HomeMy WebLinkAboutFLOOR PLAN0 1 SITE SPECIFIC FLOOR PLAN: SCALE: N.T.S. UNIT #604 BUILDING FOOTPRINT PLAN VIEW UNIT NEXT DOOP 7 a 60.0. 0 1 17 SCANNED BY 9t. Lucie County NIT EXT DOR DESIGN NOTES: � FLORIDA BUILDING CODE SIXTH EDITION (2017) ASCE 7-10 Vult=170 MPH / Vasd=131.7 MPH (3 SECOND GUST), EXPOSURE'D', ENCLOSED STPUCT , RISK CATEGORY=Il, Kd=0.85, Kzt=1.0, KZ=TABLE 30.3-1, GCpi=+/-0.18 qh = 0.00256*Kz*Kzt*Kd*V*V C P = qh ((GCp)-(GCpi)) I MRH=140', ZONE(S) AS NOTED, ROOF TYPE PRESSURES: NOTED BELOW 'MONOSLOPE', ROOF SLOPE 0.0 Ivo INSTALL ALL SYSTEMS PER VALID FLORIDA PRODUCT APPROVALS GENERAL NOTES: 1. THIS ENGINEERED PLAN IS INTENDED TO PROVIDE SITE -SPECIFIC DESIGN PRESSURES FOR WE REFERENCED STRUCrUm F RKr,�F OF WE INSTALLATION OF G!.AZED/NON-G�ED PRODUCTS AS PROPOSED AND PROVIDED BY OTHERS. NO MmnmnO EXPRESSED OR IMPLIED, IS OFFERED AS TO THE VALIDITY OR APPILICNBILT� OF ANy PROPOSED � OR COMPONENT USEMA'��Ko)yj[ THIESE PRESSURES UNLESS PRODUCr AND APPROVAL. INFORMATION IS SPECUFICALI�Y REFERENCED AND ADD�SED HEREIN. 2. NO CE11TIFICATION OR REVIEW 15 OFFERED THAT WE PROPOSED UNITS MEET ANY EGRESS REQUIREMENTS. ALL EGRESS ISSUES AAClQV' ADDRESSED BY THE PERMITTING CONTRACTOR AND WE LOCAL BUILDING OFFICIAL. 3. THIS CERTIFICATION APPLIES TO WE STRUCrURAL PERFOMANCE OF WE SYSTEM ONLY DOES NOT INCLUDE THE CERTIFICATION OF WATk I I INFILTRATION OF FIRE SAFETY. 4. THE HOST STRUCTURE IS ASSUMED TO BE ADEQUATE TO WITHSTAND WE LOADS IMPOSED BY THIS DESIGN AS WORK REPLACES WE MEWING FRAMING. IF ANY DEFICIENCIES ARE FOUND IN THE EXISTING H= STRUMIRF TWq MrTNF� q.M. IIE .�Ef� lll�.. WNIINU NUWNbIKU6IIUN AND �ERVE5 THE RIGHTTURE-INSPECIAND RE-EVALUATEDESIGN. NO WARRANTY, EITHEREXPRESSED OR IMPLIED,19CONTAINED HEREIN. SINCEIT IS NOTPRUDENT TO PERFORM DESTRUCTIVETESTING AT THISTIMEMAECONTRACTOR SHALI. VERIFY DURING CONSTRUCTION THATTHE SUBSTRATE IS OF THETfPE AND CONSI-RUCTION WAT IS IN CONFORMANCE WITHWE INTENT OF WE PRODUCT APPROVAL BEING UTIUZED WHICH MUST BE SOUND FOR INSTALLATION OF THIS SYSTEM AND SHALL NOTIFY THIS ENGINEER IF ANY DEFICIENCIES OR ABNORVAIJUIES ARE OBSERVED. USE OF THIS DDO.IMENT CONSTITUTES ACCEPTANCE OF THESE TERMS. S. SYSTEMSSHALLBEASNOTE[IHEREIN. ALL REFERENCES TO EXTRUSIONS & INSrALLAMON SHALL_ �FORM TO THAT OF MANUFACrURERS SPECIFIGNTIONS AS SUMMARIM HEREIN. 6. ANY ]UNCTURE OF EXTERIOR �R AND FENESTRATION PRODUCrS SHALL BE SEALED WITH A SEALANT COMPLYING WITH AAMA 800 AND ASTM C 920 CLASS 25 GRADE NS OR GREATER FOR PROPER JOINT EXPANSION AND CONTRACTION, AND ASTM C1281 OR AAM 812 FOR WE TYPE OF SEALANT TO BE SEI.ECTED WHICH IS OUTSIDE WE SCOPE OF THIS CERTIFICATION. 7. THE CONTRACTOR IS RESPONSIBLE TO INSULATE ALL MEMBERS FROM DISSIMILAR MATERIALS TO PREVENT ELECTROLYSIS. 8. ALL CONCRETE SHALL BE UNCRAMED ONLY WITH A MINIMUM COMPRESSIVE STRENGTH OF 3000 PS1 U.N.O. AND SHALL. BE MINIMUM 1. Sx THICKEll THAN ANY MEMBER EPISEDMENT. ALL EPDXY AND GROlff SIHVlL. MEET OR EXCEED COMPRESSIVE STRENGTH OF WE CONCRETE AND SHALI. BE IRON -FREE, NON -SHRINK AND NOWREACTIVE. 