SITE VISIT #04
Project: Courtyard Marriott Balcony Repairs
McCarthy Project No. OCENDIS006
Martin County Permit No. SLC ' 11-0249 h Floor Balconies
Location: 10978 S. Ocean Blvd.
Jensen Beach, FL
Date: June 6, 2019
Contractor: Miller Construction
Present: Robert J Selinsky P.E., Pennoni
Frank, RTI Construction
J. set/�/Z�ii
A ,
�/e * ', PSTATW
- 1 Cep ro E O 1"
0.
or�.��
ONAC
/I111{11\�
Progress: Unit 706 and 708 Balcony edges excavated with reinforcing in place
Comments:
Arrived on site, as requested by the contractor to observe the following:
1. Unit 706 and 708 balcony excavation complete. The east, north, and south sides of the
balcony have been excavated to expose the ends of two layers of approximately % Inch
diameter welded wire fabric reinforcing.
Supplemental reinforcing has been added at 24" o/c per plan with (2) #5 continuous edge
bars. Railing end posts to be coated prior to repair mortar installation.
3. SIKA Armatek 110 Epo-Cem has been added to the existing and new reinforcing. Reinstall a
second coat or add scrub coat of repair mortar prior to pouring with repair mortar.
4. Add Vector XPT zinc anodes at 24" o.c. around perimeter of deck. Check for continuity and
install per manufacture specifications.
5. OK to pour concrete per plan and specifications after anode installation. Consolidate plastic
concrete at time of placement by mechanical means.
6. Repairs are needed to the deck topping prior to re -sloping deck.
7. Concrete column between units 606 and 608 shall be repaired per detail 4/S2.0. Photo #01
CC: Richard Rohde— North South Const.
( richard.rohde(@oolhotels.com)
Robert J. Selinsky P.E., S.I. #1145
OCEND18006 — Site Visit#C June 6, 2019 Page 2
Richard Rohde -North SoWt--truction Courtyard Marriott Balcony Repairs
m
Photo# 01— Spalling Damage at Deck and Column in Need Of Repair
' RFc
on-99
FiL�o
sr •�ri� �10
<4 90 I9
/P P'4d
601 N. Congress Avenue
Unit 106A
Delray Beach, Fl. 33445
T: 561-265-6864
www.pennont.coni
SITE VISIT #17
Project: Courtyard Marriott Balcony Repairs
Pennoni Project No. OCEND18006
St. Lucie County Permit No. SLC-1811-0246 5th floor Balconies
Location: 10978 S. Ocean Blvd., Jensen Beach, FL
Weather Condition & Temperature: Partly Cloudy / 82° +/-15-25mph Winds / 1:30pm-3:30 m
1/
Date: September 18, 2019 \\\\ ��3'.SE�J4/7�i�
i
Contractor: RTI Construction
N
- * ; to
Present: James V. Barnes, Jr., Pennon! TE OF
Frank, RTI Construction
Progress: Units 500-502-& 702-704 balcony edge excavated with reinfrir�i�y®�41-
�lllj l'1111 \1\\
Comments:
Arrived on site, as requested by the contractor to observe the following:
1. ' Units 500 & 502 balcony mid deck of the balcony needs to be excavated to expose the ends of two
layers of approximately;''/<!nch diameter welded wire fabric reinforcing. (See Photograph 1). Repair
of balcony nosing edge per detail #1-sheet S2.0:
2. Supplemental reinforcing has been added at 24" o/c per plan.
3. 51KA Armatek 110 Epo-Cem needs to be added to the existing and new reinforcing. Then a
second coat Armatek 110 needs to be applied to the repair prior final pour.
4. Zinc anodes are in place at 2 feet o/c per plan. (8) anodes are to be in the repair. 2 anodes
were loose and need to be reinstalled for proper connection.
5. OK to pour concrete per plan and specifications after anode installation.
6. Consolidate plastic concrete at time of placement by mechanical means,
Units 702 & 704 balcony excavation complete. The northeast corner side edge of the balcony have
been excavated to expose the ends of two layers of approximately #5 rebar reinforcing. Repair of
balcony nosing edge per detail #3 sheet S2.0. (See Photograph 2). Placement of the forms can be
installed for the edge: repair poured with NO Zinc anodes are in place a in'the repair.
CC: Richard Rohde— North South Const
(richa rd. rohdePoolhotels. com)
Livingston Adderley, RTI
(jradderley@yahoo.com)
By: &YW l/, eR1w'd, ,or ,,
James V. Barnes, Jr., Construction Administrator
OCEND18006 — SV U17 Photos September 18, 2019 Page 2
OPL Marriott Jensen Beach Balcony Repairs
Photograph #01: 500 & 502 Deck Mid -Deck Repair Complete per Detail #1 Sheet S2.0
Photograph #02: 702 & 704 Deck Edge Repair Complete per Detail #3 Sheet S2.0