EVALUATION REPORT
Polyglass USA, Inc. Evaluation Report P12060.02.09-R24
1112 West Newport Center Drive FL52S9-R28
Deerfield Beach, FL 33442 Date of Issuance: 02/24/2009
(954) 233-1230 Revision Z4:01/24/2018
SCOPE:
This Evaluation Report Is issued under Rule 6113211-3 and the applicable rules and regulations governing the use of
construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen, P.E.
for use of the product under the Florida Building Code and Florida Building Code, Residential Volume. The products
described herein have been evaluated for compliance with the e Edition (2017) Florida Building Code sections noted
herein.
DESCRIPTION: Polyglass Roof Underlayments
LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted herein.
CONTINUED COMPLIANCE; This Evaluation Report Is valid until such time as the named product(s) changes, the referenced
Quality Assurance documentation changes, or provisions of the Code that relate to the product change. Acceptance of this
Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. of any changes to the
product(s), the Quality Assurance or the production facility locatlon(s). NEMO I etc. requires a complete review of this
Evaluation Report relative to updated Code requirements with each Code Cycle.
ADVERrISEMENT: The Evaluation Report number preceded by the words "NEMOletc. Evaluated" may be displayed in
advertising literature. If any portion of the Evaluation Report Is displayed, then it shall be done in its entirety.
INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or its
distributors and shall be.avallable for inspection at the job site at the request of the Building Official.
This Evaluation Report consists of pages I through 14.
Prepared by:
Robert J.M. Nierninen, P.E.
Florida Registration No. 59166, Florida DC4 ANE1983
The facsimile seal appearing ws authorized by Robert Nleminen,
P.E. on 01124/2018. This does not serve as an electronically
signed document.
CERWRICATION OF INDEPENDENCE:
1. NEMOl etc. does not have, nor does It intend to acquire or will it acquire, a financial interest in any company manufacturing or
distributing products it evaluates.
2. NEMOletc. is not owned, operated or controlled by any company manufacturing or distributing products it evaluates.
3. Robert Nieminen, P.E. does not have norwill acquire, a financial Interest In any company manufacturing or distributing products for
which the evaluation reports are being Issued.
4. Robert Nieminen, P.E. does not have, nor will acquire, a financial Interest In any other entity involved in the approval process of the
product.
S. This is a building code evaluation. Neither NEMO I etc. nor Robert Nfieminen, P.E. are, in anyway, the Designer of Record for any
project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained
specifically for that purpose.
ONEMOletc.
ROOFINIS COMPONENT EVALUATION:
1. SCOPE:
Product Category: Roofing
Sub-Categary; Underlayment
Compliance Statement: Roof Underlayments, as produced by Polyglass USA, Inc., have demonstrated compliance with the
following sections of the oh Edition (2017) Florida Building Code through testing in accordance with the following Standards.
Compllance Is subject to the Installation Requirements and Limitations Conditions of Use set forth herein.
2. S'rANDARDs:
Section Prope Standard Year
1504.3.1 Wind Uplift FM 4474 2011
1594.3.1 WindUplift UL 1897 2012
1507.2.3/1507.1.1 Physical Properties ASTM D226 2009
1507.2.4 /1507.1.1,1507.2.9.2 Physical Properties ASTM D1970 2015
1507.3.3 Physical Properties FRSA/TRI April 2012 2012
1507.11.2 Physical Properties ASTIV D6164 2011
1507.11.2 Physical Properties ASTM D6222 2011
TAS110 Accelerated Weathering ASTM D4798 2011
3. REFERENCES:
Entity Examination Reference Date
FM Approvals (TST 1867) Wind Uplift 3OD4091 01/12/2000
PRI (TST 5878) Physical Properties PRID1111 04108/2002
PRI (TST 5878) Physical Properties PUSA-005-02-01 01/31/2002
PRI (TST 5878) Physical Properties PUSA-013-02-01 12/23/2002
PRI (TST S878) Physical Properties PUSA-013-02-02 12/23/2002
PRI (TST 5878) Physical Properties PUSA-013-02-03 12/2312002
PRI (TST 5878) Physical Properties PUSA-018-02-01 07/14/2003
PRI (TST 5878) Physical Properties PUSA-028-02-01 07/23/2005
PRI (TST 5878) Physical Properties PUSA-033-02-01 01/12/2006
PRI JTST 5878) Physical Properties PUSA-035-02-01 09/29/2006
PRI (TST 5878) Physical Properties PUSA-055-02-02 12/10/2007
PRI (TST 5878) Physical Properties PUSA-061-02-02 01/28/2008
PRI (TST 5978) Physical Properties PUSA-076-02-01 02/22/2008
PRI O-ST 5878) Physical Properties PUSA-083-02-01 04/14/2008
PRI(TST S878) Physical Properties PUSA-088-02-01 07129/2009
MT] (TST 2508) Physical Properties JX201-17A 04/01/2008
IVITI W 2508) Physical Properties RX14EBA 0.1/29/2009
ERD (TST 6049) Physical Properties 11752.09,99-1 02/08/2000
ERD (rST 6049) Wind Uplift 11757.08.01-1 08/13/2001
ERD UST 6049) Wind Uplift 11776.06.02 01/16/2003
ERD (TST 6049) Physical Properties 02200.07.03 07/14/2003
ERD (TST 6049) Wind Uplift P1740.01.07 01/04/2007
ERD (TST 6049) Physical Properties P5110.04.07-1 04/11/2007
ERD (TST 6049) Wind Uplift P9260.03.08 03/21/2008
ERD (TST 6949) Physical Properties P13450.08.09 08/13/2009
ERD M 6049) Wind Uplift P30540.11.09-RI 11/30/2009
ERD (TST 6049) Physical Properties P11030.11.09-1 100/2009
ERD M76049) Mrind Uplift P11030.11.09-2 22/30/2609
ERD (TST 6049) Physical Properties P11030.12.09-3 11/30/2009
ERD (TST 6049) Physical Properties P33360.06.10 06/25/2010
ERD M 6049) Physical Properties P33370.03.11 03/02/2011
ERD (TST 6049) Physical Properties P33370.04.11 04/26/2011
ERD (TST 6049) Physical Properties P37300.10.21 10/19/2011
NEMOETC,LLC. Evaluation Report P12060.02.09-R24
Cmffftcote GfAvdMMIW 032,15S EDITION (ZM71 FEIC NON4iVHZ EVALUATION RS259-RZB
Polly0ass Roof underlayments; (9S4I 233-2230 Revision 24:01/24/2018
Page 2 of 14
ONEMOletc.
