HomeMy WebLinkAboutEVALUATION REPORTSCANNED BY St. Lucie County ENGINEER EVALUATE. TEST I_zJ11IJ_1IL61' YU;t Polyglass USA, Inc. 1111 West Newport Center Drive Deerfield Beach, FL 33442 1954)233-1230 iNEMO I etc. Oer*a;WafAuthoHzanon M24M 353 Christian Street, Unit #13 Oxford, Cr 06478 (203)262-9245 CONSULT CERTIFY Evaluation Report 1312060.02.09-1124 FL5259-R28 Date of Issuance:02/24/2009 Revision 24: 01/24/2018 SCOPE: This Evaluation Report is issued under Rule 61620-3 and the applicable rules and regulations governing the use of construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen, P.E. for use of the product under the Florida Building Code and Florida Building Code, Residential Volume. The products described herein have been evaluated for compliance with the a Edition (2017) Florida Building Code sections noted herein. DESCRIPTION: Palyglass Roof Underlaymerlts LABELING: labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted herein. CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the referenced Quality Assurance documentation changes, or provisions of the Code that relate to the product change. Acceptance of this Evaluation Report by the named client constitutes agreement to notify Robert Nleminen, P.E. of any changes to the product(s), the Quality Assurance or the production facility lodation(s). NEMOietc. requires a complete review of this Evaluation Report relative to updated Code requirements with each Code Cycle. ADVERTISEMENT: The Evaluation Report number preceded by the words "NEMOietc. Evaluated" may be displayed in advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety. ' INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or its distributors and shall be available for inspection at the job site at the request of the Building Official. This Evaluation Report consists of pages 1 through 14. Preparey: ��°a:vim:u.taab,ywa � ,,.,...."• y�T' � o-59iN t 46 Robert J.M. Nieminen, P.E'''` a;.. .� The fadmne sealappeadngwasauthortxetl WRobert NiemNen, Florida Registration No. 59166, Florida DCA ANE1983 -- .-r4, P.E. an 01124/201s. This does narsem man elearonlmlly signeddocument. COMFICAnON OF INDEPENDENCE 1. NEMOIete does not have, nor does it intend to acquire or will it acquire, a financial interest In any company manufacturing or distributing products it evaluates. 2. NEMO I etc. Is not owned, operated or controlled by any campany manufacturing or distributing products it evaluates. 3. Robert Nleminen, P.E. does not have nor will acquire, a financial Interest in any company manufacturing or distributing products for . which the evaluation reports are being issued. 4. Robert Nieminen, P.E. does not have, nor will acquire, a financial Interest in any other entity involved in the approval process of the product. S. This is a building code evaluation. Neither NEMO Jett. nor Robert Nieminen, P.E. are, in anyway, the Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained specifically for that purpose. ROOFING COMPONENT EVALUATION: 1. SCOPE: Product Category: Roofing Sub -Category: Underlayment Compliance Statement: Roof Underlayments, as produced by Polyglass USA, Inc., .have demonstrated compliance with the following sections of the Gr Edition (2017) Florida Building Code through testing in accordance with the following Standards. Compliance is subject to the Installation Requirements and Limitations / Conditions of Use set forth herein. 2. STANDARDS: section Property Standard Year 1504.3.1 Wind Uplift FM 4474 2011 1504.3.1 Wind Uplift UL 1897 2012 1507.2.3 / JSM= Physical Properties ASTM D226. 2009 1507.2.4 / 1507.1.1,1507.2.9.2 Physical Properties ASTM D1970 2015 1507.3.3 Physical Properties FRSA/TRI April 2012 2012 1507.12.2 Physical Properties ASTM D6164 2011 1507.1L2 Physical Properties ASfM D6222 2011 TAS 110 Accelerated Weathering ASTM D4798 2011 3. REFERENCES: )>ntft Examination Reference Date FM Approvals (TST 1867) Wind Uplift 3004091 01/12/2000 PRI (TST5878) Physical Properties PRIC1221 04/08/2002 PRI(TST5878) Physical Properties PUSA-005-02-01 01/31/2002 PRI(TSr 5878) Physical Properties PUSA-013-02-01 12/23/2002 PRI (1ST 5878) Physical Properties PUSA-013-02-02 12/23/2002 'PRI (TST 5878) Physical Properties PUSA-013-02-03 12/23/2002 FRI(TST5878) Physical Properties PUSA-018.02-01 07/14/2003 PRI M5878) Physical Properties PUSA-028.02-01 07/13/2005 PRI(TSTS878) Physical Properties PUSA-033-02-01 01/12/2005 PRI ITST 5878) Physical Properties PUSA-035-02-01 09/29/2005 Pal (TST 5878) Physical Properties PUSA-055-02-02 12/30/2007 PRI (TST 5878) Physical Properties PUSH 061-02-02 01/28/2008 PRI (TST 5878) Physical Properties PUSA-076.02-01 02/2212DOS PRI (TST 5878) Physical Properties PUSA-083-02-01 04/14/2008 PRI (TST 5878) Physical Properties PUSA-088-02-01 07/29/2009 MTI (TST 2508) Physical Properties JX20H7A 04/01/2008 MTl (TST 7508) Physical Properties RX14E8A 01/29/2009 ERD (TST 6049) Physical Properties 11752.09.99-1 02/08/2000 ERD CM 6049) Wind Uplift 11757.08.01.1 08/13/2001 HD (TST 6049) Wind Uplift 11776.06.02 01/16/2003 ERD (TST 6049) Physical Properties 02200,07.03 07/14/2003 ERD (TST 6049) Wind Uplift P1740.OL07 01/04/20(Y7 ERD(TST 6049) Physical Properties P5110.04.07-1 04/11/2007 ERD(TST 6049) Wind Uplift P9260.03.08 03/21/2008 ERD (TST 6049) Physical Properties . P13450.08.09 09/13/2009 ERD(TST6049) Wind Uplift P30540.11.09-RS 12/30/2009 ERD (TAT 6049) Physical Properties P11030.11.09.1 11/30/2009 ERD(TST 6049) Wind Uplift P11030.11.09-2 11/30/2009 ERD (TST 6049) Physical Properties P13030.11..09-3 11/30/2009 ERD(TST 6049) Physical Properties P33360.06,10 06/25/2010 ERD (TST 6049) Physical Properties P33370.03.11 03/02/2011 ERD (TST 6049) Physical Properties P33370.04.11 04/26/2011 ERD (TST6049) Physical Properties P37300.10.11 10/19/2011 NEMO ETC, LLC. Evaluation Report P32060.02.09-RZ4 cvrk7o ,fAarA=n Mnk32455. fir"EDMON(2o1'7)FSC NON-HVHZEVAUTATION Revision 24:O1� 8 Potyglasv Roof Underlaymeoas; 1934) 233-1230 Page 2 of 14 E, R Entity