Loading...
HomeMy WebLinkAboutEVALUATION REPORTSCANNED By St. Lucie County ENGINEER EVALUATE TEST EVALUATION REPORT NEMO I etc. Certylcate afAuthorlmaon 02455 353 Christian Street, Unit #13 Oxford, CT 06478 (203)262-9245 CONSULT CERTIFY Polyglass USA, Inc. Evaluation Report P12060.02.09-R24 1111 West Newport Center Drive FL5259-R28 Deerfield Beach, FL 33442 Date of Issuance:02124/2009 (954)233-1230 Revision 24:01/24/2018 SCOPE: This Evaluation Report is issued under Rule 61620-3 and the applicable rules and regulations governing the use of construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen, P.E. for use of the product under the Florida Building Code and Florida Building Code, Residential Volume. The products described herein have been evaluated for compliance with the a Edition (2017) Florida Building Code sections noted herein. DESCRIPTION: Polygiass Roof Underlayments LABEuNG: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted herein. CONTINUED COMPDANCE: This Evaluation Report is valid until such time as the named products) changes, the referenced Quality Assurance documentation changes, or provisions of the Code that relate to the product change. Acceptance of this Evaluation Report by the named client constitutes agreement to notify Robert Nleminen, P.E. of any changes to the products), the Quality Assurance or the production facility laeation(s). NEMOIetc. requires a complete review of this Evaluation Report relative to updated Code requirements with each Code Cycle. ADVERTISEMENT: The Evaluation Report number preceded by the words "NEMOJeta Evaluated" may be displayed in advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety. ' INSPEcnow Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or its distributors and shall be available for Inspection at the job site at the request of the Building Official. This Evaluation Report consists of pages 1 through 14. Prepared by:°eta fi'e"w e �=? Robert J.M. Nleminen, P.E.^'- No. 5916 Florida DCA ANF1983 Or The fadmHeseal appea ngwasauthorbetl by RobertNlemnen this does notserve as an electronically 1!: P.E.ed Florida Registration 9 � Q'..::n�� • Deem nt.' signed documene CERDFICAMON OF INDEPENDENCE: 1. NEMOIetc. does not have, nor does it intend to acquire or will it acquire, a financial interest In any company manufacturing or distributing products It evaluates. 2. NEW (etc. Is not owned, operated or controlled by any company manufacturing or distributing products It evaluates. 3. Robert Nieminen, P.E. does not have nor will acquire, a financial Interest in any company manufacturing or distributing products for . which the evaluation reports are being Issued. 4. Robert Nieminen, P.E. does not have, nor will acquire, a financialInterest in any other entity involved in the approval process of the product. S. This is a building code evaluation. Neither NEW Ietc. nor Robert Nieminen, P.E. are, in anyway, the Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained specifically for that purpose. RODHNGCOMPONENTEVAWAriom 1. SCOPE: Product Category: Roofing Sub -Category: Undedayment Compliance Statement.• Roof Underlayments, as produced by Polyglass USA, Inc., have demonstrated compliance with the fallowing sections of the a Edition (2017) Florida Building Code through testing in accordance with the following Standards. Compliance Is subject to the installation Requirements and Limitations / Conditions of Use set forth herein. 2. SrANDARDS: Section Property Standard Year 1504.3.1 Wind Uplift FM 4474 2011 SSM3.1 Wind Uplift UL 1897 2012 1507.2.3/1507.Li Physical Properties ASTM D226 2009 1507.2.4 / 1507.1.L 1507.2.9.2 Physical Properties ASTM D1970 2015 1507.3.3 Physical Properdes FRSA/TRI April 2022 2012 1507.11.2 Physical Properties ASTM D6164 2011 1507AL2 Physical Properties ASTM D6222 2011 TAS 110 Accelerated Weathering ASTM D4798 2011 3. REFERENCES: Ent Examination Reference Date FM Approvals MT 1867) Wind Uplift 30=91 01/12/2000 PRI (TST5878) Physical Properties PR101111 04/08/2002 PRI(TST5878) Physical Properties PUSA-005-02-01 01/31/2002 Pill (TST 5878) Physical Properties PUSA-013-02-01 22/23/2002 PRI 05T 5878) Physical Properties PUSA-01302-02 12/23/2002 'PRI (TST 5878) Physical Properties PUSA-013-02-03 12/23/2002 PRI tM75878) Physical Properties PUSA-018-02-01 07/14/2003 PRI WS87S) - Physical Properties PUSA-028-02-01 07/13/2005 PRI DST 5878) Physical Properties PUSA-033-02-01 01/12/2005 PRI (TST 5878) Physical Properties PUSA-035-02-01 09/29/2006 PRI (TST 5878) Physical Properties PUSA-055-02-02 12/10/2007 PRI (TST 5878) Physical Properties PUSA-061-02-02 01/28/2008 PRI (TST 5878) Physical Properties PUSA-076.02-01 02/22/2008 PRI (TST 5878) Physical Properties PUSA-083-02-01 04/14/1008 PRI M5878) . Physical Properties PUSH-088-02-01 07/29/2009 MTI (TST2508) Physical Properties Nf2OH7A D4/01/2008 MTI (TST 2508) Physical Properties IMAM O3/29/2009 ERD (TST 6049) Physlwl Properties 11752.09.99-1 02/08/2000 ERD CM 6049) Wind Uplift 11757.08.01.1 0113/2001 ERD (TST 6049), Wind Uplift 11776.05.02 01/16/2003 ERD (TST 60491 Physical Properties 02200.07.03 07/14/2003 ERD M7 SO49) Wind Uplift P1740.OL07 .01/04/2007 ERD M6049) Physical Properties 1,5110.04.07-1 04/11/2007 ERD CM 6049) Wind Uplift P9260.03.08 03/22/2008 ERD(TST6049) Physical Properties .P13450.08.09 08/13/2009 ERD tW60491 Wind Upltft P30540.11.09-R1 12/30/2009 ERD(TST 6049) Physical Properties P11030.11.09.1 31/30/2009 ERD (MT 6049) Wind Uplift P11030.11.09.2 11/30/2009 ERD (TST 6049) Physical Properties P31030.11..09.3 11/30/200.9 ERD M6049) Physical Properties P33360.06.10 06/25/2020 ERD(TSr6049) Physical, Properties P33370:03.11 03/02/2031 ERD(TST 6049) Physical Properties P33370.04.11 04/26/2011 ERD (TST 6049) Physical Properties P37300.10.11 10/19/2011 NEMO E7Cq LLC. Evaluation Report P12060.0109•R24 @rSyiLpMef/lad"G flan Csa4SS. 6's EDItiDN(2017) F8C NON.NVH2 EVALUATON F1' 8 Palyglass Roof Underlaymenrr, (954) 233.1230 Rewslon 24: 01/24/2038 Page 2 of 14 Entity ERD (TST 5049) ERD (TST 6049) ERD MT 