EntlW Examination Reference Date
ERD (TST 6049) Physical Properties P40390.08.12-1 08/06/2012
ERD [I-ST 6049) Physical Properties P40390.0a.12-2 08/07/2012
ERD (TST 6049) Physical Properties C41420.09.12-3 09/11/2012
ERD (TST 6049) Wind Uplift P39680.03.13 03/04/2013
ERD (TST 6049) Physical Properties P45370.04.13 04/26/2013
ERD (5T 6049) Wind Uplift P2738.02.07-R2 04/29/2013
ERD tTST 6049) Wind Uplift 11757.04.01-1-RI 04/30/2013
ERD DST 6049) Wind Uplift P41630.08.13 08/06/2013
ERD W 6049) Wind Uplift P11751.05.03-HI 11/26/2013
ERD (TST 6049) Wind Uplift P11781.11.03-RI 11/26/2013
ERD (TST 6049) Physical Properties P4527O.OS.14 05/12/2014
ERD (TST 6049) Physical Properties 6020.07.14-1 09/08/2014
ERD (TST 6049) Physical Properties 6020.09.14-2 09/08/2014
ERD (W 6049) Physical Properties 6020.09.14-3 09/08/2014
EIRD CIFST 6049) Physical Properties 6020.09.14-4 09/08/2014
ERD 03T 6049) Physical Properties 6020.09.14-5 09/08/2014
ERD W 6049) Physical Properties 6020.09.14-6 09/08/2014
ERD (TST 6049) Physical Properties P46520.10.24 10/03/2014
ERD W 6049) Physical Properties P43290.10.14 10/17/2014
ERD (TST 6049) Physical Properties PLYG-SC7550.03.15 03/24/2015
ERD (TSr 6049) Physical Properties P40390.04.15 04/03/2015
ERD M 6049) Physical Properties P44360.10.14-Rl 05/18/2015
ERD M 6049) Physical Properties PLY&SC8080.05.15-1 05/20/2015
ERD (17ST 6049) Wind Uplift PLYCISCS905.05.16-1 05/17/2016
ERD (TST 6049) Physical Properties PLYG-SC8080.07.16 07115/2016
IERD (TST, 6049) Wind Uplift PLYG-SC12025.lD.16 20/12/2016
ERD (TST 6049) Physical Properties PLYG-SC13040.12.25 22/27/2016
ERD (TST 6049) Physical Properties PLYG-SCII900.03.17 03/10/2017
ERD (TST 6049) Physical Properties PLYG.SC12115.08.17 09/08/2017
ICC-ES JEVL 2395) IBCComplianm ESR-1697 11/01/2014
Miami -Dade (CER 1592) IiVHZ Compliance NOA 24-0717.08 01/22/2015
Polyglass USA Manufacturing Affidavit Products Current 02/18/2009
Polyglass USA P/1-Afficlault Mule -Hide Cross Ug 03/01/2008
Polyglass USA MaterlalsAffidavit Polystick SA Compound D8/18/2011
UL, LLC (QUA9625) Quality Control Service Confirmation Exp.10/05/2018
4. PRODUCT DESCRIFnON:
4.1.1 Elastobase is a fiberglass reinforced, SBS modified bitumen base sheet.
4.1.2 Elastobase P Is a polyester -reinforced, SBS modified bitumen base sheet
4.1.3 Polyglass G2 Base is a fiberglass -reinforced, asphaltic base sheet
4.1.4 Polyglass APIP Base is a fiberglass -reinforced, APP modified bitumen base sheet.
PolystIck IMITS or Polystick IVITS PLUS is a nominal 60-mll thick rubberized asphalt waterproofing membrane, glass
fiber reinforced, surfaced with polyolefinic film surface; meets FRSA[TRI April 2012.
4.2.2 Polysrick IR-Xe is a nominal 60-mil thick rubberized asphalt waterproofing membrane, glass fiber reinforced, With an
aggregate surface; meets ASTIM D1970.
4.2.3 PoWck TU Plus Is a nominal 80-mil thick rubberized asphalt waterproofing membrane, glass fiber reinforced, with a
polyester fabric surface; meets ASIM D1970 and FRS"l April 2012.
NEMO ETC, ULC. Evaluation Report P12060.02.09-R24
GeruaoHe ofAuthevUuMn #32455 EDITION (20171 FOC NON-HVHZ EVALUATION FLSZS9.R28
Polyglass; Roof Underlayments; (954) 233-1230 Revision 24: DI/2412018
Page 3 of 14
ONEMOletc.
4.2A Polystlick TU P Is a nominal 130-mil thick rubberized asphalt waterproofing membrane, glass-fiber/polyester
reinforced, with a granular surface, meets FRSA(TR1 April 2012.
4.2.5 Polystick TU Max Is a nominal 60-mil thick rubberized asphalt waterproofing membrane with a 190 g1M2 polyester
fabric surface; meets ASTM D1970 and FRSA/TRI April 2012.
4.2.6 Pollyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR) are polyester
reinforced, APP modified bitumen cap sheets; meet FRSA/rRI April 2012.
4.2.7 Pollystick Dual PrWN is a nominal 60-mil thick dual -layer rubberized asphalt waterproofing membrane, fiberglass
reinforced, with a polyester fabric surface; meets ASTM D2970.
4.2.9 Polystick rile Prom is a nominal 60-mil thick dual -layer rubberized asphalt waterproofing membrane, fiberglass
reinforced, with a polyester fabric surface; meets ASTM D1970 and FRSA/TRI April 2012.
4.2.9 Polystick MIJ-X is a nominal 54-mil thick dual -layer rubberized asphalt waterproofing membrane, fiberglass
reinforced, with a polypropylene film surface; meets AC188 and physical requirements of ASTM D1970 (See Section
5.8).
4.3.1 Elastaillex 6 TU Is a polyester reinforced, modified bitumen file underlayment composed of a sand -surfaced SBS
modified bitumen back -side and granule -surfaced APP modified bitumen top-sIde. Elastaflex G TU Is for use as an
alternate to "Mineral Surface Rail Roofing" (ASTM D63810, Class M) in the 4SIngle Ply System" from FRSA/TRI April
2012 (04-12) beneath mechanically fastened tile roof systems or Hot Asphalt applied "Cap Sheet" in the 'Two Ply
System" from FRSA/TRI April 203.2 (04-12) beneath mechanically fastened or adhered tile roof systems.
4.3.2 Elastaflex S6 G and Elastoflex S6 G Fit are polyester reinforced, SBS modified bitumen cap sheets; meet ASTM D6164.
Elastoflex S6 6 and Elastaflex S6 6 FR are for use as an alternate to "Mineral Surface Roll Roofing' (ASTM D6380,
Class M) in the "Single Ply System" from FRSAITRI April 2012 (04-12) beneath mechanically fastened tile roof systems.