9. MR ALUMINUM ATrACHMENTS ALL ANCHORS SHALL BE SPACED WITH 2xDIAMUER END DISTANCE AND 2.SxDIMUM MIN SPACING TO 10. ALI. FASTENERS TO BE #12 X 3/4- OR GREATER 202�T4, 18-8 SERIES 300 NON-MAGNETIC STAINLESS STEEL, OR CADMIUM PLATED OR OTHERWISE CORROSION RESISTANT MATERIAI. AND SHALL COMPLY WITH All- APPLICABLE FEDERALSTATE, AND LOCAL CODES. 11. DIMENSIONS ARE SHOWN TO ILLUSTRATE DESIGN FORCES AND MM DESIGN CRITERIA. THEY MY VARY SLIGHTLY. TO WE EXTENT THAT WE OPENING AREA IS NOT SMA� THAN 5% OF WE ENGINEERED DESIGN. CONTRACTOR IS TO VERIFY ALL FIELD DIMENSIONS PRIOR TO INSTALLATION. 12. ENGINEER SUL AFFIXED HERETO VALIDATES STRUCTURAL DESIGN AS SHOWN ONLY. USE OF THIS SPECIFICATION BY CONTRACTOR, et aL INDEMNIFIES & SAVES HARMI ESS THIS ENGINEER FOR ALI. COST & DAMAGES INCLUDING LEGAL FEES & APPELLATE FEES RESULTING MOM MATERIAL FABRICATION, SYSTEM ERECTION, & CONSTRIKTION PRACRCES BEYOND THAT WHICH 15 M I m MR BY LOCAL, STATEt & FEDERAL. CODES & FROM DEVIATIONS OF THIS PLAN. 13. ENGINEERING EXPRESS HAS NOT VISITED THIS JOBSITE. INFORMATION CONTAINED HEREIN IS BASED ON CONTRACTOR SUPPLIED DATA AND MEASUREMENTS. ENGINEERING EXPRESS SHALL NOT BE HELD RESPONSIBLE OR LIABLE IN ANY WAY FOR ERRONEOUS OR INAMURATE DATA ORMEASURE�IENTS. WORK SHALL BE REM VERIFIED PRIORTO CONSIRUCTION. ENGINEEFUNGEXPRESSSHALLBENOTIFIEDMDGMN AN OPPORTUNITY TO REEVALUATE OUR WOW UPON DISCOVERY OF ANY INACCURATE INFORMATION PRIOR TO MODIFICATION OF EXISTING FIELD CONDITIONS AND FABRICATION AND INSTALLATION OF MATERIALS. 14. EXCEPT AS EXPRESSLY PROVIDED HUEIN, NO ADDITIONAL CERTIFICATIONS OR AFFIRMATIONS ARIE INTENDED. - ALTERATIONS, ADDITIONS, OR OTHER MARKINGS TO THIS DOCUMENT ARE NOT PERMITTED AND INVALIDATE OUR CERTIFICATION DESIGN INFORMATION: MARK QTY W x H (in.) ZONE DESIGN PRESSURE PRODUCT PRODUCT MODEL APPROVAL MULLION MULLION SIZE (Psf) APPROVAL # PRESSURE (psf) APPROVAL 0 (in.) SERIES SH-700 1 (1) 32.00 x 51.00 4 +�.84/-61.91 17-0630.08 ALUMINUM �()1�0 N/A N/A SINGLE HUNG WINDOW PST SERIES 2 (1) 142.00x96.00 4 �7.67 / -56.57 17�420.13 n()­HP SUDING +901-130 N/A N/A GLASS DOOR PGT SERIES 3 (1) 206.00 x 96M 4 +49.02/-S7.60 17-0420.13 770-HP SLIDING +NJ-130 N/A NIA GLASS DOOR 4A (1) 37.00 x 64.00 4 +S4.84 / -61.91 .80/_80 17-0630.01 lx2.75x0.37S 4B (1) 37.DO x 64.00 4 +54.B4 / -61.91 +801�0 17-0630.01 Ix2.75x0.37S DRAWING NOTES: FILE COPY (6((- 0 q3fS7 JEVEL OF ALTERATION I ONLY. IF LEVEL OF ALTEiUITION IS DIFFERENT, THIS BALCONIES WITH EXISTING 4r HIGH APPROVED GUARDS WHICH S� NOT L-01 THIS W 1`4 01T m q 0 w'r U0 IL w 9; . lu U L�x zz %J H 0; @�j Z E.z w III z 0 U� < < z 0 -ri- U) a U) :.,b UU GO U w LL z W Z5 < 0 0 UZ In 10� U) 0 m cL In z U) z 0 U) 0 0 LD w 'r! z > 1�1�f Gl;� FLOOR PLAN AND UNIT LAYOUT AT BUN CAU�TED USING WIDTH . HEIGHI/ 3 (DT�W AREA . H-W3) 'fl 1 1