EVALUATION REPORT
NEmo I etc.
Ceraflcute ofAuthorization AU40
353 Christian Street,, Unit #13
OxFord, CT 06478
(203)262-9245
CONSULT CERTIFY
Polyglass USA, Inc. Evaluation Report P12060.02.09-R24
1121 West Newport Center Drive FLS259-R28
Deerfield Beach, FL 33442 Date of Issuance: 02/24/2009
(954)233-1230 Revision 24:01/24/2018
SCOPE:
This Evaluation Report is issued under Rule 61620-3 and the applicable rules and regulations governingthe,usel of
construction materials In the State of Florida. The documentation submitted has been reviewed by Robert Nieminen, P.E.
for use of the product •under the Florida Building Code and Florida Building Code, Residential' Volume. The products
described herein have been evaluated for compliance with the a Edition (2017) Florida Building Code sections noted
herein.
DESCRIPTION: Polyglass Roof Underlayments
LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted herein.
CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the referenced
Quality Assurance documentation changes, or provisions of the Code that relate to the product change. Acceptance of this
Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. of any changes to the
product(s), the Quality Assurance or the production facility lodation(s). NEMOietc. requires a complete review of this
Evaluation Report relative to updated Code requirements with each code Cycle.
ADVERTISEMENT: The Evaluation Report number preceded by the words "NEMOietc. Evaluated" may be displayed in
advertising literature. If any portion of the Evaluation Report is displayed, then It shall be done in its entirety. '
INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or its
distributors and shall be available for Inspection at the job site at the request of the Building Official.
This Evaluation Report consists of pages 1 through 14.
Prepared hy:
Robert J.M. hlleminen, P.E.
A
Florida Registration No. 59164 Florida DCA ANE2983
The facslmile seal appaaringwas authorized by Robert Nleminen,
P.e. on o1/24/201e. This does notserve as an electronically
signed document'
CERTIRCATION OF INDEPENDENCE:
1. NEMOI etc does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or
distributing products it evaluates.
2. NEMOI etc is not owned, operated or controlled by any company manufacturing or distributing products It evaluates.
3. Robert Nieminen, P.E. does not have nor will acquire, a financial Interest in any company manufacturing or distributing products for
which the evaluation reports are being Issued.
4. Robert Nieminen, P.E. does not have, nor will acquire, a financial interest In any other entity involved in the approval process of the
product.
S. This is a building code evaluation. Neither NEMOIetc. nor Robert Nieminen, P.E. are, in anyway, the Designer of Recordfor any
project on which this Evaluation Report, or previous versions thereof, Is/was used for permitting or design guidance unless retained
specifically for that purpose.
r-,
ROOFING COMPONENT EVALUATION:
1. SCOPE:
ONEMOletc.
Product Category: Roofing
Sub -Category: Underlayment
Compliance Statement: Roof Underlayments, as produced by Polyglass USA, Inc., have demonstrated compliance with the
following sections of the 6" Edition (2017) Florida Building Code through testing In accordance with the following Standards.
Compliance Is subject to the Installation Requirements and Limitations/ Conditions of Use set forth herein.
2. STANDARDS:
Section
Prope
Standard
year
1504.3.1
Wind Uplift
FM 4474
2011
1504.3.1
Wind Uplift
UL 1897
2012
1507.2.3 / 1507.L1
Physical Properties
ASTM D226
2009
1507.2.4/ 1507.3.1, 15U7.2.9.2
Physical Properties
ASTM D1970
2015
1507.3.3
Physical Properties
FRSA/TRI April 2022
2012
1507.11.2
Physical Properties
ASTM D6164
2011
1507.11.2
Physical Properties
ASTM D6222
2011
TAS 110
Accelerated Weathering
ASTM D4798
2011
3. REFERENCES:
Enter
Examination
Reference
Date
FM Approvals (TST 1867)
Wind Uplift
3004091
01/12/2000
PRI (TST 5878)
Physical Properties
PRI01111
04/08/2002
PHI (TST 5878)
Physical Properties
PUSA-005-02-01
01/31/2002
PRI (TST 5878)
Physical Properties
PUSA-013.02-01
22/23/2002
PRI (TST 5878)
Physical Properties
PUSA-013-02-02
12/23/2002
PRI MT 5878)
Physical Properties
PUSA-013-02-D3
12/23/2002
PRI (('sT 5878)
Physical Properties
PUSA-018-02-01
07/14/2003
PRI(TST5978)
Physical Properties
PUSA-028-02-01
07/13/2005
PRI(fST5878)
Physical Properties
PUSA-033-02-01
01/12/2005
PRI (TST 5878)
.Physical Properties
PUSA-035-02-01
09/29/2006
PRI (TST SUB)
Physical Properties
PUSA-055-02-02
22/10/2007
PRI (TST 5878)
Physical Properties
PUSA 061-02-02
OW812009
PRI (TST 5878)
Physical Properties
PUSA-076.02-M
02/22/2D08
PRI (TST 5878)
Physical Properties
PUSA-083-02-01
04/14/2008
PRI (TST 5878)
Physical Properties
PUSA-D88-02-01
07/29/2009
MTI(TST 2508)
Physical Properties
1X20H7A
04/01/2008
MTI(TST 2508)
Physical Properties
RXI4ESA
02/29/2009
ERD (TST 6049)
Physical Properties
11752.09.99-1
02/08/2000
ERD (TST 6049)
Wind Uplift
11757.08.01-1
08/23/2001
ERD (TST 6049)
Wind Uplift
11776.06.02
01/25/2003
ERD CM 6049)
Physical Properties
02200,07.03
07/14/2003
ERD (M600)
Wind Uplift
P1740.01.07
0l/04/2007
04/11/2007
ERD(TST 6049)
Physical Properties
P5110.04.07-1
03/21/2008
ERD (TST 6049)
ERD (TST 6049)
Wind Uplift
Physical Properties
P9260.03.08
.P13450.08.09
08/13/2009
ERD (TST 6049)
Wind Uplift
P30540.11.09-R1
12/30/2009
ERD (TST 6049)
PhysicalProperties
P11030.11:09.1
12/30/2009
ERD(TST 6049)
Wind Uplift
.P11030.11.09-2
11/30/2009
ERD (TST 6049)
Physical Properties
P33030.11.093
11/30/2009
ERD (TST 6049)
Physical Properties
P33360.06.10
06/25/2010
ERD (TST 6049)
Physical Properties
P33370.03.11
03/02/2011
ERD (TST 6049)
Physical Properties
P33370.04.11
04/26/2011
ERD (TST6049)
Physical Properties
P37300.10.11
10/19/2012
Report P1206002A9-1124
NEMO ETC, U.C.Evaluation
Cvt&f afAuM4nm04n 432455:
6'r EDmON(2017) FBC NON-HVHZEVAWAMON
Revision 24: 03�/24/208
Polygram Roof Undarlayments: (954) 233-1230
Page 2 of 14
r
Entity
ERD OW 6049)
ERD W 6049)
ERD (f5T 6049)
ERD (TSr 6049)
ERD (TSf 6049)
ERD (TST 6049)
ERD (TSr 6049)
ERD (TSr 6049)
ERD (TST 6049)
ERD (TSr 6049)
ERD (TST 6049)
ERD M 6049)
ERD (TST 6049)
ERD CMT 6049)
ERD (M 6049)
ERD (TSr 6049)
ERD (rST 6049)
ERD (IST 6049)
ERD (TST 6049)
ERD (TST 6049)
ERD (TST 6049)
ERD (TSr 6049)
ERD (TSr 6049)
ERD (TST 6049)
ERD (TST 6049)
.ERD (TST 6049)
ERD (W 6049)
ERD (ISr 6049)
ERD (TST 6049)
]CC -ES (EVIL 2396)
Miami -Dade (CER 1592)
Polygiass USA
Polyglass USA
Polyglass USA
UL, U.C. (QUA9625)
4. PRODUCr DESCRIPTION:
Examination
Physical Properties
Physical Properties
Physlcal Properties
Wind Uplift
Physical Properties
Wind Uplift
Wind Uplift
Wind Uplift
Wind Uplift
Wind Uplift
Physlcal Properties
Physlcal Properties
Physical Properties
Physical Properties
Physical Properties
Physical Properties
Physical Properties
Physical Properties
Physical Properties
Physical Properties
Physical Properties
Physical Properties
Physical Properties
Wind Uplift
Physical Properties
wind Uplift
Physical Properties
Physical Properties
Physical Properties
IBC Compliance
HVHZ Compliance
Manufacturing Affidavit
PA Affidavit
Materials Affidavit.