Elastoflex S6 6 is for use as an alternate to Hot Asphalt applied "Cap Sheer in the -Two Ply System' from FRSA/Ml
April 2012 (04-12) beneath mechanically fastened or adhered tile roof systems. Elastaflex SS 6 FR is for use as an
alternate to Hot Asphalt applied "Cap Sheet" in the 'rwo Ply System" from FRSAJTRI April 2012 (04-12) beneath
mechanically fastened tile roof systems.
4.3.3 Polyflex G and Polyflex G FR are polyester reinforced, APP modified bitumen cap sheets; meet ASTM D6222.
Polyflex 6 is for use as an alternate to Heat Applied "Cap Sheet" In the 'Two Ply System" from FRSA/rRI April 2012
(04-12) beneath mechanically fastened or adhered tile roof systems. PoNflex 6 FR Is for use as an alternate to Heat
Applied 'Cap Sheet' in the �Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile
roof systems.
S. LIMITATIONS:
5.1 This is a building code evaluation. Neither NEMDJetc. nor Robert Nlerninen, P.E. are, In any way, the Designer of
Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or
design guidance unless retained specifically for that purpose.
5.2 This Evaluation Report Is not for use In the HVH7_
5.3 Fire Classification is not part of this Evaluation Report; refer to current Approved Roofing Materials Directory for fire
ratings of this product.
5.4 Polyglass Roof Underlayments may be used with any prepared roof cover where the product Is specifically referenced
within FBC approval documents. If not listed, a request may be made to the Authority Having Jurisdiction for
approval based on this evaluation combined with supporting data for the prepared roof covering.
NEMO ETC, ULC. Ewluation Report P12060.02.09-R24
certiftoote afAutharkation A32455 Gr" EDITION (2017) FBC NON.HVHZ EVALUATION F1.525%.112B
Polyglass Roof Underfaymuts; 19S4) Z33-1230 Revision 24:01/24/ZMB
Page 4 of 14
NNEMOjetc.
5.5 Allowable Roof Covers:
Underlayment
Asphalt Shingles
Nall-OnTlie
Foarn-OnTlle
metal
WoodShakes
SiShingles
Slate
Elastobase
Yes
Yes
(�5heain2-plyq�j
Yes
(aams�atinzjxysyw�)
Yes
Yes
Yes
Elastabase P
Yes
Yes
(�smnln2-ixy�)
Yes
(aamsh�in2-pjyrr�m)
YU
Yes
Yes
Polyglass G2 Baw
No
Yes
(�S�Wn2-plyzysu�)
Yes
Wc�sbeetin2-ixyn�)
No
140
No
Polyglass APP Raw
No
Yes
(am.sh�ftln2-pl,,m,.)
Yes
(B.. SMto in 2-ply Ww,.)
No
No
No
PolystIck Mrs or NITS PLUS
Yes
Yes
No
Yes
Yes
Yes
PolystIck I R-Xe
Yes
No
No
No
Yes
Yes
Polyalck TU P
No
Yes
Yes (See 5.5.1)
No
No
No
PoWickTU Plus
Yes
Yes
Yes (See S.5.1)
Yes
Yes
Yes
Poly5fick TU Max
No
Yes
Yes (See 5.5.1)
Yes
No
No
Polystick Dual Pro
Yes
No
No
Yes
Yes
Yes
Polystick Tile Pro
Yes
Yes
Yes (See 5.5.1)
yes
Yes
Yes
Polystick MU-X
Yes
No
No
Yes
Yes
Yes
Elastaflex S6 6
Yes
Yes
Yes (SeeS.5.1)
No
Yes
Yes
Elastellex S6 G FR
Yes
Yes
No
No
Yes
Yes
Elastaflex G TU
Yes
Yes
Yes (See 5.5.1)
No
Yes
Yes
PolyflexG
Yes
yes
Yes (See 5-9.1)
No
Yes
Yes
Polyfles G FR
Yes
Yes
No
No
Yes
Yes
Polyff"SAP orSAP FR
Yes
Yes
Yes (SeeS-9.1)
No
Yes
Yes
Mule -Hide SA-APP Cap Sheet
orSA-APPCapSheat(FR)
Yes
Yes
I
Yes (See S.S.1)
No
Yes
Yes
5.5.1 "Foam -On Tile is limited to use of the follomdrig Approved Tile adhesives / underlayment combinations.
21" . I 11'�"� 161.1111� 1 �1'1 . '. �7_ . . I , - -
Adhesive
Florida Product
Underlayments
Approval
DAP Foam Touch'n Sea] Stormilond Roof
FL14506
PolystickTU Plus, PolysdckTU Max
Tile Adhesive
Dow TileBand—
FL22525
Polystick TU P, PoWick TU Plus, Polyflex SAP or Tile Pro
PoWck TU P, Pclystick TU Plus, Polystick TU Max, Polystick Tile Pro,
ICP Adhesives Polysetg AH-160
FL6332
Elastaflex 6 TLI, Elastollex S6 G, Polyflex G, Polyflex SAP, Polyflex SA Cap FR,
Mule-Hlde SA-APP Cap Sheet or Mule,Hlde SA-APP Cap Sheet (FR)
PoWick TU P, Polystick TU Plus, Polystick TU Max, Polystilck Ille Pro,
iCP Adhesives PolysetO RTA-1
FL6276
ex G TLI, Elastoflex S6 G, Polyflex 6, Polyflex SAP, Polyflex SA Cap F%
=ide
I SA-APP Cap Sheet or Mule�Hide SA-APP Up Sheet (FR)
'Refer to Tile Manufacturer's urAdhesive Manufacturer's Florida ProductApprovalfar Overturning Moment Resistance Performance.
NEMO ETC, I.I.C. Evaluation Report P12060.02.09-R24
QVVftWW OfAuth�Von #3245S 6" EDITION (2017) FBC NON-HVHZ EVALUATION FLS259-R28
Polyglon;s Roof Underlayments, (934) 233-V30 Revision 24:01/24/2018
Page S of 14
ONEMOletc.
5.6 Allowable Substrates:
5.6.1 Direct -Bond to Deck:
Palystick (all variations), Dual Pro, Tile Pro, Polyflex SAP or SAP FIR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet
(FR) self -adhered to:
> New untreated plywood; ASTIVI D41 primed new untreated plywood; Existing plywood; ASTM D41 primed existing
plywood; New or existing, unprimed OSB; ASTM D41 primed CISB; Southern Yellow Pine; ASTM D42 primed
Southern Yellow Pine; ASTM D41 primed structural concrete; Huber Engineered Woods "ZIP System" Panels
(designed and installed to meet wind loads for project).
Note. Polyglass does not require priming of new or existing plywood or CISB sheathing. New or existing plywood or
OSB sheathing should be cleaned of all dirt and debris prior to application of Polystick membranes.
