HomeMy WebLinkAboutSET UP-INSTALLATIONSGENERAL NOTES:
DESIGN CRITERIA
THE STRUCTURAL SYSTEM FOR BUILDING DEPICTED HERE ON HAS BEEN DESIGNED
ACCORDING TO THE 6TH EDITION OF THE 2017 FLORIDA BUILDING CODE, ASCE 7 AND
THE ALUMINUM DESIGN MANUAL 2005. A
WIND LOADS ON THE STRUCTURE HAVE BEEN CALCULATED FOR THE FOLLOWING:
IT IS THE INTENT OF THESE DRAWINGS TO BE IN ACCORDANCE WITH APPLICABLE
CODES AND AUTHORITIES HAVING JURISDICTION. ANY DISCREPANCIES BETWEEN
THESE DRAWINGS AND APPLICABLE CODES SHALL BE IMMEDIATELY BROUGHT TO THE
ATTENTION OF THE ENGINEER.
THIS WORK REQUIRES A BUILDING PERMIT. DO NOT BEGIN WORKING UNTIL A BUILDING
PERMIT IS OBTAINED.
CONTRACTOR IS TO FURNISH ALL LABOR, MATERIALS, SERVICES AND EQUIPMENT
NECESSARY TO COMPLETE ALL WORK SHOWN ON THE DRAWINGS AND SPECIFIED
HEREIN.
DO NOT SCALE DRAWINGS, DIMENSIONS GOVERN.
THE CONTRACTOR SHALL MAKE REQUIRED ARRANGEMENTS, SECURE AND PAY FOR
ALL BARRICADES, ENCLOSURES, AND FENCING AS NEEDED FOR AND DURING THE
PROGRESS TO PROTECT ADJACENT PROPERTIES.
THE CONTRACTOR SHALL NOT PROCEED WITH ANY ADDED SERVICES OR WORK
WITHOUT NOTIFICATION TO THE OWNER.
THE CONTRACTOR IS SOLELY RESPONSIBLE FOR MEANS AND METHODS
CONSTRUCTION, AND FOR THE SEQUENCES AND PROCEDURES TO BE USED.
CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND EXISTING CONDITIONS AT THE JOB
SITE. ANY DISCREPANCIES BETWEEN PLANS, SECTIONS AND DETAILS OR THE
APPLICABLE CODES OR REGULATIONS SHALL BE BROUGHT TO THE ATTENTION OF THE
ARCHITECT OR ENGINEER DURING BIDDING OR BEFORE WORK BEGINS IN ORDER TO
CLARIFY THE REQUIREMENTS AND TO EFFECT THE NECESSARY MODIFICATIONS,
CHANGES AND/OR INSTRUCTIONS.
DRAWINGS AND DIMENSIONS ARE BASED UPON DRAWINGS SUPPLIED BY THE CLIENT.
THE ENGINEER WILL NOT BE RESPONSIBLE FOR ERRORS OR MISINTERPRETATIONS OF
THE SYSTEM DESIGNED BY US BASED ON CLIENT CONFIRMED DESIGN AND
DIMENSIONS. ADDITIONAL DRAFTING TIME EMPLOYED IN THE CHANGE OF THE DESIGN
AFTER SIGNING AND SEALING OF DRAWINGS WILL RESULT IN ADDITIONAL COST.
DO NOT SUBSTITUTE MATERIALS, EQUIPMENTS OR METHODS OF CONSTRUCTION
UNLESS SUCH SUBSTITUTIONS OR CHANGES HAVE BEEN APPROVED IN WRITING BY
THE OWNER,
THE ENGINEER HAS GENERATED THESE SHOP DRAWINGS BASED ON A PROVIDED
DESIGN THAT HAS BEEN DEVELOPED BY A LICENSED ARCHITECT OR A COMPETENT
LICENSED DESIGN PROFESSIONAL WHO CONFIRMED COMPLIANCE WITH ALL
APPLICABLE NATIONAL AND FLORIDA BUILDING CODES.
ALL CONCRETE SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28
DAYS.