6049) ERD (TST 6049) ERD M76049) ERD (TST 6049) ERD 07 6049) ERD,(TST 5049) ERD (TS(' 6049) ERD CM 6D49) ERD (f5T 6049) ERD (TST 600) ERD (TST 6049) ERD (TST 6049) ERD (TST 6049) ERD (i5T 6049) ERD (TST 6049) ERD (TST 6049) ERD (TST 6049) ERD (TST 6049) ERD (15T 6049) ERD (TST 6049) ERD CYST 6049) ERD (1ST 6049) ERD CYST 6049) ERD (TST 6049) ERD (TST 6049) ERD (TST 600) .ERD (1ST 6049) ]CC -ES (EVL 2396) Miaml-Dade (CER 1592) Polyglass USA Polyglass USA Polyglass USA UL, U.C. (QUA9625) 4. PRODUCT DESCRIPTION: Examination Physical Properties Physical Properties Physical Properties Wind Uplift Physical Properties Wind Uplift Wind Uplift Wind Uplift Wind Uplift Wind Uplift Physical Properties Physical Properties Physical Properties Physical Properties Physical Properties Physical Properties Physical Properties Physical Properties Physical Properties Physical Properties Physical Properties Physical Properties Physical Properties Wind Uplift Physical Properties Wind Uplift Physical Properties Physical Properties Physical Properties IBC Compliance HVHZ Compliance Manufacturing Affidavit P/L Affidavit Materials Affidavit Quality Control Reference P4090.08.32-1 P40390.08.32-2 C414ZO.09.12-3 P396SM03.13 P45370.04.13 P173&02.07-R2 31757.04.01-1-R1 P41630.08.13 P1175LO5.03-RI P3178L31.03-R1 P45270.05.14 6020.07.14-1 6020.09.24-2 6020.09.14-3 6020.09.24-4 6020.09.14-5 6020.09.14.E P46520.10.14 P43290.10.14 PLYG-SC7550.03.15 P40390.04AS P44350.10.14-R1 PLYG-SCSD60.05.15-1 PLYG-SC8905.05.16-1 PLYG-SCSOS0.07.36 PLYG-SC12025.10.16 PLYG-SC33040.12.16 PLYG-SC31900.03.17 PLNG SC12115.08.17 ESR-1637 NOA 14-0717.08 Products Current Mule -Hide Cross I% Palysdck SA Compound Service Confirmation 4.2.2 Elastobase Is a fiberglass reinforced, SBS modified bitumen base sheet. 4.12 Elastobase P is a polyester -reinforced, SSS modified bitumen base sheet. 4.2.3 Polyglass 62 Base Is fiberglass -reinforced, asphaltic base sheet. 4.1.4 Polyglass APP Base is a fiberglass -reinforced, APP modified bitumen base sheet. ONEMOjetc. Date O8/06/2012 D6/U7/ZD12 09/11/2012 03/04/2013 04/26/2013 04/29/2013 04/30/2013 O8/0612033 12/26/2013 11/26/203.3 05/12/203.4 09/08/2014 09/08/2014 09/08/203.4 09/O8/2034 09/08/2024 09/08/2014 10/03/2014 10/17/2014 03/24/2025 04/03/2015 05/18/2015 05/20/2025 05/27/2026 07/16/2016 10/12/2016 22/27/2026 03/10/2017 09/09/2017 11/01/2024 01/2Z/2015 02/13/2009 03/02/2008 08/28/2011 Exp.10/05/2018 42.1 Polystick MIS or PolysdCk.MM PWS Is a nominal 60-mil thick rubberized asphalt waterproofing membrane, glass fiberreinforced, surfaced with polyolefinic film surface; meets.FRSA/TRI April 2012. 4.2.2 Polystick IR-Xe,is a nominal 60-m11 thick rubberized asphalt waterproofing membrane, glass fiber reinforced, with an aggregate surface, meets ASTM D1970. 4.2.3 Polo. Ick TU Plus is a nominal 80-mll thick rubberized asphalt waterproofing membrane, glass fiber reinforced, with a polyester fabric surface; meets ASTM D1970 and FRSA/TRI April2012. MEMO Or, LLG Evaluadori Report P12060.02D9-W Maul nk efAuftrtuabn032455 a EDmON (2017) F13C NON-HVHZ EVALUATION FLSM-R28 Polyglass Roof underlayments: (es4) 233-1230 Revision 24:01/24/2018 Page 3 of 24 ONEMOJetc. 4.2A Polystick TU P is a nominal 130-mil thick rubberized asphalt waterproofing membrane; glass-fiber/polyester reinforced, with a granular surface; meets FRSA/TRI .April 2012. UZ Polystick TU Max Is a nominal 60-mll thick rubberized asphalt waterproofing membrane with a 190 g/m2 polyester fabric surface; meets ASTM D1970 and FRSA/TRI April 2012. 4,2.6 Polyflex: SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR) are polyester. reinforced, APP modified bitumencapsheets; meet FRSA/TRI April 2012. 4.2.7 PoWcc Dual Prom Is a nominal 60-mil thick dual -layer rubberized asphalt waterproofing membrane, fiberglass reinforced, with a polyesterfabric surface; meets ASTM D1970. 4.2.8 Polystick Tde ProTM is a nominal 60-mil thick dual -layer rubberized asphalt waterproofing membrane, fiberglass reinforced, with a polyester fabric surface; meets ASTM D1970 and FRSA/TRI April 2012. 4.29 Polystick MU-X is a nominal 54-mil thick, dual -layer rubberized asphalt waterproofing membrane, fiberglass reinforced, with a polypropylene film surface; meets ACIM and physical requirements of ASTM D1970 (See Section 5,8). 4.3.1 Elastaflex G TU is a polyester reinforced, modified bitumen tile underlayment composed of a sand -surfaced SBS modified bitumen back -side and granule -surfaced APP modified bitumen top -side. Elastoflex G TU is for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D6380, Class M) in the 'Single Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened file roof systems or Hot Asphalt applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI April 2012 (D4-12) beneath mechanically fastened or adhered tile roof systems. 4.3.2 Elastoffex S6 6 and Elastoflex S6 G FR are polyester reinforced, SBS modified bitumen cep sheets; meet ASTM D6164. Elastoflex S6 Gand Elestoflex S6 G FR are for use as an alternate to "Mineral Surface Roil Roofing" (ASTM D6380, ClassM) In the "Single Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened file roof systems. Elastoflex S6 G Is for use as an alternate to Hot Asphalt applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or adhered tile roof systems. Elastaflex S6 G FR Is for use as an alternate to Hot Asphalt applied "Cap Sheet" in the 'Two Ply System" from FRSA/TRI April2D32 (04-12).beneath mechanically fastened tile roof systems. 4.3.3 Polyflex 6 and Polyflex 6 FR are polyester minforced, APP modified bitumen cap sheets, meet ASTM D6222. Polyflex G Is for use as an alternate to Heat Applied "Cap Sheet' in the'Two Ply System" from FRSA/TRI April 2012 (04.12) beneath mechanically fastened or adhered tile roof systems. Polyflex G FR is for use asan alternate to Heat Applied "Cap Sheet" in the 'Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened the roof systems. S. LIWAT1ONS: 5.2 This is a building code evaluation. Neither NEMOI etc nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any project on which this Evaluation Report, or previous versions thereof, Is/was used for permitting or design guidance unless retained specifically for that purpose. 