Elastoflex G TILI, Elastoflex S6 G or Elastoflex S6 G FR in hot asphalt to:
> ASTM D41 primed structural concrete.
Polyflex 6 or Polyflex G FR torch -applied to:
> ASTM D41 primed structural concrete.
5.6.2 Bond-to-Insulabon:
Polystick (all variations), Polyflex SAP or SAP FR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) self -adhered
to:
> ASTM C2289, Type 11, Class 1 polyisocyanurate or Type V polylsocyanurate-composite Insulation; Dens Deck
DuraGuard; Dens Deck Prime; or SECUROCK Gypsum -Fiber Roof Board.
Elastoflex G TU, Elastoflex S6 G or Elastoflex S6 G FR in hot asphalt to:
> Dens Deck Prime or SECUROCK Gypsum -Fiber Roof Board.
Polyflex G or Polyflex G FR torch -applied to:
> ASTIVI D41 primed structural concrete; Dens Deck Prime or SECUROCK Gypsum -Fiber Roof Board.
For installation under mechanically attached prepared roof coverings, Insulation shall be attached per minimum
requirements of the prepared roof covering manufacturers Product Approval. For installations under foam -on tile
systems, insulation attachment shall be designed by a qualified design professional and installed based an testing of
the insuhiltlDn/underlayment system In accordance with FBC Section 15134.3.2.
5.6.3 Bond to Mechanically Attached Base Laver
Polystick (all variations), Polyflex SAP or SAP FR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) Dual Pro or
Tile Pro self -adhered to:
> ASTIVI D226, Type I or 11 felt; Elastabase; Elastobase P or Mule -Hide Nall Base.
Elastoflex G TILI, Elastoflex S6 G or Elastoflex S6 G FR In hot asphalt to:
> ASTM D226, Type I or 11 felt; Elastobase; Elastobase P, Mule -Hide Nail Base or Polyglass G2 Base.
Polyflex G or Polyflex 6 FR torch -applied to:
> Elastobase; Elastobase P, Mule -Hide Nail Base, Polyglass G2 Base or Polyglass APP Base.
For Installations under mechanically attached prepared roof coverings, base layer shall be attached -per minimum
codified requirements. For Installations under foam -on tile systems, base layer shall be attached per minimum
requirements of FIRSA/TRI April 2012 (04-12), Appendix A, Table 1, or as listed In Section 5.6.4 herein, or as tested in
accordance with FBC Section 1504.3.1.
NEMO ETC, U.C. EvaluatIon Report P12060.02.09-R24
Certfft� DfAuthu�m OV455 EDITION (ZO17) F11C NONHVHZ EVALUATION FLSZS9-RZB
PoW= Roof Underlayrnerils; (954) Z33-MO Revision 24:01124/2018
Page 6 of 14
ONEIVIOletc.
5.6.4 Wind Resistance for Underlayment Systems in Foam -On Tile Applications: FRSA/TRl April 2012 (04-12) does not
address wind uplift resistance of all underlayment systems beneath foam -on tile systems, where the underiayment
forms part of the load -path. The following wind uplift limitations apply to underlayment systems that are not
addressed in FRSA/rRl April 2012 (04-12) and are used in foam -on tile applications. Maximum Design Pressure is the
result of testing for wind load resistance based on allowable wind loads, and reflects the ultimate passing pressure
divided by 2 (the 2 to I margin of safety per FBC 2504.9.has already been applied). Refer to FRSAITRI April 2012 (04-
12), Appendix A, Table IA or FBC 1609 for determination of design wind loads.
#1 Maximum Design Pressure � -90 p
Deck: Min. 15/32-inch plywoodto meet project requirements to satisfaction of Authority Having Jurisdiction.
Primer: None
Base Ply: (Optional) PolystIck MTS or Polystick MTS PLUS, self -adhered.
Underlayment: Polystick TU P, Po[VstJck TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and
Mule-Hicle SA-APP Cap 5heet (FR), self�aclherecl.
#2 Maximum Design Pressure = -97.5 psf.,
Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Primer: PGIG0 or ASTM D41
Base Ply: (Optional) Polystick MTScr Polystick MTS PLUS, self -adhered.
Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Czp Sheet and
Mule-Filde SA-APP Cap Sheet (FIR), self�clhered and back -nailed within the selvedge�edge side laps using 12 ga. x
1%" ring shank nallsthrough 32 ga., 1-5/8" cliametertin caps spaced 12-inch o.c.
#3 Maximum Design Pressure = -105 psh
Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Primer: WB-3000
Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered.
Underlayment: Polystick TU P, PolystickTU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and
Mu[e-Hide SA-APP Cap Sheet (FR), selftclhered and back -nailed within the selvedge -edge side laps using 12 ga. x
13C ring shank nails through 32 ga., 1-5/8" diameter tin caps spaced 12-inch o.c.
#4 Maximum Design Pressure = -135 0
Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Primer: (Optional) PGIOO or ASTM D41
Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered.
Joints: Min. 4-inch wide strips of Elastcfi� SA-V over all plywood Joints,
Underlayment: Polysfick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and
Mule-Hicle SA-APP Cap Sheet (FR), self -adhered.
#5 Maximum Design Pressure � -315 P
Deck: Structural concrete to meet project requirements to satisfaction of Authority Having.luriscliction.
Primer: PGIOO or ASTM D41
Base Ply: (Optional) Polystick MIS or Polystick MTS PLUS, self -adhered.
Underlayment: PotVstick TU P, Polystick TU Plus, Polystick TU Max, Tile Pro, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap
Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered. I
#6 Maximum Design Pre
Deck: Structural concrete to meet project requirements to satisfaction of Authority Having Jurisdiction.
Primer: FG100 or ASYM D41
Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied.
#7 Maximum Design Pressure = -30.0 psf*:
Deck: Min. 25/32-Inch OSB to meet project requirements to satisfaction of Authority Havinglurisdiction.
Base Sheet: Elastabase or Mule -Hide Nall Base (poly -film top surface)
Fasteners: 11 ga. x 1.25-inch long x I -Inch head diameter round metal cap nails
Spacing: 6-inch ci.� at the 3-Inch wide side laps and 6-inch o.c. at two (2) equally spaced staggered center ram.
Base Ply: (Optional) Polystick MTS or PolysUck MTS PLUS, self -adhered.
Uncledayment; Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflax SAP FIR, Mule -Hide SA-APP Cap Sheet and
Mule -Hide SA-APP Cap Sheet (FR), self -adhered.
NEMO E-M LLC. Ewfuirtlan Report P12060.02.09-R24
Udo� ofAuthodv�n #�41Z ISYN EOMON (ZU7) F8C NON-HVHZ EVALUAI10N FLS2594128
Poly&= Roof Undedayments; (9S4) 233-1230 Revision 24:01/24/2028
Page 7 of 14
ONEMOIetc.
