HomeMy WebLinkAboutESTIMATETES Electric South
87 South US Highway 17-92, Suite B
DeBarv. FL 32713 ..
RECEIVED timate CLCIiIRIa ML
CONTRACTORS
Phone # (305) 596-0 91 or (877) 661.0691
Fax# "It
I 668-8 08 NOV 2 8 2018
E-mail office@tes .com
ST Luca Coun 1'eCQI �9 � � s n
�
Genset Services, Inc. PSL Nursing
3100 Gateway Drive
SCANNED
Pompano Beach, Florida, 33069
BY
St. Lucie County
10/30/2018 E54mate'7Fr -r 18-2129
Protect
PSL Nursing
,5 q;
_
Supply and Install (1) new 1600A 120/208V 3P vault feed from existing FPL vault to new 1600A
service rated ATS-5 to be pad mounted.
Supply and Install (1) new 1600A 3P 120/208V normal feed from new 1600A ATS to new 1600
MCB to be mounted on exterior of FPL vault.
Supply and Install (1) new 1600A load feed from new 1600A MCB to existing MSB
Remove existing FPL vault feed from MSB to FPL vault.
Supply and Install (1) 1600A feed from new 400kW generator to new 1600A ATS emergency side.
Supply and Install (1) 400A 3P 120/208V EM feed from existing generator to new ATS4
Supply and Install (1) 400A 3P 120/208V EM feed from new 400kW generator to normal side of
new ATS4
Supply and Install (1) 400A 3P 120/208V load feed from newATS-4 to existing panel GDP
Supply and install battery charger, block heater, control wiring and annunciator panel new Noise
Station.
Precast pad included
Parking lot excavation and repair included.
Commercial -Total lob Cost
1
207,000.00
207,000.00
NOTES:
All fuel work, Diesel and Gas, to be done by others
Crane by others
Engineering by others .
Electrical permitting included
All work will be done during normal business hours, except changeover
TES will conned temporary roll -up generator to main gear during shut down. Generator, fuel and
cabling to be supplied by others. '• Plan 1-week rental."
Web Sites
www.tesfla.com
TQ' r
S207,000.00
Please sign and return to begin work. Signature