REPRODUCTION OR USE FOR ANY PURPOSE OTHER THAN THAT AUTHORIZED BY THE
ENGINEER IS PROHIBITED.
ALL DIMENSIONS TO BE SITE VERIFIED BY GENERAL CONTRACTORISUBCONTRACTOR.
THE ENGINEER HAS EXCLUSIVELY DESIGNED THE STRUCTURE AND/OR BUILDING
COMPONENTS IN COMPLIANCE WITH THE APPLICABLE EDITION OF THE FLORIDA
BUILDING CODE AND DESIGN STANDARDS FOR STRUCTURAL REQUIREMENTS
ONLY.THE EXISTING STRUCTURE MUST SUPPORT THE LOADS IMPOSED BY THE
SYSTEM OR SYSTEMS. ENGINEER ON RECORD OF THE BUILDING OR CERTIFIED
PROFESSIONAL ENGINEER SHALL VERIFY THE STRUCTURE FOR SUCH LOADINGS.
DEFLECTION LIMITS ARE GREATER THAN U80.
HANDRAILS RAILS AND GUARDRAIL ASSEMBLIES HAVE BEEN DESIGNED TO RESIST A
LOAD OF 50 PLF APPLIED IN ANY DIRECTION AT THE TOP AND TO TRANSFER THIS LOAD
THROUGH THE SUPPORTS TO THE STRUCTURE AND HAVE BEEN DESIGNED TO RESIST
A SINGLE CONCENTRATED LOAD OF 200 POUNDS, APPLIED IN ANY DIRECTION AT ANY
POINT ALONG THE TOP, AND HAVE ATTACHMENT DEVICES AND SUPPORTING
STRUCTURE TO TRANSFER THIS LOADING TO APPROPRIATE STRUCTURAL ELEMENTS
OF THE BUILDING. INTERMEDIATE RAILS (ALL THOSE EXCEPT THE HANDRAIL),
BALUSTERS AND PANEL FILLERS SHALL BE DESIGNED TO WITHSTAND A HORIZONTALLY
APPLIED NORMAL LOAD OF 50 POUNDS ON AN AREA EQUAL TO ONE SQUARE FOOT
INCLUDING OPENINGS AND SPACE BETWEEN RAILS.
OPEN GUARDS SHALL HAVE BALUSTERS OR ORNAMENTAL PATTERNS SUCH THAT A
4-INCH-DIAMETER SPHERE CANNOT PASS THROUGH ANY OPENING UP TO A HEIGHT OF
34 INCHES. FROM A HEIGHT OF 34 INCHES TO 42 INCHES ABOVE THE ADJACENT
WALKING SURFACES.
h, 9RAILS AND GUARDS ARE DESIGNED IN ACCORDANCE WITH THE PROVISIONS FOR `
HLLuWABLE STRESS DESIGN (WORKING STRESS DESIGN) EXCLUSIVELY FOR THE
LOADS SPECIFIED IN SECTION 1607.7.1.
MATERIAL SPECIFICATIONS
ALUMINUM
EXTRUDED BARS, SHAPES AND TUBES: ALLOY SHALL BE 6061-T6 OR AS NOTED ON
DRAWINGS AND CONFORMING TO ASTM B221
WELDING NOTES:
QUALIFICATIONS FOR WELDING WORK: QUALIFY WELDING PROCESSES AND WELDING
OPERATORS IN ACCORDANCE WITH AWS "STANDARD QUALIFICATION PROCEDURE".
WELDERS TO BE EMPLOYED IN WORK SHALL HAVE CERTIFICATIONS OF PASSING WITH
SATISFACTORY MARKS IN ACCORDANCE WITH STRUCTURAL WELDING CODE OF THE
ENGINEER. AWS AND AISC STANDARD QUALIFICATION TESTS WITHIN PREVIOUS 12
MONTHS. IF RE -CERTIFICATION OF WELDERS IS REQUIRED, RETESTING WILL BE
CONTRACTOR'S RESPONSIBILITY.
WELD CONNECTIONS: COMPLY WITH AWS CODE FOR PROCEDURES, APPEARANCE AND
QUALITY OF WELDS, AND METHODS USED IN CORRECTING WELDING WORK.
