THRESHOLD FIELD REPORT SITE VISIT #02
Project: Courtyard Marriott Balcony Repairs
McCarthy Project No. OCEND18006
Martin County Permit No. SLC-1811-0242 2nd Floor Balconies
Location:
Date:
Contractor:
Present:
Progress:
Comments:
10978 S. Ocean Blvd.
Jensen Beach, FL
May 23, 2019
Miller Construction
Robert Selinsky P.E., Pennoni
John, RTI Construction
Unit 212 Balcony formed with reinforcing in place
Arrived on site, as requested by the contractor to observe the following:
1. Unit 212 balcony excavation complete. The east, north, and south sides of the balcony have
been excavated to expose the ends of two layers of approx. X inch diameter welded wire
fabric reinforcing. Provide min 1 Y2" cover all steel.
2. Supplemental reinforcing has been added at 24" o/c per plan.
3. Contractor to check for continuity of rebar with a multi meter and tie new rebar to existing
reinforcement prior to installing zinc anodes. Anodes to be placed at approximately 24" o.c.
4. SIKA Armatek 110 Epo-Cem has been added to the existing and new reinforcing. A second
application will be required to be installed prior to the pour for a wet to wet installation.
Alternatively, a scrub coat of the repair mortar can be
5. Bottom of railings require to be coated prior to casting in deck.
6. OK to pour concrete per plan and specifications after anodes are installed. Consolidate
plastic concrete at time of placement by mechanical means and install per manufacturer
specifications.
CC: Richard Rohde — North South Const By:
(richard.rohde@oplhotels.com) RobertJ. Selinsky P.E., S.I. #1145
_ OCEN018006 —'Site Visit i May 30, 2019 Page 2
J' Ocean Properties Courtyard Marriott Balcony Repairs
Photograph 1— Photos of Deck Repairs
Photograph 2 — Photos of Deck Repairs
THRESHOLD FIELD REPORT
1110ce o
p
N. ?Z�19
C g
O
RUC/P
CO,ry,�timP�i
601 N. Congress Avenue
Unit 106A
Delray Beach, F1.33445
T: 561-265-6864
v✓w v.pennoni.com
SITE VISIT #08.
Project: Courtyard Marriott Balcony Repairs
McCarthy Project No. OCENDIS006
St. Lucie County Permit No. SLC-1811-0242 2nd Floor Balconies
Location:
Date:
Contractor:
Present:
Progress:
Comments:
10978 S. ocean Blvd.
Jensen Beach, FL
July 23, 2019
Miller Construction
James V. Barnes, Jr., Pennonl
Frank, RTI Construction
Unit 206 &208 Balcony edges excavated with reinforcing In place
Arrived on site, as requested by the contractor to observe the following:
1. Unit 206 & 208 balcony excavation complete. The east, north, and south sides of the balcony have
been excavated to expose the ends of two layers of approximately Y4 Inch diameter welded wire
fabric reinforcing. Repair of balcony nosing edge per detail #3.sheet S2.0. (See Photographs 1&2)
2. Supplemental reinforcing has been added at 24" o/c per plan with (2) #5 continuous edge bars
3. SIKA Armatek 110 Epo-Cem to be added to the existing and new reinforcing.
4. Zinc anodes are in place at 2 feet o/c per plan. Acceptable.
5. OK to pour concrete per plan and specifications after anode installation.
6. Consolidate plastic, concrete at time of placement by mechanical means.
CC: Richard Rohde — North South Const
( richard.rohde@oplhotels.com)
Livingston Adderley, RTI
(jradderley@yahoo.com)
0 � l S 4P
0 � G
No 95
STATE OF
. ty
I IAI
Robert J. Selinsky P.E., S.I. #1145
OCEN D18006 — SVIi08 July 23, 2019 Page 2
North South Construction Marriott Balcony Reoalrs
Photograph #01: Added #5 Rebar per Detail #3 S2.0
I
Photograph #02: Example of Current Edge Repair per Detail #3 S2.0
601 N. Congress: Avenue
Unit106A
Delray. Beach, FL33445
T: 561-265-6864
www.pennonl.corn
Project: Courtyard Marriott BalconyRepairs
McCarthy Project No. OCEN018006
Martin County Permit o. LC -1811� d Floor Balconies
Location: 109.78 S. Ocean Blvd.