Quality Control
Reference
P40390.08.12-1
P40390.08.12-2
C41420.09.12-3
P39680.03.13
P45370.04.13
P1738.02.07-R2
11757.04.01-1-R1
P41630.08.13
P1175L05.03-R1
113178L31.03-R3
P45270.05.14
6020.07.14-1
6020.09.24-2
6020.09.14-3
6020.09.14-4
6020.09.14-5
6020.09.14-6
P46520.10.14
P43290.10.14
PLYG-SC7550.03.15
P40390.04:15
P44360.10.14-R1
PLYG-SCS080.05.15-1
PLYG-SC8905.05.16-1
PLYG-SCS080.07.16
PLYG-SC12025.10.16
PLYGSC13040.12.16
PLYG-SC11900.03.17
PLYG-SC12115.08.17
ESR-1697
NOA 14.0717.08
Products Current
Mule -Hide Cross I%
PolyAck SA Compound
Service Confirmation
4.f MechatdcelIV Fasteb'e'it0: derlaymel't.. V
4.2.1 Elastobase Is fiberglass reinforced, SBS modified bitumen base sheet.
4.12 Elastobase' P is a polyester -reinforced, SBS modified bitumen base sheet.
4.1.3 Polyglass 62 Base is a fiberglass -reinforced, asphaltic base sheet.
4.1.4 Polyglass APP Base is a fiberglass-relnforced, APP modified bitumen base sheet.
ONEMOjetc.
Date
08/06/2012
GBIU712012
09/12/2012
03/D4/2013
04/26/2013
04/29/2013
04/30/2013
08/06/2013
11/26/2023
11/26/2013
05/12/2014
09/08/2014
09/O8/2014
09/08/2014
09/08/2014
09/08/2014
09/08/2014
10/03/2014
10/17/2014
03/24/2019
04/03/2015
05/18/2015
05/20/2025
05/17/2016
07/16/2016
10/12/2016. -
12/27/2016
03/10/2017
08/08/2027
11/01/2014
01/22/2015
02/18/2009
03/01/2008
08/18/2011
Exp. 10/05/2018
4.2.1 Polystick MTS or Polystick MTS PLUS Is a nominal 60-mil thick rubberized asphalt waterproofing membrane, glass
fiber reinforced, surfaced with polyolefinic film surface; meets FRSA/Ml April2012.
4.2.2 Polystick IR-Xe is a nominal 60-mil thick rubberized asphalt waterproofing membrane, glass fiber reinforced, with an
aggregate surface; meets ASTM 131970.
4.2.3 Polystick TU Plus is a nominal 80-mil thick rubberized asphalt waterproofing membrane, glass fiber reinforced, with a
polyester fabric surface; meets ASTM D1970 and FRSA/TRI April 2012.
NEMO EM. LLr: Evaluation Report P32060.02.09-R24
O:rtlRcNe 0fAudvrbotlaa032455 e EDITION (2017) FBC NON-HVHZ EVALUATION Reuislan 24: 01FL=9-R28
8
Polyss giaRoof Underlaiiments; (954) 233-1230
Page 3 of 14
S.
ONEMOJetc.
4.24 Polyetick TU P is a nominal 130-mil thick rubberized asphalt waterproofing membrane, glass-fiber/polyester
reinforced, with a granular surface; meets FRSA/TRI April 2012.
4.25 Polystick TU Max is a nominal 60-mil thick rubberized asphalt waterproofing membrane with a 190 g/mz polyester
fabric surface; meets ASTM D1970 and FRSA/TRI April 2012.
4.2.6 PolyflexSAP, Polyflex SAP FR, Mule -Ride SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR) are polyester.
reinforced, APP modified bitumen sap sheets; meet FRSA/TRI April 2012.
4.23 Polystick Dual ProTM is a nominal 60-mil thick dual -layer rubberized asphalt waterproofing membrane, fiberglass
reinforced, with a, polyester fabric surface; meets ASTM D3970.
4.2.8 Polystick Tile Prone Is a nominal 60-mil thick dual -layer rubberized asphalt waterproofing membrane, fiberglass
reinforced, wlth a polyester fabric surface; meets ASTM D1970 and FRSA/rRI April 2012.
4.2.9 Polystick MU•X is a nominal 54-mil thick- dual -layer rubberized asphalt waterproofing membrane; fiberglass
reinforced, with a polypropylene film surface; meets AC188 and physical requirements of ASTM D1970 (See Section
5.8).
4.3.1 Elastoflex G TU is a polyester reinforced, modified bitumen the underlayment composed of a sand -surfaced SEIS
modified bitumen back -side and granule -surfaced APP modified bitumen top -side. Elastoflex G TU is for use as an
alternate to "Mineral Surface Roll Roofing (ASTM D6380, Class M) in the "Single Ply System" from FRSA/TRI April
2012 (04-12) beneath mechanically fastened tile roof systems or Hot Asphalt applied "Cap Sheet" in the'Two Ply
System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or adhered tile roof systems.
i
4.3.2 Elastoflex S6 G and Elastoflex S6 G FR are polyester reinforced, SRS modified bitumen cep sheets; meetASTM D6164.
Elastoflex S6 G and Elastoflex S6 G Fit are for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D6380,
Class M) In the "Single Ply System" from FRSA/rRLApril 2012 (04-22) beneath mechanically fastened tile roof systems.
Elastoflex S6 G is for use as an alternate to Hot Asphalt applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI
April 2012 (04-12) beneath mechanically fastened or adhered tile roof systems. Elastoflex S6 G FR Is for use as an
alternate to Hot. Asphalt applied "Cap Sheet" In the 'Two Ply System" from FRSA/TRI April 2012 (04-12) beneath
mechanically fastened tile roof systems.