ERD (TST 60491 ERD (TST 5049) ERD (TST 6049) ERD (TST 6049) ERD W6049) ERD (IST 6049) ERD CW 6049) ERD PST 6049) ERD (TST 6049) ERD (TST 6049) ERD (TST 6049) ERD (TST 6049) ERD (TST 6049) ERD (TST 6049) ERD (TST 6049) ERD (TST 6049) ERD M76049) ERD (TST 6049) ERD (TST 6049) ERD (TST 60491 ERD (TST 6049) ERD (TST 6049) ERD (TST 6049) ERD (TST 6049) ERD (TST 6049) ERD (TST 6049) ERD (TST 6049) ERD (i5T 6049) ERD M 6049) ICC-ES (EVIL 2396) Miaml-Dade (CER 1592) Polyglass USA Polyglass USA Polyglass USA UL, U.C. (QUA9625) PRODUCT DESCRIPTION: Examination Physical Properties Physical Properties Physical Properties Wind Uplift Physical Properties Wind Uplift Wind Uplift Wind Uplift W nd Uplift Wind Uplift Physical Properties Physical Properties Physical Properties Physical Properties Physical Properties Physical Properties Physical Properties Physical Properties Physical Properties Physical Properties Physical Properties Physical Properties Physical Properties Wind Uplift Physical Properties Wind Uplift Physical Properties Physical Properties Physical Properties IBC Compliance HvH2 Compliance Manufacturing Affidavit P/L Affidavit Materials Affidavit Quality Control Reference P40390.08.12-1 P411390.08.12-2 C41420.09.12-3 P39680.03.23 P45370.04.13 P1738.02.07-R2 11757.04.01-1-R1 P41630.08.13 P11751.05.03-R1 P1178L11.03-R1 P45270.05.14 6020.07.14-.1 6020.09.14-2 6020.09.14-3 6020.09.14-4 6020.09.14-5 6020.09.14.6 P46520.10.14 P43290.10.14 PLYG-SC7550.03.15 P40390.04.15 P44360.10.14-R1 PLYG-SC8080.05.15-1 PLYG-SC8905.05.1&1 PLYG-SC8080.07.16 PLYG-SC12025.10.36 PLYG-SC13040.12.16 PLYG-SC31900.03.17 PLYG-SC12115.08.17 ESR-1697 NOA 14-0717.08 Products Current Mule -Hide Cross I % Polystick sA Compound Service Confirmatlon 4.1.1 Elastobase Is a fiberglass reinforced, SBS modified bitumen base sheet 4.12 Elastobase P is a polyester -reinforced, sB5 modified bitumen base sheet 4.13 Polyglass G2 Base Is a fiberglass -reinforced, asphaltic base sheet 4.2.4 PolyglassAPP Base is a fiberglass -reinforced, APP modified bitumen base sheet ONEMOjetc. Date 08/06/2012 OBIU712012 09/11/2012 03/04/2013 04/26/2013 04/29/2013 04/30/2013 08/05/2013 12/26/2023 11/26/203.3 05/12/2014 09/08/2014 09/08/2014 09/08/2014 09/08/2024 09/08/2024 09/08/2014 10/03/2014 10/17/2014 03/24/2015 04/03/2015 05/18/2015 OS/20/2015 05/17/2016 07/16/2016 20/12/2016 22/27/2016 03/10/2017 08/08/2017 11/01/2014 01/22/2015 02/18/2009 03/Ol/2008 08/18/2012 Exp.10/05/2018 4.2.1 Polystick WM or Polystick MTS PLUS is a nominal 60-mil thick rubberized asphalt waterproofing membrane, glass fiber reinforced, surfaced with polyolefinic film surface; meets FRSA/TRI April 2012. 4.2.2 PolystickIR-Xe is a nominal 60-mil thick rubberized asphalt waterproofing membrane, glass fiber reinforced, with an aggregate surface; meets ASTM D1970. 4.2.3 Polystick TU Plus is a nominal 80-mil thick rubberized asphalt waterproofing membrane, glass fiber reinforced, with a polyester fabric surface; meets ASTM D1970 and FRSAfM April 2012. NEMO ETC LLC Evaluation Report P12060.02.09aM W07apv ofAW-20V19-n2455 6TM EDITION (2017)FBC NON-HVH2 EVALUATION R¢y151on 2A: 01J %224 O33 Polyglass Roof Underlaymams: (9S4) 3.93-1230 Page a of 14 I ONEMOJetc. 4.2.4 Polystick TU P Is a nominal 130-mil thick rubberized asphalt waterproofing membrane, glass-fiber/polyester reinforced; with a granular surface; meets FRSA/TRI.April 2022. 4.2.5 Polystick TU Max is a nominal 60-mil thick rubberized asphalt waterproofing membrane with a 190 g/mz polyester fabric surface, meets ASTM D1970 and FRSA/TRI April 2022. 4.2.6 Polyflex SAP, Polyflex SAP Fit, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR) are polyester. reinforced, APP modified bitumen cap sheets; meet FRSA/TRI April 2012. 4.2.7 Polystick Dual Pro'" Is a nominal 60-mil thick dual -layer rubberized asphalt waterproofing membrane, fiberglass reinforced,.with a polyesterfabric surface, meets ASTM D3970. 4.2.8 PDlystick Tile Pro'" is a nominal 60-mil thick dual -layer rubberized asphalt waterproofing membrane, fiberglass reinforced, with a polyester fabric surface; meets ASTM 01970 and FRSA/TRI April 2012. 4.2.9 Polystick MU-X is a nominal 54-mil thick, dual -layer rubberized asphalt waterproofing membrane, fiberglass reinforced, with a polypropylene film surface; meets ACM and physical requirements of ASTM D1970 (See Section 5.8). 4.3.1 Elastoflex G TU is a polyester reinforced, modified bitumen tile underlayment composed of a sand -surfaced SBs modified bitumen back -side and granule -surfaced APP modified bitumen top -side. Elastoflex G TU is for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D6380, Class M) in the "Single Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened the roof systems or Hot Asphalt applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or adhered tile roof systems. 4.32 Elastofiax S6 6 and Elastoflex S6 6 FR are polyester reinforced, SBS modified bitumen cap sheets, meet ASTM D6164. Elastoflex S6 6 and Elastoflex S6 6 FR are for use as an alternate to "Mineral Surface Roil Roofing" (ASTM D6380, Class M) In the "Single Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems. Elastoflex S6 G is for use as an alternate to Hot Asphalt applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or adhered tile roof systems. Elastoflex S6 G FR Is for use as an alternate to Hot Asphalt applied "Cap Sheet' in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems. 4.3.3 Polyflex G and Polyflex 6 FR are polyester reinforced, APP modified bitumen cap sheets; meet ASTM D6222. Polyflex -6 Is for use as an alternate to Heat Applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI April 2012 (0442) beneath mechanically fastenedor adhered tile roof systems. Polyflex G FR is for use as an alternate to Heat Applied "Cep Sheet" in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened the roof systems. 