WELDING ELECTRODES: COMPLY WITH AWS CODE AND REQUIREMENTS. FOR HIGH
STRENGTH LOW ALLOY STEEL, PROVIDE ELECTRODES, WELDING RODS AND FILLER
METALS EQUAL IN STRENGTH AND COMPATIBLE IN APPEARANCE WITH PARENT METAL
JOINED.
UNLESS OTHERWISE NOTED THE MINIMUM WELD SIZE SHALL BE ASSUMED TO BE THE
THICKNESS OF THE THINNEST MEMBER TO BE JOINED.
GENERAL CONDITIONS
IF THERE ARE ANY DISCREPANCIES HEREIN CONTACT THE ENGINEER PRIOR TO
PROCEEDING WITH THE WORK.
THIS DESIGN DOES NOT' ISTITUTE THE ENGINEERING OF ANY OTHER S ::TURES de
THAT ARE NOT SPECIFIEk �i MENTIONED HEREIN. IF THERE ARE ANY DISf mmrANCIES a`°• .......
THEREIN, CONTACT THE ENGINEER PRIOR TO PROCEEDING WITH THE WORK. _,•'� �'\, \GEI
ALL WORK PREPARED BY DE STEFANO ENGINEERING GROUP, PL (DEG), IS TIDE,'',''��
PROPERTY OF DEG AND MAY ONLY BE USED FOR ITS INTENDED USE. THE DRAWINGS' :. 6
SPECIFICATIONS AND OTHER DOCUMENTS, INCLUDING THOSE IN ELECTRONIC F08PREPARED BY DEG AND DEG'S ' I:
THROUGHCONSULTANTS WHICH THE WORK TO EEXECU ED BYRCONTRAC OR. INSTRUMENTS AS DESCR BFD-' , �� S -ATE 1:OF '
REMAIN THE PROPERTY OF DEG. SAID WORK MAY NOT BE USED AT ANY OTHER ,
LOCATION OR FOR ANY OTHER USE WITHOUT PRIOR WRITTEN AUTHORIZATION. CL nR
DEG WILL HAVE NO RESPONSIBILITY FOR THE CONTRACTOR'S, CLIENTS OR OTHER "%.;"J'/QNAL ��"
ENTITIES; MEANS, METHODS, TECHNIQUES, AND PROCEDURES USED IN ........... •.""`
CONSTRUCTION, AND WILL NOT BE HELD LIABLE FOR THE CONTRACTOR'S INADEQUATE October 3, 2018
OR UNSATISFACTORY PERFORMANCE OF THE WORK.
THESE PLANS AND ALL PROPOSED WOW
ARE SUBJECT TO ANY CORRECTIONS
SCANNED REQUIRED BY FIELD INSPECTORS THAT
BY MAY BE NECESSARY IN ORDZR TO
St. Lucie County CO&PIPLY WITH ALL APPLICABLE COVES.
12233/4"
3 SMS
�/ E/O - oo�I
ST. LUCIE COUNTY BUIL N D'
REVIEWED FOR COMP
REVIEWED BY
28-63-256 RAIL 1X1X1/8"
6063-T5 2X1X3/32" 19-63-140 1/4"X2.25" SS WITH
13-63-267 6063-T52 NEO TAPCON
13-63-227
6063-T5
FSTRUCTURAL COMPONENTS
S1 SCALE: 3"= 1'-0"
co E
c�
C
ti J
0
-- U
CD
CD0
J
IT MUST WKEPT ON JOB
ECTION(S) WILL BE MADE
Vistana Beach Club
10740 S. Ocean Drive c
Henson Beach, FL 34957 v
August 13, 2018 Fi/e:182533 aft
TYPICAL RAILING ELEVATION
(3
S2 SCALE.• 1/1"= 1=0"
6� 1
T 10"
�2 TYPICAL RAILING LENGTHS
S2 SCALE: 3116"=1'-0"
PSECTION
S2 SCALE: 2"= 1'-0"
NIL
4
'•l l6 r
S ATE OF
October 3, 2018
THESE PLANS AND ALL PROPOSED WOM
ARE SUBJECT TO ANY CORRECTIONS
REQUIRED BY FIELD INSPECTORS THAT
MAY BE NECESSAI4Y IN ORDE'N TO
COI,,PLY WITH ALL APPLICABLE CGDE3.
