastollex 6 TU
Hazleton, PA & Winter Haven, FL
ASTM D1970
Polystick IR-Xe
ASTM D1970 & FRSA/TRI April 2012
Polystick TU Plus
ASTM 01970 & FRSA/TRI April 2012
PolystickTU Max
Tuscaloosa, AL
ASTM D4601, Type 11
Polyglass G2 Base
Winter Hwen, FL
ASTM D226 (physicals)
Elastobase, Elastobase P
ASTM D6509
Polyglass APP Base
FRSA/TRI April 2012
Polystick MTS, Polystick MTS PLUS
FRSA/TRI April 2012
Polystick TU P
FRSA/TRI April 2012
Polvilex SAP, Polyflu SA P Fit
ASTM D2970
Polystick Dual Pro
ASTM D1970 & FRSA/TRI April 2012
Polystick TIle Pro
ASTM D6164
Elastofiex 56, Elastofl� S6 G FR
ASTM D6222
Polyflex G, Polyflex G FR
9. QUALITY ASSURANCE ENm:
UL, LLC — QUA9625; (314) 578-3406; k.chancellor@us.ul.com
- END OF EVALUATION REPORT -