HomeMy WebLinkAboutEVALUATION REPORTSCANNED BY St. Lucie County ENGINEER EVALUATE TEST EVALUATION REPORT NEmo I etc. Ceraflcute ofAuthorization AU40 353 Christian Street,, Unit #13 OxFord, CT 06478 (203)262-9245 CONSULT CERTIFY Polyglass USA, Inc. Evaluation Report P12060.02.09-R24 1121 West Newport Center Drive FLS259-R28 Deerfield Beach, FL 33442 Date of Issuance: 02/24/2009 (954)233-1230 Revision 24:01/24/2018 SCOPE: This Evaluation Report is issued under Rule 61620-3 and the applicable rules and regulations governingthe,usel of construction materials In the State of Florida. The documentation submitted has been reviewed by Robert Nieminen, P.E. for use of the product •under the Florida Building Code and Florida Building Code, Residential' Volume. The products described herein have been evaluated for compliance with the a Edition (2017) Florida Building Code sections noted herein. DESCRIPTION: Polyglass Roof Underlayments LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted herein. CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the referenced Quality Assurance documentation changes, or provisions of the Code that relate to the product change. Acceptance of this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. of any changes to the product(s), the Quality Assurance or the production facility lodation(s). NEMOietc. requires a complete review of this Evaluation Report relative to updated Code requirements with each code Cycle. ADVERTISEMENT: The Evaluation Report number preceded by the words "NEMOietc. Evaluated" may be displayed in advertising literature. If any portion of the Evaluation Report is displayed, then It shall be done in its entirety. ' INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or its distributors and shall be available for Inspection at the job site at the request of the Building Official. This Evaluation Report consists of pages 1 through 14. Prepared hy: Robert J.M. hlleminen, P.E. A Florida Registration No. 59164 Florida DCA ANE2983 The facslmile seal appaaringwas authorized by Robert Nleminen, P.e. on o1/24/201e. This does notserve as an electronically signed document' CERTIRCATION OF INDEPENDENCE: 1. NEMOI etc does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or distributing products it evaluates. 2. NEMOI etc is not owned, operated or controlled by any company manufacturing or distributing products It evaluates. 3. Robert Nieminen, P.E. does not have nor will acquire, a financial Interest in any company manufacturing or distributing products for which the evaluation reports are being Issued. 4. Robert Nieminen, P.E. does not have, nor will acquire, a financial interest In any other entity involved in the approval process of the product. S. This is a building code evaluation. Neither NEMOIetc. nor Robert Nieminen, P.E. are, in anyway, the Designer of Recordfor any project on which this Evaluation Report, or previous versions thereof, Is/was used for permitting or design guidance unless retained specifically for that purpose. r-, ROOFING COMPONENT EVALUATION: 1. SCOPE: ONEMOletc. Product Category: Roofing Sub -Category: Underlayment Compliance Statement: Roof Underlayments, as produced by Polyglass USA, Inc., have demonstrated compliance with the following sections of the 6" Edition (2017) Florida Building Code through testing In accordance with the following Standards. Compliance Is subject to the Installation Requirements and Limitations/ Conditions of Use set forth herein. 2. STANDARDS: Section Prope Standard year 1504.3.1 Wind Uplift FM 4474 2011 1504.3.1 Wind Uplift UL 1897 2012 1507.2.3 / 1507.L1 Physical Properties ASTM D226 2009 1507.2.4/ 1507.3.1, 15U7.2.9.2 Physical Properties ASTM D1970 2015 1507.3.3 Physical Properties FRSA/TRI April 2022 2012 1507.11.2 Physical Properties ASTM D6164 2011 1507.11.2 Physical Properties ASTM D6222 2011 TAS 110 Accelerated Weathering ASTM D4798 2011 3. REFERENCES: Enter Examination Reference Date FM Approvals (TST 1867) Wind Uplift 3004091 01/12/2000 PRI (TST 5878) Physical Properties PRI01111 04/08/2002 PHI (TST 5878) Physical Properties PUSA-005-02-01 01/31/2002 PRI (TST 5878) Physical Properties PUSA-013.02-01 22/23/2002 PRI (TST 5878) Physical Properties PUSA-013-02-02 12/23/2002 PRI MT 5878) Physical Properties PUSA-013-02-D3 12/23/2002 PRI (('sT 5878) Physical Properties PUSA-018-02-01 07/14/2003 PRI(TST5978) Physical Properties PUSA-028-02-01 07/13/2005 PRI(fST5878) Physical Properties PUSA-033-02-01 01/12/2005 PRI (TST 5878) .Physical Properties PUSA-035-02-01 09/29/2006 PRI (TST SUB) Physical Properties PUSA-055-02-02 22/10/2007 PRI (TST 5878) Physical Properties PUSA 061-02-02 OW812009 PRI (TST 5878) Physical Properties PUSA-076.02-M 02/22/2D08 PRI (TST 5878) Physical Properties PUSA-083-02-01 04/14/2008 PRI (TST 5878) Physical Properties PUSA-D88-02-01 07/29/2009 MTI(TST 2508) Physical Properties 1X20H7A 04/01/2008 MTI(TST 2508) Physical Properties RXI4ESA 02/29/2009 ERD (TST 6049) Physical Properties 11752.09.99-1 02/08/2000 ERD (TST 6049) Wind Uplift 11757.08.01-1 08/23/2001 ERD (TST 6049) Wind Uplift 11776.06.02 01/25/2003 ERD CM 6049) Physical Properties 02200,07.03 07/14/2003 ERD (M600) Wind Uplift P1740.01.07 0l/04/2007 04/11/2007 ERD(TST 6049) Physical Properties P5110.04.07-1 03/21/2008 ERD (TST 6049) ERD (TST 6049) Wind Uplift Physical Properties P9260.03.08 .P13450.08.09 08/13/2009 ERD (TST 6049) Wind Uplift P30540.11.09-R1 12/30/2009 ERD (TST 6049) PhysicalProperties P11030.11:09.1 12/30/2009 ERD(TST 6049) Wind Uplift .P11030.11.09-2 11/30/2009 ERD (TST 6049) Physical Properties P33030.11.093 11/30/2009 ERD (TST 6049) Physical Properties P33360.06.10 06/25/2010 ERD (TST 6049) Physical Properties P33370.03.11 03/02/2011 ERD (TST 6049) Physical Properties P33370.04.11 04/26/2011 ERD (TST6049) Physical Properties P37300.10.11 10/19/2012 Report P1206002A9-1124 NEMO ETC, U.C.Evaluation Cvt&f afAuM4nm04n 432455: 6'r EDmON(2017) FBC NON-HVHZEVAWAMON Revision 24: 03�/24/208 