4.3.3 Polyflex G and Polyflex G FR are polyester reinforced, APP modified bitumen cap sheets; meet ASTM D6222.
Polyflex G is for use as an alternate to Heat Applied "Cap Sheet" in the 'Two Ply System" from FRSA/TRI April 203.2
(04-12) beneath mechanically fastened or adhered tile roof systems. Polyflex G FR is for use as an alternate to Heat
Applied "Cap Sheet" in the 'Two Ply System" from FRSA/TRI April 2022 (04-12) beneath mechanically fastened the
roof systems.
LIMITATIONS:
5.1 This is a building code evaluation. Neither NEMOI etc. nor Robert Nieminen, P.E. are, In any way, the Designer of
Record for any project on which this Evaluation Report, or previous versions thereof, Is/was,used for,permitting or
design guidance unless retained specifically for that purpose.
5.2 This Evaluation Report Is not for use in the HVHZ.
5.3 .Fire Classification Is not part of this Evaluation Report; to current Approved Roofing Materials Directory for fire
ratings of this product.
5.4 Palyglass Roof Undedayments may be used with any prepared roof cover where the product Is specifically referenced
within FBC approval documents. if not listed, a request may be made to the Authority Having Jurisdiction for
approval based. on this evaluation combined with supporting data for the prepared roof covering.:
NEMO ETC, LLC. Ewluatlon Report P12060.02.09-R24
GuUlmte UfAuftdcation 032M 6t"EDITION (2017) FOC NON•HVHZ EVMUATION mRevision ?A:0FL52599-R28
8
Palyglass Roof underlaymes; (954) 233-U30 `
Page 4 of 14
ONEMOjetc.
5.5 Allowable Roof Covers:
Underlayment
Asphalt shingles
Nail -On Tile
Foam -On Tile
Meml
Wood shakes
8,shingies
Slate
Elastoba5e
Yes
paseshest n�2-PNNsteml
laasesheet n2-plywceml
Yes
Yes
Yes
ElastobaseP
Yes
Yes
( wSleemin2-plys ml
Yes
Iassesheetn2-ylysysteml
Yes
Yes
Yes
Polyglass G2 Base
No
Yes
(Base shestm 2•pNslsrem)
es
IBasesheerinz-0ysysteml
No
No
Na
Polyglass Al? Base
No
Yes
(Base Sheetln2•pry system)
Yes
IBazeShee[In 2-p1Y Mtem)
No
No
No
'PolystickMTS.or PLUS
Yes
Yes
No
Yes
Yes
Yes
Polystick lR-Xe
Yes
No
No
No
Yes
Yes
Polystld(TU P
No
Yes
Yes (See 5.5.11
No
No
No
PolystickTU Plus
Yes
Yes
Yes (see5.5.1)
Yes
Yes
Yes
PolysdckTU Max
No
Yes
Yes(See5.5.1)
Yes
No
No
Polystick Dual Pro
Yes
No
No
Yes
Yes
Yes
PolystickTllelera
Yes
Yes
Yes (See 5.5.2)
Yes
Yes
Yes
Powck MU-X
Yes
No
No
Yes
Yes
Yes
Elastaflex S6G
Yes
Yes
Yes (see 5.5.1)
No
Yes
Yes
Elastaflex S6 G FR
Yes
Yes
No
No
Yes
Yes
Elastaflex G TU
Yes
Yes
Yes (see 5-9.11
No
Yes
Yes
PalyflexG
Yes
Yes
Yes (See 55.1)
No
Yes
Yes
PolyflexG FR
Yes
Yes
No
No
Yes
Yes
PolyRex SAPorSAPFR
Yes
Yes
Yes (See5.5.1)
No
Yes
Yes
Mule-Hlde SA-APP Cap Sheet
or Cap Sheet (FR)
Yes
Yes
Yes (See 55.1)
No
Yes
Yes
5.5.1 "Foam -On Tile" is limited to use of the following Approved tile adhesives / underlayment combinations.
.'.'. TAeis3IF.AuAWit)t�'ItLB
AQYtFsi?iefUpoB@1AYIYlEN7.''.,'CQIy�BiN%LifbFls2s ;.. .
Adhesive .
Florida Product
Underlayments
Approval
DAP Foam Touch'n Seal StormBond Roof
FL14506
Polystick TU Plus, Polystick TU Max
Tile Adhesive
Dow TileBondn'
FL22525
Polystick TU P, Poystick TU Plus, Polyflex SAP or Tile Pro
Polystick TU P, Polystick TU Plus, PO"Ick TU Max, Polystick Tile Pro,
ICP Adhesives Polysete AH-160
FL6332
Elastaflex G TU, Elastoflex S6 G, Polyflex G, Polyflex SAP, Polyflex SA Cap FR,
_
Mule -Hide SA-APP Cap Sheet or Mule -Hide SA-APP Cap Sheet (FR)
Polystick TU P, Polystick TU Plus, Polystick TU Max, Polystick Tile Pro,
ICP Adhesives Polysets RTA 1
FL6276
Elastoflex G TU, Elastaflex S5 G, Polyflex G, Polyflex SAP, Polyflex SA Cap FR,
Mule -Hide SA-APP Cap Sheet or Mule -Hide SA-APP Cap Sheet (FR)
2 Referto Tile Manufacturer's or Adhesive Manufacturer's Florida ProductApproval far Overturning Moment Resistance Performance
NEMD ETC. LLC. Evaluation Report P32060.02.09-R24
Carapace pfAurhnmaaan 9324M S"EOmON(2017) FBCNON-HVHZ EVALUATION FL9259-HU
Perlyglass Roof Underlaymerds: (954) 233-1230 Revislon 24:01124/2018
Page 5 of 14
>
5.6 Allowable Substrates:
5.6.1 Direct -Bond to Deck:
Polystick (all variations), Dual Pro, Tile Pro, Polyflex SAP or SAP FR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet
(FR) self -adhered to:
D New untreated plywood; ASTM D41 primed new untreated plywood; Existing plywood; ASTM D41 primed existing
plywood; New or existing, unprimed OSB; ASTM D41 primed OSB; Southern Yellow Pine; ASTM D41 primed
Southern Yellow Pine; ASTM D41 primed structural concrete; Huber Engineered Woods "ZIP System" Panels
(designed and installed to meet wind loads for project).
Note: Polyglass does not require priming of new or existing plywood or OSB sheathing. New or existing plywood or
OSB sheathing should be cleaned of all dirt and debris prior to application of Polystick membranes.
Elastoflex G TU, Elastoflex S6 G or Elastoflex S6 G FR in hot asphalt to:
D ASTM D41 primed structural concrete.
Polyflex G or Polyflex G FR torch -applied to:.
D ASTM D41 primed structural concrete.
5.6.2 Band -to -Insulation:
Polystick (all variations), Polyflex SAP or SAP FR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) self -adhered
to:
D ASTM C1289, Type II, Class 1 polyisocyanurate or Type V polyisocyanurate-composite insulation; Dens Deck
DuraGuard; Dens Deck Prime; or SECUROCK Gypsum -Fiber Roof Board.