5. LIMITATIONS: 5.1 This is a building code evaluation. Neither NEMOI etc. nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any project on which this Evaluation Report, or previous versions thereof, Is/was used for permitting or design guidance unless retained specifically for that purpose. 5.2 This Evaluation Report Isnot for use In the HVHZ. 5.3 Fire Classification Is not part of this Evaluation Report-, refer to current Approved Roofing Materials Directory for fire ratings of this product. 5.4 Polyglass Roof Undedayments may be used with any prepared roof cover where the product Is specifically referenced within FBC approval documents. If not listed, a request may be made to the Authority Having Jurisdiction for approval based on this evaluation combined with supporting date for the prepared roof covering.. Nevo ETC, O.c. Evaluation Report P32060.02D9-R24 CarvIZDW CfA"N0rh4xo4: ASS dm EDITION (2017)FBC NON-HVHZ EVALUATION ReWnoO �. �9'a 8 Polygi m Roof Underlaymenb; (954) 233-IM 18 Page4 of 14 ONEMOjetc. 5.5 Allowable Roof Covers: • �; T�BLES'ROOFCOVER �DHhONS. h .y>.; :.••'.r •„slate Underlayment Asphalt Shingles Nail -On Tle Foam-OnTile Metal WwdShak &shingles Elastobase Yes Yes 0pses1e lag-pNsMxm) Yes (BamSheetin2-plysysRm) Yes Yes Yes Elastobase P Yes Yes pmsoaheetrn2-plys'/+eeml Yes IaeresheetntydYs ml Yes Yes Yes PalygJass G28ase No YES 19emmrne sh2plyq in) (eemshW1.es 2-Wvsnmm) No Na Na Polyglass APP Base No (easeshemine2-nnsri*.m) Yes (aamshemn2-pNarrteml No No No Polystick MTS a MTS PLUS Yes Yes No Yes Yes Yes Polystick lR-xe Yes No No No Yes Yes PolystlrkTU P No Yes Yes (Sae 55.1) No No No PolystkkTU Plus Yes Yes Yes (Sw 55.1) Yes Yes Yes PalysdckTU Max No Yes' Yes,(See5.5.1) Yes No No PdysdrknualPro Yes No No Yes Yes Yes PolystickTileFro - Yes Yes Yes (See 55.1) Yes Yes Yes Palysdck Mu-x Yes No No Yes Yes Yes Elastoff"SGG Yes Yes Yes (See55.1) No Yes Yes Elastall"S6G FR Yes Yes No No Yes Yes ElDS1011 xGTU Yes Yes Yes (see 55.11 No Yes Yes PowexG Yes Yes Yes (See 55.1) No Yes Yes PolyfluG FR Yes Yes No No Yes Yes PulyffexSAPorSAPFR Yes Yes Yes (See Sall No Yes Yes Mule-Hlde SA-APP Cap Sheet orSA-APP Cap Sheet (FR) Yes Yes Yes (See 55.1) No Yes Yes 5.5.1 "Foam-OnTlle"Is limitedto use of the following Approved tile adhesives /undedaymentcombinations. ....., s' TA0YF3/�.AUAW% fFT1LE AQWFsrvt;fUN4ER)I+4silENT'CbM�IPA7tOks1 `. ., .. ,... Adhesive Florida Product Underlayments Approval DAP Foam Tourh'n Seal StarmBond Roof FL14506 Polystick TU Plus, Polystick TU Max Tile Adhesive Dow TileBond"' FL22525 PolystickTU P, Polystick TU Plus, Polyflex SAP or Tile Pro Polystick TU P, Polystick TU Plus, Polystick TU Max, Polystick Tile Pro, ICP Adhesives Polysetm AH-160 FL6332 Elastoflex G TU, Elaswilex S6 G, Polyflex G, Polyflex SAP, Polyflex SA Cap FR, Mule -Hide SA-APP Cap Sheet or Mule-Hlde SA-APP Cap Sheet (FR) Polystick TU P, Polystick TU Plus, Polystick TU Max, Polystick Tle Pro, ICP Adhesives Polysets RTA-1 FL6276 Elastoflex GTU, Elastoflex S6 G, Polyflex G, Polyflex SAP, Polyflex SA Cap Pl6 Mule -Hide SA-APP Cap Sheet or Mule•Hide SA-APP Cap Sheet (FRI 1 Refer to Tile Manufacturer's or Adhesive Manufacturers Florida Pro duct Approval for Overturning Moment Res)$tun w Performance NEMO ETC, U.C. Evaluation Report P12060.02.09-1124 cerWlppnafavu prawpnas2ass et" EDMON 12017) FBC ND"VH2 EVAWATION Revision 24: FFL5259-RZB 8 Polyglass Roof Underlaymer16;1954) 233-1230 Page 5 of 14 ONEmo I etc. 5.6 Allowable Substrates: 5.6.1 Direct -Bond to Deck: Polystick (allvariations), Dual Pro, Tile Pro, Polyflex SAP or SAP FR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) self -adhered to: D New untreated plywood; ASTM D41 primed new untreated plywood; Existing plywood; ASTM D41 primed existing plywood; New or existing, unprimed OSB; ASTM D41 primed OSB; Southern Yellow Pine; ASTM D41 primed Southern Yellow Pine; ASTM D41 primed structural concrete; Huber Engineered Woods "ZIP System" Panels (designed and Installed to meet wind loads for project). Note. Polyglass does not require priming of new or existing plywood or OSB sheathing. New or existing plywood or OSB sheathing should be cleaned of all dirt and debris prior to application of Polystick membranes. Elastoflex G TU,. Elastoflex S6 G or Elastaflex S6 G FR in hot asphalt to: ➢ ASTM D41 primed structural concrete. Polyflex G or Polyflex G FR torch -applied to: ➢ ASTM D41 primed structural concrete. 5.6.2 Band -to -Insulation: Polystick (all variations), Polyflex SAP or SAP FR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) self -adhered to: ➢ ASTM C1289, Type ll, Class 1 polyisocyanurate or Type V polyisocyanurate-composite insulation; Dens Deck DuraGuard; Dens Deck Prime; orSECUROCK•Gypsum-Fiber Roof Board. Elastoflex G TU, Elastoflex S6 G or Elastoflex56 GFR in hot asphalt to: D Dens Deck Prime orSECUROCK Gypsum -Fiber Roof Board. Polyflex G or Polyflex G Fit torch -applied to: D ASTM D41 primed structural concrete; Dens Deck Prime or SECUROCK Gypsum -Fiber Roof Board. For installation under mechanically attached prepared roof coverings, insulation shall be attached per minimum requirements of the prepared roof covering manufacturer's Product Approval. For installations under foam -on file systems, Insulation attachment shall be designed by a qualified design professional and installed based' on testing of the Insulation/underlayment system In accordance with FBC Section 1504.3.1. 