#8 Maximum Design Pressure = -37.5 psf*
Deck: Min. 15/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Elastobase or Mule -Hide Nall Base (poly -film top surface)
Fasteners: 11 ga. x 1.25-inch long x 1-inch head diameter round metal cap nails
Spacing: 6-inch o.c. at the 3-inch wide side laps and 6-Inch o.c. at two (2) equally spaced staggered center rows.
Base Ply: (Optional) Polystick MTS or Polystick M7S PLUS, self -adhered.
Underlayment; Polystick TU P, PolystickTU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and
Mule -Hide SA-APP Cap Sheet (FIR), self -adhered.
#9 Maximum Design Pressure = -37.5 psf*
Deck: Min. 19/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: One (1) or two (2) layers ASTM D226, Type 11 felt
Fasteners: 11 ga. x 1.25-inch long x I -Inch head diameter round metal cap nails
Spacing: 6-inch o.c. at the 3-inch wide side laps and 12-Inch o.c. at two (2) equally spaced staggered center rows.
Unclarlayment: Elastofiex G TU or Elastoflex 56 6, applied in full mopping of hot asphalt
#10 Maximum Design Priessure = -45 psf*:
Deck: Min. 19132-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: One (1) layer ASTM D226, Type 11 felt
Fasteners: 11 ga. x 1.25-inch x 3/8-Inch head diameter annular ring shank roofing nails at 1-5/8-inch diameter tin caps
Spacing: 4-Inch o.c. at the 2-Inch wide side laps and 44rich o.c. at two (2) equally spaced staggered center rows.
Base Ply: (Optional; for use with self -adhering underlayment only) Polystick MTS or Polystick MTS PLUS, self -adhered.
Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Poyfl" SAP FR, Mule -Hide SA-APP Cap Sheet and
Mule-Hicle SA-APP Cap Sheet (FR), self -adhered or Elastaflex G TU, applied in full mopping of hat asphalt.
#11 Maximum Design Pressure= -45 psf*
Deck: Min. 19132-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Two (2) layers ASTM D226, Type 11 felt
Fasteners: 11 ga. x 1.25-inch long x3/8-inch head diameter annular ring shank roofing nails at 1-5/8-inch diametertincaps
Spacing: 9-Inch o.c. at the 2-inch wide side laps and 9-Inch o.c. at two (2) equally spaced staggered center rows.
Base Ply: (Optional; for use with self -adhering underlayment only) Polystick MTS or Polystick MTS PLUS, self -adhered.
Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FIR, Mule -Hide SA-APP Cap Sheet and
Mule-Hicle SA-APP Cap Sheet (FR), self -adhered or Elastoflex G TU or Elastaflex 56 G, applied in full mopping of hot
asphalt.
#12 Maximum Design Pressure = -45 ust
Deck:
Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet:
Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap)
Fasteners:
Simplex MAXX Cap Fasteners
Spacing:
9-inch o.c. at the 2-Inch wide side laps and 18-Inch o.c. at two (2) equally spaced staggered center rows.
Underlayment: Elastofiex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex 6, torch -applied.
#13 Maximum Design Pressure = -52.5 p
Deck:
Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet:
Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap)
Fasteners:
Simplex MAXX Cap Fasteners
Spacing:
9-Inch o.c. at the 2-inch wide side laps and 12-inch o.c. at two (2) equally spaced staggered center rows.
Underlayment: Elastoflex G TU or Elastaflex S6 G, applied in full mapping of hot asphalt or Polyflex G, torch -applied.
#14 Maximum Design Pressure
Deck: Min. 15/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet; Elastobase or Mule -Hide Nail Base (poly -film top surface)
Fasteners: Simplex Original Cap Nails
Spacing: 6-inch o.c. atthe 3-inch wide side laps and 6-Inch o.c. at four (4) equally spaced staggered center rows.
Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered.
Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and
Mule�Hicle SA-APP Cap Sheet (FR), self -adhered.
NEMO ETC, LLC. Evaluation Report P12060.02.09-R24
CtrViRmte offttha�kn #32455 e EDrn oN (2D17) FBC N DN-HVHZ EVALUATION FL5259-RZB
Polyglass Roof Underlayments, (9S4) 233-2230 Revision 24: 01/24/2018
Page 8 of 14
ONEMOletc.
#15 Maximum Design Pressure= -52.5
Deck: Min. 15/324nch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap)
Fasteners: Simplex Original Cap Nails
Spacing: 6-inch o.c at the 3-inch wide side laps and 6�inch o.c. at four (4) equally spaced staggered center rows.
Underlayment: Elastoflex G TU or Elastcflex S5 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied.
#16 Maximum Design Pressure = -60 p
Deck: Min. 19/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap)
Fasteners: 11 ga. x 1.25-Inch long x 3/8-inch head diameter annular ring shank roofing nails at 1-5/8-inch diameter tin caps
Spacing: 8-inch o.c. at the 4-inch wide side laps and 8-inch o.c. at three (3) equally spaced staggered center rows.
Underlayment: Elastoflex G TU or Elastollex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied.
#17 Maximum Design Pressure = -60 P
Deck: Min. 29132-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: ElastDbase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap)
Fasteners: CMG #12 Standard Roafgrip with OMG Flat Bottom Metal Plates
Spacing: 12-Inch o.c. at the 42inch wide side laps and 12-Inch o.c. at two (2) equally spaced staggered center rows.
Underlayment: Elastoflex G TU or Elastoflex SIS G, applied in full mapping of hot asphalt or Polyflex G, torch -applied.
#18 Maximum Design Pressure = -67.5 p
Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Polyglass G2 Base or Polyglass APP Base (requires use of torch -applied underloyment)
Fasteners: 12 ga. x 1.25-inch longx3/8-inch head diameter annular ring shank roofing nails at 1-5/8-inch diameter tin caps
Spacing: 8-inch o.c. at the 4-Inch wide side laps and 8-Inch o.c. at four (4) equally spaced staggered center rows.
Underlayment: Elastoflex G TU or Elastaflex 56 G, applied in full mapping of hot asphalt or torch -applied or Polyflex G, torch -
applied.
919 Maximum Design Pressure = -75 a
Deck: Min. 25/32-inch plywood to meet project requirementsto satisfaction of Authority Having Jurisdiction.
Base Sheet: Polyglass G2 Base or Polyglass APP Base (requires use of torch -applied underlayment)
Fasteners: Dekfast #14 with Dekfast Hex plates, CMG #14 HD with OMG 3" Galvalume Steel Plates, CIVIG Roofgrip #14 with
OMG Flat Bottom Plates (AccuTrac), Trufast HD With Trufast 3-inch Insulation Plates or Simplex MA)O( Cap
Fasteners
Spacing; 10-Inch o.c. at the 4-inch wide side laps and 10-Inch o.c. atthree (3) equally spaced staggered center rows.