Polygram Roof Undarlayments: (954) 233-1230 Page 2 of 14 r Entity ERD OW 6049) ERD W 6049) ERD (f5T 6049) ERD (TSr 6049) ERD (TSf 6049) ERD (TST 6049) ERD (TSr 6049) ERD (TSr 6049) ERD (TST 6049) ERD (TSr 6049) ERD (TST 6049) ERD M 6049) ERD (TST 6049) ERD CMT 6049) ERD (M 6049) ERD (TSr 6049) ERD (rST 6049) ERD (IST 6049) ERD (TST 6049) ERD (TST 6049) ERD (TST 6049) ERD (TSr 6049) ERD (TSr 6049) ERD (TST 6049) ERD (TST 6049) .ERD (TST 6049) ERD (W 6049) ERD (ISr 6049) ERD (TST 6049) ]CC -ES (EVIL 2396) Miami -Dade (CER 1592) Polygiass USA Polyglass USA Polyglass USA UL, U.C. (QUA9625) 4. PRODUCr DESCRIPTION: Examination Physical Properties Physical Properties Physlcal Properties Wind Uplift Physical Properties Wind Uplift Wind Uplift Wind Uplift Wind Uplift Wind Uplift Physlcal Properties Physlcal Properties Physical Properties Physical Properties Physical Properties Physical Properties Physical Properties Physical Properties Physical Properties Physical Properties Physical Properties Physical Properties Physical Properties Wind Uplift Physical Properties wind Uplift Physical Properties Physical Properties Physical Properties IBC Compliance HVHZ Compliance Manufacturing Affidavit PA Affidavit Materials Affidavit. Quality Control Reference P40390.08.12-1 P40390.08.12-2 C41420.09.12-3 P39680.03.13 P45370.04.13 P1738.02.07-R2 11757.04.01-1-R1 P41630.08.13 P1175L05.03-R1 113178L31.03-R3 P45270.05.14 6020.07.14-1 6020.09.24-2 6020.09.14-3 6020.09.14-4 6020.09.14-5 6020.09.14-6 P46520.10.14 P43290.10.14 PLYG-SC7550.03.15 P40390.04:15 P44360.10.14-R1 PLYG-SCS080.05.15-1 PLYG-SC8905.05.16-1 PLYG-SCS080.07.16 PLYG-SC12025.10.16 PLYGSC13040.12.16 PLYG-SC11900.03.17 PLYG-SC12115.08.17 ESR-1697 NOA 14.0717.08 Products Current Mule -Hide Cross I% PolyAck SA Compound Service Confirmation 4.f MechatdcelIV Fasteb'e'it0: derlaymel't.. V 4.2.1 Elastobase Is fiberglass reinforced, SBS modified bitumen base sheet. 4.12 Elastobase' P is a polyester -reinforced, SBS modified bitumen base sheet. 4.1.3 Polyglass 62 Base is a fiberglass -reinforced, asphaltic base sheet. 4.1.4 Polyglass APP Base is a fiberglass-relnforced, APP modified bitumen base sheet. ONEMOjetc. Date 08/06/2012 GBIU712012 09/12/2012 03/D4/2013 04/26/2013 04/29/2013 04/30/2013 08/06/2013 11/26/2023 11/26/2013 05/12/2014 09/08/2014 09/O8/2014 09/08/2014 09/08/2014 09/08/2014 09/08/2014 10/03/2014 10/17/2014 03/24/2019 04/03/2015 05/18/2015 05/20/2025 05/17/2016 07/16/2016 10/12/2016. - 12/27/2016 03/10/2017 08/08/2027 11/01/2014 01/22/2015 02/18/2009 03/01/2008 08/18/2011 Exp. 10/05/2018 4.2.1 Polystick MTS or Polystick MTS PLUS Is a nominal 60-mil thick rubberized asphalt waterproofing membrane, glass fiber reinforced, surfaced with polyolefinic film surface; meets FRSA/Ml April2012. 4.2.2 Polystick IR-Xe is a nominal 60-mil thick rubberized asphalt waterproofing membrane, glass fiber reinforced, with an aggregate surface; meets ASTM 131970. 4.2.3 Polystick TU Plus is a nominal 80-mil thick rubberized asphalt waterproofing membrane, glass fiber reinforced, with a polyester fabric surface; meets ASTM D1970 and FRSA/TRI April 2012. NEMO EM. LLr: Evaluation Report P32060.02.09-R24 O:rtlRcNe 0fAudvrbotlaa032455 e EDITION (2017) FBC NON-HVHZ EVALUATION Reuislan 24: 01FL=9-R28 8 Polyss giaRoof Underlaiiments; (954) 233-1230 Page 3 of 14 S. ONEMOJetc. 4.24 Polyetick TU P is a nominal 130-mil thick rubberized asphalt waterproofing membrane, glass-fiber/polyester reinforced, with a granular surface; meets FRSA/TRI April 2012. 4.25 Polystick TU Max is a nominal 60-mil thick rubberized asphalt waterproofing membrane with a 190 g/mz polyester fabric surface; meets ASTM D1970 and FRSA/TRI April 2012. 4.2.6 PolyflexSAP, Polyflex SAP FR, Mule -Ride SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR) are polyester. reinforced, APP modified bitumen sap sheets; meet FRSA/TRI April 2012. 4.23 Polystick Dual ProTM is a nominal 60-mil thick dual -layer rubberized asphalt waterproofing membrane, fiberglass reinforced, with a, polyester fabric surface; meets ASTM D3970. 4.2.8 Polystick Tile Prone Is a nominal 60-mil thick dual -layer rubberized asphalt waterproofing membrane, fiberglass reinforced, wlth a polyester fabric surface; meets ASTM D1970 and FRSA/rRI April 2012. 4.2.9 Polystick MU•X is a nominal 54-mil thick- dual -layer rubberized asphalt waterproofing membrane; fiberglass reinforced, with a polypropylene film surface; meets AC188 and physical requirements of ASTM D1970 (See Section 5.8). 4.3.1 Elastoflex G TU is a polyester reinforced, modified bitumen the underlayment composed of a sand -surfaced SEIS modified bitumen back -side and granule -surfaced APP modified bitumen top -side. Elastoflex G TU is for use as an alternate to "Mineral Surface Roll Roofing (ASTM D6380, Class M) in the "Single Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems or Hot Asphalt applied "Cap Sheet" in the'Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or adhered tile roof systems. i 4.3.2 Elastoflex S6 G and Elastoflex S6 G FR are polyester reinforced, SRS modified bitumen cep sheets; meetASTM D6164. Elastoflex S6 G and Elastoflex S6 G Fit are for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D6380, Class M) In the "Single Ply System" from FRSA/rRLApril 2012 (04-22) beneath mechanically fastened tile roof systems. Elastoflex S6 G is for use as an alternate to Hot Asphalt applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or adhered tile roof systems. Elastoflex S6 G FR Is for use as an alternate to Hot. Asphalt applied "Cap Sheet" In the 'Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems. 4.3.3 Polyflex G and Polyflex G FR are polyester reinforced, APP modified bitumen cap sheets; meet ASTM D6222. Polyflex G is for use as an alternate to Heat Applied "Cap Sheet" in the 'Two Ply System" from FRSA/TRI April 203.2 (04-12) beneath mechanically fastened or adhered tile roof systems. Polyflex G FR is for use as an alternate to Heat Applied "Cap Sheet" in the 'Two Ply System" from FRSA/TRI April 2022 (04-12) beneath mechanically fastened the roof systems. LIMITATIONS: 5.1 This is a building code evaluation. Neither NEMOI etc. nor Robert Nieminen, P.E. are, In any way, the Designer of Record for any project on which this Evaluation Report, or previous versions thereof, Is/was,used for,permitting or design guidance unless retained specifically for that purpose. 