5.6.3 Bond to Mechanically Attached Base Laver: ' Polystick (all variations), Polyflex SAP or SAP FR, Mule -Hide SA-APP Cap Sheet ar SA-APP Cap Sheet (FR) Dual Pro or Tile Pro self -adhered to: ' D ASTM D226, Typed or 11 felt; Elastobase; Elastobase P or Mule -Hide Nall Base. Elastoflex G TU, Elastoflex S6 G or Elastoflex S6 G FR in hot asphalt to: D ASTM D226, Type I or II felt; Elestobase; Elastobase P, Mule -Hide Nail Base or Polyglass,G2 Base. Polyflex G or Polyflex G FR torch -applied to: D Elastobase; Elastobase P, Mule -Hide Mail Base, Polyglass.G2 Base or Polyglass APP Base. For installations under mechanically attached prepared roof coverings, base layer shall be attached per minimum codified requirements. For Installations under foam -on tile systems, base layer shall be attached per minimum requirements of FRSA/TRI April 2012 (04-12), Appendix A, Table 1, or as listed' In Section 5.6A herein, or as tested In accordance with FBC Section 1504.3.1. MEMO ETC,'LLC. Evaluation Repon P12060M.09-R24 avtUmmofAumurhad"n N33 eEDMON 12C17)FBC WON-HVHZ EVALUATION FL5Z594rZ8 Palyglass Roof UnderlaymeMs; (9541233-2230 Revision 24:01124/2018 Page 6 of 14 ( ONEMOletc. S.SA Wind Resistance for Underlayment Systems in Foam -On Tile Applications: FRSA/TRI April 2012 (04-12) does not address wind uplift resistance of all underlayment systems beneath foam -on tile systems, where the underlayment forms part of the load -path. The following wind uplift limitations apply to underlayment systems that are not addressed In FRSA/TRI April 2012 (04-12) and are used in foam -on the applications. Maximum Design Pressure is the result of testing for wind load resistance based on allowable wind loads, and reflects the ultimate passing pressure divided by 2 (the 2 to 1 margin of safety per FBC 15049 has already been applied). Refer to FRSA/TRI April 2012 (04- 12), Appendix A, Table 3A or FBC 1609 for determination of design wind loads. #1 Maximum Design Pressure=-90 osf: Deck Min. 15/32-inch'plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Primer. None Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered. Underlaymem: Polystick TU P, Polystick TU Plus,.PolysUck TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), selfadhered. #2 Maximum Design Pressure--97.5 Osf: Deck: Min.15/32-inch plywood to meet project requirements to satisfaction of Authority Havinglurisdlceon. Primer: PG100 or ASTM D41 Base Ply: (Optional) Polystick NITS or Polystick MTS PLUS, self -adhered. Undedayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA•APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), se fadhered and back -nailed within the selvedge -edge side laps using 12 ga. x 1X" ring shank nails through 32 ga., 1-5/8" diameter tin caps spaced 12-inch o.c. #3 Maximum Design Pressure =-105 Oaf. -Deck: Min. 15/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Primer: WB-3000 Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered. Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA•APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered and back -nailed within the selvedge -edge side laps using 12 ga. x 1Y." ring shank nails through 32 ga.,1-5/8° diametertin caps spaced 12-Inch c.c. #4 Maximum Design Pressure --235 usf: Deck: Min.15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Primer. (Optional) PG200 or ASTM D41 Base Ply_: (Optional) Polystck MTS or Polystick MTS PLUS, self -adhered. Joints: Min. 4-inch wide strips of Elastoflex SA-V over all plywood joints. Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), selfadhered. #5 Maximum Design Pressure =-315 psf: Deck: Structural concrete to meet project requirements to satisfaction of Authority Having Jurisdiction. Primer: PG100 orASTM D41 Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered. Undedayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Tile Pro, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR),selfadhered. #6 Maximum Design Pressure=.622.513 Deck: Structural concrete to meet project requirements to satisfaction of Authority Having Jurisdiction. Primer. PG100 or ASTM D42 Undedayment: Elastagex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied. #7 Maximum Design Pressure=-30.0 Psf* Deck Min. 15/324nch OSB to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase or Mule -Hide Nall Base(polµfilm top surface) Fasteners: 11 Be. x 1.25-inch long x 1-inch head diameter round metal cap nails Spacing: 6-Inch o.o at the 3-Inch wide side laps and 6-inch o.c. at two (2) equally spaced staggered center rows. Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered. Underlaymem: Polystick TU P, Polysdck TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered. ' NEMO ET . LLG Evaluation Report P32060.0204-R24 a-riUkara ofAutwuWan0324M eEINTION (20171 FBC NOWHVH2 EVALUATION N.5759-R2B Polyglm Roof Undedaymeals; (954) Z33-1230 Revision 24:01/24/2018 Page7 of 14 ONEM01eft. #8 Maximum Desien Pressure =-37.5 Dsf Deck: Min. 15/32-Inch plywood to meet project requiremeirts to satisfaction of Authority Having Jurisdiction. Base Sheet: Elestobase or Mule -Hide Nail Base (poly -film top surface) Fasteners: 11 Be. x 1.25-inch long x 1-inch head diameter round metal cap nails Spacing: 6-inch o.c. at the 3-Inch wide side laps and 6-Inch o.c, at two (2) equally spaced staggered center rows. Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered. Underlayment: Polystick TU P, Polystick TU Plus, Polystick Tu Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered. #9 Maximum Design Pressure =37.5 Dsf': Deck: Min.19/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: One (1) or two (2) layers ASTM D226, Type II felt Fasteners: 11 ga. x 1.25-inch long x 1-Inch head diameter round metal cap nails Spacing: 6-Inch o.c. at the 3-Inch wide side laps and 12-Inch o.c. at two (2) equally spaced staggered center rows Underlayment: Elastoflex G TU or Elastoflex S6 6,applied in full mopping of hot asphalt #10 Maximum Desien Pressure a -45 Osfr: Deck: Min.19/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: One (1) layer ASTM D226, Type 11 felt Fasteners: 11 ga.x L25lnchx3/8-inch head diameter annular ring shank roofing nails at 1-5/8-inch diameter tin caps Spacing: 4-Inch o.c. at the 2-inch wide side laps and 4-inch c.e at two (2) equally spaced staggered center rows. Base Ply: (Optional; for use with self -adhering underiayment only) Polystick 90 or Polystick MTS PLUS, self -adhered. Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP,Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered or Elastoflex G TU, applied in full mopping of hot asphalt #21 Maximum Design Pressure=-45 W: Deck: Min.19/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.. Base Sheet: Two (2) layers ASTM D226, Type II felt Fasteners: 11 go.x 1.25-Inch long x3/8-inch head diameter annular ring shank roaring nails at 1-5/8-Inch diameter tin caps Spacing: 9-Inch o.c. at the 2-Inch wide side laps and 9-Inch o.a, at two (2) equally spaced staggered center rows. Base Ply: (Optional; for use with self -adhering underlayment only) Polystick MTS or Polystick MTS PLUS,selfadhered. Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered or Mastaflex G TU or Elastof!" S6 G, applied in full mapping of hot asphalt #12 Maximum Design Pressure =-45 Dsf: Deck: Min. 35/32-Inch plywood to meet project requirements to satisfaction of Authority HavingJurisdiction. Base Sheet: Elastobase(sanded top surface for hotasphalt or torch -applied cap or poly -film surface for torch -applied cap) Fasteners: Simplex MAXX Cap Fasteners ' Spacing: 9-Inch c.c. at the 2-inch wide side laps and 18-Inch o.c. attwo (2) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mapping of hotasphalt or Polyflex G, torch -applied. #13 Maximum Design Pressure = -52.S 0 Deck: Min.15/324nch plywood to meet project requirements to satisfaction of Authority Havingludsdiction. Base Sheet: Elastabase (sanded top surface far hat -asphalt or torch -applied cap or poly -film surface for torch -applied rap) Fasteners: Simplex MAXX Cap Fasteners Spacing: 9-Inch o.c. at the 2-inch wide side laps and 22-inch o.c. att" 2) equally spaced staggered center rows. Underlayment: Elastallm G TU or Elastoll" S6 G, applied In full mopping of hot asphalt or Polyflex G, torchapplled. #14 Maximum Design Pressure =-52.5 asf: Deck Min.15/32-inch plywood to meet project.requirementsto satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase or Mule -Hide Nall Base (poly -film top surface) Fasteners:- Simplex Original Cap Nails ' Spacing: 6-Inch o.c. at the 3-inch wide side laps and 64nch o.e at four (4) equally spaced staggered center rows. Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, selfadhered. Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered. NEMO ETC, LLC. i Evaluation Report P120E0.02.09-1124 9kr4QroteufAuthadmtW#3243S braEDITION PM71 FBC NON-HVH2 EVALUATION FLSf59•RZB Polyglass Roof Undedayments; (954) 233-1230 Revision 24: 01/24/2018 Page 8 of 14 ONEMOletc. #15 Maximum Design Pressure=-52.5 to ' Deck: Min. 15/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet. Eiastobase(sanded top surface for hot -asphalt or torch -applied rap or poly -film surface for torch -applied cap) Fasteners: Simplex Original Cap, Nails Spacing: 6-Inch o.c. at the 3-Inch wide side laps and 6-inch o.o at four (4) equally spaced staggered center rows. Underlayment Elastoflex G TU or Elastoflex 56 G, applied in full mopping of hot asphalt or PolyBex G, torch -applied. #16 Maximum Design Pressure = .60 111 Deck: Min.19/32-Inch plywood to meet project requirements to satisfaction of Authority Havinglurisdlctlon. Base Sheet: Elastobase(sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap) Fasteners: 11 ga. x 1.25dnch long x 3/8-inch head diameter annular ring shank roofing nails at 1-5/8-Inch diametertln caps Spacing. 8-Inch o.c, at the 4-inch wide side laps and 8-Inch oaa at three (3) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex 55 G, applied in full mopping of hot asphalt or Pohrfiex G, torch -applied. #17 Maximum Design Pressure =-60Dsf: Deck: Min.19/32-inch plywood to meet project requirements to satisfaction of Authority HavingJurisdiction. Base Sheet Elastobase(sanded top surface for hotasphalt or torch -applied cap or poly -film surface for torch-appiled rap) Fasteners: OMG #12 Standard Roofgrip with 0MG Flat Bottom Metal Plates Spacing: 12-inch o.c. at the 4-Inch wide side laps and 12-Inch o.c. at two (2) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex 56 G, applied in full mopping of hot asphalt or PolyHex G, torch -applied. #18 Maximum Design Pressure=-67.5 p5f: Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet. Polyglass G2 Base or Polyglass APP Base (requires use of torch -applied undedayment) Fasteners: 12 Be. x 125-Inch long x 3/8-inch head diameter annular ring shank roofing nails at 1-5/8-Inch diametertin caps Spacing: 8-inch o.a at the 4-Inch wide side laps and 8-Inch o.c. at four (4) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G, applied In full mopping of hot asphalt or torch -applied or PolyRex G, torch. applied. #19 Maximum Design Pressure=-75 osE Deck Min.15/32-Inch plywood to meet project requirements to satisfaction of Authority Having.lurisdiction. Base Sheet: Polyglass G2 Base or Polyglass APP Base (requires use of torch -applied underlayment) Fasteners: Dekfast #14 with Dekfast Hex plates, OMG #14 HD with OMG 3" Galvalume Steel Plates, OMG Roofgrlp #14 with OMG Flat Bottom Plates (AccuTrac), Tmfast HD with Trufast 3-Inch Insulation Plates or Simplex MAX% Cap Fasteners Spacing: 30-inch o.c. atthe 4-Inch wide side laps and 104nch o c atfhree (3) equally spaced staggered center rows. Underlayment Elastoflex G TU or Elastoflex 56 G, applied in full mopping of hot asphalt or torch -applied or PolyBex G, torch. applied. #20 Maximum Design Pressure=-90 osf: Deck: Min.15/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet Elastobase(sanded top surface for hotasphalt or torch -applied cap or poly -film surface fortordh-applled,cap) Fasteners: Simplex MAX% Cap Fasteners Spacing: 64nch o.c. at the 2-Inch wide side laps and 6-inch o.c. at two (2) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or POlyRex G, torch -applied. #21 Maximum Design Pressure =-90 Dsf: Deck: Mtn. 15/32-inch plywood to meet projectrequiremems to satisfaction of Authority HavingJurisdiction. Base Sheet: Elastabase(sanded top surface for hotasphalt or torch -applied cap or poly -film surface fortorchapplied hap) Fasteners: CMG #12Standard Rdofgrip or OMG #14 Heavy Duty with OMG 3" Round Metal Plates or OMG Flat Bottom Metal Plates Spacing: 6-inch o.c "a 4-inch wide side laps and 6-Inch o.c at three (3) equally spaced staggered center rows. Undedeyment.