5.2 This Evaluation Report Is not for use in the HVHZ 5.3 Fire Classification Is not part of this Evaluation Report refer to current Approved Roofing Materials Directory for fire ratings of this produce , 5.4 Polyglass Roof Underiayments may be used with any prepared roof cover where the product is specifically referenced within FBC approval documents. if not listed, a request may be made to. the Authority Having Jurisdiction for approval based on this evaluation combined with supporting data for the prepared roof covering.. MUD E7tq ILC. Evaluation Report P12060.02A9-R24 Maputo efA.VWnZff=OA7455 ar" EDmON(2017) Fae NON-RVNz eVAWATION Revision 24:01/7A/2016 Polyg�Roef Undeilaymems;(954) 233-12R0 i Page 4 of 14 ONEMOjetc. 5.5 Allowable Roof Covers: „,'FA.BCEl RooF''CovER OPTIONS. >>. .� Underlaymem AsphaRShingles Na"nTile Foam-on]tle Metal WoodShakes &ShinR1es Slam Elasmhase Yes Yes (Base Shen inzpl sMeml Yes (aasesbeetn22-dYsystem) Yes Yes Yes ElasmbaseP Yes yes asasesheetln2-plvpvsmml Yes la.msheam 2yiYms+s) Yes Yes Yes Polygiaw G2 Base No Imseshea nYes PNsvmeml (eamsheetnes dv sysmm) No No No Polyglass APP Base No Yes (aamsheetln2•vk'v/+tam) Yes (eem SheRln2-ph/sysrem) No No No Polystick MTS or MTS PLUS Yes Yes No Yes Yes yes Po[WUck lR-Xe Yes No. No No Yes Yes PolockTU P No Yes Yes (See5.5.1) No No No PolysdckTU Plus Yes Yes Yes (See5.5.3) Yes Yes Yes PolysockTU Max No Yes' Yes (See55.1) Yes No No PolysackEwlPm Yes No No Yes yes I Yes PolystickTilelim Yes Yes Yes (See 5.5.1) Yes Yes Yes Pohadck MU-X Yes No No Yes Yes Yes E18stoflaxS6G Yes Yes Yes (See5.5.1) No Yes Yes Elastofl"SSG FR Yes Yes No No Yes Yes Elastoflex GTU Yes Yes Yes (See 55-11 No Yes Yes PowlexG Yes Yes Yes (See 55.1) No Yes Yes PolyflexG FR Yes Yes No No Yes Yes PalyflexSAP or SAP FR Yes Yes Yes (See 55.1) No Yes Yes Mul&Hlde SA-APP Cap Sheet or SA-APP Cap Sheet (FR) Yes Yes Yes (See 55.1) No Yes Yes 5.5.1 "Foam -On Tile' is limited to use of the following Approved the adhesives / underlayment combinations. . ,,:•: :.... TapIE3A: At1Q1N%�qf{:'PIuiAAQ;;1�?ryEIUd141ER}AYaIIENx'�Ni�iPlA716}151:..•� •.' Adhesive . Florida Product Underlayments Approval DAP Foam Touch'n Seal Stormilond Roof FL14506 Polystick TU Plus, Polystick TU Max Tile Adhesive DowTileBond"' FL22525 PolystickTU P, PolWick TU Plus, Palyflex SAP or Tile Pro Polystick TU P, Polystick TU Plus, Polystick TU Max, Polystick Tile Pro, ICP Adhesives Polyset" AH-160 FL6332 Elastaflex G TU, Elastoflex 56 G, Polyflex G, Polyflex SAP, Palyflex SA Cap FR, Mule -Hide SA-APP Cap Sheet or Mule -Hide SA-APP Cap Sheet (FR) Polystiek TU P, Polystick TU Plus, Polystick TU Max, Polysdck Tile Pro, ICP Adhesives Polyseta RThl FL6276 Elastoflex G TU, Elestoflex 56 G, Polyflex G, PGlyflex SAP, Polyflex SA Cap FR, Mule-Hlde SA-APP Cap Sheet or Mule -Hide SA-APP Cap Sheet (FRI x Referto Tile Manufacturer's or Adhesive Manufacturers Florida ProductApprovol for Overtuming MomentResismnm Perfamsance NEMO ETC, LLC. Ewluadon Report P12060.07 09-R24 [ertylmrcsyAYrhvraatlana3245S firs EDITION (2a17) FBC NON-HVH2 EVALUATION RBNslan 24: 0U4� 2g l20 Polyglass Roof Undedaymelds; (954) 733-1230 Pages idle NNEMOJetc. 5.6 Allowable Substrates; 5.6.1 Direct -Bond to Deck: Polystick (all variations), Dual Pro, Tile Pro, Polyflex SAP or SAP FR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet .(FR) self -adhered to: D New untreated plywood; ASTM D41 primed new untreated plywood; Existing plywood; ASTM D41 primed existing plywood; New or existing, unprimed OSB, ASTM D41 primed OSB; Southern Yellow Pine; ASTM D41 primed Southern Yellow Pine; ASTM D41 primed structural concrete; Huber Engineered Woods 'ZIP System" Panels (designed and installed to meet wind loads for project). Note: Polyglass does not require priming of new or existing plywood or OSB sheathing. New or existing plywood or OSB sheathing should be cleaned of all dirt and debris prior to application of Polystick membranes. Elastoflex G TU; Elastoflex S6 G or Elastoflex S6 G FR in hot asphalt to: D ASTM D41 primed structural concrete. Polyflex G or Polyflex G FR torch -applied to: D ASTM D41 primed structural concrete. 5.6.2 Band -to -Insulation: Polystick (all variations), Polyflex SAP or SAP FR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) self -adhered to: D ASTM C1289, Type 11, Class 1 polyisocyanurate or Type V polyisocyanurate-composite Insulation; Dens Deck DuraGuard; Dens Deck Prime, or SECUROCK Gypsum -Fiber Roof Board. Elastoflex G TU, Elastoflex S6 G or Elastoflex S6 G FR in hot asphalt to: D Dens Deck Prime orSECUROCK Gypsum -Fiber Roof Board. Polyflex G or Polyflex G FIR torch -applied to: D ASTM D41 primed structural concrete; Dens Deck Prime or SECUROCK Gypsum -Fiber Roof Board. For installation under mechanically attached prepared roof coverings, Insulation shall be attached per minimum requirements of the prepared roof covering manufacturer's Product Approval. For installations under foam -on tile systems, Insulation attachment shall be designed,by a qualified design professional and installed based on testing of the insulation/underlayment system in accordance with FBC Section 1504.3.1. 5.63 Bond to Mechanimily Attached Base Laver: Polystick (all variations), Polyflex SAP or SAP FR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) Dual Pro or Tile Pro self -adhered to: D ASTM D226, Type I or 11 felt; Elastobase; Elastobase P or Mule -Hide Nall Base. Elastoflex G TU, Elastoflex 56 G or Elastoflex S6 G FR In hot asphalt to: D ASTM D226, Type I or 11 felt; Elastobase; Elastobase P, Mule -Hide Nall Base or Polyglass G2 Base. PolyOex G or Polyflex G FR torch -applied to: D Elastobase; Elastobase P, Mule -Hide Nall Base, Polyglass G2 Base or Polyglass APP Base. For installations under mechanically attached prepared roof coverings, base layer shall be attached per minimum codified requirements. For installations under foam -on tile systems, base layer shall be attached per minimum requirements of FRSA(TRI April 2012 (04-12), Appendix A, Table 1, or as listed in Section 5.6.4 herein, or as tested In accordance with FBC Section 15043.1. NEMO ETC, U.C. Ewluadon Report P32060.02A9-1174 eer =i afA"MakmbnCa741S eEDITION 12017) FBCNON-HVHZ EVALUATION FL5S99*ZB PDiyglaw Roof Underlaymards; (9541233-2230 Revision 24.01/24/2018 Page 6 of 14 ONEIVIOletc. 