5.2 This Evaluation Report Is not for use in the HVHZ. 5.3 .Fire Classification Is not part of this Evaluation Report; to current Approved Roofing Materials Directory for fire ratings of this product. 5.4 Palyglass Roof Undedayments may be used with any prepared roof cover where the product Is specifically referenced within FBC approval documents. if not listed, a request may be made to the Authority Having Jurisdiction for approval based. on this evaluation combined with supporting data for the prepared roof covering.: NEMO ETC, LLC. Ewluatlon Report P12060.02.09-R24 GuUlmte UfAuftdcation 032M 6t"EDITION (2017) FOC NON•HVHZ EVMUATION mRevision ?A:0FL52599-R28 8 Palyglass Roof underlaymes; (954) 233-U30 ` Page 4 of 14 ONEMOjetc. 5.5 Allowable Roof Covers: Underlayment Asphalt shingles Nail -On Tile Foam -On Tile Meml Wood shakes 8,shingies Slate Elastoba5e Yes paseshest n�2-PNNsteml laasesheet n2-plywceml Yes Yes Yes ElastobaseP Yes Yes ( wSleemin2-plys ml Yes Iassesheetn2-ylysysteml Yes Yes Yes Polyglass G2 Base No Yes (Base shestm 2•pNslsrem) es IBasesheerinz-0ysysteml No No Na Polyglass Al? Base No Yes (Base Sheetln2•pry system) Yes IBazeShee[In 2-p1Y Mtem) No No No 'PolystickMTS.or PLUS Yes Yes No Yes Yes Yes Polystick lR-Xe Yes No No No Yes Yes Polystld(TU P No Yes Yes (See 5.5.11 No No No PolystickTU Plus Yes Yes Yes (see5.5.1) Yes Yes Yes PolysdckTU Max No Yes Yes(See5.5.1) Yes No No Polystick Dual Pro Yes No No Yes Yes Yes PolystickTllelera Yes Yes Yes (See 5.5.2) Yes Yes Yes Powck MU-X Yes No No Yes Yes Yes Elastaflex S6G Yes Yes Yes (see 5.5.1) No Yes Yes Elastaflex S6 G FR Yes Yes No No Yes Yes Elastaflex G TU Yes Yes Yes (see 5-9.11 No Yes Yes PalyflexG Yes Yes Yes (See 55.1) No Yes Yes PolyflexG FR Yes Yes No No Yes Yes PolyRex SAPorSAPFR Yes Yes Yes (See5.5.1) No Yes Yes Mule-Hlde SA-APP Cap Sheet or Cap Sheet (FR) Yes Yes Yes (See 55.1) No Yes Yes 5.5.1 "Foam -On Tile" is limited to use of the following Approved tile adhesives / underlayment combinations. .'.'. TAeis3IF.AuAWit)t�'ItLB AQYtFsi?iefUpoB@1AYIYlEN7.''.,'CQIy�BiN%LifbFls2s ;.. . Adhesive . Florida Product Underlayments Approval DAP Foam Touch'n Seal StormBond Roof FL14506 Polystick TU Plus, Polystick TU Max Tile Adhesive Dow TileBondn' FL22525 Polystick TU P, Poystick TU Plus, Polyflex SAP or Tile Pro Polystick TU P, Polystick TU Plus, PO"Ick TU Max, Polystick Tile Pro, ICP Adhesives Polysete AH-160 FL6332 Elastaflex G TU, Elastoflex S6 G, Polyflex G, Polyflex SAP, Polyflex SA Cap FR, _ Mule -Hide SA-APP Cap Sheet or Mule -Hide SA-APP Cap Sheet (FR) Polystick TU P, Polystick TU Plus, Polystick TU Max, Polystick Tile Pro, ICP Adhesives Polysets RTA 1 FL6276 Elastoflex G TU, Elastaflex S5 G, Polyflex G, Polyflex SAP, Polyflex SA Cap FR, Mule -Hide SA-APP Cap Sheet or Mule -Hide SA-APP Cap Sheet (FR) 2 Referto Tile Manufacturer's or Adhesive Manufacturer's Florida ProductApproval far Overturning Moment Resistance Performance NEMD ETC. LLC. Evaluation Report P32060.02.09-R24 Carapace pfAurhnmaaan 9324M S"EOmON(2017) FBCNON-HVHZ EVALUATION FL9259-HU Perlyglass Roof Underlaymerds: (954) 233-1230 Revislon 24:01124/2018 Page 5 of 14 > 5.6 Allowable Substrates: 5.6.1 Direct -Bond to Deck: Polystick (all variations), Dual Pro, Tile Pro, Polyflex SAP or SAP FR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) self -adhered to: D New untreated plywood; ASTM D41 primed new untreated plywood; Existing plywood; ASTM D41 primed existing plywood; New or existing, unprimed OSB; ASTM D41 primed OSB; Southern Yellow Pine; ASTM D41 primed Southern Yellow Pine; ASTM D41 primed structural concrete; Huber Engineered Woods "ZIP System" Panels (designed and installed to meet wind loads for project). Note: Polyglass does not require priming of new or existing plywood or OSB sheathing. New or existing plywood or OSB sheathing should be cleaned of all dirt and debris prior to application of Polystick membranes. Elastoflex G TU, Elastoflex S6 G or Elastoflex S6 G FR in hot asphalt to: D ASTM D41 primed structural concrete. Polyflex G or Polyflex G FR torch -applied to:. D ASTM D41 primed structural concrete. 5.6.2 Band -to -Insulation: Polystick (all variations), Polyflex SAP or SAP FR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) self -adhered to: D ASTM C1289, Type II, Class 1 polyisocyanurate or Type V polyisocyanurate-composite insulation; Dens Deck DuraGuard; Dens Deck Prime; or SECUROCK Gypsum -Fiber Roof Board. Elastoflex G TU, Elastoflex S6 G or ElastoflexS6 G FR in hot asphalt to: D Dens Deck Prime or SECUROCK Gypsum -Fiber Roof Board. Polyflex G or Polyflex G FR torch -applied to: D ASTM D41 primed structural concrete; Dens Deck Prime or SECUROCK Gypsum -Fiber Roof Board. For installation under mechanically attached prepared roof coverings, Insulation shall be attached per minimum requirements of the prepared roof covering manufacturer's Product Approval. For installations under foam -on tile systems, Insulation attachment shall be designed by a qualified design professional and installed based on testing of the Insulation/underlayment system In accordance with FBC Section 1504.3.1. 