Underlayment: Elastaflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or torch -applied or Polyflex G, torch -
applied.
#20 Maximum Design Pressure = -90 P
Deck: Min. 15/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap)
Fasteners: Simplex MAXX Cap Fasteners
Spacing: 6-inch o.c. at the 2-inch wide side laps and 62inch o.c. at two (2) equally spaced staggered center rows.
Underlayment: Elastaflex G TU or Elastoflex S6 G, applied in full mopping of hat asphalt or Polyflex G, torch -applied.
#21 Maximum Design Pressure = -90 ps
Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Elastabase (sanded top surface for hot-asphait or torch -applied cap or poly -film surface for torch -applied cap)
Fasteners: OMG #12 Standard Roofgnp or OMG #14 Heavy Duty with 0MG 3" Round Metal Plates or CMG Flat Bottom Metal
Plates
Spacing; 6-inch o.c. at the 4-inch wide side laps and 6-inch o.c. at three (3) equally spaced staggered center rows.
Undeflayment: Elastoflex G TU or Elastofiex S6 G, applied in full mopping of hot asphalt or Polyflex G, tcrch-appIied.
#22 Maximum Design Pressure = -90 y
Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Elastobase (sanded top surface)
Fasteners: Trufast #12 DP or Trufast #14 HD with Trufast 3" Metal Insulation Plates
Spacing: 6-Inch o.c. at the 4-Inch wide side laps and &inch o.c. at three (3) equally spaced staggered center rows.
Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hat asphalt.
NEW ETC, I.I.C. Evaluation Report P12060.02.09-R24
GertimW cfA.thwao�. #M4W e EDIT] ON 12017) FBC NON-HVHZ EvALuA nON I FL5259-R28
Polyglass Roof Underlayments; (954) 233-1230 Revision 24:01/24/2028
Page 9 of 14
ONEMOletc.
#23 Maximum Design Pressure = -90 P
Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Polyglass 62 Base or Polyglass APP Base (requires use of torch -applied underloyment)
Fasteners: Dekfast #14 with Delcfast Hex plates, OMG #14 HD with OMG 3" Galvalume Steel Plates, CIAG Roofgpip #14 with
CIVIG Flat Bottom Plates (AccuTrac), Trufast HD with Trufast 3-inch Insulation Plates or Simplex MAXX Cap
Fasteners
Spacing: 9-inch o.c. atthe 4-inch wide side laps and 9-Inch a.c. at four (4) equally spaced staggered center rows.
Underlayment: Elastoflex 6 TU or Elastoflex S6 G, applied In full mopping of hot asphalt or torch -applied or Polyflex G, torch -
applied.
#24 Maximum Design Pressure = -97.5 P
Deck: Min. 19/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Elastabase or Mule -Hide Nall Base (poly -film top surface)
Fasteners: 11 ga. x 1.25-inch x 3/8-inch head diameter annular ring shank roofing nails at 2-5/8-inch diametertincaps
Spacing: 44nch D.C. at the 4-Inch wide side laps and 4minch o.c. at four (4) equally spaced staggered center rows.
Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered.
Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and
Mule -Hide SA-APP Cap Sheet (FRI, self -adhered.
#25 Maximum Design Pressure= -105 p
Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Elastabase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied Cap)
Fasteners: Simplex MAXX Cap Fasteners
Spacing: 6minch o.c. at the 2-inch wide side laps and S-inch o.c. at three (3) equally spaced staggered center rows.
Underlayment: EIastoflexGTU or Elastafl"SS G, applied In full mopping of hot asphalt or PolyflexG, torch -applied.
#26 Maximum Design Pressure = -112.5 ps
Deck: Min. 19/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Elastobase or Mule -Hide Nail Base (poly -film top surface)
Fasteners: 11 ga. x 1.254inch x 3/8-inch head diameter annular ring shank roofing nails at 1-5/8-Inch diameter tin caps
Spacing: 6-Inch D.C. at the 4-inch Wide side laps and 6-Inch o.c. at four (4) equally spaced staggered center rows.
Primer: PG100 or ASTM D41 primer at all tin -caps
Base Ply: Polystick MTS or Polystick MTS PLUS, self -adhered
Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex,SAP FR, Mule -Hide SA-APP Cap Sheet and
Mule,Hide SA-APP Cap Sheet (FRI, self -adhered.
#27 Maximum Design Pressure= -120 p :
Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap)
Fasteners: CMG #12 Standard Roolgrip or OMG #14 Heavy Duty with 0MG 3" Round Metal Plates or OMG Flat Bottom Metal
Plates
Spacing! 6-inch D.C. at the 4winch wide side laps'and 6-inch o.c. at five (5) equally spaced staggered center rows.
Underlayment: Elastollex IS TU or Elastoflex S6 G, applied In full mopping of hot asphalt or Polyflex G, torch -applied.
#28 Maximum Design Pressure = -120-psf,
Deck: Min. 15/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Elastabase (sanded top surface)
Fasteners: Trufast #12 DP or Trufast #14 HD with Trufast 3" Metal Insulation Plates
Spacing: 6-inch o.c. at the 4-Inch wide side laps and 6-inch o.c. at five (5) equally spaced staggered Center rows.
Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt
5.6.4.1 All other direct -deck, adhered Polyglass underlayment systems beneath foam -on file systems carry a Maximum
Design Pressure of -45 psf.
NEMO ETC, LLC. Evaluation Report P12060.02.09-R24
C,rfif,coti, OfAutindwfon 932455 EDITION (2017) FBC NON4iVHZ EVALUATION FL5259-R29
Polyglaz Roof Underlayments; (954) 233-1230 Revision 24:01/24/2018
Page 10 of 14
ONEMOjetc.
5.6.4.2 For mechanically attached Base Sheet, the maximum design pressure for the selected assembly shall meet or exceed
that required under FRSA/TRI April 2012 (04-12), Appendix A, Table IA.
Alternatively, the maximum design pressure for the selected assembly shall meet or exceed the Zone I design
pressure determined in accordance with FBC 1609. In this case, Zones 2 and 3 shall employ an attachment density
designed by a qualified design professional to resist the elevated pressure criteria. Commonly used methods are
ANSI/SPRI WDI, FM Loss Prevention Data Sheet 1-29 and Roofing Application Standard RAS 117. Assemblies marked
with an asterisk* carry the limitations set forth In Section 2.2.10.2 of FM Loss Prevention Data Sheet 1-29 (January
2016) for Zone 2/3 enhancements.
5.7 Exposure Limitations:
Elastobase, Elastobase P, Polyglass G2 Base or Polyglass APP Base shall not be left exposed for longer than 30-days
after installation.