• Elastoflex G TU or Elastaflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied. #22 Maximum Design Pressure =-90 osf: Deck: Min.15/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase (sanded tap surface) Fasteners: Trufast#12 DP orTrubst#14 HD with Tndast 3" Metal insulation Plates Spacing: 6-inch o.c. at the 4-Inch wide side laps and 6-Inch o.e at three (3) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S5 G, applied in full mopping of hot asphalt NEMO Etc, LLG Evaluatlan Report 1)32050.02.09-1124 DuWccM ofAUftdmaon#32455 as"EDITION (2017) FBC NON44VHZ EVALUATION nc259428 Polyglass Rod undedayments; (954) 2 &AM Revision 24: OJJ2412MS Page 9 of 24 NNEMoletc. #23 Maximum Design Pressure=-90psE Deck: - . Min.15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.Base Sheet: Polyglass GZ Base or Polyglass APP Base (requires use of torch-opplled undafayment) Fasteners: Deldast #14 with Dekfast Hex, plates, OMG #14 HD with OMG 3" Galvalume Steel Plates, OMG Roofgrip #14 with OMG Flat Bottom. Plates (AccuTrac), Trufast HD with Trufast 3-Inch Insulation Plates or Simplex MAXX Cap Fasteners Spacing. 9-inch ac, at the flinch wide side laps and 9-Inch am at four (4) equally spaced staggered center rows. Underlaymem: Elastoflex G TU or Elastoflex S6 G, applied In full mopping of hot asphalt or torch -applied or Polyflex G, torch - applied. #24 Maximum Design Pressure =-97.5-psF. Deck: Min. 19/32-Inch plywood to meet project requirements to satisfaction of Authority Havinglurisdictlon. Base Sheet: Elastobase or Mule -Hide Nail Base(polµfilm top surface) Fasteners: 11 ga. x 1.254nch x 3/8-Inch head diameter annular ring shank roofing nails at l-5/8-inch dlametertin caps Spacing: 44nch o.a at the 4-inch wide side laps and flinch am at four (4) equally spacedstaggered center rows. Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered. Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, PolyOax SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered. #25 Maxi mumDesign Pressure =-105psf: Deck: Min.15/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase(sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap) Fasteners: Simplex MAXX Cap Fasteners Spacing: &Inch am at the 2-Inch wide side laps and 6-Inch am at three (3) equally spaced staggered center rows. Underlaymem Elastoflex G TU or Elasta8exS6 G, applied In full mopping of hot asphalt or Polyflex G, torch -applied. #26 Maximum Design Pressure=-112.5 P Deck: MIn. 19/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase or Mule -Hide Nail Base(polµflim top surface) Fasteners: 11 ga. x 1.254nch x 3/8-inch head diameter annular ring shank roofing nails at 1-5/8-Inch diameter tin caps Spacing: 6-Inch am at the flinch wide side laps and 6-inch am at four (4) equally spaced staggered center rows. Primer. PG100 or ASTM D42 primer at all tin -caps Base Ply: Polystick MTS or Polystick MTS PLUS, self -adhered Underlaymem: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered. #27 Maximum Design Pressure= -120 1) Deck: Min. 15/32-Inch plywood to meet project requirememsto satisfaction of Authority Havinglurisdiction. Base Sheet: Elastobase(sanded top surface for hot -asphalt or torch -applied cap or polµflim surface fortorch-applied cap) Fasteners. OMG #12 Standard Roofgrip or OMG #14 Heavy Duty with OMG 3" Round Metal Plates or OMG Flat Bottom Metal Plates Spacing. 64nch am at the 4-inch wide side laps and 6-Inch am at five (5) equally spaced staggered center rows. Underlaymem: Elastoflex G TU or Elastoflex S6 G, applied In full mopping of hot asphalt or Poyflex G, torch-applled. #28 Maximum Design Pressure =-120 osf: Deck: Min. 15/32-inch plywood to meet project requirememsto satisfaction of Authority Having.lurisdictlon. Base Sheet: Elastobase(sanded top surface) Fasteners: Trufast#12 DP or Trufast#14 HD with Trufast 3" Metal Insulation Plates Spacing. 6-Inch am at the 4-inch wide side laps and 6-inch o.c at five (5) equally spaced staggered center rows. Underlaymem: Elastoflex G TU or Elastofiex S6 G, applied in full mopping of hot asphalt. 5.6.4.1 All other direct -deck, adhered Polyglass underlayment systems beneath foam -on the systems carry a Maximum Design Pressure of-45 psf. NEMO EM LLC. Evaluation Report P32060.02A9-R24 raOjlmxajAWmr/m0on 63240 6EDITION (2017)FBC NON-HVHZ EVAWATION FLSU9-R28 Poly&ss Root Underlayments; (9541233-1230 Revision 24: M/24/2019 Page 10 of 14 ONEMOjetc. 5.6.4.2 For mechanically attached Base Sheet, the maximum design pressure for the selected assembly shall meet or exceed that required under FRSA/fRI April 2012 (04-12), Appendix A, Table 1A. Alternatively, the maximum design pressure for the selected assembly shall meet or exceed the Zone 1 design pressure determined In accordance with FBC 1609. In this case, Zones 2.and 3 shall employ an attachment density designed by a qualified design professional to resist the elevated pressure criteria. Commonly used methods are ANSI/SPRI WD1, FM Loss Prevention Data Sheet 1-29 and Roofing Application Standard RAS 217. Assemblies marked with an asterisk* carry the limitations set forth in Section 2.2.20.1 of FM Loss Prevention Data Sheet 1-29 (January 2016) for Zane 2/3 enhancements. 5.7 Exposure Limitations: Elastobase, Elastobase P, Polyglass G2 Base or Polyglass APP Base shall not be left exposed for longer than 30-days after installation. Polystick IR-Xeor Polystick MU-X shall not be left exposed for longer than 90-days after installation. Polystick MT$ MTS PLUS, TU P, TU Plus, TU Max, Dual Pro, Tile Pro or Elastaflex G TU shall not be left exposed for longerthan 180-days after installation. Polyflex SAP or SAP FR, or Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) does not have an exposure limitation, unless the prepared roof covering is to be adhesive -set tile, in which case the maximum exposure Is 30 days. Elastoflex 56 G or Elastoflex 56 G FR or Polyflex G or Polyflex G FR does not have an exposure limitation, unless the prepared roof covering Is to be adhesive -set tile (Elastoflex S6 G or Polyflex G only), in which rase the maximum exposure is 180 days. 5.8 Polystick MU-X has been found through comparative testing to have a lesser coefficient of friction than ASTM D226 roofing felt in a dry condition, tested at standard laboratory conditions. Agreement between purchaser and seller, as set forth in Section 4.3, Note 1 ofASTM D1970-15, should be established as to slip resistance. 