0
N
012
1 d
V
(7
O R
� o m I w
Z cc
�5
1m dN
)M RAIL W
o >o `m
(*
Nqq
Z
a �
�W;
N
N $0
A
0 Z
S o
� � m
0
E H E
� C%
Vistana Beach Club
10740 S. Ocean Drive
CZ
v
Henson Beach, FL 34957
August 13, 2018 File:182533
of 2
GENERAL NOTES:
THE STRUCTURAL SYSTEM FOR BUILDING DEPICTED HERE ON HAS BEEN DESIGNED
ACCORDING TO THE 6TH EDITION OF THE 2017 FLORIDA BUILDING CODE, ASCE 7 AND
THE ALUMINUM DESIGN MANUAL 2005.
IT IS THE INTENT OF THESE DRAWINGS TO BE IN ACCORDANCE WITH APPLICABLE
CODES AND AUTHORITIES HAVING JURISDICTION. ANY DISCREPANCIES BETWEEN
THESE DRAWINGS AND APPLICABLE CODES SHALL BE IMMEDIATELY BROUGHT TO THE
ATTENTION OF THE ENGINEER.
THIS WORK REQUIRES A BUILDING PERMIT. DO NOT BEGIN WORKING UNTIL A BUILDING
PERMIT IS OBTAINED.
CONTRACTOR IS TO FURNISH ALL LABOR, MATERIALS, SERVICES AND EQUIPMENT
NECESSARY TO COMPLETE ALL WORK SHOWN ON THE DRAWINGS AND SPECIFIED
HEREIN.
- DO NOT SCALE DRAWINGS, DIMENSIONS GOVERN.
THE CONTRACTOR SHALL MAKE REQUIRED ARRANGEMENTS, SECURE AND PAY FOR
ALL BARRICADES, ENCLOSURES, AND FENCING AS NEEDED FOR AND DURING. THE
PROGRESS TO PROTECT ADJACENT PROPERTIES.
THE CONTRACTOR SHALL NOT PROCEED WITH ANY ADDED SERVICES OR WORK
WITHOUT NOTIFICATION TO THE OWNER.
THE CONTRACTOR IS SOLELY RESPONSIBLE FOR MEANS AND METHODS
CONSTRUCTION, AND FOR THE SEQUENCES AND PROCEDURES TO BE USED.
CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND EXISTING CONDITIONS AT THE JOB
SITE. ANY DISCREPANCIES BETWEEN PLANS, SECTIONS AND DETAILS OR THE
APPLICABLE CODES OR REGULATIONS SHALL BE BROUGHT TO THE ATTENTION OF THE
ARCHITECT OR ENGINEER DURING BIDDING OR BEFORE WORK BEGINS IN ORDER TO
CLARIFY THE REQUIREMENTS AND TO EFFECT THE NECESSARY MODIFICATIONS,
CHANGES AND/OR INSTRUCTIONS.
DRAWINGS AND DIMENSIONS ARE BASED UPON DRAWINGS SUPPLIED BY THE CLIENT.
THE ENGINEER WILL NOT BE RESPONSIBLE FOR ERRORS OR MISINTERPRETATIONS OF
THE SYSTEM DESIGNED BY US BASED ON CLIENT CONFIRMED DESIGN AND
DIMENSIONS. ADDITIONAL DRAFTING TIME EMPLOYED IN THE CHANGE OF THE DESIGN
AFTER SIGNING AND SEALING OF DRAWINGS WILL RESULT IN ADDITIONAL COST.
DO NOT SUBSTITUTE MATERIALS, EQUIPMENTS OR METHODS OF CONSTRUCTION
UNLESS SUCH SUBSTITUTIONS OR CHANGES HAVE BEEN APPROVED IN WRITING BY
THE OWNER.