Polystick IR-Xe or Polystick MU-X shall not be left exposed for longer than 913-days after installation.
Polystick MTS, IVITS PLUS, TU P, TU Plus, TU Max, Qual Pro, Tile Pro or Elastoflex G TU shall not be left exposed for
longer than 180-days after installation.
Polyflex SAP or SAP FR, or Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) does not have an exposure
limitation, unless the prepared roof covering is to be adhesive -set tile, in which case the maximum exposure is 30
days.
Elastoflex SIS G or Elastoflex S6 G Fit or Polyflex G or Polyflex G FR does not have an exposure limitation, unless the
prepared roof covering is to be adhesive -set tile (Elastoflex SIS G or Polyflex 6 only), in which case the maximum
exposure is 180 days.
5.8 Polystick MU-X has been found through comparative testing to have a lesser coefficient of friction than ASTM D226
roofing felt in a dry condition, tested at standard laboratory conditions. Agreement between purchaser and seller, as
set forth in Section 4.3, Note 1 of ASTM D1970-15, should be established as to slip resistance.
5.9 Tile Slippage Limitations (FRSA(TRI April 2012 (04-12)):
When loading roof tiles an the underlayment In direct -deck tile assemblies, the maximum roof slope shall be as
follows. These slope limitations can only be exceeded by using battens during loading of the roof tiles.
Underlayment
Tile Profile
Staging Method
MaximumSlope
Elastoflex G TU
Flat
10-tile stack
7:12
Lugged
8-tile stack (6 over 2)
6:12
Elastoflex S6 G or S6 G FR
Flat or Lugged
6-tile stack (4 over 2)
4:12
Polystick MTS or MTS PLUS
Flat
6-tile stack (4 over 2)
5:12
Lugged
6-tile stack (4 over 2)
4:12
Polystick Tile Pro
Flat or Lugged
6-tile stack (4 over 2)
7:12
Polystick TU Max
Flat
&tile stack (4 over 2) or 10-tile stack
7:12
Logged
6-tille stack (4 over 2)
7:12
Lugged
ID -tile stack
6:12
PolystickTU P
Flat
6-tile stack (4 over 2)
6:12
Lugged
G-tile stack (4 over 2)
4:12
PolystickTU Plus
Flat or Lugged
6-Ule stack (4 over 2)
7:12
Flat or Lugged
ID -tile stack
6:22
Polyflex G or G FR
Flat u!2
2� L
6-tile stack (4 over 2)
4:1
Polyflex SA P or SA P FR
Flat or Lu ed
6-tile stack (4 over 2)
4:22
NEMO ETC� I.I.C. Evaluation Report P12060.02.09-R24
Cerilflvate afAuthorkation 032455 e ED171 ON 12017) FBC NON.HVHZ EVALUATION FL5259.R28
Polylitass Roof Underlayments; (9S4) 233-2230 RevWion24:O1/24/2018
Page 11 of 14
ONEMOletc.
6. INSTALLATION:
6.1 Polyglass; Roof Underlayments shall be installed in accordance with Polyglass published installation requirements
subjectto the Limitations setforth in Section 5 herein and thespecifics noted below.
6.2 Re -fasten any loose decking panels, and check for protruding nail heads. Sweep the substrate thoroughly to remove
any dust and debris prior to application, and prime the substrate (if applicable).
6.3.1 Non -'rile Applications:
Shall be installed in compliance with the codified requirements for ASTIVI D226, Type 11 underlayment in FBC Table
1507.1.1 for the type of prepared roof covering to be installed.
Elastobase, Elastobase P or Mule -Hide Nail Base may be covered with a layer of Polystick, Polyflex SAP, Polyflex SA
P FR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR), self -adhered, Elastoftex G TU, Elastoflex SIS G or
Elastoflex SIS G FR in hot asphalt or Polyflex 6 or Polyflex 6 FR, torch applied. Roof cover limitations are those are
those associated with the tap -layer underlayment, as set forth in Table 1.
6.3.2 Tile Applications:
-Elastobase, Elastobase P or Mule -Hide Nail Base are limited to use as a mechanically attached base sheet in the "Two
Ply System" from FRSA/TRI April 2012 (04-12). Reference is made to Table I and Section 5.6.4 herein, coupled with
FRSA/TRI April 2012 (04-12) Installation Manual.
R,
LAP
6.4.1 Shall be installed In compliance With the codified requirements for ASTIVI D1970 (except Polystick TU P) underlayment
6.4.2
In FBC Table 1507.1.2 for the type of prepared roof covering to be installed.
Direct -to -Deck with Mechanically Fastened Roof Covers:
All self -adhering materials, with the exception of Polystick TU Plus, PoWex SAP or SAP FR and Mule -Hide SA-APP
Cap Sheet or SA-APP Cap Sheet (FR) should be back -nailed In selvage edge seam in accordance with Polyglass / Mule -
Hide back nailing guidelines. Nails Shall be corrosion resistant, 22 gauge ring -shank type with a minimum 1-inch
diameter metal disk or Simplex -type metal cap nail, at a minimum rate of 12" o.c. Polystick TU Plus should be back -
nailed using the above noted fasteners and spacing, in area marked "nail area, area Para clavar' on the face of
membrane. The head lap membrane is to cover the area being back -nailed.
All seal -lap seams (selvage laps) must be
firmly rolled with a minimum 28 lb. hand
roller to ensure full contact and adhesion.
For Dual Pro and Tile Pro, align the edge of
the top sheet to the end of the glue pattern
(the sheet Will overlap the fabric).
View of Ovelap Seam of Owl Pm and Tile Pw
All over -fabric and over -granule end -laps shall have a 6-inch wide, uniform layer of Polyplus So Premium Modified
Wet/Dry Cement or Polyglass PG5GQ Modified Cement applied in between the application of the lap.
Polystick TU Plus, Dual Pro and Tile Pro may not be used in any exposed application such as crickets, exposed valleys,
or exposed roof to wall details
NEMO ETC, U.C. Evaluation Report P12060.02.09-R24
cert;flnAe of AUUMMaVan #324SS G�H EDITION (2017) FBC NON-WMZ EvALuA-nON FL5259-RZB
PoWass Roof Underlayments; (9s4)233-1230 Revision 24: 01/24/2018
Page 12 of 14
ONEMIll
Repair of Polystlick membranes is to be accomplished by applying Polyplus 50 Premium Modified Wet/Dry Cement or
Polyglass PGS00 Modified Cement to the area in need of repair, followed by a minimum 6 x 6 inch patch of the
Polystick material of like kind, set and hand rolled in place over the repair area. Patch laps, if needed, shall be
installed in a water shedding manner.