Jensen Beach, FL
Date: June 25, 2019
Contractor: Miller"Construction
Present: Robert Sellnslry P.E„ Pennon!
.Frank, RTI Construction
Progress: Unit.212 Balcony edges excavaied with reinforcing in place.
Comments:
Arrived on site, as requested by the contractor to observe the following:
1. Unit 212 balcony excavation complete. The east, north, and south sides of the balcony have,
(been excavated to expose the ends&two layers,of approximately Y4 inch diameter welded
wire fabric reinforcing..
2. Supplemental reinforcing has been added at 24 o/c per plan with (2) #i5 continuous edge
bars.
I SIKA:Armatek 110 Epo-Cem has been, added to the existing and new reinforcing.
4, Zinc anodes are in place at 2 feet o/c per plan. Acceptable.
5. OK to pour concrete per plan and specifications after anode installation.
6. Consolidate.plastic concrete at time of placement by mechanical means.
Znclosure: Photograph
CC: Richard Rohde —North South Const.
( richard.rohde2oplhotels.com)
Livingston Adderley, RTI
(jradderley@:yahoo°.com)
By:
Robert J. Selinsky P
l�u►nrri,
;ENSF•:;S�-f--�i
2//// If
i
OCEN618006—SVn06 June25, 2019 Page 2
North South Construction Courtyard Marriott Balcony Repairs
Photo #101— Unit'212 Balcony Anode in Place
THRESHOLD FIELD REPORT
Project: Courtyard Marriott Balcony Repairs
2nd - 61h Floors Balconies
McCarthy Project No. OCEND18006
e/)p
601 N. Congress Avenue
Unit 106A
Delray Beach,.Fl. 33445
T: 561-265-6864
w v.pennonl.com
SITE VISIT #07
St. Lucie County Perm it.NCXSL'G1-811 0W;A43,0245, 0246,0248,0249
Location:
10978 S. Ocean Blvd.
Jensen Beach, FL
Date:
July 12, 2019
Contractor:
Miller Construction
Present:
James V: Barnes, Jr., Pennoni
RobertJ. Selinsky P.E., Pennoni
Frank, RTI Construction
Progress: 2nd 3rd 4th 5th, and 6th floors balcony edges excavated with reinforcing in
place.
Comments:
Arrived on site, as requested by the contractor to observe the following:
1. Contractor requested that a shoring plan be generated for the balcony demolition phase as
requested by the St. Lucie County Building Inspector. Pennoni to prepare shoring for typical
deck and send to RTI.
2. The area of the overhead walkway at the receiving area was reviewed with the contractor.
There was significant chunks of spalling concrete debris lodged between the deck and
overhead piping could become dislodged. We recommend that the contractor remove the
concrete. (See Photographs 18i2)
3. 2nd floor units 4306, 308; 3rd floor units #206, 208 balcony; 4th floor units #406, 808; 5th floor
units #506, 508 and, 6t' floor units #606, 608 balcony partial demolition is not complete.
Contractor to refer to details 5 and 9 on S2.0 for guidance. The west side and center of the
balcony need to have had more areas excavated to expose the ends of two layers of the deck
reinforcing. The 6th floor concrete column between units'606 and 60fi fpflair utilizing detail 2
and 4 on 5.2.0.