5.9 Tile SlipoaRe Limitations (FRSA/TRI April 2012 (04-12)): When loading roof tiles on the underlayment In direct -deck tile assemblies, the maximum roof slope shall be as follows. These slope limitations can only be exceeded by using battens during loading of the roof tiles. ' „'( :.TIIEJ)LIPPAG 1DN11TAT1aNSFA,RID(RF b 4sr".k4 , - UndedaymentY Tile Profile Staging Method Maximum Slope Elastaflex G TU Flat 10tile stack 7:12 Lugged 8-tile stack(6 over 2) 6:12 Elastoflex S6 G or S6 G FR Flat or Lugged 6-tile stack (4 over 2) 4:12 Polystick MTS or MTS PLUS Flat 6-tile stack (4 over 2) 5:12 Lugged 6-tile stack (4 over 2) 4:12 PalystickTile Pro Flat or Lugged 6-tile stack (4 over 2) 7:12 Poly &TU Max Flat 6-tile stack (4 over 2) or 10-tile stack 7:12 Lugged tithe stack (4 over 2) 7:12 Lugged 10-tile stack 6:22 ' PolysdckTUP Flat 6-tile stack (4 over 2) 6:12 Lugged 6-tile stack (4 over 2) 4:12 PolystickTU Plus Flat or Lugged 6-t1le stack (4 over 2) 712 Flat or Lugged 10-tile stack 6:12 PoJyflex G or G FR Flat or Lugged 6-tile stack (4 over 2) 4:12 Polyflex SA P or SA P FR Flat or Lugged &tile stack (4 over 2) 4:12 NEMO ETC, LM Evaluation Report P12060,02.09-R24 @roTimra afaotharoWkn u32455 Go EDITION (2017)FBC NON-HVHZEVILLUATION Reyslan 7A: FL5259-R29 Polyglass Roof underlaymentr (954) 233-1230 Page 21 of 14 ONEN!ojetc. 6. INSTALLATION: 6.1 Polyglass Roof Underlayments shall be installed in accordance with Polyglass published installation requirements subject to the Limitations set forth in Section 5 herein and the specifics noted below. 6.2 Re -fasten any loose decking panels, and check for protruding nail heads. Sweep the substrate thoroughly to remove any dust and debris prior to application, and prime the substrate (if applicable). 6.3.1 Non Tile Applications: Shall be installed in compliance with the codified requirements for ASTM 0226, Type II underlayment in FBC Table 1507.L1 for the type of prepared roof covering to be installed. Elastobase, Elastobase P or Mule -Hide Nag Base may be covered with a layer of Polystick, Polyflex SAP, Polyflex SA P FR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR), self -adhered, Elastoflex G TU, Elastoflex S6 G or Elastoflex 56 6 FR in hot asphalt or Polyflex G or Polyflex G Fit, torch applied. Roof cover limitations are those are those associated with the top -layer underlayment, as set forth in Table 1, 6.3.2 Tile Applications: Efastobase, Elastobase P or Mule -Hide Nail Base are limited to use as a mechanically attached base sheet in the `Two Ply System" from FRSA/TRI April 2012 (04-12). Reference is made to Table 1 and. Section 5.6.4 herein, coupled with FRSA/TRI April 2012 (04-12) Installation Manual. &4 Polystic)cliff;S,hN[FSPkUS,I „TUPrTtJ'PljjgrTlflyflex•SA¢rPQfjiflel(S1fPP8,% , MulE=Hide SAR��apS�ke�RoriVlule�AfdeSA91PP;ppS�D'eet(F)Z),, `; - ° ` 6.4.1 Shall be Installed in compliance with the codified requirements for ASTM D1970 (except PolystickTU P) underlayment 6.4.2 In FBC Table 1507.L1for the type of prepared roof covering to be installed. Direct-to-Deckwith Mechanically Fastened Roof Covers: ,. All self -adhering materials, with the exception of Polystick TU Plus, Polyflex SAP or SAP FR and Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) should be back -nailed in selvage edge seam In accordance with Polyglass / Mule - Hide back nailing guidelines. Nails shall be corrosion resistant, 11 gauge ring -shank type with a minimum 24nch diameter metal disk or Simplex -type metal cap nail, at a minimum rate of 12" o.c. Polystic k TU Plusshould be back - nailed using the above noted fasteners and spacing, in area marked "nail area, area Para clever" on the Mee of membrane. The head lap membrane is to cover the area being back -nailed. All seal4ap seams (selvage laps) must be firmly rolled with a minimum 28 lb. hand roller to ensure full contact and adhesion. For Dual Pro and rile Pro, align the edge of the top sheet to the end of the glue pattern (the sheet will overlap the fabric). . ja view of ovelop Seam of oval Pro and Tile Pro All over -fabric and over -granule end -laps shall have a 6-Inch wide, uniform layer of Polyplus 50 Premium Modified Wet/Dry Cement or Polyglass PG500 Modified Cement applied In between the application of the lap. Polystick TU Plus, Dual Pro and rife Pro may not be used in any exposed application such as wickets, exposed valleys, or exposed roof to wall details NEMO ETC, LLC. Evaluation Report P12060A2.09-R24 arv&e of AUftrQ%6m#32455 a EOMON(20171 FBC NON+MCEVAWATION FL5259-1128 Polyglaw Roof underlaymekmg (954) 299-1230 Revision 24:01/24/2018 Page 12 of 14 ONEMOletc. Repair of Polystick membranes is to be accomplished by applying Polyplus 50 Premium Mod -died Wat/DryCement,or Polyglass PGS00 Modified Cement to the area in need of repair, followed by a minimum 6 x 6 inch patch of the Polystick material of like kind, set and hand rolled In place over the repair area. Patch laps, If needed, shall be Installed in a water shedding manner. All Potystick membranes shall be installed to ensure full contact with approved substrates. Polygiass requires a minimum of 404b weighted -roller or, on steep slopes, use of a stiff broom with approximately40-lbs of load applied for the field membrane. Hand rollers are acceptable for rolling of patches, laps (min. 28lb roller) or small areas of the roof that are not accessible to a large roller or broom. 