All Polystick membranes shall be installed to ensure full contact with approved substrates. Polyglass requires a
minimum of 40-lb weighted -roller or, on steep slopes, use of a stiff broom with approximately 40-lbs of load applied
for the field membrane. Hand rollers are acceptable for rolling of patches, laps (min. 28 lb roller) or small areas of the
roof that are not accessible to a large roller or broom.
6.4.3 Tile Applications (not allowed for Palystick Dual Pro, IR-Xe or Polystick MU-X):
Reference is made to FRSA/TRI April 2012 (04-12) Installation Manual and Table I herein, using the instructions
noted above as a guideline.
For mechanically fastened tile roofing over 2-ply system, consisting of Base Sheet and self -adhering top sheet(s), Base
Sheet fastening shall be not less than FIRSAITIRI April 2012 (04-2Z), Table 1.
For adhesive -set tile applications, refer to Section 5.6.4 herein.
6.4.4 Two (2) Ply Underlayment Systems:
Pollystick MTS or MTS PLUS followed by Polystick MTS, MTS PLUS, TLI P, TILI Plus, TU Max, Tile Pro, MLI-X or Polyflex
SAP is allowable for use under mechanically attached prepared roof systems. Limits of use are those associated with
the top -layer material. This Is not a requirement, but is allowable if a 2-ply underlayment system is desired.
Polystick IVITS or MYS PLUS followed by Polystick TU P, TLI Plus, TLI Max, Tile Pro or Polynex SAP is allowable for use
under foam -on tile systems. Limits of use are those associated with the top -layer material. This is not a requirement,
but is allowable if a 2-ply underlayment system is desired.
6.5.1 ElastoflexGTU, ElastoflexS6G or ElastaflexS66 Fit shall be installed in compliance with current Polyglass published
installation requirements. For use in tile applications:
Elastuflex 6 TLI is for use as an alternate to "Mineral Surface Roll Roofing" (ASTIVI D6380, Class M) in the "Single
Ply System" from FRSA/TRl April 2012 (04-22) beneath mechanically fastened tile roof systems or the Hot Asphalt
applied "Cap Sheet" in the "Two Ply System" from FRSAjrRI April 2012 (04-12) beneath mechanically fastened or
adhered tile roof systems.
v' Elastoflex SIS 6 is for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D6380, Class M) in the "Single Ply
System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems or the Hot Asphalt
applied "Cap Sheef in the 'Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or
adhered tile roof systems.
v' Elastoflex S6 6 FIR Is for use as an alternate to "Mineral Surface Roll Roofing" (ASTIVI D6380, Class M) in the "Single
Ply Systern' from FRSA/TRl April 2012 (04-12) beneath mechanically fastened tile roof. systems or the Hot Asphalt
applied "Cap Sheet" in the �Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile
roof systems.
6.5.2 For hot -asphalt -applications, Elastoflex G TLI, Elastaflex S6 G or Elastaflex S6 G FR shall be fully asphalt -applied to the
substrates noted in Section 5.6. Side laps shall be minimum 3-inch and end -laps minimum 6-Inch wide, off -set
minimum 3 feet from course to course. Side and end laps shall be fully adhered in a complete mopping of hot asphalt
with asphalt extending approximately 3/8-inch beyond the lap edge.
6.6.1 Polyflex G or Polyflex 6 FR shall be installed in compliance with current Polyglass published installation requirements.
For use in tile applications:
• Polyflex G is for use as an alternate to the Heat Applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI April
2012 (04-12) beneath mechanically fastened or adhered tile roof systems (Base Sheet Limited per 5.6.3).
• Polyflex G FR is for use as an alternate to the Heat Applied "Cap Sheet" in the 'Two Ply System" from FRSA/TRI
April 2012 (04-12) beneath mechanically fastened tile roof systems (Base Sheet Limited per S.6.3).
NENIO ETC, ULC. Evaluation Report P12060.02.09-R24
�jk� of ALithadratian =455 e eDITION (20171 FBC NON-HVHZ EVALUATION FL5259-RZS
PoIntlass Roof Underlayments; (954) 233-1230 Revision 24:01/24/2018
Page 13 of 24
ONEN10jetc.
6.6.2 Polyflex 6 or Polyflex 6 FIR shall be fully torch -applied to the substrates noted in Section 5.6. Side laps shall be
minimum 3-inch and end -laps minimum 6-inch wide, off -set minimum 3 feet from course to course. Side and end
laps shall be fully heat -welded and inspected to ensure minimum 3/8-inch flow of modified compound beyond the lap
edge.
6.7 Tile Staging:
6.7.1 Tile shall he loaded and staged in a manner that prevents tile slippage and/or damage to the undeflayment. Referto
Table 2 herein, and Polyglass published requirements for tile staging.
6.7.2 Battens and/or Counter -battens, as required by the tile manufacturer and FRSA/TRI April 2012 (04-12) must be used
on all roof slopes greater than 7:12. Precautions should be taken as needed, such as the use of battens or nail -
boards, to prevent tile sliding and/or damage to the underlayment during the loading process.
6.7.3 Polyglass specifies the minimum cure time after installation of self -adhering membranes and before loading of
roofing tiles Is forty-eight (48) hours.
7. BUILDING PERMIT REQUIREMENTS:
As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of this product.
8. MANUFACTURING PLANTS:
Contact the noted QA agency for information on product locations covered for F.A.C. 6IG20-3 CIA requirements. The following
plants have qualified products under their respective physical properties specifications.
I "'; - �' �' ' " '- I �_' "1 1-1-1.
1. - -1 1 � I '�" 'I
Fernley, NV, Hazleton, PA & Winter Haven, FL
ASTM D1970
Polystick MU-X
Hazleton, PA
M-D 13-0004
Elastoflex G TU
Hazleton, PA & Winter Haven, FL
ASTM D3.970
Polystick 1R-Xe
ASTM D1970 & FRSAjrrRJ April 2012
Polystick TUI Plus
ASTM D1970 & FRSA(TRJ April 2012
Polystick TU Max
Tuscaloosa, AL
ASTM D4601, Type 11
Polyglass G2 Base
Winter Haven, FL
ASTM D226 (physicals)
Elastobase, ElaStDbase P
ASTIVI D6SG9
Polvglass APP Base
FRSA/TRI April 2012
PolVstick MTS, Polystick MTS PLUS
FRSA/TR1 April 2012
Polystick TU P
FRSAITRI April 2012
Polyflex SAP, Polyflex SA P FR
ASTM D1970
Polystick Dual Pro
ASTM D1970 & FRSA/TRI April 2012
Polystick Tile Pro
ASTM D6164
Elastoflex S6, Elastoflex S6 G FR
ASTM D6222
Polyflex G, Polyflex G FR
9. QUALITY ASSURANCE ENTITY:
UL, LLC—QUA9625; (314) 578-3406; k.chancellor@us.ul.com
-END OF EVALUATION REPORT -