Enclosure: Photographs
N 49 2 •1Y
CC: Richard Rohde — North South Const Bv:
( richard.rohde@oplhotels.com) Robew�J hI9s§ �.FE°rS.L-j1#4�
Livingston Adderley, RTI i� .,a�e
0
(jradderley@yahoo.com) �0fdAl t��\\\\
OCEND18006-SVH07 July 12, 2019 Page 2
North South Construction Courtyard Marriott Balcony Repairs
Photograph 1: Spalling Debris Area
Photograph2: Dislodged Debris on Pipes
'-1
OCEND18006-SV407 July 12, 2019 Page 3
North South Construction Courtyard Marriott Balcony Repairs
Photograph 3: Example of Current Edge Repairs
Photograph 4: Mid -Center 4th Floor -Unit 408 Declt Above
OCEND19006-SVIl07 July 12, 2019 Page 4
North South Construction Courtyard Marriott'Balcony Repairs
Photograph 5: Underside Spa III at,M.id-Center4th Floor-Unit'408
THRESHOLD EEL® REPORT
601 N. Congress Avenue
Unit 106A
Delray Beach, Fi. 33445
T: 561-265-6864
www.pehnonlxom
SATE VMT #13
Project: Courtyard Marriott Balcony Repairs
McCarthy. Project No. OCEND18006
St Lucie County Permit NOaSLTG5dJ3 3'-1f2ib2 2nd Floor Balcony Columns
SLC-1811-0243 6th Floor Balcony Columns
Location:
Date:
Contractor:
Present:
Progress:
SLC-1811-0245 4th Floor Balcony
10978 S.'Ocean Blvd.
Jensen Beach, FL
August 21, 2019
RTI Construction
James V. Barnes, Jr., Pennoni
Frank, RTI Construction
N 9 2 1
�'. STATE O lzz
N
�pN�l 11�
Units 206 &.208 and Units 606 & 608 Balcony party wall columns and Unit
405 & 408 Balcony deck excavated with reinforcing in place
Comments:
Arrived on site, as requested by the contractor to observe the following:
1. Weather conditions were 930 partly cloudy to sunny. It had just rained 1 hour earlier.
2. Units 206 & 208 and Units 606 &.608 party wall columns were excavated, formed and poured
before today's rain began. Contractor provided photos. (See Photographs 1-4)
3. Units 406 & 408 balcony deck excavation complete. The mid deck area of the balconies have
been excavated to expose the ends of two layers of approximately % Inch diameter welded
wire fabric reinforcing. Repair is not ready to pour. (See Photographs 5-6)
4. Supplemental reinforcing has been added at 24" o/c per plan with (2) #5 continuous edge
bars.
5. SIKA Armatek 110 Epo-Cem is to be added added to the existing and new reinforcing before
contractor pours the repair.
6. Seven - Zinc anodes are to be placed at 24" o/c per plan. The locations weredetermined and
marked for the contractor.
7. OK to form the area and pour concrete per plan and specifications after anode installation is
verified,
OCEND18006—SV R13 August 21, 2019 Page 2
OPL Marriott Jensen Beach Balcony Repairs
8. Consolidate plastic concrete at time of placement by mechanical means.
CC: Richard Rohde — North South Const
( richard.rohdeC@oplhotels.com)
Livingston Adderley, RTI
(]radderlevOyahoo.com)
By, ctvrzee (/• FGUZlw, �oz
James V. Barnes, Jr., Construction Coordinator
i
r l
OCEND18006 — SV #13 August 21,.2019 Page
OPL Marriott Jensen Beach Balcony Repairs
Photograph #01
206 & 208 Party Wall Column Repair Excavated
(RTI Provided)
Photograph #03
606 & 608 Party Wall Column Repair Excavated
(RTI Provided)
Photograph #02
206 & 208 Party Wall Column
Repair Completed
Photograph #04
606 & 608Party Wall Column
Repair Completed
I
OCEN D18006 — SV #13 August 21,. 2019 Page 4
OPL Marriott Jensen Beach Balcony Repairs
7
Photograph#05: 406 & 408 Surface Deck Repair Complete per Detail #1 Sheet S2.0
Photograph #06: 406 & 408Surface Deck Repair Complete per Detail #1 Sheet S2.0