5.6.4 Wind Resistance for U n den ent Systems In Foam -On The Applications: FRSAJTRI April 2012 (04-12) does not address wind uplift resistance of all underlayment systems beneath foam -on tile systems, where the underlayment forms part of the load -path. The following wind uplift limitations apply to underlayment systems that are not addressed In FRSA/TRI April 2012 (04-12) and are used in foam -on tile applications. Maximum Design Pressure is the result of testing for wind load resistance based on allowable wind loads, and reflects the ultimate passing pressure divided by 2 (the 2 to 1 margin of safety per FBC 15042 has already been applied). Refer to FRSA/TRI April 2012,(04- 12), Appendix A, Table 1A or FBC 1609 for determination of design wind loads. #1 Maximum Design Pressure =-90osf: Deck: Min.15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Primer. None Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, selfadhered. Underlaymekd: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), selfadhered. #2 Maximum Design Pressure =-97.5 ttsf, Deck: MIn.15/32-inch plywood to meet project requirements to satisfaction of Authority HavingJurisdiction. Primer: PG300 or ASTM D41 Base Ply: (Optional) Polystick MTS or Polystick Mrs PLUS, self -adhered. Undedayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflax SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered and back -nailed within the selvedge -edge side laps using 12 ga. x IN" ring shank nails through 32 ga., 1-5/8' diameter tin caps spaced 12-inch o.c. #3 Maximum Design Pressure=-105 osF. Deck: Min. 15/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Primer: WB-3000 Base Ply: (Optional) Polystick MTS or PolVsdck MTS PLUS, self -adhered. Underayment Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered and back -nailed within the selvedge -edge side laps using 12 ga. x 23r ring shank nails through 32 ga., 1-5/8' diametertin caps spaced12-Inch o.c. #4 Maximum Design Pressure =-135 osf: Deck: Min. 15/32-Inch plywood to meet projectrequirementstosatlsfaction of Authority Havinglurisdiction. Pdmer. (Optional) PG300 orASfM D41 Base Ply: (Optional) Polystick Mrs or Polystiek MTS PLUS, self -adhered. Johns: - Min. 4-Inch wide strips of Elastoflex SA-V over all plywood joints. Underayment Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FRI, self -adhered. #5 Maximum Design Pressure =-315 osf. Deck: Structural concrete to meet project requirements to satisfaction of Authority Having Jurisdiction. Primer: PG100 or ASTM D41 Base Ply. (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered. Underlaymerm Polystick TU P, Polystick TU Plus, Polystick TU Max, Tile Pro, PolyRax SAP. Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), selfadhered. #6 Maximum Design Pressure=-622.5 osf: Deck: Structural concrete to meet project requirements to satisfaction of Authority Havinglurisdiction. Primer: P5100 orASTM D41 Undedayment Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hbt asphalt or Polyflex G, torch -applied. #7 Maximum Design Pressure=-30.0 Osfr: Deck: Min, 15/32-inch OSB to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase or Mule -Hide Nail Base (poly -film top surface) Fasteners: 11 ga. x 0-5-Inch long x 1-inch head diameter round metal cap nails Spacing: 54nch mc. at the 3-inch wide side laps and.64nch o.c at two (2) equally spaced staggered center rows. Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered. Underayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered. NEMO ETC, LLC, evaluation Report P12000.02A9-RZ4 ClItYkax qrauthareoVmASZ435 6T" EDmON MU71 FBC NON-HVHZ EVALUATION FL5259-RIG Peiygiass Roof Undedayments: (954) Z33-1230 Revldon 24: 01/24/2018 Page 7 of 14 ONEMOJetc. 418 Maximum Desien Pressure =-37.5 psf* Deck: Min. 15/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase or Mule -Hide Nail Base (poly -film top surface) Fasteners: 11 ga. x 1.254nch long x ].-Inch head diameter round metal cap nails Spacing: 6-inchor at the 3-Inch wide side laps and 6-Inch mc. at two (2) equally spaced staggered center rows. Base Ply: (Optional) Polystick MTS or Polystick WITS PLUS, self -adhered. Underlayment: Polystick TU P, Polystick TU Plus, Polystick TV Max, Polyffm SAP, Polyflex SAP Fit, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), selfadhered. #9 Max(mumDesienPressure =-37.5psF* Deck: Min.19/324nch plywood to meet project requirements to satisfaction of Authority HavingJurisdiction. Base Sheet: One (1) ortwo (2) layers ASTM D226, Type II felt Fasteners: 11 ga. x 1.25-Inrh long x i-Inch head diameter round metal cap nails Spacing: 6-Inch o.c at the 3-Inch wide side laps and 12-Inch o.a. at two (2) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt #10 Maximum Design Pressure=-45 PA* Deck: Min.19/32dnch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: One (1) layer ASTM D226, Type 11 felt Fasteners: 11 Be. x1.254nchx3/9-inch head diameter annular ring shank roofing nails at 2-5/84nch diameter tin caps Spacing: 4-Inch mm at the 24nch wide side laps and 4-inch o.c at two 12) equally spaced staggered center rows. Base Ply: (Optional; for use with self -adhering underlaymem only) Polysdck MTS or Polystick MTS PLUS, seHadhered. Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyllex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered or Elastoflex G TU, applied in full mopping of hot asphalt #11 Maximum Design Pressure=-45 psf Deck: Min.19/32-inch plywood to meet project requirements to satisfaction of Authority HaWrig.lurisdiction,. Base Sheet: Two (2) layers ASTM D226, Type II felt Fasteners: 11 ga. x1.25-Inch long 3/8-inch head diameter annular ring shank roofing nails at 1-5/8-inch diameter tin caps Spacing: 9-inch o.c at the 2-Inch wide side laps and 9-Inch me. at two (2) equally spaced staggered center rows. Base Ply: (Optional; for use with self -adhering undedayment only) Polystick MTS or Polystick MTS PLUS, self -adhered. Underlayment Polystick TU P, Polystick TU Plus,Polystick TU Max, Payflex SAP, Polyflex SAP Fit, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered or Elasto8ex G TU or Elastoflex S6 G, applied in full mapping of hot asphalt #22 Maximum Design Pressure =-45 Deck: Min.15/324nch plywood to meet project requirements to satisfaction of Authority Having.lurisdlction. Base Sheet: -Elastobase(sanded top surface for hotasphalt or torch -applied cap or poly -film surface for torch -applied cap) Fasteners: Simplex MAXX Cap Fasteners Spacing: 9-Inch mt at the 2-inch wide side laps and 18-Inch o.e. attwo (2) equally spaced staggered center rows. Underlayment ElastaRex G TU or Elastoflex S6 G, applied In fullmapping of hot asphalt or Polyflex G, torch -applied. #13 Maximum Desien Pressure =-52.5 psf: Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority HavingJurisdiction. Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cep or poly -film surface for torch -applied cap) Fasteners: Simplex MAXXCap Fasteners Spacing: B-inch mc. at the 2-Inch wide side laps and 22-Inch me. at two (2) equally spaced staggered center rows. Underiaymerd: Mastafleii G TU or Elastoflex S6 G, applied In full mopping of hot asphalt or Polyflex G, torchapplled. #24 Maximum Design Pressure =-525 Dees: Min.15/32-Inch plywood to meet project requirementstosatisfaction of Authority HaAnglurisdictlon. Basesheet: Elastobase or Mule-HldeNall Base(poly-film top surface) Fasteners: Simplex Original Cap Nails Spacing: S-Inch o.c at the 34nch wide side laps and &mch me. at four (4) equally spaced staggered center rows Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, selfadhered. Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered. NEMO ET , LLC. Ewluatlon Report P12060.02A9-1124 Cerajimte kVAUdiodntio 02455 eEOITIOPI(P017)FBC NON-HVH2EVAWATION FLS259-R28 Polygtass Roof Undedayments; (954) 233-MO Revision 24: 01/24/2013 Page 8 of 14 NNEMOJetc. #15 Maximum Desien Pressure=-52.5 psf: Deck: Min.15/324nch plywood to meet project requirements to satisfaction of Authority Havinglurlsdiction. Base Sheet Elastobase(sanded top surface for hat -asphalt or torch -applied cap or poly -film surfacefortordtapplied rap) Fasteners: Simplex Original Cap Nails Spacing: 6-inch o.a at the 3-Inch wide side laps and 6-inch o.c. at four (4) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torchappill #16 Maximum Design Pressure=-60 psf: Deck: Min.19/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdlction. Base Sheet: Elastobase(sanded top surface for hart -asphalt or torch -applied cap or poly -film surface fortorchapplied cap) Fasteners: 11 ga. x 125-Inch long x 3/8-inch head diameter annular ring shank roofing nails at 1-5/8-Inch diametertin caps Spacing: 8-Inch o.a at the 4-Inch wide side laps and B-Inch o.e at three (3) equally spaced staggered center rows. Undedayment: Elastoflex G TU or Elastoflex S6 G, applied In full mopping of hat asphalt or Polyflex G, torch -applied. #17 Maximum Design Pressure =-60 ps(: Deck Min.19/32-inch plywood to meet project requirements to satisfaction of Authority HavinfiJurisdlction. Base Sheet Elastobase(sandedtop surface for hot -asphalt or torch -applied rap or poly -film surface for torchappliedcap) Fasteners: OMG#12 Standard Roofgrip with OMG Flat Bottom Metal Plates Spacing: 12-Inch o.c. at the 4-Inch wide side laps and 12-inch o c, at two (2) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex 56 G, applied in full mopping of hot asphalt or Polyfiex G, torch -applied. #18 Maximum Design Pressure=-67.5 psi: Deck Min.15/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Polyglass G2 Base or Polyglass APP Base (requires use of torch -applied underlaymeMj Fasteners: 12 ga. x 125-Inch long x 3/8-inch head diameter annular ring shank roofing nails at 1-5/8-inch diameter tin ceps Spacing: 8-Inch ax at the 4-Inch wide side laps and.B-Inch o.c at four (4) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elasto0ex S6.6, applied In full mopping of hot asphalt or torch -applied or Polyflex G, torch - applied. #19 Maximum Design Pressure =-75 a Deck Min.15/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Polyglass G2 Base or Polyglass APP Base (requires use of torch -applied underloymentj Fasteners: Dekfast #24 with Dekfast Hex plates, OMG #14 HD with OMG r Galvalume Steel Plates, OMG Roofgrip #14 with OMG Flat Bottom Plates (AccuTrac), Tmfast HD with Trubst 3-Inch Insulation Plates or Simplex MA%X Cap Fasteners Spacing: 10-Inch o.c. atthe 4-inch wide side laps and 104nch mc. atthree (3) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G, applied In full mopping of hot asphalt or torch -applied or Polyflex G, torch - applied. #20 Maximum Design Pressure=-90 osf: Deck. Mtn. 15/32-inch plywood to meet project requirements to satisfaction of Authority. Having Jurisdiction. Base Sheet Elastobase(sanded top surface for hot -asphalt or torch.applied cep or poly -film surface fortorchapplied cap) Fasteners: Simplex MAXX Cap Fasteners Spacing: 6-inch c.c. atthe 2-Inch wide side laps and &•inch ac. at two (2) equally spaced staggered center rows. Underlayment Elastoflex G TU or Elastaflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied. #21 Maximum Design Pressure =-90 asf: Deck: Min.15/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase(sanded top surface for hotasphalt or torch -applied cap or poly -film surface for torch -applied cap) Fasteners: CMG #12 Standard Roofgrip or OMG #14 Heavy Duty with OMG 3' Round Metal Plates or OMG flat Bottom Metal Plates Spacing: Finch o.a at the 4-inch wide side laps and 6-Inch o.e at three (3) equally spaced