5.6.3 Bond to Mechanically Attached Base Laver: Polystick (all variations), Polyflex SAP or SAP FR, Mule -Hide SA-APP-Cap Sheet or SA-APP Cap Sheet (FR) Dual Pro or Tile Pro self -adhered to: ➢ ASTM D226, Type I or II felt; Elastobase; Elastobase P or Mule -Hide Nail Base. Elastoflex G TU, Elastoflex 56 G or Elastoflex S6 G FR In hot asphaltto: D ASTM 0226, Type I or II felt; Elastobase; Elastobase P, Mule -Hide Nail Base or Polyglass G2 Base. Polyfex G or Polyflex G FR torch -applied to: D Elastobase; Elastobase P, Mule -Hide Nail Base, Polyglass G2 Base or Polyglass APP Base. For installations under mechanically attached prepared roof coverings, base layer shall be attached per minimum codified requirements. For installations under foam -on the systems, base layer shall be attached per minimum requirements of FRSA/TRI April 2012 (04-12), Appendix A, Table 1, or as listed in Section 5.6.4 herein, or as tested in accordance with FBC Section 1504.3.2. NEMO ETC U.C. Evaluation Report P32060.02.09-R24 rertflax44fAuth4rhotbna32455 eEDITION 12017) FBCNON-HVHZ EVAWAMON FLSZ59-RZB Polyglass Roof Underlaymernsl (9541233-2230 flevislon 24: 01/24/2018 Page 6 of 24 ONEMOletc. 5.6.4 Wind Resistance for Underlayment Systems in Foam -On Tile Aoollrations: FRSA/TRI April 2012 (04-22) does not address wind uplift resistance of all underlayment systems beneath foam -on tile systems, where the underlayment forms part of the load -path. The following wind uplift limitations apply to underlayment systems that are not addressed In FRSA/rRI April 2012 (04-12) and are used in foam -on the applications. Maximum Design Pressure is the result of testing for wind load resistance based on allowable wind loads, and reflects the ultimate passing pressure divided by 2 (the 2 to 1 margin of safety per FBC 1504.9 has already been applied). Refer to FRSA/TRI April 2012 (04- 12), Appendix A, Table lA or FBC 1609 for determination of design wind loads. #1 Maximum Design Pressure = -90 It Deck: Min.15/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Primer. None Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered. Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (Fit), self -adhered. #2, Maximum Design Pressure =-97.5 psf: Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Primer: P6100 or AStM D41 Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered. Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (Fit), self -adhered and back -nailed within the selvedge -edge side laps using 12 ga. x IN' ring shank nails through 32 ga.,1-5/8' diameter tin caps spaced 124nch o.c #3 Maximum Design Pressure=.105 osF. Deck: Min.15/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Primer: WB-3000 Base Ply: (Optional) Polystick NITS or Polystick MTS PLUS, self -adhered. Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR. Mule -Hide SA-APP Cap Sheet and Mule�Hide SA-APP Cap Sheet (FR), self -adhered and back -nailed within the selvedge -edge side laps using 12 ga. x 1'h' ring shank nails through 32 ga.,1-5/a' diametertin caps spaced 12-Inch o.c. #4 Maximum Design Pressure =-135 psf: Deck: Min, 35/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Primer. (Optional) PG300 or ASTM D42 Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered. Joints: Min. flinch wide strips of Elastoflex SMV over all plywood joints. Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), selfadhered. #5 Maximum Design Pressure = 315 psf: Deck: Structural concrete to meet project requirements to satisfaction of Authority HavingJurisdiction. Primer: PG100 orASTM D41 Base Ply: , (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered. Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Tile Pro, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (Fit), selfadhered. 96 Maximum Design Pressure=.622.5 osf: Deck: Structuralconcrete to meet project requirements to satisfaction of Authority Having Jurisdiction. Primer. PG100or ASTM D41 Undedaymem: Elastoflex G TU or Elastollex S6 G, applied in full mopping of hot asphalt or Polyflex G, torchapplied., #7 Maximum Design Pressure =-30.0 psf Deck: Min.15/32-inch OSB to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase or Mule -Hide Nall Base (poly -film top surface) Fasteners: 11 Be. x 2125-inch long x 1-inch head diameter round metal cap nails Spacing: 6-Inch o.c. at the 3-Inch wide side laps and 64nch o.c, at two (2) equally spaced staggered center rows. Base Ply: (Optional) Polystick NITS or Polystick MTS PLUS, self -adhered. Underlayment: Polystick TU P, Polystick TUPlus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered. NEMO ETC, U.C. Ewlvation Report P12060.02.09-R24 rertytmm oJAudmdz nn B32455 6'sEDITION(2017)FBC N0N-HVH2 EVALUATION FLUS.4428 Puiyglass Roof Undurlaymentsi (9541233-1230 Recision 24: OW412018 .Page 7 of 14 �#8 Maximum Design Pressure =-37.5 psf•: NNEMO etc. Deck: MIn.35/32-Inch plywood to meet project requirements to satisfaction of Authority Havingiurlsdlction. Base Sheet. Elastobase or Mule -Hide Nail Base (poly -film top surface) Fasteners: 11 ga, x 1.25-inch long x 1-inch head diameter round metal cap nails Spacing: 6-inch o.c at the 3-Inch wide side laps and &-inch o.c. at two (2) equally spaced staggered center rows. Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered. Underlayment: Polystick TU P, Polystick TU Plus; Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered. _ #9 Maximum Design Pressure =-37.5psf": Deck: Min.19/32-Inch plywood to meet project requirements to satisfaction of Authority Having.lurlsdiction. Base Sheet: One (1) or two (2) layers ASTM D226, Type II felt Fasteners: 11 ga. x 1.25-inch long x 1-Inch head diameter round metal cep nails Spacing: 64nch o.c at the 3-Inch wide side laps and 12-Inch o.c. at two (2) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt #10 Maximum Design Pressure --45 nsf•; Deck: Min.19/32-Inch plywood to meet project requirements to satisfaction of Authority Having.lurisdiction. Base.Sheet: One (1) layer ASTM 0226, Type II felt Fasteners: 11 ga. x 1.25-Inch x 3/8-Inch head diameter annular ring shank roofing nails at 2-5/8-Inch diameter tin caps Spacing: 44nch mm at the 2-Inch wide side laps and 4-Inch a.e at two (2) equally spaced staggered center rows. Base Ply: (Optional; for use with selfadhedng underlaymem only) Polystick MTS or Polystick MTS PLUS, self -adhered. Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Poh/flex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered or Elastoflex G TU, applied in full mopping of hot asphalt #11 Maximum Design Pressure =-45 psf•: Deck: Min.19/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction, . Base Sheet: Two (2) layers ASTM D226, Type II felt Fasteners: 11 go. x1.25-Inch longx 3/8 inch head diameter annular ring shank roofing nails at 1-5/8-Inch diametertincaps Spacing: 9-Inch a.c at the 2-Inch wide side laps and 94nch o.c. at two (2) equally spaced staggered center rows. Base Ply: (Optional; for use with selfadhering underlayment only) Polystick MTS or Polystick MTS PLUS, self -adhered. Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyliex SAP, Palyfiex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered or Elastoflm G TU or Elastoflex S6 G, applied in full mapping of hot asphalt #12 Maximum Design Pressure=-45 Deck: MIn.15/32-Inch plywood to meet project requirements to satisfaction of Authority Hawngiurisdlction, Base Sheet: Elastobase (sanded top surface for hotasphalt or torch -applied cap or poly -film surface for torch -applied cap) Fasteners: Simplex MAXX Cap Fasteners Spacing: 9-Inch o.c. at the 24nch wide side laps and 184nch o.c. at two (2) equally spaced staggered center rows. Underlayment Elastaflex G TU or Elastoflex S6 G, applied In full mopping of hot asphalt or Polyff" G, torchapplled. #13 MaxlmurnMeslgnPressure=-52.5psf. Deck: Min.15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cep or polµfilm surface for torchapplied cap) Fasteners: Simplex MAXX Cap Fasteners Spacing: 9-inch o.c. at the 2-Inch wide side laps and 12-Inch o.c. at two (2) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoll" S6 G, applied in full mopping of hot asphalt or Polyflex G, torchapplied. #14 Maximum Design Pressure=-52.5a Deck: MIn.15/32-Inch plywood to meet project requirementsto satisfaction of Authority. Havinglurisdiction. Base Sheet: Elastobase or Mule -Hide Nail Base (poly -film top surface) Fasteners: Simplex Original Cap Nails Spacing: &Inch o.c at the 3-inch wide side laps and 64nch o.c at four (4) equally spaced staggered center rows. Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered. Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered. NEMO ETC, LLC. Evaluation Report P12060.02A9-1124 Cer0arte afAUMadmtian#32455 6t"EDITION RU71 FBC NON-HVHZ EVAWATION F1.5159-1128 Palyeass Roof Undedayments; (954) 233-1230 Revision 24: 01/24/2018 Page 8 of 14 ONEMOJetc. #15 Maximum Design Pressure =-52.5 psf: Deck: Min.15/32-Inch plywood to meet project requirements to satisfacton afAuthorlty Havinglunsdiction. Base Sheet.. Elastobase(sanded top surface for hot -asphalt or torchapplied cap or poly -film surface for torch -applied cap) Fasteners: Simplex Original Cap. Nails Spacing: 6-Inch o.c at the 3-Inch wide side laps and 6-Inch o.c. at four (4) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied. #16 Maximum Design Pressure =-60 psi; Deck: Min.19/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase (sa nded top surface for hot -asphalt ortorchapplied cap or poly -film surface for torch -applied cap) Fasteners: 11 ga. x 125-Inch long x 3/84nch head diameter annular ring shank roofing nails at 1-5/8-Inch diametertin caps Spacing: 8-Inch o.c. at the flinch wide side laps and 8-Inch c.c. at three (3) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S5 G, applied In full mopping of hot asphalt or Polyflex G, torch -applied. #17 Maximum Design Pressure =-60 psi: Deck: Min.19/32-inch plywood to meet project requirements to satisfaction of Authority Havinglurisdiction. Base Sheet: Elastobase(sandedtopsurfaceforhatasphaltortorchappliedcaporpoly-film surface for torchappiledcap) Fasteners: OMG#12 Standard R00%dp with OMG Flat Bottom Metal Plates Spacing: 12-Inch o.c. at the 4-Inch wide side laps and 12-Inch o.c. at two (2) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied. #28 Maximum Design Pressure =-67.5 psi: Deck: Min.15/324nch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Polyglass G2 Base or Polyglass APP Base (requires use of torch -applied undedayment) Fasteners: 12 ga. x 12S-Inch long x 3/8-inch head diameter annular ring shank roofing nails at 1-5/8-11nch diameter tin caps Spacing: f-Inch o.e at the 4-Inch wide side laps and 94nch o.c at four (4) equal IV spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G, applied In full mapping of hot asphalt or torch -applied or Polyflex G, torch - applied. #19 Maximum Design Pressure=-7512 Deck; Min, 15/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Polyglass G2 Base or Polyglass APP Base (requires use of torch -applied underlayment) Fasteners: Dekfast #14 with Dekfast Hex plates, OMG #14 HD with OMG r Galvalume Steel Plates, OMG Roofgrip #14 with OMG Flat Bottom Plates (ACcuTrac), Trufast HD with Trufast 3-Inch Insulation Plates or Simplex MAXX Cap Fasteners Spacing: 10-Inch o.c. atthe 4-Inch wide side laps and 104mch a.c at three (3) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex 56 G, applied In full mopping of hot asphalt or torch -applied or Polyflex G, torch - applied. #20 MaximumDesign Pressure =-90osfi Deck: Min.15/32-inch plywood to meet projectrequiremems to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase(sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap) Fasteners: Simplex MAXX Cap Fasteners Spacing: 64nch o.c. at the 2-Inch wide side laps and 6-inch o.c. at two (2) equally spaced staggered center rows. Underlayment: Elastaflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied. #21 Maximum Design Pressure =-90 psi: Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase(sanded top surface for hotasphalt or torch -applied cap or poly -film surface for torch -applied cap) Fasteners: CMG #12 Standard Rcofgrlp or OMG #14 Heavy Duty with OMG 3" Round Metal Plates or OMG Flat Bottom Metal Plates Spacing: &:•inch o.c at the 4-inch wide side laps and 6-Inch o.c at three (3) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 