Elastoflex G TU, Elastoflex S6 G or ElastoflexS6 G FR in hot asphalt to:
D Dens Deck Prime or SECUROCK Gypsum -Fiber Roof Board.
Polyflex G or Polyflex G FR torch -applied to:
D ASTM D41 primed structural concrete; Dens Deck Prime or SECUROCK Gypsum -Fiber Roof Board.
For installation under mechanically attached prepared roof coverings, Insulation shall be attached per minimum
requirements of the prepared roof covering manufacturer's Product Approval. For installations under foam -on tile
systems, Insulation attachment shall be designed by a qualified design professional and installed based on testing of
the Insulation/underlayment system In accordance with FBC Section 1504.3.1.
5.6.3 Bond to Mechanically Attached Base Laver:
Polystick (all variations), Polyflex SAP or SAP FR, Mule -Hide SA-APP-Cap Sheet or SA-APP Cap Sheet (FR) Dual Pro or
Tile Pro self -adhered to:
➢ ASTM D226, Type I or II felt; Elastobase; Elastobase P or Mule -Hide Nail Base.
Elastoflex G TU, Elastoflex 56 G or Elastoflex S6 G FR In hot asphaltto:
D ASTM 0226, Type I or II felt; Elastobase; Elastobase P, Mule -Hide Nail Base or Polyglass G2 Base.
Polyfex G or Polyflex G FR torch -applied to:
D Elastobase; Elastobase P, Mule -Hide Nail Base, Polyglass G2 Base or Polyglass APP Base.
For installations under mechanically attached prepared roof coverings, base layer shall be attached per minimum
codified requirements. For installations under foam -on the systems, base layer shall be attached per minimum
requirements of FRSA/TRI April 2012 (04-12), Appendix A, Table 1, or as listed in Section 5.6.4 herein, or as tested in
accordance with FBC Section 1504.3.2.
NEMO ETC U.C. Evaluation Report P32060.02.09-R24
rertflax44fAuth4rhotbna32455 eEDITION 12017) FBCNON-HVHZ EVAWAMON FLSZ59-RZB
Polyglass Roof Underlaymernsl (9541233-2230 flevislon 24: 01/24/2018
Page 6 of 24
ONEMOletc.
5.6.4 Wind Resistance for Underlayment Systems in Foam -On Tile Aoollrations: FRSA/TRI April 2012 (04-22) does not
address wind uplift resistance of all underlayment systems beneath foam -on tile systems, where the underlayment
forms part of the load -path. The following wind uplift limitations apply to underlayment systems that are not
addressed In FRSA/rRI April 2012 (04-12) and are used in foam -on the applications. Maximum Design Pressure is the
result of testing for wind load resistance based on allowable wind loads, and reflects the ultimate passing pressure
divided by 2 (the 2 to 1 margin of safety per FBC 1504.9 has already been applied). Refer to FRSA/TRI April 2012 (04-
12), Appendix A, Table lA or FBC 1609 for determination of design wind loads.
#1 Maximum Design Pressure = -90 It
Deck: Min.15/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Primer. None
Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered.
Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and
Mule -Hide SA-APP Cap Sheet (Fit), self -adhered.
#2, Maximum Design Pressure =-97.5 psf:
Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Primer: P6100 or AStM D41
Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered.
Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and
Mule -Hide SA-APP Cap Sheet (Fit), self -adhered and back -nailed within the selvedge -edge side laps using 12 ga. x
IN' ring shank nails through 32 ga.,1-5/8' diameter tin caps spaced 124nch o.c
#3 Maximum Design Pressure=.105 osF.
Deck: Min.15/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Primer: WB-3000
Base Ply: (Optional) Polystick NITS or Polystick MTS PLUS, self -adhered.
Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR. Mule -Hide SA-APP Cap Sheet and
Mule�Hide SA-APP Cap Sheet (FR), self -adhered and back -nailed within the selvedge -edge side laps using 12 ga. x
1'h' ring shank nails through 32 ga.,1-5/a' diametertin caps spaced 12-Inch o.c.
#4 Maximum Design Pressure =-135 psf:
Deck: Min, 35/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Primer. (Optional) PG300 or ASTM D42
Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered.
Joints: Min. flinch wide strips of Elastoflex SMV over all plywood joints.
Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and
Mule -Hide SA-APP Cap Sheet (FR), selfadhered.
#5 Maximum Design Pressure = 315 psf:
Deck: Structural concrete to meet project requirements to satisfaction of Authority HavingJurisdiction.
Primer: PG100 orASTM D41
Base Ply: , (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered.
Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Tile Pro, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap
Sheet and Mule -Hide SA-APP Cap Sheet (Fit), selfadhered.
96 Maximum Design Pressure=.622.5 osf:
Deck: Structuralconcrete to meet project requirements to satisfaction of Authority Having Jurisdiction.
Primer. PG100or ASTM D41
Undedaymem: Elastoflex G TU or Elastollex S6 G, applied in full mopping of hot asphalt or Polyflex G, torchapplied.,
#7 Maximum Design Pressure =-30.0 psf
Deck: Min.15/32-inch OSB to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Elastobase or Mule -Hide Nall Base (poly -film top surface)
Fasteners: 11 Be. x 2125-inch long x 1-inch head diameter round metal cap nails
Spacing: 6-Inch o.c. at the 3-Inch wide side laps and 64nch o.c, at two (2) equally spaced staggered center rows.
Base Ply: (Optional) Polystick NITS or Polystick MTS PLUS, self -adhered.
Underlayment: Polystick TU P, Polystick TUPlus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and
Mule -Hide SA-APP Cap Sheet (FR), self -adhered.
NEMO ETC, U.C. Ewlvation Report P12060.02.09-R24
rertytmm oJAudmdz nn B32455 6'sEDITION(2017)FBC N0N-HVH2 EVALUATION FLUS.4428
Puiyglass Roof Undurlaymentsi (9541233-1230 Recision 24: OW412018
.Page 7 of 14
�#8 Maximum Design Pressure =-37.5 psf•: NNEMO etc.
Deck: MIn.35/32-Inch plywood to meet project requirements to satisfaction of Authority Havingiurlsdlction.
Base Sheet. Elastobase or Mule -Hide Nail Base (poly -film top surface)
Fasteners: 11 ga, x 1.25-inch long x 1-inch head diameter round metal cap nails
Spacing: 6-inch o.c at the 3-Inch wide side laps and &-inch o.c. at two (2) equally spaced staggered center rows.
Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered.
Underlayment: Polystick TU P, Polystick TU Plus; Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and
Mule -Hide SA-APP Cap Sheet (FR), self -adhered. _
#9 Maximum Design Pressure =-37.5psf":
Deck: Min.19/32-Inch plywood to meet project requirements to satisfaction of Authority Having.lurlsdiction.
Base Sheet: One (1) or two (2) layers ASTM D226, Type II felt
Fasteners: 11 ga. x 1.25-inch long x 1-Inch head diameter round metal cep nails
Spacing: 64nch o.c at the 3-Inch wide side laps and 12-Inch o.c. at two (2) equally spaced staggered center rows.
Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt
#10 Maximum Design Pressure --45 nsf•;
Deck: Min.19/32-Inch plywood to meet project requirements to satisfaction of Authority Having.lurisdiction.
Base.Sheet: One (1) layer ASTM 0226, Type II felt
Fasteners: 11 ga. x 1.25-Inch x 3/8-Inch head diameter annular ring shank roofing nails at 2-5/8-Inch diameter tin caps
Spacing: 44nch mm at the 2-Inch wide side laps and 4-Inch a.e at two (2) equally spaced staggered center rows.
Base Ply: (Optional; for use with selfadhedng underlaymem only) Polystick MTS or Polystick MTS PLUS, self -adhered.
Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Poh/flex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and
Mule -Hide SA-APP Cap Sheet (FR), self -adhered or Elastoflex G TU, applied in full mopping of hot asphalt
#11 Maximum Design Pressure =-45 psf•:
Deck: Min.19/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction, .
Base Sheet: Two (2) layers ASTM D226, Type II felt
Fasteners: 11 go. x1.25-Inch longx 3/8 inch head diameter annular ring shank roofing nails at 1-5/8-Inch diametertincaps
Spacing: 9-Inch a.c at the 2-Inch wide side laps and 94nch o.c. at two (2) equally spaced staggered center rows.
Base Ply: (Optional; for use with selfadhering underlayment only) Polystick MTS or Polystick MTS PLUS, self -adhered.
Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyliex SAP, Palyfiex SAP FR, Mule -Hide SA-APP Cap Sheet and
Mule -Hide SA-APP Cap Sheet (FR), self -adhered or Elastoflm G TU or Elastoflex S6 G, applied in full mapping of hot
asphalt
#12 Maximum Design Pressure=-45
Deck: MIn.15/32-Inch plywood to meet project requirements to satisfaction of Authority Hawngiurisdlction,
Base Sheet: Elastobase (sanded top surface for hotasphalt or torch -applied cap or poly -film surface for torch -applied cap)
Fasteners: Simplex MAXX Cap Fasteners
Spacing: 9-Inch o.c. at the 24nch wide side laps and 184nch o.c. at two (2) equally spaced staggered center rows.
Underlayment Elastaflex G TU or Elastoflex S6 G, applied In full mopping of hot asphalt or Polyff" G, torchapplled.
#13 MaxlmurnMeslgnPressure=-52.5psf.
Deck: Min.15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cep or polµfilm surface for torchapplied cap)
Fasteners: Simplex MAXX Cap Fasteners
Spacing: 9-inch o.c. at the 2-Inch wide side laps and 12-Inch o.c. at two (2) equally spaced staggered center rows.
Underlayment: Elastoflex G TU or Elastoll" S6 G, applied in full mopping of hot asphalt or Polyflex G, torchapplied.
#14 Maximum Design Pressure=-52.5a
Deck: MIn.15/32-Inch plywood to meet project requirementsto satisfaction of Authority. Havinglurisdiction.
Base Sheet: Elastobase or Mule -Hide Nail Base (poly -film top surface)
Fasteners: Simplex Original Cap Nails
Spacing: &Inch o.c at the 3-inch wide side laps and 64nch o.c at four (4) equally spaced staggered center rows.
Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered.
Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and
Mule -Hide SA-APP Cap Sheet (FR), self -adhered.
NEMO ETC, LLC. Evaluation Report P12060.02A9-1124
Cer0arte afAUMadmtian#32455 6t"EDITION RU71 FBC NON-HVHZ EVAWATION F1.5159-1128
Palyeass Roof Undedayments; (954) 233-1230 Revision 24: 01/24/2018
Page 8 of 14
ONEMOJetc.
#15 Maximum Design Pressure =-52.5 psf:
Deck: Min.15/32-Inch plywood to meet project requirements to satisfacton afAuthorlty Havinglunsdiction.
Base Sheet.. Elastobase(sanded top surface for hot -asphalt or torchapplied cap or poly -film surface for torch -applied cap)
Fasteners: Simplex Original Cap. Nails
Spacing: 6-Inch o.c at the 3-Inch wide side laps and 6-Inch o.c. at four (4) equally spaced staggered center rows.
Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied.
#16 Maximum Design Pressure =-60 psi;
Deck: Min.19/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Elastobase (sa nded top surface for hot -asphalt ortorchapplied cap or poly -film surface for torch -applied cap)
Fasteners: 11 ga. x 125-Inch long x 3/84nch head diameter annular ring shank roofing nails at 1-5/8-Inch diametertin caps
Spacing: 8-Inch o.c. at the flinch wide side laps and 8-Inch c.c. at three (3) equally spaced staggered center rows.
Underlayment: Elastoflex G TU or Elastoflex S5 G, applied In full mopping of hot asphalt or Polyflex G, torch -applied.
#17 Maximum Design Pressure =-60 psi:
Deck: Min.19/32-inch plywood to meet project requirements to satisfaction of Authority Havinglurisdiction.
Base Sheet: Elastobase(sandedtopsurfaceforhatasphaltortorchappliedcaporpoly-film surface for torchappiledcap)
Fasteners: OMG#12 Standard R00%dp with OMG Flat Bottom Metal Plates
Spacing: 12-Inch o.c. at the 4-Inch wide side laps and 12-Inch o.c. at two (2) equally spaced staggered center rows.
Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied.
#28 Maximum Design Pressure =-67.5 psi:
Deck: Min.15/324nch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Polyglass G2 Base or Polyglass APP Base (requires use of torch -applied undedayment)
Fasteners: 12 ga. x 12S-Inch long x 3/8-inch head diameter annular ring shank roofing nails at 1-5/8-11nch diameter tin caps
Spacing: f-Inch o.e at the 4-Inch wide side laps and 94nch o.c at four (4) equal IV spaced staggered center rows.
Underlayment: Elastoflex G TU or Elastoflex S6 G, applied In full mapping of hot asphalt or torch -applied or Polyflex G, torch -
applied.
#19 Maximum Design Pressure=-7512
Deck; Min, 15/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Polyglass G2 Base or Polyglass APP Base (requires use of torch -applied underlayment)
Fasteners: Dekfast #14 with Dekfast Hex plates, OMG #14 HD with OMG r Galvalume Steel Plates, OMG Roofgrip #14 with
OMG Flat Bottom Plates (ACcuTrac), Trufast HD with Trufast 3-Inch Insulation Plates or Simplex MAXX Cap
Fasteners
Spacing: 10-Inch o.c. atthe 4-Inch wide side laps and 104mch a.c at three (3) equally spaced staggered center rows.
Underlayment: Elastoflex G TU or Elastoflex 56 G, applied In full mopping of hot asphalt or torch -applied or Polyflex G, torch -
applied.
#20 MaximumDesign Pressure =-90osfi
Deck: Min.15/32-inch plywood to meet projectrequiremems to satisfaction of Authority Having Jurisdiction.
Base Sheet: Elastobase(sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap)
Fasteners: Simplex MAXX Cap Fasteners
Spacing: 64nch o.c. at the 2-Inch wide side laps and 6-inch o.c. at two (2) equally spaced staggered center rows.
