46280 (043405-7403240741) Project Details: DUTCHER CONDO DOOR REPLACEMENT
J&G CARPENTRY, INC.
7030 S.W. 16TH COURT PEMBROKE
PINES, FL
9400 S. OCEAN DRIVE, UNIT 706B
JENSEN BEACH, FL
Wind Load Design Pressure Calculations (Components & Cladding)
Site Information
Building Classification:
enclosed
Wind Speed (V It):
170 mph
Exposure Category:
d
Roof Type:
monoslope
Roof Slope (B):
1.2 deg
Mean Roof Height (h):
88.0 ft
Min. Building Dimension (L):
52.0 ft
Parapet >_ 3 feet?
No
General Calculation
Directionality Factor (Kd):
0.85
Gust -Effect Factor (G):
0.85
Internal Pressure
Coefficient (GC,,,):
± 0.18
Topographical Factor (K,t):
1.0
Velocity Pressure Exposure
Coefficient K
1.40
Velocity Pressure (qh):
88.13 psf
End Zone (a):
5.2 ft
ASD Method:
P = 0.6w
NOTES: Design is in accordance with ASCE 7-10 (ASD method) and the Florida Building Code Sixth Edition (2017). Results
are not valid for use unless approved via original signature and raised engineer seal of a PE from Engineering Express. V%WQMwit g� sed Engineer
Results are based on contractor -supplied data and shall be field verified by others prior to use. Selection & Installation of\ 16AT i
t i
products shall be approved using these dimensions and pressures as verified by others. \\\ C+':,.NSE"
Note: For openings to be properly rated in Zone 4, no part of the opening shall be within 5.2 feet of any building catner� , R�U 4 r Ol �18
This engineer has not field visited this location and if this cannot be clearly identified by others, the opening shall be rk : 4 On DI ISLO, WE
evaluated prior to installation of any fenestration. All other Information provided above including mean roof heigpt,o ' _ i{
building minimum dimensions, opening sizes,& other supporting data was provided by others. For definitions of t�e• PE$ 28 : Z_
above terms, visit EngineeringExpress.com/Wlki"'. Cert $8
.On'.,• FLO,.
�''r�FESSIoNP�;.
160 SW 12TH AVENUE, SUITE 106, DEERFIELD BEACH, FLORIDA 33442
46280 (043405-7403240741) PHONE: (954) 354-0660—FAX: (954) 354-0443
AutoPrint ENGINEERINGEXPRESS.COM PAGE 1 OF 1