6,.applied in full mopping of hot asphalt or Polyflex G, torch -applied. #22 Maximum Design Pressure=-90 psf. Deck: Min.15/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase (sanded top surface) Fasteners: Trufast#12 DP or Trubst#14 HD with Trufast 30 Metal Insulation Plates Spacing: 54nch o.c at the 4-inch wide side laps and 6-Inch o.c at three (3) equal ly spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt NEMO EM LLC. Evaluation Report P12060.02.09404 rera(rcate PlAxderhadona324sa 61e EDITION(2017) FBC N0N4WH2 EVAWAMON FLVS9.gyg Polyglass Roof Undedaymentst (954) 233-1230 Revision 24:01/24/2018 Page 9 of 14 ONEMoletc. #23 Maximum Design Pressure=-90 Dsfi Deck: Min. 15/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Polyglass GZ Base or Polyglass APP Base (requires use of torch -applied underlayment) Fasteners: Dekfast #14 with Dekfast Hex plates, OMG #14 HD with OMG 3" Galvalume Steel Plates, OMG Roofgrip #14 with OMG Flat Bottom Plates (AccuTrac), Tnjfast HD with Trufast 34nch. Insulation Plates or Simplex MAXX Cap Fasteners spacing: 9-Inch o.c, at the 4-Inch wide side laps and 94nch o.c. at four (4) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G, applied In full mopping of hot asphalt or torch -applied or Polyflex G, torch - applied. #24 Maximum Design Pressure = -97.5 is Deck: Min. 19/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastabase or Mule -Hide Nail Base (poly -film top surface) Fasteners: 11 ga. x 1.25•Inch x 3/8-Inch head diameter annular ring shank roofing nails at 1-5/8-Inch diametertincaps Spacing: 4-Inch o.c at the flinch wide side laps and flinch c.c. at four (4) equally spaced staggered center rows. Base Ply: (Optional)Polystick MTS or Polystick MTS PLUS, self -adhered. Underlayment: Palystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap. Sheet and Mule -Hide SA-APP Cap Sheet (FR), seff-adhered. #25 Maximum Design Pressure=-105 osf: Deck: Min.25/32-Inch plywood to meet project requirements to satisfaction of Authority Havinglurisciction. Base Sheet: Elastobase(sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cep) Fasteners: Simplex MAXX Cap Fasteners Spacing: 6-Inch o.c at the 2-Inch wide side laps and 64nch o.c. at three (3) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied. #26 Maximum Design Pressure =-112.5 is ' Deck: Min. 19/32-Inch plywood to meet project requirements to satisfaction of Authority Havinglurlsdiction. Base Sheet: Elastobase or Mule -Hide Nail ease (poly -film top surface) Fasteners: 11 ga. x 1.25-inch x 3/8-inch head diameter annular ring shank roofing nails at 1-5/8-Inch diameter tin caps Spacing: 6-Inch o.c at the 4-Inch wide side laps and 6-Inch o.c. at four (4) equally spaced staggered center rows. Primer: PG200 or ASTM D42 primer at all tin -caps Base Ply: Polystick MTS or Polystick MTS PLUS, selfadhered Underloyment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered. #27 Maximum Design Pressure=-220ttsf: Deck: Min.15/32-Inch plywood to meet project requirements to satisfaction of Authority Havingiurisdiction. Base Sheet: Elastobase(sanded top surface for hot -asphalt or torch -applied cap or poly -film surface fortorch-applied cap) Fasteners: OMG #12 Standard Roafgrip or OMG #14 Heavy Duty with OMG 3" Round Metal Plates or OMG Flat Bottom Metal Plates Spacing: 6-Inch o.c, at the flinch wide side laps and 6-inch o.c at five (5) equally spaced staggered center rows, Underlayment: Elastoflex G TU or Elastoflex 56 G, applied In full mopping of hot asphalt or Polyflex G, torchapplied. #28 Maximum Design Pressure=-120 osf•. Deck: Min.15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase (sanded top surface) Fasteners: Trofast#12 DP or TTufast#24 HD with Trufast 3" Metal Insulation Plates Spacing. 6-inch o.c. at the flinch wide side laps and 6-inch o.c at five (5) equally spaced staggered center rows.. Underlayment'. Elastoflex 6 TU orElastoflex S6 G, applied In full mopping of. hot asphalt. 5.6.4.1 All other direct -deck, adhered Polyglass underlayment systems beneath foam -an the systems carry a Maximum Design Pressure of-45 psf. NEMO ETC, LLC. Evaluation Report PI2A60.02A9-R24 raefkateafAuOmr&adan 03ZUS 6�EDITION(2017) FRC NON4MZ EVALUATION F15259-R28 Polyglass Roof Underiayments; (9541233-ILM Revision 24: 01%14/2018 Page 10 of 24 ONEM010C. 5.6.4.2 For mechanically attached Base Sheet, the maximum design pressure for the selected assembly shall meet or exceed that required under FRSA/TRI April 2022 (04-12), Appendix A, Table 1A. Altematively; the maximum design pressure for the selected assembly shall meet or exceed the Zane 1 design. pressure determined In accordance with FBC 1609. In this case, Zones 2 and 3 shall employ an attachment density designed by a qualified design professional to resist the elevated pressure criteria.. Commonly used methods are ANSI/SPRI WDl, FM Loss Prevention Data Sheet 1-29 and Roofing Application Standard RAS 117. Assemblies marked with an asterisk* carry the limitations set forth in Section 2.2.20.1 of FM Loss Prevention Data Sheet 1-29 (January 2016) for Zane 2/3 enhancements. 5.7 Exposure Limitations: Elastobase, Elastoba_se P, Polyglass G2 Base or Polygiass APP Base shall not be left exposed for longer than 30-days after installation. Polystick IR-Xe or Polystick MU-X shall not be left exposed for longer than 90-days after installation. Polystick MTS, MTS PLUS, TU P, TU Plus, TU Max, Dual Pro, Tile Pro or Elastoflex G TU shall not be left exposed for longerthan 180-days after installation. Polyflex SAP or SAP FR, or Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) does not have an exposure limitation, unless the prepared roof covering Is to be adhesive -set tile, in which case the maximum exposure Is 30 days. Elastoflex S6 G or Elastoflex S6 G FR or Polyflex G or. Polyflex,G FR does not have an exposure limitation, unless the prepared roof covering Is to be adhesive -set tile (Elastaflex S6 G or Polyflex G only), in which case the maximum exposure is 180 days. 5.8 Polystick MU-X has been found through comparative testing to have.a lesser coefficient of friction than ASTM D226 roofing felt in a dry condition, tested at standard laboratory conditions. Agreement between purchaser and seller, as setforth In Section 4.3, Note 1 ofASTM D1970-15, should be established as to slip resistance. 