staggered center rows. Underlayment Elastoflex G TU or Elastoflex 56 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied.. #22 Maximum Design Pressure=-90 psf. Deck: Min.15/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase (sanded top surface) Fasteners: Trufast#12 DP or Trufast#24 HD with Trufast 3' Metal Insulation Plates Spacing: 64nch o.c at the 44nch wide side laps and 6-Inch o.e at three (3) equally spaced staggered center rows. Underlaymmt Elastoflex G TU or Elastoflex S6 G, applied In full mopping of hot asphalt. NEW ETc. LLG Evaluation Report P12060.0209-R74 artifiram gFAUffWkW9n#32455 eEDITION (2017) FBC NON-MZEVAWATION pM59-RZ8 PNyglass Roof undedayna nts; (9541233-tt90 Revision 24: 01/24/201B Page 9 of 14 ONEMoletc. #23 Maximum Design Pressure =-90 osi: Deck: Min. 25/32-Inch plywood to meet project requiremems to satisfaction ofAuthorlty Havinglurisdicbon. Base Sheet: Polygiaw GZ Base or Polyglass APP Base (requires use of torch -applied undedayment) Fasteners: Deklest #14 with Dekfast Hex plates, OMG #14 HD with OMG r Galvalume Steel Plates, DMG Roofgrip #14 with OMG Flat Bottom Plates (AeeuTrac), Trufast HD with Trufast 34nch Insulation Plates or Slmplex MAXX Cap Fasteners Spacing: 9-Inch mc. at the 4-inch wide side laps and 9-Inch o.c. at four (4) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastofiex S6 G, applied In full mopping of hot asphalt or tomhapplied or Polyflex G, torch - applied. #24 Maximum Design Pressu re = -97.5 Is Deck: Min.29/32-Inch plywood to meet project requirements to satisfaction of Authority HOVIngJurisdiRlon. Base Sheet: Elastabase or Mule -Hide Nail Base (poly -film top surface) Fasteners: 11 ga. x 1.254nch x 3/8-Inch head diameter annular ring shank roofing nails at 1-5/8-Inch diameter tin caps Spacing: 44nch o.a at the 4-Inch wide side laps and 4-inch c.c. at four (4) equally spaced staggeredcenter rows. Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered. Underlayment: Polystick TU P, PolystickTU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered. #25 Maximum Design Pressure =-105 Dsf: Deck: MIn.15/32-Inch plywood to meet project requirements to satisfaction of Authority HavingJurisdiction. Base Sheet: Elastobase(sanded top surface for hot -asphalt or torch -applied cap or polyfilm surface for torch -applied rap). Fasteners: Simplex MAXX Cap Fasteners Spacing: 6-Inch o.o at the 2-Inch wide side laps and 6-Inch o.c. at three (3) equally spaced staggered center rows. Undedayment Elastoll G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, tomhapplied. #26 Maximum Design Pressure = -112.5 osF. Deck: MIn.19/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elostobase or Mule -Hide Nail Base (poly film top surface) Fasteners: 11 go. x1.25-inch x3)8-inch head diameter annular sing shank roofing nails at 1-5/8-Inch diameter tin caps Spacing: 6-Inch o.r at the flinch wide side laps and 6-inch o.c. atfour (4) equally spaced staggered center rows. Primer: PG1OO orASfM D41 primerat all tin -caps Base Ply: Polystick MTS or Polystick MTSPLUS, self -adhered Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), selfadhered. #27 Maximum Design Pressure=-120osf: Deck: Min. 15/32-Inch plywood to meet project requirementsto satisfaction of Authority Havinglurisdiction. Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied rap or poly -film surface for torch -applied cap) Fasteners: OMG #12 Standard Roofgdp or OMG #14 Heavy Duty with OMG 3" Round Metal Plates or OMG Flat Bottom Metal Plates Spacing. 64nch o.a at the 4-Inch wide side laps and 6-inch o.c. atfive(5) equally spaced staggered center rows. Underlayment: ElastoOex G TU or Elasta0ex SG G, applied in full mopping of hot asphalt or Palyflex G, torch -applied. #28 Maximum Design Pressure=-120 osf: Deck Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase(sanded top surface) Fasteners: Trufast#12 DP or Trufast #14 HD with Trufast 3" Metal Insulation Plates Spacing. &Inch o.c. at the 44neh wide side laps and 6-Inch o.e at five (5) equally spaced staggered center rows. Underlayment. Elastoflex G TU or Elastofiex S6 G, applied In full mopping of hot asphalt. 5.6.4.1 All other direct -deck, adhered Polyglass underlayment systems beneath foam -on the systems carry a Maximum Design Pressure of-45 psf. NEMO EM LLC. Evaluation Report P12060.02A9-R24 07WAMWCfAuN lionlon#3ZM 6'v EDITION(2017) FBC NON4HVHZEVALtIATION F15259-62a Polyglaw Roof Undesiayments, (954) 233.2230 Revision 24: M/24/2018 Page 10 of 14 I ONEMoletc. 5.6.4.2 For mechanically attached Base Sheet, the maximum design pressure for the selected assembly shall meet or exceed that required under FRSA/TRI April 2012 (04-12), Appendix A, Table 1A. Alternatively, the maximum design pressure for the selected assembly shall meet or exceed the Zone 1 design pressure determined In accordance with FBC 1609. in this case, Zones 2 and 3 shall employ an attachment density designed by a qualified design professional to resist the elevated pressure criteria. Commonly used methods are ANSI/SPRI WD3, FM Lass Prevention Data Sheet 1-29 and Roofing Application Standard RAS117. Assemblies marked with an asterisk` carry the limitations set forth in Section 2.2.10.1 of FM Loss Prevention Data Sheet 1-29 (January 2016) for Zone 2/3 enhancements. 5.7 Exposure Limitations: Elastobase, Elastobase P, Polyglass G2 Base or Polyglass APP Base shall not be left exposed for longer than 30-days after installation. Polystick IR-Xe or Polystick MU-X shall not be left exposed for longer than 90-days after Installation. Polystick MTS, MTS PLUS, TU P, TU Plus, TU Max, Dual Pro, Tile Pro or Elastoflex G TU shall not be left exposed for longerthan 180-days after installation. Polyflex SAP or SAP FR, or Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) does. not have an exposure limitation, unless the prepared roof covering is to be adhesive -set tile, in which case the maximum exposure is 30 days. Elastoflex S5 G or Elastoflex 56 G FR or Polyflex G or Polyflex G FR does not have an exposure limitation, unless the prepared roof covering is to be adhesive -set file (Elastoflex S6 G or Polyflex G only), in which case the maximum exposure Is 180 days. 5.8 Polystick MU-X has been found through comparative testing to have a lesser coefficient of friction than ASTM D226 roofing felt in a dry condition, tested at standard laboratory conditions. Agreement between purchaser and seller, as set forth in Section 4.3, Note 1 of ASTM D1970-15, should be established as to slip resistance. 