Underlayment: Elastaflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied.
#21 Maximum Design Pressure =-90 psi:
Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Elastobase(sanded top surface for hotasphalt or torch -applied cap or poly -film surface for torch -applied cap)
Fasteners: CMG #12 Standard Rcofgrlp or OMG #14 Heavy Duty with OMG 3" Round Metal Plates or OMG Flat Bottom Metal
Plates
Spacing: &:•inch o.c at the 4-inch wide side laps and 6-Inch o.c at three (3) equally spaced staggered center rows.
Underlayment: Elastoflex G TU or Elastoflex S6 6,.applied in full mopping of hot asphalt or Polyflex G, torch -applied.
#22 Maximum Design Pressure=-90 psf.
Deck: Min.15/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Elastobase (sanded top surface)
Fasteners: Trufast#12 DP or Trubst#14 HD with Trufast 30 Metal Insulation Plates
Spacing: 54nch o.c at the 4-inch wide side laps and 6-Inch o.c at three (3) equal ly spaced staggered center rows.
Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt
NEMO EM LLC. Evaluation Report P12060.02.09404
rera(rcate PlAxderhadona324sa 61e EDITION(2017) FBC N0N4WH2 EVAWAMON FLVS9.gyg
Polyglass Roof Undedaymentst (954) 233-1230 Revision 24:01/24/2018
Page 9 of 14
ONEMoletc.
#23 Maximum Design Pressure=-90 Dsfi
Deck: Min. 15/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Polyglass GZ Base or Polyglass APP Base (requires use of torch -applied underlayment)
Fasteners: Dekfast #14 with Dekfast Hex plates, OMG #14 HD with OMG 3" Galvalume Steel Plates, OMG Roofgrip #14 with
OMG Flat Bottom Plates (AccuTrac), Tnjfast HD with Trufast 34nch. Insulation Plates or Simplex MAXX Cap
Fasteners
spacing: 9-Inch o.c, at the 4-Inch wide side laps and 94nch o.c. at four (4) equally spaced staggered center rows.
Underlayment: Elastoflex G TU or Elastoflex S6 G, applied In full mopping of hot asphalt or torch -applied or Polyflex G, torch -
applied.
#24 Maximum Design Pressure = -97.5 is
Deck: Min. 19/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Elastabase or Mule -Hide Nail Base (poly -film top surface)
Fasteners: 11 ga. x 1.25•Inch x 3/8-Inch head diameter annular ring shank roofing nails at 1-5/8-Inch diametertincaps
Spacing: 4-Inch o.c at the flinch wide side laps and flinch c.c. at four (4) equally spaced staggered center rows.
Base Ply: (Optional)Polystick MTS or Polystick MTS PLUS, self -adhered.
Underlayment: Palystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap. Sheet and
Mule -Hide SA-APP Cap Sheet (FR), seff-adhered.
#25 Maximum Design Pressure=-105 osf:
Deck: Min.25/32-Inch plywood to meet project requirements to satisfaction of Authority Havinglurisciction.
Base Sheet: Elastobase(sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cep)
Fasteners: Simplex MAXX Cap Fasteners
Spacing: 6-Inch o.c at the 2-Inch wide side laps and 64nch o.c. at three (3) equally spaced staggered center rows.
Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied.
#26 Maximum Design Pressure =-112.5 is '
Deck: Min. 19/32-Inch plywood to meet project requirements to satisfaction of Authority Havinglurlsdiction.
Base Sheet: Elastobase or Mule -Hide Nail ease (poly -film top surface)
Fasteners: 11 ga. x 1.25-inch x 3/8-inch head diameter annular ring shank roofing nails at 1-5/8-Inch diameter tin caps
Spacing: 6-Inch o.c at the 4-Inch wide side laps and 6-Inch o.c. at four (4) equally spaced staggered center rows.
Primer: PG200 or ASTM D42 primer at all tin -caps
Base Ply: Polystick MTS or Polystick MTS PLUS, selfadhered
Underloyment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and
Mule -Hide SA-APP Cap Sheet (FR), self -adhered.
#27 Maximum Design Pressure=-220ttsf:
Deck: Min.15/32-Inch plywood to meet project requirements to satisfaction of Authority Havingiurisdiction.
Base Sheet: Elastobase(sanded top surface for hot -asphalt or torch -applied cap or poly -film surface fortorch-applied cap)
Fasteners: OMG #12 Standard Roafgrip or OMG #14 Heavy Duty with OMG 3" Round Metal Plates or OMG Flat Bottom Metal
Plates
Spacing: 6-Inch o.c, at the flinch wide side laps and 6-inch o.c at five (5) equally spaced staggered center rows,
Underlayment: Elastoflex G TU or Elastoflex 56 G, applied In full mopping of hot asphalt or Polyflex G, torchapplied.
#28 Maximum Design Pressure=-120 osf•.
Deck: Min.15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction.
Base Sheet: Elastobase (sanded top surface)
Fasteners: Trofast#12 DP or TTufast#24 HD with Trufast 3" Metal Insulation Plates
Spacing. 6-inch o.c. at the flinch wide side laps and 6-inch o.c at five (5) equally spaced staggered center rows..
Underlayment'. Elastoflex 6 TU orElastoflex S6 G, applied In full mopping of. hot asphalt.
5.6.4.1 All other direct -deck, adhered Polyglass underlayment systems beneath foam -an the systems carry a Maximum
Design Pressure of-45 psf.
NEMO ETC, LLC. Evaluation Report PI2A60.02A9-R24
raefkateafAuOmr&adan 03ZUS 6�EDITION(2017) FRC NON4MZ EVALUATION F15259-R28
Polyglass Roof Underiayments; (9541233-ILM Revision 24: 01%14/2018
Page 10 of 24
ONEM010C.
5.6.4.2 For mechanically attached Base Sheet, the maximum design pressure for the selected assembly shall meet or exceed
that required under FRSA/TRI April 2022 (04-12), Appendix A, Table 1A.
Altematively; the maximum design pressure for the selected assembly shall meet or exceed the Zane 1 design.
pressure determined In accordance with FBC 1609. In this case, Zones 2 and 3 shall employ an attachment density
designed by a qualified design professional to resist the elevated pressure criteria.. Commonly used methods are
ANSI/SPRI WDl, FM Loss Prevention Data Sheet 1-29 and Roofing Application Standard RAS 117. Assemblies marked
with an asterisk* carry the limitations set forth in Section 2.2.20.1 of FM Loss Prevention Data Sheet 1-29 (January
2016) for Zane 2/3 enhancements.
5.7 Exposure Limitations:
Elastobase, Elastoba_se P, Polyglass G2 Base or Polygiass APP Base shall not be left exposed for longer than 30-days
after installation.
Polystick IR-Xe or Polystick MU-X shall not be left exposed for longer than 90-days after installation.
Polystick MTS, MTS PLUS, TU P, TU Plus, TU Max, Dual Pro, Tile Pro or Elastoflex G TU shall not be left exposed for
longerthan 180-days after installation.