5.9 Tile Slippage Limitations (FRSA/TRI April 2012 (04-12% When loading roof tiles on the underlayment in direct -deck the assemblies, the maximum roof slope shall be as follows. These slope limitations can only be exceeded by using battens during loading of the roof tiles. ' ,.' :;.yi:+�. .-; .;TABS'Z::TILE.SLIPPAGk;LMRA`fIGNSEOi<;WRNS'Gi-DE.EIC;nIb`JKI��jtf�ilON9,. •,i.,.":i.. '. . Undedayment rile Profile Staging Method Maximum Slope Elastaflex G TU Flat 10-tile stack 7:12 _ Lagged Mile stack (6 over 2) 6:12 ElastoflexS5 G or S6 G FR Flat or Lugged 6-tile stack (4 over 2) 4.12 " Polystick MTS or MTS PLUS Flat 6-tile stack (4 over 2) 5:12 Lugged 6-tile stack (4 Over 2) 4:12 PolystickTlle Pro Flat or Lugged &tile stack (4 over 2) 7:12 Polystick TU Max .Flat 6-tile stack (4 over 2) or 10-tile stack 7:12 Lugged &flestack(4over2) 7:12 Lugged 10-tile stack 6:22 Polystick TUP Flat &tile stack (4 over 2) 6:12 Lugged 6-tile stack (4 over 2) 4:12 PolystickTU Plus Flat or Lugged 6-tile stack (4 over 2) 7:12 - Flat or Lugged 10•tile stack 6:12 Polyflex G or G FR Flat or Lugged 6-tile stack (4 over 2) 4:12 Polyflax SA P or SA P FR Flat or Lugged I 6-tile stack (4 over 2) 1 4:12 NEMO ETC, Luc. Evaluation Report P32060.02.09-R24 CEraYmte MfAomMOM0 v124Z 6TM EDITION (2017)FBC NON-HVH2 EVALUATION FL5259-08 Polygiass Roof Underlayments; 1954) 233-1280 Wslon 24:01/24/2018 Page 11 of 14 ONEN[Ojetc. 6. INSTALLATION: 6.1 Polyglass Roof Underlayments shall be installed in accordance with Polyglass published installation requirements subject to the Limitations set forth in Section 5 herein and the specifics noted below. 6.2 Re -fasten any loose decking panels, and check for protruding nail heads. Sweep the substrate thoroughlyto remove any dust and debris prior to application, and prime the substrate (if applicable). 6 3 . Elastobase Elan o aseTgc Mu)e j de.Na)f 6.3.1 Non -Tile Annilcations* Shall be Installed in compliance with the codified requirements for ASTM D226, Type it underlayment in FBC Table 2507.1.1 for the type of prepared roof covering to be installed. Elastohas% Elastobase P or Mule -Hide Nail Base may be covered with a layer of Polysticlr, Polyflex SAP, Polyflex SA P FR,, Mule -Hide SA-APP Cap Sheen or SA-APP Cap Sheet (FR), self -adhered, Elastoflex 6 TU, Elastoflex S6 G or Elastoflex 56 6 FR in hot asphalt or Polyflex 6 or Polyflex 6 FR, torch applied. Roof cover limitations are those are those associated with the top -layer underlayment, asset forth in Table 1, 6.3.2 Tile Applications: Elastobase, Elastobase P or Mule -Hide Nail Base are limited to use as a mechanically attached base sheet in the "Two Ply System" from FR5A/TRI April 2012 (04-12). Reference is made to Table 1 and Section 5.6.4 herein, coupled with FRSA/TRI April 2012 (04-12) Installation: Manual. 6.4: Polystigkl)flT5,p4TS.PW8,1.*;,TUPrTU."PI4rTi(MaxiDualPrb�Til;O;prgarfJIHZ(.otPolyRekSAP,P4il��t8l4PFlt,; • MuledfideSA.APRFap'$Ite tbr:MuleTill" A•APR pShBef' 6.4.1 Shall be installed in compliance with the codified requirements for ASTM D1970 (except PolystickTU P) underlayment. 6A.2 In FBC Table 1507.1.1 for the type of prepared roof covering to be installed. Direct -to -Deck with Mechanically Fastened Roof Covers: All self -adhering materials, with the exception of Polystick TU Plus, Polyflex SAP or SAP FR and Mule-H(de SA-APP Cap Sheet or SA-APP Cap Sheet (FR) should be back -nailed in selvage edge seam in accordance with Polyglass / Mule - Hide back nailing guidelines. Nails shall be corrosion resistant, 11 gauge ring -shank type with a minimum 1-Inch diameter metal disk or Simplex -type metal cap nail, at a minimum rate of 12" o.c. Polystick TU Plus should be back - nailed using the above noted fasteners and spacing, In area marked "nail area, area pare clever' on the face of membrane. The head lap membrane is to cover the area being back -nailed. All seai-lap seams (selvage laps) must be firmly rolled with a minimum 28 lb. hand roller to ensure full contact and adhesion. For Dual Pro and Tile Pro, align the edgeof the top sheet to the end of the glue pattern (the sheet will overlap the fabric). ja viewaf Dvelap Seam of Dual Pro and 711e Pm All over -fabric and over -granule end -laps shall have a 6-inch wide, uniform layer of Polyplus 50 Premium Modified Wet/Dry Cement or Polyglass PGSOo Modified Cement applied In between the application of the lap. Polystick TU Plus, Dual Pro and Tile Pro may not be used in any exposed application such as crickets, exposed valleys, or exposed roof to wall details NEMO Etc, U.C. Evaluatlon Report P32050.02.09-RZ4 affijkaeof4uthor&aUaao324W G"' EDMON(2p17) FBC NO"VMZEVALUATION P1.525931128 Polyglass Roof Unearlayments; (954) 233-1230 Revision 24: 01/20MB Page 12 of 14 r�. ONEIVIOjeft. Repair of Polystick membranes is to be accomplished by applying Polpplus 50 Premium Modified Wet/Dry Cement or Polyglass PGS00 Modified Cement to the area in need of repair, followed by a minimum 6 x 6 inch patch of the Polystick material of like kind, set and hand rolled In place over the repair area. Patch laps, if needed, shall be Installed in a water shedding manner. All Polystick membranes shall be installed to ensure full contact with approved substrates. Polyglass requires a minimum of 40-lb weighted -roller or, on steep slopes, use of a stiff broom with approximately 404bs of load applied for the field membrane. Hand rallers are acceptable for rolling of patches, laps (min. 28lb roller) or small areas of the roof that are not accessible to a large roller or broom. 