THE ENGINEER HAS GENERATED THESE SHOP DRAWINGS BASED ON A PROVIDED
DESIGN THAT HAS BEEN DEVELOPED BY A LICENSED ARCHITECT OR A COMPETENT
LICENSED DESIGN PROFESSIONAL WHO CONFIRMED COMPLIANCE WITH ALL
APPLICABLE NATIONAL AND FLORIDA BUILDING CODES.
ALL CONCRETE SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28
DAYS.
REPRODUCTION OR USE FOR ANY PURPOSE OTHER THAN THAT AUTHORIZED BY THE
ENGINEER IS PROHIBITED.
ALL DIMENSIONS TO BE SITE VERIFIED BY GENERAL CONTRACTORISUBCONTRACTOR.
THE ENGINEER HAS EXCLUSIVELY DESIGNED THE STRUCTURE AND/OR BUILDING
COMPONENTS IN COMPLIANCE WITH THE APPLICABLE EDITION OF THE FLORIDA
BUILDING CODE AND DESIGN STANDARDS FOR STRUCTURAL REQUIREMENTS
ONLY.THE EXISTING STRUCTURE MUST SUPPORT THE LOADS IMPOSED BY THE
SYSTEM OR SYSTEMS. ENGINEER ON RECORD OF THE BUILDING OR CERTIFIED
PROFESSIONAL ENGINEER SHALL VERIFY THE STRUCTURE FOR SUCH LOADINGS.
DEFLECTION LIMITS ARE GREATER THAN L/80.
HANDRAILS RAILS AND GUARDRAIL ASSEMBLIES HAVE BEEN DESIGNED TO RESIST A
LOAD OF 50 PLF APPLIED IN ANY DIRECTION AT THE TOP AND TO TRANSFER THIS LOAD
THROUGH THESUPPORTSTO THE STRUCTURE AND HAVE BEEN DESIGNED TO RESIST
A SINGLE CONCENTRATED LOAD OF 200 POUNDS, APPLIED IN ANY DIRECTION AT ANY
POINT ALONG THE TOP, AND HAVE ATTACHMENT DEVICES AND SUPPORTING
STRUCTURE TO TRANSFER THIS LOADING TO APPROPRIATE STRUCTURAL ELEMENTS
OF THE BUILDING. INTERMEDIATE RAILS (ALL THOSE EXCEPT THE HANDRAIL),
BALUSTERS AND PANEL FILLERS SHALL BE DESIGNED TO WITHSTAND A HORIZONTALLY
APPLIED NORMAL LOAD OF 50 POUNDS ON AN AREA EQUAL TO ONE SQUARE FOOT
INCLUDING OPENINGS AND SPACE BETWEEN RAILS.
OPEN GUARDS SHALL HAVE BALUSTERS OR ORNAMENTAL PATTERNS SUCH THAT A
4-INCH-DIAMETER SPHERE CANNOT PASS THROUGH ANY OPENING UP TO A HEIGHT OF
34 INCHES. FROM A HEIGHT OF 34 INCHES TO 42 INCHES ABOVE THE ADJACENT
WALKING SURFACES.
HANDRAILS AND GUARDS ARE DESIGNED IN ACCORDANCE WITH THE PROVISIONS FOR
ALLOWABLE STRESS DESIGN (WORKING STRESS DESIGN) EXCLUSIVELY FOR THE
LOADS SPECIFIED IN SECTION 1607.7.1.
ALUMINUM
EXTRUDED BARS, SHAPES AND TUBES: ALLOY SHALL BE 6061-T6 OR AS NOTED ON
DRAWINGS AND CONFORMING TO ASTM B221
WELDING NOTES:
QUALIFICATIONS FOR WELDING WORK: QUALIFY WELDING PROCESSES AND WELDING
OPERATORS IN ACCORDANCE WITH AWS "STANDARD QUALIFICATION PROCEDURE".