Polyflex SAP or SAP FR, or Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) does not have an exposure
limitation, unless the prepared roof covering Is to be adhesive -set tile, in which case the maximum exposure Is 30
days.
Elastoflex S6 G or Elastoflex S6 G FR or Polyflex G or. Polyflex,G FR does not have an exposure limitation, unless the
prepared roof covering Is to be adhesive -set tile (Elastaflex S6 G or Polyflex G only), in which case the maximum
exposure is 180 days.
5.8 Polystick MU-X has been found through comparative testing to have.a lesser coefficient of friction than ASTM D226
roofing felt in a dry condition, tested at standard laboratory conditions. Agreement between purchaser and seller, as
setforth In Section 4.3, Note 1 ofASTM D1970-15, should be established as to slip resistance.
5.9 Tile Slippage Limitations (FRSA/TRI April 2012 (04-12%
When loading roof tiles on the underlayment in direct -deck the assemblies, the maximum roof slope shall be as
follows. These slope limitations can only be exceeded by using battens during loading of the roof tiles.
' ,.' :;.yi:+�. .-; .;TABS'Z::TILE.SLIPPAGk;LMRA`fIGNSEOi<;WRNS'Gi-DE.EIC;nIb`JKI��jtf�ilON9,. •,i.,.":i.. '. .
Undedayment
rile Profile
Staging Method
Maximum Slope
Elastaflex G TU
Flat
10-tile stack
7:12 _
Lagged
Mile stack (6 over 2)
6:12
ElastoflexS5 G or S6 G FR
Flat or Lugged
6-tile stack (4 over 2)
4.12 "
Polystick MTS or MTS PLUS
Flat
6-tile stack (4 over 2)
5:12
Lugged
6-tile stack (4 Over 2)
4:12
PolystickTlle Pro
Flat or Lugged
&tile stack (4 over 2)
7:12
Polystick TU Max
.Flat
6-tile stack (4 over 2) or 10-tile stack
7:12
Lugged
&flestack(4over2)
7:12
Lugged
10-tile stack
6:22
Polystick TUP
Flat
&tile stack (4 over 2)
6:12
Lugged
6-tile stack (4 over 2)
4:12
PolystickTU Plus
Flat or Lugged
6-tile stack (4 over 2)
7:12
- Flat or Lugged
10•tile stack
6:12
Polyflex G or G FR
Flat or Lugged
6-tile stack (4 over 2)
4:12
Polyflax SA P or SA P FR
Flat or Lugged
I 6-tile stack (4 over 2)
1 4:12
NEMO ETC, Luc. Evaluation Report P32060.02.09-R24
CEraYmte MfAomMOM0 v124Z 6TM EDITION (2017)FBC NON-HVH2 EVALUATION FL5259-08
Polygiass Roof Underlayments; 1954) 233-1280 Wslon 24:01/24/2018
Page 11 of 14
ONEN[Ojetc.
6. INSTALLATION:
6.1 Polyglass Roof Underlayments shall be installed in accordance with Polyglass published installation requirements
subject to the Limitations set forth in Section 5 herein and the specifics noted below.
6.2 Re -fasten any loose decking panels, and check for protruding nail heads. Sweep the substrate thoroughlyto remove
any dust and debris prior to application, and prime the substrate (if applicable).
6 3 . Elastobase Elan o aseTgc Mu)e j de.Na)f
6.3.1 Non -Tile Annilcations*
Shall be Installed in compliance with the codified requirements for ASTM D226, Type it underlayment in FBC Table
2507.1.1 for the type of prepared roof covering to be installed.
Elastohas% Elastobase P or Mule -Hide Nail Base may be covered with a layer of Polysticlr, Polyflex SAP, Polyflex SA
P FR,, Mule -Hide SA-APP Cap Sheen or SA-APP Cap Sheet (FR), self -adhered, Elastoflex 6 TU, Elastoflex S6 G or
Elastoflex 56 6 FR in hot asphalt or Polyflex 6 or Polyflex 6 FR, torch applied. Roof cover limitations are those are
those associated with the top -layer underlayment, asset forth in Table 1,
6.3.2 Tile Applications:
Elastobase, Elastobase P or Mule -Hide Nail Base are limited to use as a mechanically attached base sheet in the "Two
Ply System" from FR5A/TRI April 2012 (04-12). Reference is made to Table 1 and Section 5.6.4 herein, coupled with
FRSA/TRI April 2012 (04-12) Installation: Manual.
6.4: Polystigkl)flT5,p4TS.PW8,1.*;,TUPrTU."PI4rTi(MaxiDualPrb�Til;O;prgarfJIHZ(.otPolyRekSAP,P4il��t8l4PFlt,;
• MuledfideSA.APRFap'$Ite tbr:MuleTill" A•APR pShBef'
6.4.1 Shall be installed in compliance with the codified requirements for ASTM D1970 (except PolystickTU P) underlayment.
6A.2
In FBC Table 1507.1.1 for the type of prepared roof covering to be installed.
Direct -to -Deck with Mechanically Fastened Roof Covers:
All self -adhering materials, with the exception of Polystick TU Plus, Polyflex SAP or SAP FR and Mule-H(de SA-APP
Cap Sheet or SA-APP Cap Sheet (FR) should be back -nailed in selvage edge seam in accordance with Polyglass / Mule -
Hide back nailing guidelines. Nails shall be corrosion resistant, 11 gauge ring -shank type with a minimum 1-Inch
diameter metal disk or Simplex -type metal cap nail, at a minimum rate of 12" o.c. Polystick TU Plus should be back -
nailed using the above noted fasteners and spacing, In area marked "nail area, area pare clever' on the face of
membrane. The head lap membrane is to cover the area being back -nailed.
All seai-lap seams (selvage laps) must be
firmly rolled with a minimum 28 lb. hand
roller to ensure full contact and adhesion.
For Dual Pro and Tile Pro, align the edgeof
the top sheet to the end of the glue pattern
(the sheet will overlap the fabric). ja
viewaf Dvelap Seam of Dual Pro and 711e Pm
All over -fabric and over -granule end -laps shall have a 6-inch wide, uniform layer of Polyplus 50 Premium Modified
Wet/Dry Cement or Polyglass PGSOo Modified Cement applied In between the application of the lap.
Polystick TU Plus, Dual Pro and Tile Pro may not be used in any exposed application such as crickets, exposed valleys,
or exposed roof to wall details
NEMO Etc, U.C. Evaluatlon Report P32050.02.09-RZ4
affijkaeof4uthor&aUaao324W G"' EDMON(2p17) FBC NO"VMZEVALUATION P1.525931128
Polyglass Roof Unearlayments; (954) 233-1230 Revision 24: 01/20MB
Page 12 of 14
r�.
ONEIVIOjeft.
Repair of Polystick membranes is to be accomplished by applying Polpplus 50 Premium Modified Wet/Dry Cement or
Polyglass PGS00 Modified Cement to the area in need of repair, followed by a minimum 6 x 6 inch patch of the
Polystick material of like kind, set and hand rolled In place over the repair area. Patch laps, if needed, shall be
Installed in a water shedding manner.