6.4.3 Tile Applications (not allowed for Polystick Oual P% IR Xe orPolotick MUO: Reference is made to FRSA%TRI April 2012 (04-12) Installation Manual and Table 1 herein, using the instructions noted above as a guideline. For mechanically fastened tile roofing over 2-ply system, consisting of Base Sheet and self -adhering top sheet(s), Base Sheet fastening shall be not less than FRSA/TRI April 2012 (04-12), Table i For adhesive -set file applications, refer to Section 5.5A herein. 6.4.4 Two (21 Ply Underlayment Systems: - Polystick MTS or MTS PLUS followed by Polystick MTS, MTS PLUS, TU P, TU Plus, TU Max, Tile Pro, MU-X or Polyflax SAP is allowable for use under mechanically attached prepared roof systems. Limits of use are those associated with thetop-layer material. This is not a requirement, but is allowable if a 2-ply underlayment system is desired.. Polystick MTS or MTS PLUS followed by Polystick TU P, TU Plus, TU Max, Tile Pro or Polyflex SAP is allowable for use under foam -on tile systems. Umlts of use are those associated with the top -layer material. This is not arequirement, but Is allowable if a 2-olv underlavment system is desired. 6.5.1 Elastaflax G TU, Elastoflex S6,6 or Elastaflex S6 6 FR shall be installed in compliance with current Polyglass published Installation requirements. For use In tile applications: ✓ Elastaflex 6 TU is for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D6380, Class M) in. the "Single Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems or the Hot Asphalt applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI April 2012 (04-22) beneath mechanically fastened or adhered tile roof systems. ✓ Elastoflex S6 6 Is for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D6380, Class M) In the "Single Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems or the Hot Asphalt applied "Cap Sheet" in the 'Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or adhered tile roof systems. ✓ Elastoflex S6 6 FR is for use as an alternate to "Mineral Surface Roll Roofing" (ASTM 06380, Class M) in the "Single Ply System" from FRSA/TRI April 2012 (04-22) beneath mechanically fastened tile roof systems or the Hot Asphalt applied "Cap Sheet' in the "Two Ply System" from FRSA/TRI April 2022 (04-22) beneath mechanically fastened tile roof systems. 6.5.2 For hot -asphalt -applications, Elastoflex G TU, Elastoflex S6 6 or ElastofiexS6 G FR shall be fully asphalt -applied to the substratesnoted In Section 5.6. Side laps shall be minimum 3-Inch and end -laps minimum 6-Inch wide, offset minimum 3 feet from course to course. Side and end laps shall be fully adhered in a complete mopping of hot asphalt with. asphalt extending approximately 3/84nch beyond the lap edge. 6.6.1 Polyflex G or PoWex 6 FR shall be Installed in compliance with current Polyglass published Installation requirements. For use In tile applications: ✓ Polyflex G is for use as an alternate to the Heat Applied "Cap Sheet" in the 'Two Ply System" from FRSA/TIO April 2012 (04-12) beneath mechanically fastened or adhered tile roof systems (Base Sheet Limited per 5.6.3). ✓ Polyflex G FR is for use as an alternate to the Heat Applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI April 2022 (04-12) beneath mechanically fastened the roof systems (Base Sheet Limited per 5.6:3). NEMO Or, U.C. Evaluation Report P22060.02M.R24 CeRUhvte 4JAlOar Wxe2455 6r"EDmON(Z017)FBC NON-HVHZ EVALUATION FL5289-R28 poly&= Roof Underlayments; (964) 233-123D Revision 24: 01/24/2018 Page 13 of 14 ONEMOJeft. 6.6.2 Polyflex G or Polyflex 6 FR shall be fully torch -applied to the substrates noted in Section 5.6. Side laps shall be minimum 34nch and end -laps minimum 64nch wide, off -set minimum 3 feet from course to course. Side and end laps shall be fully heat -welded and inspected to ensure minimum 3/8-Inch flow of modified compound beyond the lap edge. 6_7 Tile Steel= 6.7.1 Tile shall be loaded and staged in a manner that prevents the slippage and/or damage to the underlayment Refer to Tablet herein, and Polyglass published requirements for tile staging. . 6.7.2 Battens and/or Counter -battens, as required by the tile manufacturer and FRSA/TRI April 2012 (04-12) must be used on all roof slopes greater than 7:12. Precautions should be taken as needed, such as the use of battens or sail- boards, to prevent tle sliding and/or damage to the underlayment during the loading process. 6.7.3 Polyglass specifies the minimum cure time after installation of self -adhering membranes and before loading of roofing tiles is forty-eight (48) hours. 7. BUILDING PERmrr REQUIREMENT& As required by the Building Official or Authority Having Jurisdiction in orderto properly evaluate the Installation of this product. S. MANUFACruinmG PLANTS: 9. Contact the noted CIA agency for information on product locations covered for F.A.C. 61620-3 QA requirements. The following plants have qualified products under their respective physical properties specifications. :PfaM�.;'. .�. •' .;•�'. .,.'.., �S e'ctfi Femley, NV, Hazleton, PA & Winter Haven, FL ASTM D1970 Pol stick MU-X Hazleton, PA M-D 13-0004 Elastoflex G TU Hazleton, PA & Winter Haven, FL ASTM D2970 Polystick lR-Xe ASTM D2970 & FRSA/TRI April 2012 Pol stick TU Plus ASTM D1970 & FRSA/TRI April 2012 Poiystick TU Max Tuscaloosa, AL ASTM D4601, Type If Poiyglass G2 Base Winter Haven, FL ASTM D226 (P IcAs) Elastobase, Elastobase P ASTM D6509 Polvnlass APP Base FRSA/TRI April 2012 Pal ck MTS, Poll ck MTS PLUS FRSA/TRI April 2012 PolVsnck TU P FRSA/Tltl April 2012 Polyflex SAP, Poi ex SA P FR ASTM D1970 Polystick Dual Pro ASTM D2970 & FRSA/TRI April 2012 PDlystick Tile Pro ASTM D6164 Elastollex S6, Elastoflex S6 G FR ASTMD6222. Polyflex G,.Polyflex 6 FR QUALITY ASSURANcE ENTITY: UL, LLC—QUA9625; (314)'578-3406; k.chancellor@us,ul.com -END OF EVALUATION REPORT- NEMO M U.C. CertftW fAuNoraation N3265 firs EDITION(2617)FBCNON-HVHZEVALUAT10N Potyglass Roof Underlaymer=; (954) 7d3,12•TO Evaluation Report P32060.02A9-R24 FL5254-R7B Revislan 24: 01/24/2018 Page 114 of 14