WELDERS TO BE EMPLOYED IN WORK SHALL HAVE CERTIFICATIONS OF PASSING WITH
SATISFACTORY MARKS IN ACCORDANCE WITH STRUCTURAL WELDING CODE OF THE
ENGINEER. AWS AND AISC STANDARD QUALIFICATION TESTS WITHIN PREVIOUS 12
MONTHS. IF RE -CERTIFICATION OF WELDERS IS REQUIRED, RETESTING WILL BE
CONTRACTOR'S RESPONSIBILITY.
WELD CONNECTIONS: COMPLY WITH AWS CODE FOR PROCEDURES, APPEARANCE AND
QUALITY OF WELDS, AND METHODS USED IN CORRECTING WELDING WORK..
WELDING ELECTRODES: COMPLY WITH AWS CODE AND REQUIREMENTS. FOR HIGH
STRENGTH LOW ALLOY STEEL, PROVIDE ELECTRODES, WELDING RODS AND FILLER
METALS EQUAL IN STRENGTH AND COMPATIBLE IN APPEARANCE WITH PARENT METAL
JOINED.
UNLESS OTHERWISE NOTED THE MINIMUM WELD SIZE SHALL BE ASSUMED TO BE THE
THICKNESS OF THE THINNEST MEMBER TO BE JOINED.
GENERAL CONDITIONS
IF THERE ARE ANY DISCREPANCIES HEREIN CONTACT THE ENGINEER
PROCEEDING WITH THE WORK.
THIS DESIGN DOES NOT CONSTITUTE THE ENGINEERING OF ANY OTHER STF
THAT ARE NOT SPECIFICALLY MENTIONED HEREIN. IF THERE ARE ANY DISCR
THEREIN, CONTACT THE ENGINEER PRIOR TO PROCEEDING WITH THE WORK.
ALL WORK PREPARED BY DE STEFANO ENGINEERING GROUP, PL (DEG), IS Y;((<7,.'•
PROPERTY OF DEG AND MAY ONLY BE USED FOR ITS INTENDED USE. THE DRAWINdliu F
SPECIFICATIONS AND OTHER DOCUMENTS, INCLUDING THOSE IN ELECTRONIC FORM.-"",,, NALEN
PREPARED BY DEG AND DEG'S CONSULTANTS ARE INSTRUMENTS OF SERVICE ""a....m..•..n"`^
THROUGH WHICH THE WORK TO BE EXECUTED BY CONTRACTOR. AS DESCRIBED August 15, 2018
REMAIN THE PROPERTY OF DEG. SAID WORK MAY NOT BE USED AT ANY OTHER
LOCATION OR FOR ANY OTHER USE WITHOUT PRIOR WRITTEN AUTHORIZATION.
DEG WILL HAVE NO RESPONSIBILITY FOR THE CONTRACTORS, CLIENTS OR OTHER
ENTITIES; MEANS, METHODS, TECHNIQUES, AND PROCEDURES USED IN
CONSTRUCTION, AND WILL NOT BE HELD LIABLE FOR THE CONTRACTOR'S INADEQUATE
OR UNSATISFACTORY PERFORMANCE OF THE WORK.
28-63-256 RAIL 1X1X1/8"
6063-T5 2=3/32" 19-63-140
13-63-267 6063-T52
13-63-227
6063-T5
0C_T 0 2 2018
Si. Lucle County, permitting
12 3/4"
3 SMS - -- - - - -
1/4"X2.25" SS WITH
NED TAPCON
STRUCTURAL COMPONENTS
Sl SCALE: 3"= 1'-0"
Visfana Beach Club
10740 S. Ocean Drive
Henson Beach, FL 34957
August 13, 2018 File:182533
TYPICAL RAILING ELEVATION
S2 SCALE., 12"= 1'-0"
60" MAX.
39'-0"
61
60" MAX.
71 O"
�2 TYPICAL RAILING LENGTHS
S2 SCALE., 3116"= 1'-0" -
SECTION
S2 SCALE.,2"=1'-0"
41L
)M RAIL
?� 0 E
6
o ; SATE OF =�
F ORVD
I1I111111111111\\\\\\
August 15, 2018
,.r
Vistana Beach Club
10740 S. Ocean Drive
Henson Beach, FL 34957
August 13, 2018 File.182533
Wa
0
0
wC
J
A
U
012
0 c
0