All Polystick membranes shall be installed to ensure full contact with approved substrates. Polyglass requires a
minimum of 40-lb weighted -roller or, on steep slopes, use of a stiff broom with approximately 404bs of load applied
for the field membrane. Hand rallers are acceptable for rolling of patches, laps (min. 28lb roller) or small areas of the
roof that are not accessible to a large roller or broom.
6.4.3 Tile Applications (not allowed for Polystick Oual P% IR Xe orPolotick MUO:
Reference is made to FRSA%TRI April 2012 (04-12) Installation Manual and Table 1 herein, using the instructions
noted above as a guideline.
For mechanically fastened tile roofing over 2-ply system, consisting of Base Sheet and self -adhering top sheet(s), Base
Sheet fastening shall be not less than FRSA/TRI April 2012 (04-12), Table i
For adhesive -set file applications, refer to Section 5.5A herein.
6.4.4 Two (21 Ply Underlayment Systems: -
Polystick MTS or MTS PLUS followed by Polystick MTS, MTS PLUS, TU P, TU Plus, TU Max, Tile Pro, MU-X or Polyflax
SAP is allowable for use under mechanically attached prepared roof systems. Limits of use are those associated with
thetop-layer material. This is not a requirement, but is allowable if a 2-ply underlayment system is desired..
Polystick MTS or MTS PLUS followed by Polystick TU P, TU Plus, TU Max, Tile Pro or Polyflex SAP is allowable for use
under foam -on tile systems. Umlts of use are those associated with the top -layer material. This is not arequirement,
but Is allowable if a 2-olv underlavment system is desired.
6.5.1 Elastaflax G TU, Elastoflex S6,6 or Elastaflex S6 6 FR shall be installed in compliance with current Polyglass published
Installation requirements. For use In tile applications:
✓ Elastaflex 6 TU is for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D6380, Class M) in. the "Single
Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems or the Hot Asphalt
applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI April 2012 (04-22) beneath mechanically fastened or
adhered tile roof systems.
✓ Elastoflex S6 6 Is for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D6380, Class M) In the "Single Ply
System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems or the Hot Asphalt
applied "Cap Sheet" in the 'Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or
adhered tile roof systems.
✓ Elastoflex S6 6 FR is for use as an alternate to "Mineral Surface Roll Roofing" (ASTM 06380, Class M) in the "Single
Ply System" from FRSA/TRI April 2012 (04-22) beneath mechanically fastened tile roof systems or the Hot Asphalt
applied "Cap Sheet' in the "Two Ply System" from FRSA/TRI April 2022 (04-22) beneath mechanically fastened tile
roof systems.
6.5.2 For hot -asphalt -applications, Elastoflex G TU, Elastoflex S6 6 or ElastofiexS6 G FR shall be fully asphalt -applied to the
substratesnoted In Section 5.6. Side laps shall be minimum 3-Inch and end -laps minimum 6-Inch wide, offset
minimum 3 feet from course to course. Side and end laps shall be fully adhered in a complete mopping of hot asphalt
with. asphalt extending approximately 3/84nch beyond the lap edge.
6.6.1 Polyflex G or PoWex 6 FR shall be Installed in compliance with current Polyglass published Installation requirements.
For use In tile applications:
✓ Polyflex G is for use as an alternate to the Heat Applied "Cap Sheet" in the 'Two Ply System" from FRSA/TIO April
2012 (04-12) beneath mechanically fastened or adhered tile roof systems (Base Sheet Limited per 5.6.3).
✓ Polyflex G FR is for use as an alternate to the Heat Applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI
April 2022 (04-12) beneath mechanically fastened the roof systems (Base Sheet Limited per 5.6:3).
NEMO Or, U.C. Evaluation Report P22060.02M.R24
CeRUhvte 4JAlOar Wxe2455 6r"EDmON(Z017)FBC NON-HVHZ EVALUATION FL5289-R28
poly&= Roof Underlayments; (964) 233-123D Revision 24: 01/24/2018
Page 13 of 14
ONEMOJeft.
6.6.2 Polyflex G or Polyflex 6 FR shall be fully torch -applied to the substrates noted in Section 5.6. Side laps shall be
minimum 34nch and end -laps minimum 64nch wide, off -set minimum 3 feet from course to course. Side and end
laps shall be fully heat -welded and inspected to ensure minimum 3/8-Inch flow of modified compound beyond the lap
edge.
6_7 Tile Steel=
6.7.1 Tile shall be loaded and staged in a manner that prevents the slippage and/or damage to the underlayment Refer to
Tablet herein, and Polyglass published requirements for tile staging.
.
6.7.2 Battens and/or Counter -battens, as required by the tile manufacturer and FRSA/TRI April 2012 (04-12) must be used
on all roof slopes greater than 7:12. Precautions should be taken as needed, such as the use of battens or sail-
boards, to prevent tle sliding and/or damage to the underlayment during the loading process.
6.7.3 Polyglass specifies the minimum cure time after installation of self -adhering membranes and before loading of
roofing tiles is forty-eight (48) hours.
7. BUILDING PERmrr REQUIREMENT&
As required by the Building Official or Authority Having Jurisdiction in orderto properly evaluate the Installation of this product.
S. MANUFACruinmG PLANTS:
9.
Contact the noted CIA agency for information on product locations covered for F.A.C. 61620-3 QA requirements. The following
plants have qualified products under their respective physical properties specifications.
:PfaM�.;'. .�. •' .;•�'. .,.'..,
�S e'ctfi
Femley, NV, Hazleton, PA & Winter Haven, FL
ASTM D1970
Pol stick MU-X
Hazleton, PA
M-D 13-0004
Elastoflex G TU
Hazleton, PA & Winter Haven, FL
ASTM D2970
Polystick lR-Xe
ASTM D2970 & FRSA/TRI April 2012
Pol stick TU Plus
ASTM D1970 & FRSA/TRI April 2012
Poiystick TU Max
Tuscaloosa, AL
ASTM D4601, Type If
Poiyglass G2 Base
Winter Haven, FL
ASTM D226 (P IcAs)
Elastobase, Elastobase P
ASTM D6509
Polvnlass APP Base
FRSA/TRI April 2012
Pal ck MTS, Poll ck MTS PLUS
FRSA/TRI April 2012
PolVsnck TU P
FRSA/Tltl April 2012
Polyflex SAP, Poi ex SA P FR
ASTM D1970
Polystick Dual Pro
ASTM D2970 & FRSA/TRI April 2012
PDlystick Tile Pro
ASTM D6164
Elastollex S6, Elastoflex S6 G FR
ASTMD6222.
Polyflex G,.Polyflex 6 FR
QUALITY ASSURANcE ENTITY:
UL, LLC—QUA9625; (314)'578-3406; k.chancellor@us,ul.com
-END OF EVALUATION REPORT-
NEMO M U.C.
CertftW fAuNoraation N3265 firs EDITION(2617)FBCNON-HVHZEVALUAT10N
Potyglass Roof Underlaymer=; (954) 7d3,12•TO
Evaluation Report P32060.02A9-R24
FL5254-R7B
Revislan 24: 01/24/2018
Page 114 of 14