6.4.3 TIIeApplications (not allowed for Polystick Dual Pro, l8-XeorPblystickMUX): Reference is made to FRSA%TRI April 2012 (04-12) Installation Manual and Table i herein, using the instructions noted above as a guideline. _ For mechanically fastened file roofing over 2-ply system, consisting of Base Sheet and self -adhering top sheet(s), Base Sheet fastening shall be not less than FRSA/TRI April 2012 (04-12), Table L For adhesive -set the applications, refer to Section 5.6A herein. 6.4A Two (2) Ply Underlayment Systems: Polystick MTS or MTS PLUS followed by Palystck MTS, M73 PLUS, TU P, TU Pius, TU Max, Tile Pro, MU-X or Polyflex SAP is allowable for use under mechanically attached prepared roof systems. Limits of use are those associated with the top -layer material. This Is not a requirement, but is allowable if a 2-ply underlayment system is desired. Polystick MTS or MTS PLUS followed by Polystick TU P, TU Plus, TU Max, Tile Pro or Polyflex SAP is allowable for use under foam -on the systems. Limits of use are those associated with the top -layer material. This Is not a requirement, but is allowable if a 2-ply underlayment system is desired. 6.5.1 Elastoflex G TU, Elastofiex S6 G or Elastoflex S6 G FR shall be installed in compliance with current Polyglass published Installation requirements. For use In the applications: ✓ Elastoflex G TU is for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D6380, Class M) In the "Single Ply System" from FRSA/Ml April 2012 (04-12) beneath mechanically fastened the roof systems or the Hot Asphalt applied "Cap Sheer in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or adhered tile roof systems. ✓ Elastoflex S6 G.is for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D6380, Class M) In the "Single Ply System" from FRSA/fRI April 2012 (04-12) beneath mechanically fastened the roof systems or the Hot Asphalt applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI April 2012 (04-121 beneath mechanically fastened or adhered tile roof systems. ✓ Elastoflex S6 G FR Is for use as an alternate to "Mineral Surface Roll Roofing" (ASfM D6380, Class M) in the "Single Ply System" from FRSA/TRI April 203.2 (04-22).beneath mechanically fastened tile roof systems or the Hot Asphalt applied "Cap Sheet" in the 'Two Ply System" from FRSA/rRI April 2012 (04-12) beneath mechanically fastened tie roof systems. 6.5.2 For hot -asphalt -applications, Elastoflex G TU, ElastoflexS6 G or Elastoflex S6 G FR shall be fully asphalt -applied to the substrates noted In Section 5.6. Side laps shall be minimum 34nch and end -laps minimum 64nch wide, off -set minimum 3 feet from course to course. Side and end laps shall be fully adhered in a complete mopping of hot asphalt with asphalt extending approximately 3/84nch beyond the lap edge. 6.6.1 PoWex G or Polyflex G FR shall be installed In compliance with current Polyglass published installation requirements. For use in the applications: ✓ Polyflex G Is for use as an alternate to the Heat Applied "Cap Sheet' In the "rwo Ply System" from FRSA/TRI April 2022 (04-12) beneath mechanically fastened or adhered the roof systems (Base Sheet Llmlted per 5.6.3). ✓ Polyflex G FR is for use as an alternate to the Heat Applied "Cap Sheet" in the 'Two Ply System" from FRSAJTRI April 2012 (04-22) beneath mechanically fastened tile roof systems (Base Sheet Umited per 5.6.3). NEMO ETC, LLG Ewivatlon Report P12060A2M.R24 @rtrfMQfAath0@anonr3249 eTM EDmON(2017)FDC NON-HVNZ EVAWATION FLS2.59-R23 Polyglass Roof Underlaymcros: (954) 233-1230 Revision 24: 01/24/2018 Page 23 of 14 ONEMOjetc. 6.6.2 Polyflex 6 or Polyflex G FR shall be fully torch -applied to the substrates noted in Section S.S. Side laps shall be minimum 3-Inch and end -laps minimum 6-Inch wide, off -set minimum 3 feet from course to course. Side and end laps shall be fully heat -welded and inspected to ensure minimum 3/8-Inch flow of modified compound beyond the lap edge. 6_7 Tile Staeine: 6.7.1 Tile shall be loaded and staged Ina manner that prevents the slippage and/or damage to the undedayment. Refer to Table 2 herein, and Polyglass published requirements for tile staging. 6.7.2 Battens and/or Counter -battens, as required by the the manufacturer and FRSA/TRI April 2012 (04-12) must be used on all roof slopes greater than 7:12. Precautions should be taken as needed, such as the use of battens or nail - hoards, to prevent tile sliding and/or damage to the underlayment during the loading process. 6.7.3 Polyglass specifies the minimum cure time after Installation of self -adhering membranes and before loading iof roofing tiles Is forty-eight (48) hours. 7. BUILDING PERMIT REQUIREMENTS: As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of this product 8. .MANUFACTURING PLANTS: Contact the noted OA agency for information on product locations covered for F.A.C. 61620-3 CIA requirements. The following plants have qualified products under their respective physical properties specifications. PIaMi..". s eciPcatuiii s r25; `t,: yt i Prddu s ` Femley, NV, Hazleton; PA&Writer Haven, FL ASTM D1970 Polystick MU-X Hazleton, PA M-D 13-0004 . Elastoflex G TU Hazleton, PA & Winter Haven, FL ASTM D1970 Polystick IR-Xe ASrM D1.970 & FRSA/rRl April 2012 Pol stick TU Plus ASTM D1970 & FRSA/rRI April 2012 PolystickTU Max Tuscaloosa, AL ASTM D4601, Type II Polyglass G2 Base Writer Haven, FL ASTM D226 (ph lwls) Elastobase, Elastobase P ASTM D6509 Polyglass APP Base FR5A/rRl April 2012 Polystick MTS, PoWck MTS PLUS FRSA/TRIApril 2012 P01 sack TU P FRSA/TRI April 2012 Polyflex SAP, Polyflex SA P FR ASTM D1970 Polystick Dual Pro AsTM D1970 & FRSA/TRI April 2012 Polystick Tile Pro ASTM D6164 Elastoll" S6, Ela5toflex S6 G FR ASTM D6222 PoWex G, Polvflex G FR 9. QUALITy ASSURANCE ENTITY: UL, iLC— QUA9625; (314) 578-3406, k.chancellor@us.ul.com - END OF EVALUATION REPORT - MEMO Ert, U.C. Evaluation Report P32060.02.09-R24 rem7fmte cffttharmtianN32455 eEDITIoN(2017)FBCNON-RVRZEVALUATION FL3259-RZS Polyglass Roof Underlaymens, (964) 233.=() Revision 24; 01/24/2018 Page 14 of 14