5.9 Tile Silobage Limitations (FRSA/TRI April 2012104-1211i When loading roof tiles on the underlayment In direct -deck the assemblies, the maximum roof slope shall be as follows. These slope limitations can only be exceeded by using battens during loading of the roof tiles. . ... ..•.. `.iABA�it:-Td{E.SLiPRA1'G,E;iIMITA`fIGNSFGgR30(ft�k' i�'4.,1_iF...P.rl:`IIb`�ISI .,I�TION,S... ; •:r "'�::: Undedayment Tile Profile Staging Method Maximum Slope Elastaflex G TU Flat 10-tile stack 7:12 lugged 8dlle stack (6 over 2) 6:12. Elastaflex%6 or S6 G FR Flat or Lugged &tile stack (4 over 2) 4:12 Polystick MTS or MTS PLUS Flat &tile stack (4 over 2) 5:12 Lugged 6-tile stack (4 aver 2) 4:22 PolystickTlle Pro Flat or Lugged &tllestack(4over2) 7:12 PoWck TU Max Flat 6-tfle stack (4 over 2) or 20-tile stack 7:12 Lugged 6-tile stack (4 over 2) 7:12- Lugged - 10•tile stack 6:12 PolystickTU P Flat &tile stack (4 over 2) 6:12 Luged 6-tile stack (4 over 2) 4-12 PolysdckTU Plus Flat or Lugged &tile stack (4 over 2) 712 Flat or Lugged 10-tile stack 6:12 POlyflexG orG FR Flat or Lugged 6-tile stack (4 over 2) 4:12 Polyflex SA P or SA P FR Flat or Lugged 6-tile stack (4 over 2) 4:12 NEMO ETC, LLC. Evaluadon Report P12060.02.09-1124 amrmke oJaumwumnn o224S5 aEDITION(2a17)F9CNON4IVHZEVALUATION FL6269-R211 Polyglass Roof Underlaymentr (964) 233-12R0 RVASbn 24: OV2412018 Page 21 of 14 ONEMO I etc. 6. INSTALLATION: 6.1 Polyglass Roof Underlayments shall be installed in accordance with Polyglass published installation requirements subjectto the Limitations set forth in Section 5 herein and the specifics noted below. 6.2 Re -fasten any loose decking panels, and check for protruding nail heads. Sweep the substrate thoroughly to remove any dust and debris prior to application, and prime the substrate (if applicable). .. 6.3 Elastpbase;Elastdba5e:?gciNple-Nide'NaifHasec .., .. •. .. ., ,...w-,;,,,.;•,, ;;-.:, . . 6.3.1 Non -Tile Applications: Shall be installed in compliance with the codified requirements for ASTM D226, Type ii undeHayment in FBC Table 1507.L1 for the type of prepared roof covering to be installed. Elastobase; Elastobase P or Mule -Hide Nail Base may covered with a layer of.Polystick, Polyflex SAP, Polyflex SA P FR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR), self -adhered, Elastoflex G TU, Masroflex S6 6 or Elastoflex S6 G FR in hot asphalt or Polyflex G or Polyflex G FR, torch applied. Roof cover limitations are those are those associated with the top -layer underlayment, as set forth in Table 1, 6.3.2 Tile Applications: Elastobase, Elastobase P or Mule -Hide Nail Base'are limited to. use as a mechanically attachedbase sheet in the "Two Ply System"'from FRSA/TRI April 2022 (04-12). Reference is made to Table 1 and Section S.6.4 herein, coupled with FRSA/TRIApril 2012 (04-12) Installation Manual. ,6.4: Polystjt,,k:,IyFSS!PU9,S.s:7(r.'7fe,TU..Pi fPiF15r'1't(Mdl4Dyd��ftfT%.l!Idlair';INU�Z(:pe:Po(yfiek•SAh::P4Cy(IeiGSkR': . MulHide�'A.A.aR'Cap'S'hteFtDr,`1V141e-Ailde;SA1PPpSh'eei(t,')tj3:`:' 6.4.1 Shall be Installed In compliance with the codified requirements for ASTM D1970 (except Polystick7U P) undedayment 6.4.2 In FBC Table 1507.L3 for the type of prepared roof covering to be installed. Direct -to -Deck with Mechanically Fastened Roof Covers: All self -adhering materials, with the exception of Polystick TU Plus, Polyflex SAP or SAP FR and Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) should be back -nailed in selvage edge seam In accordance with Polyglass / Mule - Hide back nailing guidelines. Nails shall be corrosion resistant, 11 gauge ring -shank type with a minimum 24nch diameter metal disk or Simplex -type metal cap nail, at a minimum rate of 12" o.e. Polystick TU Plus should be back - nailed using the above noted fasteners and spacing, in area marked "nail area, area pars clever" on the face of membrane. The head lap membrane is to cover the area being back -nailed. All seal -lap seams (selvage laps) must be firmly rolled with a minimum 28 lb. hand roller to ensure full contact and adhesion. For Dual Pro and Tile Pro, align the edge of the top sheet to the end of the glue pattern (the sheet will overlap the fabric). LAW View of OvelaP Seam of peal Pro and the Pm All over -fabric and over -granule end -laps shall have a &Inch wide, uniform layer of PDlyplus So Premium Modred Wet/Dry Cement or Polyglass PGSOO Modified Cement applied In between the application of the lap. PolystickTU:Plus, Dual Pro and Tile Pro may not be used in any exposed application such as crickets, exposed valleys, or exposed roof to wall details NEMO ETC, LM Evaluation Report P12060.02.09•R24 @rpf5aw afAummtmdan d3240 ew EDITION (2037) FBC NCWHVHZ EVALUATION FLU99-RZB Pol2glas4 Roof underlayments; (934) 233-2230 Revision 24:02/20018 Page 12 of 14 ONEMOjetc. Repair of Polystick membranes Is to be accomplished by applying Polyplus 50 Premium Modified Wet/Dry Cement or Polyglass PG500 Modified Cement to the area in need of repair, followed bya minimum 6 x 6 inch patch of the Polystick material of like kind, set and hand rolled in place over the repair area. Patch laps, If needed, shall be Installed In a water shedding manner. Al PoWick membranes shall be Installed to ensure full contact with approved substrates. Polyglass requires a minimum of 40-lb weighted -roller or, on steep slopes, use of a stiff broom with approximately40-lbs of load applied for the field membrane. Hand rollers are acceptable for rolling of patches, laps (min. 28111 roller) or small areas of the roof that are not accessible to a large roller or broom. 