HomeMy WebLinkAboutDOOR REPLACEMENT PLANf -
ST. LUCIE COUNTY
BUILDING DIVISION
REVIEWED
FOR COMPLIANCZ
DATE
MUST BE KEPT ON JOE
NO INSPECTION WILL BE
THESE PLANS AND ALL PROPOSED WQRI-'%
ARE SUBJECT TO ANY CORAM IONS
REQUIRED BY MW IN19PE-CTORS THAT
L14Y BE NECESSARY IN ORDER TO
COMPLYWITH ALL APPLICAME CODES.
CONCEALED FASTENERS OR A17ACHMENTS
ARE THE RESPONSIBILMY OF THE
CONTRACTOR OF RECORD
DO Will Oil
yj A a I
PLACE DOOR IN I OPENING ONLY..
W DOOR TO BE IMPACT RESISTANT-
RRICANE SHUTTERS NOT REQUIRED
OPENING
PRODUCT
DESIGN
OPENING
SQ..
I
WIND
I PRESSURES
APPROVAL
PRESSURES
I
COMMENTS
NO. WDTH. HGT.
FTG
ZONE
POS. NEG.
(N.O.A. #)
POS. NEG.
36 1 80
20.01
4
54.5 1 -55.1
FI-16708.1
65.0 1 -65.0
FRONT ENTRY - LSMI
REPLACE EXISTING DOORS AS DESIGNATED WITH NEW FLORIDA BUILDING CODE APPROVED DOORS.
NOCHANGEINSIZE. NO MODIFICATION TO OPENINGS.
ALL DOOR FRAMES TO BE ATTACHED THROUGH EXISTING BUCKS WITH 1/41, TAPCON SCREWS INTO CONCRETE
WITH A MINIMUM 1 1/4" PENETRATION PER MANUFACTURER'S PRODUCT APPROVAL DOCUMENTS.
LESS THAN 30% OF STRUCTURE'S VALUE. NOT A RENOVATED BUILDING. EXEMPT FROM 2017 ENERGY CONSERVATION CODE.
SEE WIND LOAD CHART ON NEXT PAGE FOR SPECIFIC OPENING PRESSURES
DESIGN PRESSURES OF PRODUCT MEET OR EXCEED SPECIFIC OPENING PRESSURES
MEAN ROOF HEIGHT= 71 FT 6 IN
ALBANESE CONDO UNIT
5151 N. HIGHWAY AlA, UNIT 81 1-A
FORT PIERCE, FLORIDA
DOOR REPLACEMENT PLAN