6.4.3 Tile Applications (nut allowed forP6]wtkk Dual Pro. IRXe or Polvsrick M&A Reference Is made to FRSA%TRI April 2012 (04-12) Installation Manual and Table 1 herein, using the instructions noted above as a guideline. For mechanically fastened tile roofing over 2-ply system, consisting of Base Sheet and self -adhering top sheet(s), Base Sheet fastening shall be not less than FRSA/TRI April 2012 (04-12),Table L For adhesive -set tile applications, refer to Section SAA herein. 6.4,4 Two (21 Ply Underlavment Systems: Polystick MTS or MTS PLUS followed by Polystick MTS, MTS PLUS, TU P, TU Plus, TU Max, Tile Pro, MU-X or Polyflex SAP Is allowable for use under mechanically attached prepared roof systems. Limits of use are those associated with the top4ayer material. This Is not a requirement, but is allowable if a 2-ply underlayment system is desired. Polystfck MTS or MTS PLUS followed by PoWck TU P, TU Plus, TU Max, Tile Pro or Polyflex SAP is allowable for use under foam -on the systems Umlts of use are those associated with the top -layer material. This Is not a requirement, but is allowable if a 2-Div underiavmerlt system Is desired. 6.5.1 Elastaflex 6 TU, Elastoflex S6 G or Ehastoflex S6 G FR shall be installed in compliance with current Polyglass published Installation requirements. For use In tile applications: ✓ Elastaflex G TU is for use as an alternate to "Mineral Surface Roil Roofing" (ASTM D6380, Class M) in the "Single Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems or the Hot Asphalt applied "Cap Sheer in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or adhered tile roof systems. ✓ Elastoflex S6 G is for use as an alternate to "Mineral Surface Roll Roofing" [ASTM D6380, Gass M) in the "Single Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened the roof systems or the Hot Asphalt applied "Cap Sheet' in the 'Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or adhered tie roof systems. ✓ Elastaflex S6 6 FR is for use as an alternate to "Mineral Surface Rail Roofing" (ASTM D6380, Class M) in the "Single Ply System" from FRS'A/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems or the Hot Asphalt applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems. 6.5.2 For hot -asphalt -applications, Elastaflex G TU, Elastaflex SS 6 or Elastaflex S6 G FR shall be fUlly 2Sphalt-applied to the substrates noted in Section 5.6. Side laps shall be minimum 3-Inch and end -laps minimum 64nch wide„ off -set minimum 3 feet from course to course. Side and end laps shall be fully adhered In a complete mopping of hot asphalt with asphalt extending approximately 3/94nch beyond the lap edge. 6.6.2 Polydex G or Polyflex G FR shall be Installed in compliance with current Polyglass published Installation requirements. For use in tile applications: ✓ Polyflex G is for use as an alternate to the Heat Applied "Cap Sheet" In the "Two Ply System" from FRSA/TRI April 2022 (04-12) beneath mechanically fastened or adhered tile roof systems (Base Sheet Limited per 5.6.3). ✓ Polyflex G FR is for useas an alternate to the Heat Applied "Cap Sheet" In the 'Two Ply System" from FRSA/TRI April 2022 (04-22) beneath mechanically fastened the roof systems (Base Sheet Limited per 5.6.3). NEMO ETC, LLC. Evaluation Report P320a0MM-R24 Q:dUmf04(AOM0rMbn432M EDITION(2017) FBC NON44VN2 EVALUATION FILMS.= Polyglaa roof Underiaymmds; 19SQ 233-3T3o Revision 24:01/2412018 Page 13 of 14 i ONEMO[etc. 6.6.2 Polyflex 6 or Polyflex 6 FR shall be fully torch -applied to the substrates noted in Section 5.6. Side laps shall be minimum 34nch and end -laps minimum 6-Inch wide, off -set minimum 3 feet from course to course. Side and end laps shall be fully heat -welded and inspected to ensure minimum 3/8-Inch flow of modified compound beyond the lap edge. 6_7 TileStaeinw, 6.7.1 Tile shall be loaded and staged Ina manner that prevents tile slippage and/or damage to the underlayment. Refer to Table 2 herein, and Polyglass published requirements for tile staging. 6.7.2 Battens and/or Counter -battens, as required by the the manufacturer and FRSA/1RI April 2012 (04-12) must be used on all roof.slopes greater then 7:12. Precautions should be taken as needed, such as the use of battens or nail - boards, to prevent the sliding end/or damage to the underlayment during the loading process. 6.7.3 Poigiass specifies the minimum are time after Installation of self -adhering membranes and ,before loading of roofing tiles Is forty-eight (48) hours. 7. BUILDING PERMIT REQUIREMENTS: As required by the Building Offldal or Authority Having Jurisdiction in orderto properly evaluate the installation of this product. 8. MANUFALTURING PLANTS: Contact the noted CIA agency for information on product locations covered for FA.C. 616ZG-3 QA requirements. The following plants have qualified products under their respective physical properties specifications. WaM>..' .'• .:., [ , . ; :'••-.:;:.., • r.. S ec'ifieatrorrta.....�:`:� .., , G, :.' rd d s' Fernley, NV, Hazleton, PA & Winter Haven FL ASTM D1970 Polystick MU-X Hazleton, PA M-D 13.0DD4 Elastoflex G TU Hazleton, PA & Winter Haven, FL ASTM D1970 Polystick IR-Xe ASTM D1970 & FRSA/TRI April 2012 Poly4ckTU Plus ASTM D1970 & FRSA/rRl April 2012 PolystickTU Max Tuscaloosa, AL ASTM D4601, Type II Polvalass G2 Base winter Hawn, FL ASTM D226 (physicals) Elastobase, Elastobase P ASTM 05509 - Polvelass APP Base FRSA/TRI April 2012 Polystick MTS, Polystick MTS PLUS FRSA/rRIA d12012 Pol sbckTUP - FRSAJTRI A r112012 Polyflex SAP, Pa ex SAP FR ASTM 01970 Polystick Dual Pro ASTM D2970 & FRSA/rRl April 2012 Polvsdck'nle Pro ASTM OM64 Elastofex 56, Elastoflex S6 G FR ASTM D6222. Polyflex G Polyflex G FR 9. Quarry ASSURANCE ENTITY: UL, LLC—QUA9625; (314) 578-3406, kchancellor@us.ul.com - END ,OF EVALUATION REPORT - NEMO ETC, U.C. Evaluation Report P12060M,05-R24 Gartfmte dAuMarkaWn#32455 67"EDITION 12017) FSC NON-RVHZEVALUAnON FL52S9-R7E PolyGaw Roof Underlaymem , (954) 2334MO Revislan 24: 01/24/2018 Page 24 of 14